PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED

Size: px
Start display at page:

Download "PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED"

Transcription

1 Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B Ontario-NBC CODE REFERENCE: Division B / DESCRIPTION OF THE PROPOSED AMENDMENT This proposed change would harmonize for loads due to snow and rain requirements with the model National Building Code of Canada. EXISTING 2012 BUILDING CODE PROVISION(S) Loads Due to Snow and Rain Specified Load Due to Rain or to Snow and Associated Rain (1) The specified load on a roof or any other building surface subject to snow and associated rain shall be the snow load specified in Article , or the rain load specified in Article , whichever produces the more critical effect Specified Snow Load (See Appendix A.) (1) The specified load, S, due to snow and associated rain accumulation on a roof or any other building surface subject to snow accumulation shall be calculated from the formula, where, S = I s [S s (C b C w C s C a ) + S r ] I s = importance factor for snow load as provided in Table , S s = 1-in-50-year ground snow load, in kpa, determined in accordance with Subsection , C b = basic roof snow load factor in Sentence (2), C w = wind exposure factor in Sentences (3) and (4), C s = slope factor in Sentences (5), (6) and (7), C a = shape factor in Sentence (8), and S r = 1-in-50-year associated rain load, in kpa, determined in accordance with Subsection , but not greater than S s (C b C w C s C a ). Building and Development Branch Page 1

2 Table Importance Factor for Snow Load, IS Forming Part of Sentence (1) Importance Category Importance Factor, Is ULS SLS Low Normal High Post-disaster Column (2) The basic roof snow load factor, C b, shall be 0.8, except that for large roofs it shall be, (a) 1.0 (30/l c ) 2, for roofs with C w = 1.0 and l c greater than or equal to 70 m, or (b) 1.3 (140/l c ) 2, for roofs with C w = 0.75 or 0.5 and l c greater than or equal to 200 m, where, l c = characteristic length of the upper or lower roof, defined as 2w-w²/l, in metres, w = smaller plan dimension of the roof, in metres, l = larger plan dimension of the roof, in metres. (3) Except as provided for in Sentence (4), the wind exposure factor, C w, shall be 1.0. (4) For buildings in the Low and Normal Importance Categories as set out in Table B., the wind exposure factor given in Sentence (3) may be reduced to 0.75, or to 0.5 in exposed areas north of the treeline, where, (a) the building is exposed on all sides to wind over open terrain as defined in Clause (5)(a), and is expected to remain so during its life, (b) the area of roof under consideration is exposed to the wind on all sides with no significant obstructions on the roof, such as parapet walls, within a distance of at least 10 times the difference between the height of the obstruction and C b C w S s /γ metres, where γ is the unit weight of snow on roofs, and (See Appendix A.) (c) the loading does not involve the accumulation of snow due to drifting from adjacent surfaces. (5) Except as provided for in Sentences (6) and (7), the slope factor, C s, shall be, (a) 1.0 where the roof slope, α, is equal to or less than 30, (b) (70 - α)/40 where α is greater than 30 but not greater than 70, and (c) 0 where α exceeds 70. (6) The slope factor, C s, for unobstructed slippery roofs where snow and ice can slide completely off the roof shall be, (a) 1.0 when the roof slope, α, is equal to or less than 15, (b) (60 - α)/45 when α is greater than 15, but not greater than 60, and (c) 0 when α exceeds 60. (7) The slope factor, C s, shall be 1.0 when used in conjunction with shape factors for increased snow loads as given in Clauses (8)(b) and (e). (8) The shape factor, C a, shall be 1.0, except that where appropriate for the shape of the roof, it shall be assigned other values that account for, (a) non-uniform snow loads on gable, arched or curved roofs and domes, (b) increased snow loads in valleys, (c) increased non-uniform snow loads due to snow drifting onto a roof that is at a level lower than other parts of the same building or at a level lower than another building within 5 m of it, Building and Development Branch Page 2

3 (d) increased non-uniform snow loads on areas adjacent to roof projections, such as penthouses, large chimneys and equipment, and (e) increased snow or ice loads due to snow sliding or meltwater draining from adjacent roofs Full and Partial Loading (1) A roof or other building surface and its structural members subject to loads due to snow accumulation shall be designed for the specified load in Sentence (1), distributed over the entire loaded area. (2) In addition to the distribution in Sentence (1), flat roofs and shed roofs, gable roofs of 15 slope or less, and arched or curved roofs shall be designed for the specified uniform snow load indicated in Sentence (1), which shall be calculated using C a = 1.0, distributed on any one portion of the loaded area, and half of this load on the remainder of the loaded area, in such a way as to produce the most critical effects on the member concerned. (See Appendix A.) Specified Rain Load (1) Except as provided in Sentence (4), the specified load, S, due to the accumulation of rainwater on a surface whose position, shape and deflection under load make such an accumulation possible, is that resulting from the one-day rainfall determined in conformance with Subsection and applied over the horizontal projection of the surface and all tributary surfaces. (See Appendix A.) (2) The provisions of Sentence (1) apply whether or not the surface is provided with a means of drainage, such as rainwater leaders. (3) Except as provided for in Sentence (1), loads due to rain need not be considered to act simultaneously with loads due to snow. (See Appendix A.) (4) Where scuppers are provided and where the position, shape and deflection of the loaded surface make an accumulation of rainwater possible, the loads due to rain shall be the lesser of either the one-day rainfall determined in conformance with Subsection or a depth of rainwater equal to 30 mm above the level of the scuppers, applied over the horizontal projection of the surface and tributary areas. A Coefficients for Snow Loads on Roofs. Information on coefficients for snow loads on roofs can be found in the Commentary entitled Snow Loads in the User s Guide - NBC 2010, Structural Commentaries (Part 4 of Division B). A (4)(b) Unit Weight of Snow. Information on the unit weight of snow can be found in the Commentary entitled Snow Loads in the User s Guide - NBC 2010, Structural Commentaries (Part 4 of Division B). A (2) Full and Partial Loading under Snow Loads. Information on full and partial snow loading on roofs can be found in the Commentary entitled Snow Loads in the User s Guide - NBC 2010, Structural Commentaries (Part 4 of Division B). A (1) Rain Loads. Information on rain loads can be found in the Commentary entitled Rain Loads in the User s Guide - NBC 2010, Structural Commentaries (Part 4 of Division B). A (3) Flow Control Drains. Part 7 contains requirements regarding the use of flow control roof drains. The designer must ensure that the building complies with both Part 4 and Part 7. Building and Development Branch Page 3

4 PROPOSED CODE CHANGE Revise existing Sentence (2) and its related appendix note as follows: Loads Due to Snow and Rain Specified Load Due to Rain or to Snow and Associated Rain (1) The specified load on a roof or any other building surface subject to snow and associated rain shall be the snow load specified in Article , or the rain load specified in Article , whichever produces the more critical effect Specified Snow Load (See Appendix A.) (1) The specified load, S, due to snow and associated rain accumulation on a roof or any other building surface subject to snow accumulation shall be calculated from the formula, where, S = I s [S s (C b C w C s C a ) + S r ] I s = importance factor for snow load as provided in Table , S s = 1-in-50-year ground snow load, in kpa, determined in accordance with Subsection , C b = basic roof snow load factor in Sentence (2), C w = wind exposure factor in Sentences (3) and (4), C s = slope factor in Sentences (5), (6) and (7), C a = shape accumulation factor in Sentence (8), and S r = 1-in-50-year associated rain load, in kpa, determined in accordance with Subsection , but not greater than S s (C b C w C s C a ). Table Importance Factor for Snow Load, IS Forming Part of Sentence (1) Importance Category Importance Factor, Is ULS SLS Low Normal High Post-disaster Column (2) The basic roof snow load factor, C b, shall be 0.8, except that for large roofs it shall be, (a) 1.0 (30/l c ) 2, for roofs with C w = 1.0 and l c greater than or equal to 70 m, or (b) 1.3 (140/l c ) 2, for roofs with C w = 0.75 or 0.5 and l c greater than or equal to 200 m, where, l c = characteristic length of the upper or lower roof, defined as 2w-w²/l, in metres, w = smaller plan dimension of the roof, in metres, l = larger plan dimension of the roof, in metres. Building and Development Branch Page 4

5 (3) Except as provided for in Sentence (4), the wind exposure factor, C w, shall be 1.0. (4) For buildings in the Low and Normal Importance Categories as set out in Table B., the wind exposure factor given in Sentence (3) may be reduced to 0.75 in rural areas only, or to 0.5 in exposed areas north of the treeline, where, (a) the building is exposed on all sides to wind over open terrain as defined in Clause (5)(a), and is expected to remain so during its life, (b) the area of roof under consideration is exposed to the wind on all sides with no significant obstructions on the roof, such as parapet walls, within a distance of at least 10 times the difference between the height of the obstruction and C b C w S s /γ metres, where γ is the unit weight of snow on roofs as specified in Article , and (c) the loading does not involve the accumulation of snow due to drifting from adjacent surfaces. (5) Except as provided for in Sentences (6) and (7), the slope factor, C s, shall be, (a) 1.0 where the roof slope, α, is equal to or less than 30, (b) (70 - α)/40 where α is greater than 30 but not greater than 70, and (c) 0 where α exceeds 70. (6) The slope factor, C s, for unobstructed slippery roofs where snow and ice can slide completely off the roof shall be, (a) 1.0 when the roof slope, α, is equal to or less than 15, (b) (60 - α)/45 when α is greater than 15, but not greater than 60, and (c) 0 when α exceeds 60. (7) Unless otherwise stated in this Subsection, Tthe slope factor, C s, shall be 1.0 when used in conjunction with shape accumulation factors for increased snow loads as given in Clauses (8)(b) and (e). (8) The shape accumulation factor, C a, shall be 1.0, corresponding to the uniform snow load case, except that where appropriate for the shape of the roof, it shall be assigned other values that account for, (a) non-uniform snow loads on gable, arched or curved roofs and domes, increased non-uniform snow loads due to snow drifting onto a roof that is at a level lower than other parts of the same building or at a level lower than another building within 5 m of it, as specified in Articles , and (b) increased snow loads in valleys, increased non-uniform snow loads on areas adjacent to roof projections, such as penthouses, large chimneys and equipment, as prescribed in Articles and (c) increased non-uniform snow loads due to snow drifting onto a roof that is at a level lower than other parts of the same building or at a level lower than another building within 5 m of it, non-uniform snow loads on gable, arched or curved roofs and domes, as prescribed in Articles and (d) increased non-uniform snow loads on areas adjacent to roof projections, such as penthouses, large chimneys and equipment, and increased snow or ice loads due to snow sliding as prescribed in Article (e) increased snow or ice loads due to snow sliding or meltwater draining from adjacent roofs. Increased snow loads in roof valleys, as prescribed in Article , and (f) increased snow or ice loads due to snow sliding or meltwater draining from adjacent building elements and roof projections. (9) For shapes not addressed in Sentence (8), C a corresponding to the non-uniform snow load case shall be established based on applicable field observations, special analyses including local climatic effects, appropriate model tests or a combination of these methods Full and Partial Loading (1) A roof or other building surface and its structural members subject to loads due to snow accumulation shall be designed for the specified load in Sentence (1), distributed over the entire loaded area. (2) In addition to the distribution in Sentence (1), flat roofs and shed roofs, gable roofs of 15 slope or less, and arched or curved roofs shall be designed for the specified uniform snow load indicated in Sentence (1), which shall be Building and Development Branch Page 5

6 calculated using C a = 1.0, distributed on any one portion of the loaded area, and half of this load on the remainder of the loaded area, in such a way as to produce the most critical effects on the member concerned. (See Appendix A.) Specified Rain Load (1) Except as provided in Sentence (4), the specified load, S, due to the accumulation of rainwater on a surface whose position, shape and deflection under load make such an accumulation possible, is that resulting from the one-day rainfall determined in conformance with Subsection and applied over the horizontal projection of the surface and all tributary surfaces. (See Appendix A.) (2) The provisions of Sentence (1) apply whether or not the surface is provided with a means of drainage, such as rainwater leaders. (3) Except as provided for in Sentence (1), loads due to rain need not be considered to act simultaneously with loads due to snow. (See Appendix A.) (4) Where scuppers are provided and where the position, shape and deflection of the loaded surface make an accumulation of rainwater possible, the loads due to rain shall be the lesser of either the one-day rainfall determined in conformance with Subsection or a depth of rainwater equal to 30 mm above the level of the scuppers, applied over the horizontal projection of the surface and tributary areas Multi-Level Roofs (1) The drifting load of snow on a roof adjacent to a higher roof shall be taken as trapezoidal as shown in Figure A, where the accumulation factor is C a = C a0 (C a0 1)(x/x d ) for 0 x x d or where C a = 1.0 for x > x d C a0 = peak value of C a at x=0 as specified in Sentences (3) and (4) and as shown in Figure A, x = distance from roof step as shown in Figure A, and x d = length of drift as specified in Sentence (2) and as shown in Figure A. (2) The length of the drift, x d, shall be calculated as follows: Where x d = 5 C bs s γ (C a0 1) γ = specific weignt of snow as specified in Article (3) The value of C a0 for Cases I, II, and III shall be the lesser of C a0 = β γh C b S s and C a0 = F C b Building and Development Branch Page 6

7 Where β = 1.0 for Case I, and 0.67 for Cases II and III, and h = difference in elevation between the lower roof surface and the top of the parapet on the upper roof as shown in Figure A, F = 0.35β γ l cs 5h p S s + C b, but F 5 for C ws = 1.0 where C ws = value for C w applicable to the source of drifting, l cs = the characteristic length of the source area for drifting, defined as l cs = 2w s w s 2 U, where and l s are respectively the shorter and longer dimensions of the relevant source areas for snow drifting shown in Figure B. for Cases I, II, and III. h p = h p 0.8S γ, but 0 h p l cs 5 l s where h p = height of the roof perimeter parapet of the source area, to be taken as zero unless all the roof edges of the source area have parapets, (4) The value of C a0 shall be the highest of Cases I, II and III, considering the different roof source areas for drifting snow, as specified in Sentence (3) and Figure B. Figure A Snow Load Factors for Lower Level Roofs Forming Part of Sentence (1), (3), and (1) Notes to Figure A: IMAGE REQUIRED (1) If a > 5 m or h 0.8S s /γ, drifting from the higher roof need not be considered. (2) For lower roofs with parapets, C s = 1.0, otherwise it varies as a function of slope α as defined in Sentences (5) and (6). Building and Development Branch Page 7

8 Figure B. Snow Load Factors for Lower Level Roofs Forming Part of Sentence (1), (3), and (4) IMAGE REQUIRED Horizontal Gap between a Roof and a Higher Roof (1) Where the roof of one building is separated by a distance, a, from an adjacent building with a higher roof as shown in Figure A, the influence of the adjacent building on the value of the accumulation factor, C a, for the lower roof shall be determined as follows: (a) if a > 5 m, the influence of the adjacent building can be ignored on C a for the lower, and (b) if a <5 m, the influence of C a for the lower roof shall be calculated in accordance with Article for values of x a Areas Adjacent to Roof Projections (1) Except as provided in Sentences (2) and (3), the accumulation factor, C a, for areas adjacent to roof-mounted vertical projections shall be calculated in accordance with Sentence (1), using the following values for the peak accumulation factor, C a0, and the drift length, x d : (a) C a0 shall be taken as the lesser of 0.67 γh γl and 0 + 1, and C b S s 7.5C b S s (b) x d shall be taken as the lesser of 3.35h and (2/3)l 0, where See Appendix A. h = height of the project, and l 0 = longest horizontal dimension of the projection. (2) C a is permitted to be calculated in accordance with Article for longer projections. (See Appendix A.) (3) Where the longest horizontal dimension of the roof projection, l 0, is less than 3 m, the drift surcharge adjacent to the projection need not be considered Snow Drift at Corners (1) The drift loads on the lower level roof against the two faces of an outside corner of an upper level roof or roof obstruction shall be extended radially around the corner as shown in Figure A and may be taken as the least severe of the drift loads lying against the two faces of the corner. (2) The drift loads on the lower level roof against the two faces of an inside corner of an upper level roof or a parapet shall be calculated for each face and applied as far as the bisector of the corner angle as shown in Figure B. Building and Development Branch Page 8

9 Figure A Snow Load at outside corner Forming Part of Sentence (1) IMAGE REQUIRED Figure B Snow Load at inside corner Forming Part of Sentence (2) IMAGE REQUIRED Gable Roofs (See Appendix A.) (1) For all gable roofs, the full and partial load cases defined in Article shall be considered. (2) For gable roofs with slope, α > 15, the unbalanced load case shall also be considered by setting the values of the accumulation factor, C a, as follows: (a) on the upwind side of the roof peak, C a shall be taken as 0, and (b) on the downwind side of the roof peak, C a shall be taken as (i) α/20, where 15 α 20, and (ii) 1.25, where 20 < α 90. (3) For all gable roofs, the slope factor, C s, shall be as prescribed in Sentences (5) and (6). (4) For all gable roofs, the wind exposure factor, C w, shall be (a) as per Sentences (3) and (4) for the full and partial load cases, and (b) 1.0 for the unbalanced load case referred to in Sentence (2) Arch Roofs, Curved Roofs and Domes (1) For all arch roofs, curved roofs and domes, the full and partial load cases defined in Article shall be considered. (2) For arch roofs, curved roofs and domes with rise-to-span ratio h/b > 0.05 (see Figure A), the load cases provided in Sentences (3) to (7) shall also be considered. Building and Development Branch Page 9

10 (3) For arch roofs with a slope at the edge α e 30 (see Figure A and Table ), C a, shall be (a) taken as 0 on the upwind side of the peak, and (b) on the downwind side of the peak, taken as xh C a = for 0.05 < h 0.12 and 0.03C b b 2 b C a = 4x for h > 0.12 C b b b where x = horizontal distance from the roof peak, h = height of arch, and b = width of arch. Figure A Accumulation factors for arch roofs and curved roofs Forming Part of Sentence (2) to (4) IMAGE REQUIRED Note to Figure: (1) Refer to Table for applicable values of C w and Sentences (5) and (6) for applicable values of C s. (4) For arch roofs with slope at the edge α e > 30 (see Figure A and Table ), C a, shall be (a) taken as 0 on the upwind side of the peak, and (b) on the downwind side of the peak, (i) for the part of the roof between the peak and point where the slope α = 30, taken as xh C a = for 0.05 < h 0.12, and 0.06C b x 30 b b 2x C a = for h > 0.12 C b x 30 b where x, h, b = as specified in Sentence (2), and x 30 = value of x where the slope α = 30, and (ii) for the part of the roof where the slope α >30, taken as h C a = for 0.05 < h 0.12, and 0.06C b b b C a = 2 for h > 0.12 C b b (5) Except as provided in Sentence (6), C a for curved roofs shall be determined in accordance with the requirements for arch roofs stated in Sentences (3) and (4). Building and Development Branch Page 10

11 (6) Where the slope, α, of a curved roof at its peak is greater than 10, C a shall be determined in accordance with the requirements for gable roofs stated in Article using a slope equal to the mean slope of the curved roof. (7) For domes of circular plan form (see Figure B), C a shall (a) along the central axis parallel to the wind, vary in the same way as for an arch roof with the same rise-to-span ratio, h/b, and (b) off this axis, vary according to C a (x,y) = C a (x,0) 1 y r where C a (x,y) = value of C a at location (x,y), C a (x,0) = value of C a on the central axis parallel to the wind, x = distance along the central axis parallel to the wind, y = horizontal coordinate normal to the x direction, and r = radio of dome. (8) For all arch roofs, curved roofs and domes, the slope factor, C s, shall be as prescribed in Sentences (5) and (6). (9) For all arch roofs, curved roofs and domes, the wind exposure factor, C w, shall be as prescribed in Table Figure B Unbalanced snow accumulation factor on a circular dome Forming Part of Sentence (7) IMAGE REQUIRED Note to Figure: (1) Refer to Table for applicable values of Cw and Sentences (5) and (6) for applicable values of Cs. (2) Refer to Sentences (3) and (4) for the calculation of Ca(x,0). Building and Development Branch Page 11

12 Table Load Cases for Arch Roofs, Curved Roofs and Domes Load Case Range of application All Factors Arch and Curved Roofs C w C a C a C a Upwind Side Downwind Side Downwind Side Case I All values of h/b As stated by Sentences (3)and (4) Slope at edge 30 h/b > 0.05 all values of x C a = xh 0.03C b b 2 for h b 0.12 C a = 4x C b b for h b > 0.12 Case II Slope at edge>30 h/b > < x <x xh C a = for h C b x 30 b b 2x C a = for h > 0.12 C b x 30 b C a (x,y) = C a (x,0) 1 y r Slope at edge>30 h/b >0.05 x 30 x C a = xh 0.06C b b for h b 0.12 C a = 2 C b for h b > Snow Loads Due to Sliding (1) Except as provided in Sentence (2), when an upper roof, or part thereof, slopes downwards with a slope α > 0 towards a lower roof, the snow load, S, on the lower roof, determined in accordance with Articles and shall be augmented according to Sentence (3) to allow for the additional load resulting from sliding snow. (2) Sentence (1) need not apply where (a) sliding from the upper roof is prevented by a parapet or other effective means, or (b) the upper roof is not considered slippery and has an angle of slope less than 20 (3) The total weight of additional snow resulting from sliding shall be taken as half the total weight of snow resulting from the uniform load case prescribed in Article (a) the accumulation factor C a = 1.0 for the relevant part of the upper roof, (b) the slope factor, C s, based on the slope of the lower roof, as prescribed in Sentences (5) and (6), and Building and Development Branch Page 12

13 (c) the sliding snow distributed on the lower roof such that it is a maximum for x = 0 and decreases linearly to 0 at x = x d, as shown in Figure , where x and x d are as defined in Article Figure Snow distribution on lower roof with sloped upper roof Forming Part of Sentence (3) IMAGE REQUIRED Valleys in Curved or Sloped Roofs (1) For valleys in curved or sloped roofs with slope greater α >10, in addition to the full and partial load cases defined in Article , the non-uniform load cases II and III in Sentences (2) and (3) shall be considered to account for sliding, creeping and movement of meltwater. (2) For case II (see Figure ), the accumulation factor, C a, shall be calculated as follows: where C a = 1 for 0 < x b 4, and C b C a = 0.5 for b 4 < x b 2 C b x = horizontal distance from the bottom of the valley, and b = twice the horizontal distance between the bottom of the valley and the peak of the roof surface in question. (3) For case III (see Figure ), C a shall be calculated as follows: C a = 1.5 for 0 < x b 8, and C b C a = 0.5 for b 8 < x b 2 C b where x and b re defined in Sentence (2) Building and Development Branch Page 13

14 Figure Snow loads in valleys of sloped or curved roofs Forming Part of Sentence (2) and (3) Note to Figure: (1) C W = 1, as per Sentence (3).. (2) C S = 1, as per Sentence (7). IMAGE REQUIRED Specific Weight of Snow (1) For the purposes of calculating snow loads in drifts, the specific weight of snow, γ, shall be taken as the lesser of γ = 4.0 kn/m 3, and Snow Removal γ = 0.43S S kn/m 3 (1) Snow removal by mechanical, thermal, manual or other systems and procedures implemented for this purpose shall not be used as the basis to reduce design snow loads Ice Loading of Structures (1) For lattice structures connected to the building, and other building components or appurtenances involving small width elements subject to significant ice accretion, the weight of ice accretion and the effective area presented to wind shall be as prescribed in CSA S37, Antennas, Towers, and Antenna-Supporting Structures.. A (4)(b) Unit Weight of Snow. Information on the unit weight of snow can be found in the Commentary entitled Snow Loads in the User s Guide - NBC 2010, Structural Commentaries (Part 4 of Division B). A (2) Basic Roof Snow Load Factor. Figure A (2) shows the basic roof snow load factor, C b, plotted against l c C 2 w. Figure A (2) Basic roof snow load factor, Cb IMAGE REQUIRED A (1) Roof Projections. Elevator, air-conditioning and fan housings, small penthouses and wide chimneys are examples of roof projections. A (1) Figure A (1) IMAGE REQUIRED Building and Development Branch Page 14

15 A (2) Values of Ca for Small Roof Projections. Calculating C a in accordance with Article rather than Sentence (1) results in lower values for small projections. A Snow on Gable Roofs. Figure Figure A Load Cases for Gable Roofs IMAGE REQUIRED Notes to Figure : (1) Case II loading does not apply to gable roofs with slopes of 15 or less, to single-sloped (shed) roofs, or to flat roofs.. (2) The value of Cw for load case I is as prescribed in Sentences (3) and (4). (3) Varies as a function of slope,, as defined in Sentences (5) and (6). RATIONALE FOR CHANGE Problem/General Background Article Commentary material is being transferred to the code, and the provision allowing the reduced exposure factor is not tied to the material. The reduced wind exposure factor should not be used in urban areas as it is unlikely that the building will be exposed on all sides to wind over open terrain over its expected service life. Commentary material is being transferred to the Code, and the provision for the slope factor to be used for increased snow loads due to roof shape is not tied to the material. Commentary material is being transferred to the code, and the provision for the shape factor is not tied to the material. There is no provision dealing with roof shapes not explicitly addressed. Article The material on snow design for multi-level roofs is in the Part 4 User's Guide. Article The material on snow design for adjacent roofs with a gap between them is in the Part 4 User's Guide. Article The material on snow design for roofs with obstructions is in the Part 4 User's Guide. Article Designers must extrapolate the snow accumulation from a higher roof to a lower roof around corners. Building and Development Branch Page 15

16 Article The material on snow design for gable roofs is in the Part 4 User's Guide. Article The material on snow design for arch roofs, curved roofs and domes is in the Part 4 User's Guide. Article The material on snow design for sliding snow is in the Part 4 User's Guide, and has some guidance that is not specific. Article The material on snow design for valleys is in the Part 4 User's Guide. Article The density of snow in an area of snow build up is not the same as an area of uniform snow accumulation, and it varies with the depth of the snow build up. Article The material on snow removal is in the Part 4 User's Guide. Article There is no design criteria in the code for ice loading on lattice structures. Justification/Explanation This proposed change would harmonize requirements with the model National Building Code of Canada. Article Provide references to the new material and restrict the use of the lower factor to rural areas. Revise to be compatible with the transferred commentary material. Article Transfer it into the body of the code. Article Transfer it into the body of the code. Article Transfer it into the body of the code. Building and Development Branch Page 16

17 Article Provide explicit guidance. Article Transfer it into the body of the code. Article Transfer it into the body of the code. Article Transfer it into the body of the code and enhance the transferred material by providing specific design criteria. Article Transfer it into the body of the code. Article Define a specific gravity in areas of snow build up as a function of the snow depth. Article Transfer it into the body of the code. Article Introduce a requirement Cost/Benefit Implications Article None any costs are applicable to the referenced provisions. None typically building officials do not allow the use of the lower factor in urban areas. Article Article Article Building and Development Branch Page 17

18 Article Article Article Article Article Article None. Article Transfer it into the body of the code. Article None designers already use the CSA S37 standard for this application. Enforcement Implications Article Facilitates enforcement by providing clearer application Article Article Article Article Building and Development Branch Page 18

19 Article Article Article Article Article None. Article Transfer it into the body of the code. Article None designers already use the CSA S37 standard for this application. Who is Affected Building officials, consultants, builders, building owners Objective Based Analysis Provision Objective/Functional Statement Division B Specified Snow Load (2) [F20-OS2.1] Building and Development Branch Page 19

20 Provision Objective/Functional Statement (3) [F20-OS2.1] (4) (5) [F20-OS2.1] (6) [F20-OS2.1] (7) [F20-OS2.1] (8) [F20-OS2.1] Applies to portion of Code text: The shape accumulation factor, C a, shall be 1.0, Applies to portion of Code text: The shape accumulation factor, C a, shall be 1.0, [a] to [e] [F20-OS2.1] Applies to roof shapes and configurations that call for a higher shape accumulation factor. [a] to [e] Applies to roof shapes and configurations that call for a higher shape accumulation factor. (9) [F20-OS2.1] Building and Development Branch Page 20

21 Provision Objective/Functional Statement Division B Full and Partial Loading (2) [F20-OS2.1] Division B Specified Rain Load (2) [F20-OS2.1] (3) (4) [F20-OS2.1] Division B Multi-level Roofs (2) [F20-OS2.1] Building and Development Branch Page 21

22 Provision Objective/Functional Statement (3) [F20-OS2.1] (4) [F20-OS2.1] Division B Horizontal Gap between a Roof and a Higher Roof Division B Areas Adjacent to Roof Projections (2) (3) Division B Snow Drift at Corners (2) [F20-OS2.1] Building and Development Branch Page 22

23 Provision Objective/Functional Statement Division B Gable Roofs (2) [F20-OS2.1] (3) (4) [F20-OS2.1] Division B Arch Roofs, Curved Roofs and Domes (2) [F20-OS2.1] (3) [F20-OS2.1] (4) [F20-OS2.1] Building and Development Branch Page 23

24 Provision Objective/Functional Statement (5) [F20-OS2.1] (6) [F20-OS2.1] (7) [F20-OS2.1] (8) (9) [F20-OS2.1] Division B Snow Loads Due to Sliding (2) (3) [F20-OS2.1] Division B Valleys in Curved or Sloped Roofs Building and Development Branch Page 24

25 Provision Objective/Functional Statement (2) [F20-OS2.1] (3) [F20-OS2.1] Division B Specific Weight of Snow Division B Snow Removal Division B Ice Loading of Structures OTHER SUPPORTING MATERIALS Building and Development Branch Page 25