FIRESTOP SUBMITTAL PACKAGE

Size: px
Start display at page:

Download "FIRESTOP SUBMITTAL PACKAGE"

Transcription

1 FIESTOP SUBMITTAL PACKAGE Fluted Deck Sealant Project: Date: Submitted by: 210 Evans Way Somerville, NJ (800) (908) Fax (908)

2 GENEAL CETIFICATE OF CONFOMANCE JUNE 2013 Description: SpecSeal Firestop Products; Pensil Silicone Sealants; EZ-Path Fire ated Pathways; eady Sleeve Firestop Sleeves; STI Firestop Products Included Products: SpecSeal Series SSS Intumescent Sealant SpecSeal Series LCI Intumescent Sealant SpecSeal Series LC Firestop Sealant SpecSeal Series ES Elastomeric Sealant SpecSeal Series SIL300 Silicone Sealant SpecSeal Series SIL300SL Silicone Sealant Pensil PEN300 Silicone Sealant Pensil PEN300SL Silicone Sealant Pensil PEN200 Silicone Foam BlazeStop WF300 Firestop Caulk SpecSeal Series AS200 Elastomeric Spray SpecSeal Series FT Fast Tack Firestop Spray SpecSeal Series SSP Putty & Putty Pads SpecSeal Series EP PowerShield Box Insert SpecSeal Series SSM Firestop Mortar SpecSeal Series SSB Firestop Pillows SpecSeal Series CS Composite Sheet SpecSeal Series SSW Wrap Strips SpecSeal Series LCC Firestop Collars SpecSeal Series SSC Firestop Collars SpecSeal Series TC Firestop Collars SpecSeal Series FP Firestop Plugs SpecSeal Series CD Cast-In Firestop Devices FyreFlange Firestop Angle EZ-Path Series 22 EZ-Path Series 33 EZ-Path Series 44 or 44+ eady Sleeve eady Sleeve Split EZ-Path Firestop Grommet SpecSeal Series SSAMW Mineral Wool SpecSeal SpeedFlex Fire ated Joint Profile SpecSeal Closet Flange Firestop Gasket SpecSeal Series CS105 Cable Spray SpecSeal SpeedFlex Track Top Gasket These products are tested to one or more of the following standards: ASTM E814 (ANSI/UL1479) Standard Test Method for Fire Tests of Penetration Firestop Systems ASTM E1966 (ANSI/UL2079) Standard Test Method for Fire-esistive Joint Systems ASTM E119 (ANSI/UL263) Standard Test Methods for Fire Tests of Building Construction and Materials ASTM E2307 Standard Test Method for Determining Fire esistance of Perimeter Fire Barrier Systems Using Intermediate Scale, Multi-Story Test Apparatus ASTM E1399 Standard Test Method for Cyclic Movement and Measuring the Minimum and Maximum Joint Widths of Architectural Joint Systems ASTM E84 (ANSI/UL723) Standard Test Method for Surface Burning Characteristics of Building Materials CAN/ULC S115 Standard Method of Fire Tests of Firestop Systems CAN/ULC S101 Standard Methods of Fire Endurance Tests of Building Construction and Materials Chemical Content Statement: No asbestos, PCB s, lead, or water-soluble intumescent ingredients are used or contained in these products. James P. Stahl Jr., CFPS Vice President of Engineering Paul M. Jankowski Quality Control Manager Certificate of Conformance Technical Service

3 System No. HW-D-0034 Ì83HWDÇÂBÈANÇ#..pÎ ANSI/UL2079 Assembly atings - 1 and 2 Hr (See Item 2) Nominal Joint Width - 1 In. Class II Movement Capabilities - 7% or 25% Compression or Extension (See Items 1C, 1A-D) L ating At Ambient - Less Than 1 CFM/sq ft L ating At 400 F - Less Than 1 CFM/sq ft CAN/ULC S115 F atings - 1 and 2 Hr (See Item 2) FT atings - 1 and 2 Hr (See Item 2) FH atings - 1 and 2 Hr (See Item 2) FTH atings - 1 and 2 Hr (See Item 2) Nominal Joint Width - 1 In. Class II Movement Capabilities - 7% or 25% Compression or Extension (See Items 1C, 1A-D) L ating At Ambient - Less Than 1 CFM/sq ft L ating At 400 F - Less Than 1 CFM/sq ft 1. Floor Assembly - The fire-rated fluted steel deck/concrete floor assembly shall be constructed of the materials and in the manner described in the individual Floor-Ceiling Design in the UL Fire esistance Directory and shall include the following construction features: A. Steel Floor And Form Units* - Max 3 in. (76 mm) deep galv steel fluted floor units. B. Concrete - Min 2-1/2 in. (64 mm) thick reinforced concrete, as measured from the top plane of the floor units. C. Spray-Applied Fire esistive Material* - (Optional, Not Shown) - After installation of the ceiling runner (Item 2A) or deflection channel (Item 3A), steel floor units to be sprayed with a min 5/16 in. (8 mm) to max 11/16 in. (17 mm) thickness of material in accordance with the specifications in the individual D700 or D800 Series Design. When spray applied fire resistive material is used, ceiling runner or deflection channel to be provided with 2 in. (51 mm) flanges. Excess material to be scraped from flanges of ceiling runner or deflection channel prior to installation of gypsum board. When Spray-Applied Fire esistance Material is used, Class II Movement Capabilities restricted to COMPESSION ONLY. ISOLATEK INTENATIONAL - Type 300 W GACE & CO - CONN - MK-6/HY eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: March 14, 2014 HW-D-0034 PAGE 1 OF 4

4 1A. oof Assembly - (Not Shown) - As an alternate to the floor assembly (Item 1), a fire rated fluted steel deck roof assembly may be used. The roof assembly shall be constructed of the materials and in the manner described in the individual P700, P800 or P900 Series oof-ceiling Design in the UL Fire esistance Directory. The hourly fire rating of the roof assembly shall be equal to or greater than the hourly fire rating of the wall assembly. The roof assembly shall include the following construction features: A. Steel oof Deck - Max 3 in. (76 mm) deep galv steel fluted roof deck. B. oof Insulation - Min 2-1/4 in. (57 mm) thick poured insulating concrete, as measured from the top plane of the steel roof deck. C. oof Covering* - Hot-mopped or cold-application materials compatible with insulating concrete. D. Spray-Applied Fire esistive Material* - (Optional, Not Shown) - After installation of the ceiling runner (Item 2A) or deflection channel (Item 3A), steel floor units to be sprayed with a min 5/16 in. (8 mm) to max 11/16 in. (17 mm) thickness of material in accordance with the specifications in the individual P700 or P800 Series Design. When spray applied fire resistive material is used, ceiling runner or deflection channel to be provided with 2 in. (51 mm) flanges. Excess material to be scraped from flanges of ceiling runner or deflection channel prior to installation of gypsum board. When Spray-Applied Fire esistance Material is used, Class II Movement Capabilities restricted to COMPESSION ONLY. ISOLATEK INTENATIONAL - Type 300 W GACE & CO - CONN - MK-6/HY 1B. Floor Assembly - (Not Shown) - As an alternate to the floor assembly (Item 1), min 4-1/2 in. (114 mm) thick structural concrete ( pcf or kg/m3) or min 6 in. (152 mm) thick hollow-core Precast Concrete Units*. See Precast Concrete Units (CFTV) category in Fire esistance Directory for names of manufacturers. 2. Wall Assembly - The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described in the individual U400 or V400 Series Wall and Partition Design in the UL Fire esistance Directory and shall include the following construction features: A. Steel Floor and Ceiling unners - Floor and ceiling runners of wall assembly shall consist of galv steel channels sized to accommodate steel studs. Ceiling runner to be provided with min 1-1/4 in. (32 mm) to max 2 in. (51 mm) flanges. When deflection channel (Item 3A) is used, flange height of ceiling runner is to be equal to or greater than flange height of deflection channel and the ceiling runner is to nest within the deflection channel with a 1/2 to 3/4 in. (13 to 19 mm) gap maintained between the top of the ceiling runner and the top of the deflection channel. When deflection channel is not used, ceiling runner to be provided with min. 1-1/2 in. (38 mm) flanges. Ceiling runner installed perpendicular to direction of fluted steel deck and secured to valleys with steel masonry anchors or welds spaced max 24 in. (610 mm) OC. A1. Light Gauge Framing* - Slotted Ceiling unner - As an alternate to the ceiling runner in Item 2A, ceiling runner to consist of galv steel channel with slotted flanges sized to accommodate steel studs (Items 2B). Ceiling runner installed perpendicular to direction of fluted steel deck and secured to valleys with steel masonry anchors spaced max 24 in. (610 mm) OC. When slotted ceiling runner is used, deflection channel (Item 3A) shall not be used. BADY CONSTUCTION INNOVATIONS INC, DBA SLIPTACK SYSTEMS - SLP-TK CALIFONIA EXPANDED METAL PODUCTS CO - CST CLAKDIETICH BUILDING SYSTEMS - Type SLT, SLT-H MAINO/WAE, DIV OF WAE INDUSTIES INC - Type SLT QUAIL UN BUILDING MATEIALS INC - Slotted Deflection Track SCAFCO STEEL STUD MANUFACTUING CO STEELE INC - Steeler Slotted Ceiling unner TELLING INDUSTIES L L C - True-Action Deflection Track A2. Light Gauge Framing - Floor and Ceiling unners - As an alternate to the ceiling and floor runners in Item 2A, 2A1 and 2A2, floor and ceiling runners to consist of galv steel channel sized to accommodate the Light Gauge Framing* Slotted Stud (Item 2B1) or Light Gauge Framing* Slider C-Clip System (Item 2B2). Floor and ceiling runners to be provided with min 1-1/4 in. and 3 in. (32 and 76 mm) flanges, respectively. Ceiling runner installed perpendicular to direction of fluted steel deck and secured to valleys with steel masonry anchors spaced max 12 in. (305 mm) OC. When ceiling runner is used, deflection channel (Item 3A) shall not be used. STEELE INC - Floor and Ceiling unners eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: March 14, 2014 HW-D-0034 PAGE 2OF 4

5 A3. Light Gauge Framing*- Notched Ceiling unner - As an alternate to the ceiling runners in Items 2A through 2A3, notched ceiling runners to consist of C-shaped galv steel channel with notched return flanges sized to accommodate steel studs (Item 2B). Notched ceiling runner installed perpendicular to direction of fluted steel deck and secured to valleys with steel masonry anchors spaced max 24 in. (610 mm) OC. When notched ceiling runner is used, deflection channel (Item 3A) shall not be used. OLMA SUPPLY INC - Type SC A4. Steel Framing Members* - Sound Isolation Clips - (Not Shown) - As an alternate attachment means for the ceiling runner to the bottom of the floor or roof assembly when no deflection channel (Item 3A) is used, sound isolation clips installed in accordance with the accompanying installation instructions. Sound isolation clip installed through nom 1 in. (25 mm) diam hole in ceiling runner and attached to top of ceiling runner using four min No. 8 by 1/2 in. (13 mm) long self-tapping galv steel screws. Sound isolation clips to be installed adjacent to every stud location but not more than 24 in. (610 mm) OC and attached to the underside of floor or roof assembly using min 3/16 in. (5 mm) diam by 2-1/2 in. (64 mm) long steel masonry anchors. PAC INTENATIONAL INC - Type SIC-U-HD B. Studs - Steel studs to be min 3-1/2 in (89 mm) wide. Studs cut 1/2 to 3/4 in. (13 to 19 mm) less in length than assembly height with bottom nesting in and secured to floor runner. When deflection channel (Item 3A) is used, steel studs attached to ceiling runner with sheet metal screws located 1/2 in. (13 mm) below the bottom to the deflection channel. When deflection channel is not used, studs to nest in ceiling runner without attachment. When slotted ceiling runner (Item 2A2) is used, steel studs secured to slotted ceiling runner with No. 8 by 1/2 in. (13 mm) long wafer head steel screws at midheight of slot on each side of wall. Stud spacing not to exceed 24 in. (610 mm) OC. B1. Light Gauge Framing* - Slotted Studs - Slotted steel stud to be used in conjunction with Light Gauge Framing* - Floor and Ceiling unners (Item 2A3). Slotted steel studs to be min 3-1/2 in. (89 mm) wide. Slotted steel studs cut 1 in. (25 mm) less in length than assembly height with bottom nesting in and secured to both ceiling and floor runners. Ceiling runner secured to preformed slot within steel stud by means of No. 10 by 3/4 in. (19 mm) long low profile head steel screw. Floor runner attached to bottom of steel stud by means of No. 8 by 1/2 in. (13 mm) long pan head steel screw. Slotted steel stud spacing not to exceed 24 in. (610 mm) OC. STEELE INC - Slotted Stud B2. Light Gauge Framing* - Slider C-Clip System - As an alternate to the Light Gauge Framing* - Slotted Steel Studs (Item 2B1), a Slider C-Clip System consisting of a C shaped steel clip with a slotted opening and a steel stud to be used in conjunction with Light Gauge Framing - Floor and Ceiling unners (Item 2A3). Steel clips and studs to be min 3-1/2 in. (89 mm) wide. Steel clip inserted into inside flange of steel stud without attachment. Total length of steel stud cut 1 in. (25 mm) less than assembly height with bottom of steel stud nesting in and secured to floor runner. Floor runner attached to bottom of steel stud by means of No. 8 by 1/2 in. (13 mm) long pan head steel screw. Ceiling runner secured to steel C-Clip by means of No. 10 by 3/4 in. (19 mm) long pan head steel screw located 3/8 in. (10 mm) below top of ceiling runner. Top row of gypsum board screws shall be centered within the preformed slot of the C-Clip. Steel stud and steel clips spacing not to exceed 24 in. (610 mm) OC. STEELE INC - Slider C Clip System C. Gypsum Board* - Gypsum board sheets installed to a min total thickness of 5/8 in. or 1-1/4 in. (16 or 32 mm) on each side of wall for 1 hr or 2 hr fire rated wall, respectively. Wall to be constructed in the individual U400 or V400 Series Design in the UL Fire esistance Directory, except that a nom 1 in. (25 mm) gap shall be maintained between the top of the wallboard and the bottom surface of the steel floor or roof deck. The screws attaching the gypsum board to the studs along the top of the wall shall be located 1 in. (25 mm) below the bottom of the ceiling runner. No gypsum board attachment screws shall be driven into the ceiling runner or into the optional deflection channel The hourly fire rating of the joint system is dependent upon the hourly fire rating of the wall assembly in which it is installed. 2A. Through Penetrant - (Optional, Not Shown) - Nom 3/8 in. or 1/2 in. (10 or 13 mm) diam rigid steel conduit, steel electrical metallic tubing (EMT) or 1-1/2 in. (38 mm) Sch 40 PVC conduit may be installed within the flutes of the steel floor or roof deck. The conduit or EMT shall be located near the middepth of the steel deck with a clearance of 1/2 to 1-1/2 in. 13 to 38 mm) between the conduit or EMT and the steel deck. A max of one conduit or EMT is permitted in an individual flute. When conduit or EMT is installed in flute of steel deck, the hourly rating of the joint system is 1 hr. eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: March 14, 2014 HW-D-0034 PAGE 3 OF 4

6 3. Joint System - Max separation between bottom of floor or roof deck and top of wall (at time of installation of joint system) is 1 in. (25 mm). The joint system is designed to accommodate a max 7% (for SpecSeal LC150 Sealant) or 25 % (for SpecSeal ES Sealant) compression or extension from its installed width. The joint system shall consist of forming and fill materials, with or without a deflection channel (Item 3A), as follows: A. Deflection Channel - (Optional) - Max 2 in. (51 mm) deep min 24 gauge galv steel channel sized to accommodate ceiling runner (Item 2A). Deflection channel installed perpendicular to direction of fluted steel deck and secured to valleys of with steel masonry anchors or welds spaced max 24 in. (610 mm) OC. The ceiling runner (Item 2A) is installed within the deflection channel to maintain a 1/2 to 3/4 in. (13 to 19 mm) gap between the top of the ceiling runner and the top of the deflection channel. The ceiling runner nests inside the deflection channel without attachment. B. Forming Material* - Min 4-1/4 in. or 5-5/8 in. (108 or 149 mm) depth, for 1 hr or 2 hr fire rated wall, respectively, of 4 pcf (64 kg/m3) mineral wool batt insulation cut to the shape of the fluted deck, approx 20 percent larger than the area of the flutes and compressed into the flutes of the steel floor or roof deck between the top of the deflection channel and the steel floor or roof deck. When sound isolation clips (Item 2A5) are used, the space between the top of the ceiling runner and the underside of the floor or roof shall be tightly packed with mineral wool batt insulation. Additional 2 in. (51 mm) thick by 1 in. (25 mm) wide sections of mineral wool batt insulation are compressed 50 percent and installed cut edge first to fill the 1 in. (25 mm) gap between the top of the wall and bottom of the steel floor or roof deck. The forming material shall be recessed from each surface of wall to accommodate the required thickness of fill material. THEMAFIBE INC - Type SAF OCK WOOL MANUFACTUING CO - Delta Safing OCKWOOL MALAYSIA SDN BHD - Safe OXUL INC - Safe C. Fill, Void or Cavity Material* - Sealant - Min 1/4 in. (6 mm) thickness of fill material installed on each side of the wall in the flutes of the steel floor or roof deck and between the top of the wall and the bottom of the steel floor or roof deck, flush with each surface of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal ES Sealant, SpecSeal LC150 Sealant *Bearing the UL Classification Mark eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: March 14, 2014 HW-D-0034 PAGE 4 OF 4

7 Assembly atings - 1 and 2 Hr (See Item 2) Maximum Joint Width - 3/4 in. Class II Movement Capabilities - 25% Compression Ì74HWDÇ$t,2,@Î 1A 1B A 1B 2A 3C 2B A 2C 2B 2A 2C 1A 1B Section A-A 1A 3C 3B 2B 2C 2A 1. Floor Assembly - The fire-rated fluted steel deck/concrete floor assembly shall be constructed of the materials and in the manner described in the individual D900 Series Floor-Ceiling Design in the UL Fire esistance Directory and shall include the following construction features: A. Steel Floor And Form Units* - Max 3 in. (76 mm) deep galv steel fluted floor units. B. Concrete - Min 2-1/2 in. (64 mm) thick reinforced concrete, as measured from the top plane of the floor units. C. Spray-Applied Fire esistive Material* - (Optional, Not Shown) - After installation of the ceiling runner (Item 2A) or deflection channel (Item 3A), steel floor units to be sprayed with a min 5/16 in. (8 mm) to max 11/16 in. (17 mm) thickness of material in accordance with the specifications in the individual D700 or D800 Series Design. When spray applied fire resistive material is used, ceiling runner or deflection channel to be provided with 2 in. (51 mm) flanges. Excess material to be scraped from flanges of ceiling runner or deflection channel prior to installation of gypsum board. ISOLATEK INTENATIONAL - Type 300 W GACE & CO - CONN - MK-6/HY 1A. oof Assembly - (Not Shown) - As an alternate to the floor assembly (Item 1), a fire rated fluted steel deck roof assembly may be used. The roof assembly shall be constructed of the materials and in the manner described in the individual P700, P800 or P900 Series oof-ceiling Design in the UL Fire esistance Directory. The hourly fire rating of the roof assembly shall be equal to or greater than the hourly fire rating of the wall assembly. The roof assembly shall include the following construction features: A. Steel oof Deck - Max 3 in. (76 mm) deep galv steel fluted roof deck. B. oof Insulation - Min 2-1/4 in. (57 mm) thick poured insulating concrete, as measured from the top plane of the steel roof deck. C. oof Covering* - Hot-mopped or cold-application materials compatible with insulating concrete. eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: December 18, 2012 HW-D-0484 PAGE 1OF 3

8 D. Spray-Applied Fire esistive Material* - (Optional, Not Shown) - After installation of the ceiling runner (Item 2A) or deflection channel (Item 3A), steel floor units to be sprayed with a min 5/16 in. (8 mm) to max 11/16 in. (17 mm) thickness of material in accordance with the specifications in the individual P700 or P800 Series Design. When spray applied fire resistive material is used, ceiling runner or deflection channel to be provided with 2 in. (51 mm) flanges. Excess material to be scraped from flanges of ceiling runner or deflection channel prior to installation of gypsum board. ISOLATEK INTENATIONAL - Type 300 W GACE & CO - CONN - MK-6/HY 2. Wall Assembly - The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described in the individual U400 Series Wall or Partition Design in the UL Fire esistance Directory and shall include the following construction features: A. Steel Floor And Ceiling unners - Floor and ceiling runners of wall assembly shall consist of galv steel channels sized to accommodate steel studs. Ceiling runner to be provided with min 1-1/4 in. (32 mm) to max 2 in. (51 mm) flanges. When deflection channel (Item 3A) is used, flange height of ceiling runner is to be equal to or greater than flange height of deflection channel and the ceiling runner is to nest within the deflection channel with a 1/2 in. (13 mm) to 3/4 in. (19 mm) gap maintained between the top of the ceiling runner and the top of the deflection channel. Ceiling runner secured to valleys with steel masonry anchors or welds spaced max 24 in. (610 mm) OC. A1. Light Gauge Framing* - Clipped Ceiling unner - As an alternate to the ceiling runner in Item 2A, clipped runner to consist of galv steel channel with clips preformed in track flanges which positively engage the inside flange of the steel studs (Item 2B). Track sized to accommodate steel studs (Item 2B). Track flanges to be min 2-1/2 in. (64 mm) long. Clipped ceiling runner installed perpendicular to direction of fluted steel deck and secured to valleys with steel masonry anchors spaced max 24 in. (610 mm) OC. When clipped ceiling runner is used, deflection channel (Item 3A) shall not be used. TOTAL STEEL SOLUTIONS L L C - Snap Trak A2. Light Gauge Framing* - Notched Ceiling unner - As an alternate to the ceiling runners in Items 2A and 2A1, notched ceiling runners to consist of C-shaped galv steel channel with notched return flanges sized to accommodate steel studs (Item 2B). Notched ceiling runner installed perpendicular to direction of fluted steel deck and secured to valleys with steel masonry anchors spaced max 24 in. (610 mm) OC. When notched ceiling runner is used, deflection channel (Item 3A) shall not be used. OLMA SUPPLY INC - Type SC A3. Light Gauge Framing* - Slotted Ceiling unner - Slotted ceiling runner may be used as an alternate to the ceiling runner in Item 2A. Slotted ceiling runner to consist of galv steel channel with slotted flanges sized to accommodate steel studs (Item 3B). Ceiling runner installed perpendicular to direction of fluted steel deck and secured to valleys with steel masonry anchors spaced max 24 in. (610 mm) OC. When slotted ceiling runner is used, deflection channel (Item 3A) shall not be used. BADY CONSTUCTION INNOVATIONS INC, DBA SLIPTACK SYSTEMS - SLP-TK CALIFONIA EXPANDED METAL PODUCTS CO - CST CLAKDIETICH BUILDING SYSTEMS - Type SLT, SLT-H MAINO/WAE, DIV OF WAE INDUSTIES INC - Type SLT METAL-LITE INC - The System B. Studs - Steel studs to be min 3-1/2 in. (89 mm) wide. Studs cut 1/2 in. (13 mm) to 3/4 in. (19 mm) less in length than assembly height with bottom nesting in and secured to floor runner. When deflection channel (Item 3A) is used, steel studs attached to ceiling runner with sheet metal screws located 1/2 in. (13 mm) below the bottom of the deflection channel. When deflection channel is not used, studs to nest in ceiling runner without attachment. eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: December 18, 2012 HW-D-0484 PAGE 2OF 3

9 C. Gypsum Board* - Gypsum board sheets installed to a min total thickness of 5/8 in. (16 mm) and 1-1/4 in. (32 mm) on each side of wall for 1 and 2 hr fire rated assemblies, respectively. Wall to be constructed as specified in the individual Wall and Partition Design in the UL Fire esistance Directory, except that the gypsum board is cut to follow the contour of the steel floor units with a nom 3/4 in. (19 mm) gap maintained between the gypsum board and the steel deck. In addition, the top row of screws shall be installed into the steel studs 1/2 to 1 in. (13 to 25 mm) below the bottom edge of the ceiling runner flange. The hourly fire rating of the joint system is dependent on the hourly fire rating of the wall assembly in which it is installed. 3. Joint System - Max separation between bottom of floor or roof deck and top of wall is 3/4 in. (19 mm). The joint system is designed to accommodate a max 25 percent compression from its installed width. The joint system consists of the following: A. Deflection Channel - (Optional, Not Shown) - Max 2 in. (51 mm) deep min 24 gauge galv steel channel sized to accommodate ceiling runner (Item 2A). Deflection channel installed perpendicular to direction of fluted steel deck and secured to valleys with steel masonry anchors or welds spaced max 24 in. (610 mm) OC. The ceiling runner is installed within the deflection channel to maintain a 1/2 in. (13 mm) to 3/4 in. (19 mm) gap between the top of the ceiling runner and the top of the deflection channel. The ceiling runner is not fastened to the deflection channel. B. Forming Material - (Optional, Not Shown) - In 2 hr fire rated wall assemblies, foam backer rod friction fit into joint opening and recessed minimum 1/2 in. (13 mm) from each surface of wall. C. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within joint opening on both sides of wall, flush with both surfaces of wall. As an option in 1 hr fire rated walls, bond breaker tape applied to ceiling channel (Item 2A) or deflection channel (Item 3A) prior to installation of fill material. SPECIFIED TECHNOLOGIES INC - SpecSeal LC150 Sealant, SpecSeal LE600 Sealant *Bearing the UL Classification Mark eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: December 18, 2012 HW-D-0484 PAGE 3 OF 3

10 Assembly atings - 1 and 2 Hr (See Item 2) L ating At Ambient - Less Than 1 CFM/Lin Ft (See Item 3B) L ating At 400 F - Less Than 1 CFM/Lin Ft (See Item 3B) Joint Width - 3/4 In. Max Ì88BWSÇÂ#ÈANÇ!7.ÊÎ 1. Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight ( pcf or kg/m3) structural concrete. Floor may also be constructed of any 6 in. (152 mm) thick UL Classified hollow-core Precast Concrete Units*. See Precast Concrete Units category in the Fire esistance Directory for names of manufactures. 2. Wall Assembly - The 1 or 2 h fire-rated gypsum board/steel stud wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall or Partition Design in the UL Fire esistance Directory. In addition, the wall may incorporate a head-of-wall joint system constructed as specified in the HW Series Joint Systems in the UL Fire esistance Directory. The wall shall include the following construction features: A. Steel Floor unner - Floor runners of wall assembly shall consist of min No. 25 gauge galv steel channels sized to accommodate steel studs (Item 2B). Floor runners to be provided with min 1-1/4 in. (32 mm) flanges. unners secured with steel fasteners spaced 12 in. (305 mm) OC. B. Studs - Steel studs to be min 3-1/2 in. (89 mm) wide. Studs cut 1/2 to 3/4 in. (13 to 19 mm) less in length than assembly height with bottom nesting in, resting on and fastened to floor runner with sheet metal screws. Stud spacing not to exceed 24 in. (610 mm) OC. C. Gypsum Board* - Gypsum board installed to a min total thickness of 5/8 in. (16 mm) or 1-1/4 in. (32 mm) on each side of wall for a 1 or 2 hr fire rated wall, respectively. Wall to be constructed as specified in the individual U400 or V400 Series Design in the UL Fire esistance Directory except that a max 3/4 in. (19 mm) gap shall be maintained between the bottom of the gypsum board and the top of the concrete floor. The hourly fire rating of the joint system is equal to the hourly fire rating of the wall. 3. Joint System - Max separation between top of floor and bottom of gypsum board is 3/4 in. (19 mm). The joint system consists of a packing material and a fill material, as follows: A. Packing Material - (Optional, Not Shown) - Mineral wool batt insulation, polyethylene backer rod or glass fiber insulation firmly packed into the gap between the bottom of the gypsum board and the top of the concrete floor and recessed from each surface of the wall to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material*-Sealant - Min 1/2 in. (13 mm) thickness of fill material installed on each side of the wall between the bottom of the gypsum board and the top of the concrete floor, flush with each surface of the wall. When mineral wool batt insulation is used as a packing material, min thickness of fill material on each side of the wall is 1/4 in. (6 mm). SPECIFIED TECHNOLOGIES INC - SpecSeal ES Sealant, SpecSeal LCI Sealant, SpecSeal LC150 Sealant, Pensil 300 Sealant or SpecSeal Series SIL300. Note: L atings apply when SpecSeal ES Sealant is used. *Bearing the UL Classification Mark eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: January 23, 2014 BW-S-0003 PAGE 1 OF 1

11 Assembly atings - 1 and 2 Hr (See Item 2) Joint Width - 1/2 In. Max L ating At Ambient - Less Than 1 CFM/Lin Ft L ating At 400 F - Less Than 1 CFM/Lin Ft Ì89BWSÇÂ4ÈANÇ!7.BÎ 1. Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight ( pcf or kg/m3) structural concrete. Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow-core Precast Concrete Units*. See Precast Concrete Units (CFTV) category in the Fire esistance Directory for names of manufactures. 2. Wall Assembly - The 1 or 2 hr fire rated gypsum board/steel stud shaft wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Design in the UL Fire esistance Directory. In addition, the wall may incorporate a head-of-wall joint system constructed as specified in the HW Series Joint Systems in the UL Fire esistance Directory. The wall shall include the following construction features: A. Steel Floor unner - "J"-shaped runners, min 2-1/2 in. (64 mm) deep, with unequal legs of 1 in. (25 mm) and 2 in. (51 mm), fabricated from min 24 MSG galv steel. unners positioned with short leg toward finished side of wall. unners attached to structural supports with steel fasteners located not greater than 2 in. (51 mm) from ends and not greater than 24 in. (610 mm) OC. B. Studs - "C-H", "E" (back-to-back) or "C-T"-shaped studs, min 2-1/2 in. (64 mm) deep, fabricated from min 25 MSG galv steel. Cut to lengths 3/8 to 1/2 in. (10 to 13 mm) less than floor-to-ceiling height and spaced 24 in. (610 mm) OC. C. Gypsum Board* - 1 in. (25 mm) thick gypsum liner panels and 1/2 in., 5/8 in. or 3/4 in. (13, 16 or 19 mm) thick gypsum panels installed as specified in the individual U400 or V400 Series shaft wall designs in the UL Fire esistance Directory. The hourly fire rating of the joint system is equal to the hourly fire rating of the wall. 3. Fill, Void or Cavity Material* - Sealant - Max separation between top of floor and bottom of gypsum board on the finish side of wall is 1/2 in. (13 mm). Min 1/2 in. (13 mm) thickness of fill material installed on finish side of the wall between the bottom of the gypsum board and the top of the concrete floor, flush with surface of the finish side of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal ES Sealant, SpecSeal LCI Sealant, SpecSeal LC150 Sealant, Pensil 300 Sealant or SpecSeal Series SIL300 Silicone Firestop Sealant *Bearing the UL Classification Mark eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: January 23, 2014 BW-S-0020 PAGE 1 OF 1

12 System No. WW-D-1090 Ì80WWDÇ*zÈANÇ"<.ÇÎ ANSI/UL2079 Assembly ating - 1 and 2 Hr (See Item 2) Nominal Joint Width - 4 in. (102 mm) Class II Movement Capabilities - 7, 15 and 25 % Compression or Extension (See Item 3) L ating At Ambient - Less Than 1 CFM/sq ft L ating At 400 F - Less Than 1 CFM/sq ft CAN/ULC S115 F ating - 1 and 2 Hr (See Item 2) FT ating - 1 and 2 Hr (See Item 2) FH ating - 1 and 2 Hr (See Item 2) FTH ating - 1 and 2 Hr (See Item 2) Nominal Joint Width - 4 in. (102 mm) Class II Movement Capabilities - 7, 15 and 25 % Compression or Extension (See Item 3) L ating At Ambient - Less Than 1 CFM/sq ft L ating At 400 F - Less Than 1 CFM/sq ft 1 3B 2A 1 3B 2A 3A 2B 3A 2B CONFIGUATION A CONFIGUATION B 1. Wall Assembly - Min 6 in. (152 mm) thick reinforced lightweight or normal weight ( pcf or kg/m3) structural concrete. Additionally, thickness of concrete wall shall be equal to or greater than thickness of gypsum board wall. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CAZT) category in the Fire esistance Directory for names of manufacturers. 2. Wall Assembly - The 1 or 2 h fire-rated gypsum board/steel stud wall assembly shall be constructed of the materials and in the manner specified in the individual U400, V400 or W400 Series Wall and Partition Design in the UL Fire esistance Directory and shall include the following construction features: A. Studs - Min 3-1/2 in. (89 mm) wide steel studs spaced max 24 in. (610 mm) OC. B. Gypsum Board* - The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design in the UL Fire esistance Directory. The hourly ratings of the joint system are equal to the hourly rating of the gypsum wall assembly. CONFIGUATION A 3. Joint - Max width of joint (at time of installation) is 4 in. (102 mm). The joint system is designed to accommodate for various percentages in compression or extension from its installed width depending on the product used (See Table Below). The joint system shall consist of forming and fill materials as follows: eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: February 28, 2014 WW-D-1090 PAGE 1 OF 2

13 A. Forming Material* - Min 4 pcf (64 kg/m3) mineral wool batt insulation installed in joint opening as a permanent form. Pieces of batt cut to min width of 4 in. (102 mm) and installed edge-first into joint opening, parallel with joint direction, such that batt sections are compressed min 50 percent in thickness and such that the compressed batt sections are recessed from each surface of the wall to accommodate the required thickness of fill material (Item 3B). Adjoining lengths of batt to be tightly-butted with butted seams spaced min 16 in. (406 mm) apart along the length of the joint. IIG MINWOOL L L C - MinWool-1200 Safing OCK WOOL MANUFACTUING CO - Delta Board OCKWOOL MALAYSIA SDN BHD - SAFE OXUL INC - SAFE THEMAFIBE INC - Type SAF B. Fill, Void or Cavity Material* Sealant - Min 5/8 in. (16 mm) thickness of fill material installed on each side of the wall between the side of the gypsum board and the face of the concrete wall assembly, flush with each surface of the gypsum wall. SPECIFIED TECHNOLOGIES INC - SpecSeal ES Sealant, SpecSeal LC150 Sealant, SpecSeal LCI Sealant and SpecSeal SIL300 Series Sealant The Movement Capabilities for each product are shown in following table: Product Movement Capabilities, % Compression Extension ES Sealant ES Sealant LC150 Sealant LCI Sealant SIL300 Sealant CONFIGUATION B 3. Joint - Max width of joint (at time of installation) 4 in. (102 mm). The joint system is designed to accommodate a max 25% in compression or extension from its installed width. The joint system shall consist of forming and fill materials as follows: A. Forming Material* - Sections of min 4 pcf (64 kg/m3) density mineral wool batt compressed 50 percent in thickness and installed cut edge first to completely fill the gap between the gypsum board and the concrete wall. The forming material shall be installed flush with both surfaces of wall. IIG MINWOOL L L C - MinWool-1200 Safing OCK WOOL MANUFACTUING CO - Delta Board OCKWOOL MALAYSIA SDN BHD - SAFE OXUL INC - SAFE THEMAFIBE INC - Type SAF B. Fill, Void or Cavity Material* - Sealant - Min 1/16 in. (1.6 mm) dry thickness (1/8 in. or 3.2 mm wet thickness) of fill material spray applied over the forming material (Item 3A) on each side of the wall and overlap a min 1/2 in. (13 mm) onto gypsum board and concrete wall on both sides of the wall. SPECIFIED TECHNOLOGIES INC - SpecSeal AS200 Elastomeric Spray *Bearing the UL Classification Mark eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: February 28, 2014 WW-D-1090 PAGE 2 OF 2

14 System No. WW-D-0103 Ì86WWDÇ!#ÈANÇ"<.iÎ ANSI/UL2079 Assembly ating - 1 and 2 Hr (See Item 2) Nominal Joint Width - 3/4 in. (19 mm) Class II Movement Capabilities - 7, 12.5, 25 and 40 % Compression or Extension (See Item 3) L ating At Ambient - Less Than 1 CFM/sq ft L ating At 400 F - Less Than 1 CFM/sq ft CAN/ULC S115 F ating - 1 and 2 Hr (See Item 2) FT ating - 1 and 2 Hr (See Item 2) FH ating - 1 and 2 Hr (See Item 2) FTH ating - 1 and 2 Hr (See Item 2) Nominal Joint Width - 3/4 in. (19 mm) Class II Movement Capabilities - 7, 12.5, 25 and 40 % Compression or Extension (See Item 3) L ating At Ambient - Less Than 1 CFM/sq ft L ating At 400 F - Less Than 1 CFM/sq ft 2C 2A 2C 2A 3A 1 1 2B 3C 2B 3B CONFIGUATION A CONFIGUATION B 1. Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight ( pcf or kg/m3) structural concrete. 2. Wall Assembly - The 1 or 2 hr fire-rated gypsum board/steel stud wall assembly shall be constructed of the materials and in the manner specified in the individual U400, V400 or W400 Series Wall and Partition Design in the UL Fire esistance Directory and shall include the following construction features: A. Steel unners - Steel runners shall consist of min 25 gauge galv steel channels sized to accommodate steel studs (Item 2B). Steel runner to be provided with 1-1/4 in. (32 mm) flanges. Steel runner secured to concrete wall assembly with steel concrete fasteners spaced 12 in. (305 mm) OC. B. Studs - Steel studs to be min 3-1/2 in. (89 mm) wide. Studs cut 1/2 to 3/4 in. (13 to 19 mm) less in length than the assembly height with the bottom nesting in and resting on floor runner and with the top nesting in the ceiling runner without attachment. First stud adjacent to the concrete wall assembly to be located max 4 in. (102 mm) from the surface of the concrete wall. Stud spacing not to exceed 24 in. (610 mm) OC. C. Gypsum Board* - Gypsum board sheets installed to a min total thickness of 5/8 in. (16 mm) and 1-1/4 in. (32 mm) on each side of wall for 1 and 2 hr fire rated assemblies, respectively. Wall to be constructed as specified in the individual Wall and Partition Design in the UL Fire esistance Directory, except that a max 3/4 in. (19 mm) gap shall be maintained between the side of gypsum board and face of concrete wall assembly. The screws attaching the gypsum board to the first stud shall be located 4 in. (102 mm) from face of concrete wall assembly. Gypsum board not attached to side runner. The hourly ratings of the joint system are equal to the hourly rating of the gypsum wall assembly. eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: February 28, 2014 WW-D-0103 PAGE 1 OF 2

15 CONFIGUATION A 3. Joint - Max separation between the side of the gypsum board and the face of the concrete wall assembly is 3/4 in. (19 mm). The joint system is designed to accommodate for various percentages in compression or extension from its installed width depending on the product used (See Table Below). The joint system shall consist of forming and fill materials as follows: A. Bond Breaker Tape - (Not shown) - Polyethylene tape supplied in rolls. Tape applied to flanges of steel runners (Item 2A) to prevent bonding of the sealant to steel runners. Bond breaker tape is optional when movement capability of the joint is limited to compression only. B. Forming Material - (Optional, Not Shown) - In 2 hr fire rated wall assemblies, foam backer rod friction fit into joint opening and recessed minimum 5/8 in. (16 mm) from each surface of wall. C. Fill, Void or Cavity Material* Sealant - Min 5/8 in. (16 mm) thickness of fill material installed on each side of the wall between the side of the gypsum board and the face of the concrete wall assembly, flush with each surface of the gypsum wall. SPECIFIED TECHNOLOGIES INC - SpecSeal ES Sealant, SpecSeal LC150 Sealant, SpecSeal LCI Sealant and SpecSeal SIL300 Series Sealant The Movement Capabilities for each product are shown in following table: Product Movement Capabilities Compression % Extension % ES Sealant ES Sealant LC150 Sealant LCI Sealant SIL300 Sealant SIL300 Sealant 25 0 CONFIGUATION B 3. Joint - Max separation between the side of the gypsum board and the face of the concrete wall assembly is 3/4 in. (19 mm). The joint system is designed to accommodate a max 40% compression or extension from its installed width. The joint system shall consist of forming and fill materials as follows: A. Forming Material* - Sections of min 4 pcf (64 kg/m3) density mineral wool batt compressed 50 percent in thickness and installed cut edge first to completely fill the gap between the gypsum board and the concrete wall. The forming material shall be installed flush with both surfaces of wall. IIG MINWOOL L L C - MinWool-1200 Safing OCK WOOL MANUFACTUING CO - Delta Board OCKWOOL MALAYSIA SDN BHD - SAFE OXUL INC - SAFE THEMAFIBE INC - Type SAF B. Fill, Void or Cavity Material* - Sealant - Min 1/16 in. (1.6 mm) dry thickness (1/8 in. or 3.2 mm wet thickness) of fill material spray applied over the forming material (Item 3A) on each side of the wall and overlap a min 1/2 in. (13 mm) onto gypsum board and concrete wall on both sides of the wall. SPECIFIED TECHNOLOGIES INC - SpecSeal AS200 Elastomeric Spray *Bearing the UL Classification Mark eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: February 28, 2014 WW-D-0103 PAGE 2 OF 2

16 PODUCT DATA SHEET SEIES LC ENDOTHEMIC SEALANT APPLICATIONS SpecSeal Series LC Sealant is designed primarily for sealing construction joints and gaps as well as penetrations for noncombustible penetrants. SpecSeal Series LC has been tested and approved for single metallic pipe penetrations up to 24" (610 mm) as well as multiple penetrants through both masonry and gypsum wallboard constructions. Additional systems have been tested for steel sleeved penetrations as well as some common electrical and communications cable penetrations and joint penetrations. See STI s Product & Application Guide as well as the UL Fire esistance Directory for complete listings. PODUCT DESCIPTION SpecSeal Series LC Sealant is a latex-based, high solids firestop compound. This material, when properly installed, will effectively seal penetration openings and joints against the spread of fire, smoke, toxic gasses and water. SpecSeal Series LC Sealant is engineered to adhere well to virtually all construction surfaces and may be applied using a standard caulk gun or by troweling with a standard mason s trowel or with a putty knife. SpecSeal Series LC Sealant dries without shrinking to form a flexible shield against the propagation of fire. Its premium latex binder system is totally resistant to water and will not re-emulsify after drying. SpecSeal Series LC Sealant is non-halogenated, contains no asbestos, inorganic fibers or solvents. FEATUE BENEFIT Water-Based Endothermic Fillers High Solids Formula Paintable Safe... No Solvents! ed Color Installer Friendly Excellent Smoke Seal Easy installation, cleanup, and disposal. Absorb heat & release water. No shrinkage! Paintable (when dry) Non-Halogenated! Low VOC s Easy identification and inspection. Excellent caulking properties along with high build capabilities. Flexible PEFOMANCE SpecSeal Series LC Sealant is the basis for systems that meet the exacting criteria of ASTM E1966 (UL2079) as well as the time-temperature requirements of ASTM E119. Tested systems will provide up to a 3 hour rating utilizing as little as 1/4" (6 mm) of sealant depth (1/2" (13 mm) for 4 hours). 3L73 FILL, VOID O CAVITY MATEIALS FO USE IN JOINT SYSTEMS AND THOUGH-PENETATION FIESTOP SYSTEMS. SEE UL DIECTOY OF PODUCTS CETIFIED FO CANADA AND UL FIE ESISTANCE DIECTOY. PHYSICAL POPETIES Properties Series LC Color ed Odor Mild Latex Density 11.4 lb./gal. Solids Content 80% + 2% ph In Service Temperature 185 F (<85 C) SPECIFICATIONS The firestopping sealant shall be a one-part, latex-based compound. The sealant shall dry to form a flexible non-shrinking penetration seal and shall be capable of allowing pipe movement and shall contain no solvents, water soluble fillers, or inorganic fibers. The sealant shall be thixotropic and shall be capable of caulking or troweling on to vertical surfaces or overhead. The sealant shall be UL Classified and tested to the requirements of ASTM E814 (UL1479). SPECIFIED DIVISIONS Storage Temperature 40 F (4 C) - 95 F (35 C) DIV Through-Penetration Firestopping Flame Spread 0* Smoke Developed 10* STC ating (ASTM E90/ASTM C919) 61 VOC Content (EPA Method 24/ASTM D3960) Shelf Life 0.33 lb/gal.(40 g/l) 2 Years *ASTM E84 14% Surface coverage. (Modified test for sealants and caulks.) DIV DIV DIV Special Construction Fire Suppression & Supervisory Systems Mechanical Insulation Fire Protection Basic Electrical Materials & Methods Technical Service STI Product Data Sheet Series LC Endothermic Sealant FOD /2010 1

17 INSTALLATION INSTUCTIONS GENEAL: Areas to be protected must be clean and free of oil, loose dirt, rust or scale. Installation temperatures must be between 35 F (2 C) and 100 F (38 C). Allow product to dry a minimum of 24 hours before exposure to moisture. SYSTEM SELECTION: Consult UL Fire esistance Directory, STI Product & Application Guide, or drawings provided by the manufacturer for specific details concerning installation design and requirements. FOMING: Some installations may require forming as either an integral part of the system or as an option to facilitate installation. In systems where forming is required, mineral wool batting (3" (76 mm) nom. thickness, min. 4 lb./cu. ft. 64 kg/m 3 density) is recommended. Mineral wool is to be highly compressed and friction fitted into the opening. Position forming or packing material to allow for the proper depth of fill material. INSTALLATION OF FILL MATEIAL: SpecSeal Series LC sealant may be installed by caulking using a standard caulking gun or from bulk containers using a bulk loading caulk gun, or by manually troweling using a mason s trowel or putty knife. If the sealant tends to pull back from a surface, clean the surface with a damp rag or sponge and reapply. Install sealant to required depth. Work sealant into all areas exercising care to eliminate voids or seams. The surface of the sealant can be smoothed using a putty knife dipped in water. Adding water to the sealant itself is not recommended. Sealant (when dry) may be sanded and painted using most non-solvent based paints. In gypsum wallboard penetrations, crown sealant a minimum of 1/4" (6 mm) from penetrant to wallboard surface at a point approx. 1/2" (13 mm) or more from opening. COVE PLATE: In some designs a galvanized steel cover plate (28 gauge) may be used to upgrade the fire resistance rating to 4 hours. Consult STI Product and Application Guide for dimensional and fastening requirements. LIMITATIONS: SpecSeal Series LC Sealant is water-based and cures through the evaporation of water. Low temperatures as well as high humidity may retard drying. Non-porous or impermeable backing materials, plates or coatings may retard the drying process. Do not paint or seal in any way that prevents contact with air until sealant has dried through completely. MAINTENANCE Inspection: Installations should be inspected periodically for subsequent damage. Any damage should be repaired using SpecSeal Series LC Sealant as per the original approved design. etrofit: When adding or removing penetrants, care should be taken to minimize damage to the seal. eseal using SpecSeal Series LC Sealant as per the approved design. NOTE: New penetrants of a different nature than the original design may require a totally new firestop design or extensive modifications to the existing design. eseal openings as per the requirements of the modified design. TECHNICAL SEVICE Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL Systems, Material Safety Data Sheets and other technical information is available at the Technical Library at PECAUTIONAY INFOMATION Consult Material Safety Data Sheet for additional information on the safe handling and disposal of this material. Wash areas of skin contact with soap and water. Avoid contact with eyes. The use of an OSHA or NIOSH approved mask for dust and mist environment is recommended. Apply in areas with adequate ventilation. CAUTION: COATING IS CONDUCTIVE UNTIL DY. DO NOT APPLY TO O IN THE PESENCE OF ENEGIZED ELECTICAL CONDUCTOS. AVAILABILITY SpecSeal Series LC Sealant is available from authorized distributors worldwide. Consult factory for names and locations of the nearest sales representatives or distributors. Cat. No. Description Packaging Size LC150 Endothermic Firestop Sealant 10.1 oz. Tube 18.2 cu in. (300 ml) LC120 Endothermic Firestop Sealant 20 oz. Sausage 36 cu. in. (592 ml) LC129 Endothermic Firestop Sealant 29 oz. Tube 52 cu. in. (858 ml) LC155 Endothermic Firestop Sealant 5 gal. Pail 1,155 cu. in. (19 liters) CITY OF NEW YOK MEA M IMPOTANT NOTICE: All statements, technical information, and recommendations contained herein are based upon testing believed to be reliable, but the accuracy and completeness thereof is not guaranteed. WAANTY Specified Technologies Inc. manufactures its goods in a manner to be free of defects. Should any defect occur in its goods (within one year), Specified Technologies Inc., upon prompt notification, will at its option, exchange or repair the goods or refund the purchase price. LIMITATIONS AND EXCLUSIONS: THIS WAANTY IS IN LIEU OF ALL OTHE EPESENTATIONS EXPESSED O IMPLIED (INCLUDING THE IMPLIED WAANTIES OF MECHANTABILITY O FITNESS FO USE) AND UNDE NO CICUMSTANCES SHALL SPECIFIED TECHNOLOGIES INC. BE ESPONSIBLE FO ANY INCIDENTAL O CONSEQUENTIAL POPETY DAMAGE O LOSSES. PIO TO USE, THE USE SHALL DETEMINE THE SUITABILITY OF THE PODUCT FO ITS INTENDED USE, AND THE USE ASSUMES ALL ISKS AND LIABILITY FO SUBSEQUENT USE. No statement or recommendation not contained herein shall have any force or effect unless in an agreement signed by officers of seller and manufacturer. MADE IN THE USA COPYIGHT 2008 SPECIFIED TECHNOLOGIES, INC. 210 Evans Way Somerville, NJ Toll Free: F: STI Product Data Sheet Series LC Endothermic Sealant FOD /2010 Technical Service