1 Architectural Inspection Building Assessment Survey Asset: P.S QUEENS, STREET, New York, Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior :06 AM :48 AM AA : Architectural - Associate :43 AM :02 PM Asset Data Was the building fully accessible for inspection Inspection Access Comment Principal(s) Information Custodian Fireman Principal Name Organization Did you meet with this Principal? Did this Principal provide feedback? Summary of Principal's Feedback Answer Building Square Footage 60,000 Comments on the Area Comments on the Stories (Floors) plus Basements Comments on the Number of Classrooms 27 No Exterior Walls (under construction) Interiors/ Locker Room Shower (storage) Security Lighting (scaffolding) Chimney, Coping, Cornice, Parapets, Louvers, Roofing/Leaders/Gutters/Roof Drains/Skylight Roof Vent (under construction) Window Guards, Window Lintels, (construction fencing) Site/Playground (no key); Site/Paving/Student Use/Concrete (construction fencing); Site/Seating/Benches/Metal/Wood/Plastic (construction fencing) Denise Fuccillo P.S Queens Yes Yes The Principal provided the following comments: 1. The Public Address system is very antiquated, still operable but not sufficient for today's safety standards. 2. The lighting in the Gymnasium is insufficient and needs to be upgraded. 3. The lighting in the Auditorium is insufficient and needs to be upgraded. Christopher Varvi Kevin Dandrea None 3+B+PH Comments on the Year Built 1954 Student Population 528 Staff Population 70 Weather Facade Photo Fair PB/A&W Page 1 of 37

2 Main Entrance Photo Building Assessment Survey Corner of 140th Street and 31st Drive - North view Roof Photo Facade A - 140th Street Have any Systems/Major Building Components been upgraded? Have there been any New Building Additions? Tandem Schools? Leased Space? Priority Roof 4 - South view Yes Systems: Partial Roofing,Parapets, Coping repairs, Partial exterior walls repointing; Window Guards repair; Areaway Gratings replacement; Auditorium Curtains replacement; Exterior Stairs repair Year: 2011 Systems: Partial Bulkhead repair Year: 2005 Systems: Windows, Window Guards replacement Year: 2003 Systems: Roofing Replacement Year: 1999 No No No Priority Exist Last Year? Priority Category Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage PB/A&W Page 2 of 37

3 Last Year? No condition recorded Structural Engineer Required Building Assessment Survey Structural Type Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No condition recorded Accessibility Accessibility Status Is the primary or secondary entrance on an accessible route? Is the building a multi-story building? Are all floors of the building accessible through compliant means? Are SOME floors other than the 1st floor and basement accessible through compliant means? Do any of the following spaces exist on the First floor? Classroom, Art Room, Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs For the rooms that do exist, are SOME of them accessible on the 1st floor? Boys and Girls or Unisex accessible toilets exist on the 1st floor? Yes Yes No No Yes Yes No Physical Breakdown Structure Exists Complies Required FUNCTIONAL ACCESSIBILITY Exterior Routes Exterior Entrances & Exits Exterior H/C Lifts No Yes Exterior Ramps and Railings Yes Yes Interior Routes Corridor and Lobby H/C Lifts No Yes Interior Corridor Doors and Hardware Yes Yes Interior Corridors and Lobbies No Change in Elevation Interior Elevators Interior Lobby Doors and Hardware Interior Ramps Rooms & Spaces Art Rooms Room 201 No Not on Accessible Route Auditorium 1st Floor No No Stage Access Wheelchair Parking Cafeteria 1st Floor Yes Classrooms 1st Floor Yes Computer Rooms Room 200 No Not on Accessible Route Gymnasium 1st Floor Yes Library Main Office Room 103 Yes Multi-purpose Room Nurse's Room Room 125 Yes Pool Science Lab No No No No No No Yes Yes PB/A&W Page 3 of 37

4 Building Assessment Survey Physical Breakdown Structure Exists Complies Required Rooms & Spaces Toilet Rooms (Boys) 1st Floor No Accessory Arrangement Clear opening < 32" Insufficient Latch Clearance No Lever-type Hardware Sink Arrangement Turning Radius Urinal Arrangement Water Closet Arrangement Toilet Rooms (Girls) 1st Floor No Accessory Arrangement Clear opening < 32" Insufficient Latch Clearance No Lever-type Hardware Sink Arrangement Turning Radius Water Closet Arrangement Toilet Rooms (Staff) 1st Floor No Accessory Arrangement Clear opening < 32" Insufficient Latch Clearance No Lever-type Hardware Sink Arrangement Turning Radius Water Closet Arrangement Building Template Inspection Architectural EXTERIOR AREAWAY AWNINGS AND CANOPIES CHIMNEY COPING CORNICE DOORS DOORS AND FRAMES Inaccessible Inaccessible Under Construction Under Construction 1 - Good PB/A&W Page 4 of 37

5 Building Assessment Survey Architectural Inspection EXTERIOR DOORS DOORS AND FRAMES DOOR HARDWARE LINTELS TRANSOM/SIDE LIGHT EXTERIOR WALLS Material Type(s) Masonry Replacement Quantity 28,000 Replacement Uom Instance on All Facades Under Construction Instance Quantity 28,000 Instance EXTERIOR SOFFITS LOADING DOCK LOUVER Inaccessible PARAPETS Material Type(s) Masonry Replacement Quantity 7,100 Replacement Uom C.F. Instance on All Roofs Under Construction Instance Quantity 7,100 Instance C.F. PLAZA DECK ROOF Roofing Replacement Quantity 31,000 Replacement Uom ROOF HATCH/SMOKE HATCH 5 - Poor DETERIORATED Roof Plan reference Quantity 1 PB/A&W Page 5 of 37

6 Building Assessment Survey Architectural Inspection EXTERIOR ROOF Roofing ROOF HATCH/SMOKE HATCH EACH Urgency of Action PRIORITY 4 Photo1 RH2 LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS ROOF BARRIER ROOF CAGE ROOF FENCE ROOFING Instance on Modified Bitumen: All Roofs Instance Inaccessible 3 - Fair Instance Quantity 31,000 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 1999 Source of Installation Roof Plan reference No Documented MODIFIED BITUMEN: ROOFING: MAJOR ACTIVE ROOF LEAKS IN INSTRUCTIONAL SPACE Quantity 40 Urgency of Action PRIORITY 5 ROOFING WITHOUT MAJOR EQUIPMENT REMOVAL PB/A&W Page 6 of 37

7 EXTERIOR ROOF Roofing ROOFING Photo1 Building Assessment Survey ROOFING DRAINS Specialties BULKHEAD/PENTHOUSE Roof Plan reference Roof 7-1st Floor Locker Room shown. Roof 3 - Corridor near Cafeteria similar Under Construction 3 - Fair BULKHEAD/PENTHOUSE WALLS/: GYPSUM BOARD DAMAGED/DETERIORATED Quantity 60 MAINTENANCE Photo1 CUPOLA/ SPIRES/ TOWERS DORMER BH1 PB/A&W Page 7 of 37

8 Building Assessment Survey Architectural Inspection EXTERIOR ROOF Specialties DUNNAGE STEEL SKYLIGHT/ROOF VENT Under Construction ROOF/GRAVITY TANK STAIRS/RAMPS: EXTERIOR BUILDING CHEEK/FLANK WALLS 3 - Fair STONE: DETERIORATED EXPANSION JOINT Roof Plan reference Quantity 10 L.F. Urgency of Action PRIORITY 4 Photo1 RAILINGS Roof Plan reference Facade J - Exit 3 - Fair BROKEN BRACKET Quantity 1 PB/A&W Page 8 of 37

9 Building Assessment Survey Architectural Inspection EXTERIOR STAIRS/RAMPS: EXTERIOR RAILINGS EACH Urgency of Action PRIORITY 4 Photo1 Roof Plan reference Facade F - HC Ramp RUST - MINOR Quantity 10 L.F. MAINTENANCE Photo1 STAIRS/RAMPS Facade F - HC Ramp 4 - Between Fair and Poor STONE: DETERIORATED SUBSTRATE PB/A&W Page 9 of 37

10 EXTERIOR STAIRS/RAMPS: EXTERIOR STAIRS/RAMPS Roof Plan reference Building Assessment Survey Quantity 10 SUBSTRATE AND RESET Urgency of Action PRIORITY 4 Photo1 Roof Plan reference Facade F - Exit CONCRETE: CRACKS/SPALLING - MAJOR Quantity 10 Urgency of Action PRIORITY 4 PB/A&W Page 10 of 37

11 EXTERIOR STAIRS/RAMPS: EXTERIOR STAIRS/RAMPS Photo1 Building Assessment Survey Facade A - South Exit WINDOWS Replacement Quantity 7,000 Replacement Uom EXTERIOR GUARDS Inaccessible LINTELS Inaccessible WINDOWS Material Type(s) Aluminum Instance on Aluminum - Double Hung: All Facades Instance Instance Quantity 7,000 Instance Installation Year 2003 Source of Installation Documented POOLS STRUCTURAL COLUMNS/BEAMS/BEARING WALLS FLOOR STRUCTURE 3 - Fair CONCRETE SLAB ON GRADE: MINOR CRACKS Location/Instance Basement Quantity 50 REPAIR Purpose of Action LEVEL 5 PB/A&W Page 11 of 37

12 STRUCTURAL FLOOR STRUCTURE Photo1 Building Assessment Survey North storage room shown FOUNDATION WALLS Material Type(s) Location/Instance Quantity 120 Concrete 4 - Between Fair and Poor CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONAL SPACE Basement Urgency of Action PRIORITY 5 Purpose of Action LEVEL 5 Photo1 INSTALL WATERPROOFING Storage Room shown, also in sprinkler control valve area R, Y, Y, N ROOF STRUCTURE VAULTS-BUNKERS Foundation Walls 3 - Fair CRACKS, SPALLING Location/Instance Basement Quantity 30 REPAIR Purpose of Action LEVEL 5 PB/A&W Page 12 of 37

13 STRUCTURAL VAULTS-BUNKERS Foundation Walls Photo1 Building Assessment Survey Vault Foundation Wall Slab Structure 3 - Fair CONCRETE SLAB ON GRADE: THRU CRACKS Location/Instance Basement Quantity 30 REPAIR Purpose of Action LEVEL 5 Photo1 Vault Slab Vault/Ash Hoist Doors and Framing 3 - Fair MINOR RUSTING Location/Instance Basement Quantity 2 EACH REPAIR PB/A&W Page 13 of 37

14 Building Assessment Survey Architectural Inspection STRUCTURAL VAULTS-BUNKERS Vault/Ash Hoist Doors and Framing Photo1 Vault Hoist Doors AUDITORIUM seats Ceiling seats PLASTER: CRACKS/SPALLING Location/Instance Near the Entrance, Stage Quantity 70 Urgency of Action PRIORITY 4 Purpose of Action LEVEL 4 Photo1 Door(s) seats Fixed H/C Lift seats Fixed Seating seats Location/Instance Quantity 36 Near the Entrance P 4 - Between Fair and Poor DAMAGED/BROKEN/INOPERABLE Seat G/101, M/4, K/2, L/102, 103, and others PB/A&W Page 14 of 37

15 Building Assessment Survey Architectural Inspection AUDITORIUM Fixed Seating EACH Photo1 Seat M/4 Floor Finish seats Sliding-folding Partition seats Stage seats Stage seats DAMAGED FLOOR Location/Instance Rear of Stage Quantity 20 Photo1 Stage Curtain Rigging seats Rear of Stage PB/A&W Page 15 of 37

16 Building Assessment Survey Architectural Inspection AUDITORIUM Stage Stage Curtain Rigging Stage Curtains seats Walls seats MASONRY: CRACKS/SPALLING Location/Instance Stage right, left Quantity 20 Urgency of Action PRIORITY 4 Purpose of Action LEVEL 4 Photo1 Stage right P Window Curtains/Shades/Blinds seats CAFETERIA Ceiling PLASTER: CRACKS/SPALLING Location/Instance Near the Kitchen, Rear of Room Quantity 60 PB/A&W Page 16 of 37

17 CAFETERIA Ceiling Photo1 Building Assessment Survey Rear of Room Door(s) Fixed Equipment Floor Finish Sliding-folding Partition Stage Walls Window Curtains/Shades/Blinds CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING - ACTIVE LEAK Location/Instance Quantity 20 Corridor near Cafeteria Urgency of Action PRIORITY 5 PB/A&W Page 17 of 37

18 Building Assessment Survey Architectural Inspection CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling Photo1 Corridor near Cafeteria PLASTER: CRACKS/SPALLING Location/Instance Room 102, 303, 306, 307, 317, and others Quantity 300 Photo1 Room 306 Door(s) 5 - Poor METAL: DETERIORATED DOOR Location/Instance Exit 1 Vestibule Quantity 1 EACH MAINTENANCE Photo1 PB/A&W Page 18 of 37

19 Building Assessment Survey Architectural Inspection CLASSROOMS/CORRIDORS/ADMIN SPACES Door(s) Exit 1 Vestibule WOOD: DETERIORATED DOOR Location/Instance Rooms 303, 306, 318 Quantity 3 EACH MAINTENANCE Photo1 Room 318 Floor Finish TERRAZZO: CRACKS Location/Instance Main Entrance Vestibule Quantity 20 Photo1 Main Entrance Vestibule Location/Instance Room 200 Quantity 10 VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 PB/A&W Page 19 of 37

20 Building Assessment Survey Architectural Inspection CLASSROOMS/CORRIDORS/ADMIN SPACES Floor Finish Photo1 Room 200 VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Location/Instance Room 201, 203, 213, 303, 306, and others Quantity 500 Photo1 Room 306 Walls PLASTER: CRACKS/SPALLING Location/Instance Room 200 Quantity 20 Urgency of Action PRIORITY 4 Purpose of Action LEVEL 4 Photo1 PB/A&W Page 20 of 37

21 CLASSROOMS/CORRIDORS/ADMIN SPACES Walls Location/Instance Quantity 140 Room P PLASTER: CRACKS/SPALLING Room 307, 317. Corridor near Room 117, 317. Corridor near Stair F/3, and others Photo1 Building Assessment Survey Room 307 Specialties GYMNASIUM Ceiling Under Construction Door(s) Fixed Equipment Floor Finish 3 - Fair WOOD: DAMAGED/DETERIORATED Location/Instance Rear of Room Quantity 200 PB/A&W Page 21 of 37

22 GYMNASIUM Floor Finish Photo1 Building Assessment Survey Rear of Room Seating Sliding-folding Partition Stage Walls Window Curtains/Shades/Blinds DOOR HARDWARE GUARDS KITCHEN Ceiling Door(s) Location/Instance Quantity Fair 3 - Fair WOOD: DETERIORATED DOOR Storage Room EACH MAINTENANCE PB/A&W Page 22 of 37

23 KITCHEN Door(s) Photo1 Building Assessment Survey Storage Room Floor Finish CERAMIC TILE: BROKEN/MISSING TILES Location/Instance Prep Area Quantity 10 Photo1 Prep Area Walls LIBRARY LOCKER ROOM Ceiling Alternative use Instance on 2nd Floor Alternative use Location/Instance Yes Yes PLASTER: CRACKS/SPALLING - ACTIVE LEAK Near the windows PB/A&W Page 23 of 37

24 Building Assessment Survey Architectural Inspection LOCKER ROOM Ceiling Quantity 20 Urgency of Action PRIORITY 5 Photo1 Door(s) Instance on 2nd Floor Floor Finish Instance on 2nd Floor Locker Room Lockers Instance on 2nd Floor Walls Instance on 2nd Floor MULTI-PURPOSE ROOM SCIENCE DEMO ROOM Instance on Room 304 Alternative use Fixed Equipment Instance on Room 304 Near the windows No PB/A&W Page 24 of 37

25 Building Assessment Survey Architectural Inspection SCIENCE DEMO ROOM Fixed Equipment SCIENCE LAB SCIENCE PREP ROOM SHOWER ROOM Alternative use Yes Instance on 2nd Floor Inaccessible Ceiling Door(s) Floor Finish 3 - Fair CERAMIC TILE: BROKEN/MISSING TILES Location/Instance Near the Entrance Quantity 10 Photo1 Near the Entrance Walls CERAMIC TILE: BROKEN/ MISSING Location/Instance Near the Entrance Quantity 10 PB/A&W Page 25 of 37

26 SHOWER ROOM Walls Photo1 Building Assessment Survey Near the Entrance STAIRS/RAMPS: Do Letter Stair Signs Exist? Yes Ceiling PLASTER: CRACKS/SPALLING Location/Instance Stair C/Basement Quantity 20 Urgency of Action PRIORITY 4 Purpose of Action LEVEL 4 Photo1 Stair C/Basement H PLASTER: CRACKS/SPALLING Location/Instance Stair B/1, D/3 Quantity 60 PB/A&W Page 26 of 37

27 STAIRS/RAMPS: Ceiling Photo1 Building Assessment Survey Stair D/3 Door(s) Partition Railings Stairs and Landings 4 - Between Fair and Poor VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Location/Instance Stair A/1, B/1, D/2, 3, F/2, and others Quantity 400 Photo1 Stair D/3 Walls Location/Instance Quantity 20 PLASTER: CRACKS/SPALLING Stair C/Basement Urgency of Action PRIORITY 4 Purpose of Action LEVEL 4 PB/A&W Page 27 of 37

28 STAIRS/RAMPS: Walls Photo1 Building Assessment Survey Stair C/Basement X GLAZED BLOCK: CRACKS/SPALLING Location/Instance Stair B/1, D/1 Exit Vestibule Quantity 30 Photo1 Stair D/1 Exit Vestibule PLASTER: CRACKS/SPALLING Location/Instance Stair A/2, D/3, F/2, 3 Quantity 40 Photo1 Stair A/2 PB/A&W Page 28 of 37

29 Building Assessment Survey Architectural Inspection TOILET ROOMS - STAFF Ceiling Door(s) 5 - Poor WOOD: DETERIORATED DOOR Location/Instance Inside Rooms 208, 307 Quantity 2 EACH MAINTENANCE Photo1 Inside Room 307 Floor Finish Stalls 5 - Poor RUST - MAJOR Location/Instance Inside Rooms 307, 113. Room 130 Quantity 3 EACH Photo1 Walls Inside Room 113 PB/A&W Page 29 of 37

30 Building Assessment Survey Architectural Inspection TOILET ROOMS - STAFF Walls CERAMIC TILE: BROKEN/ MISSING Location/Instance Room 208. Inside Room 233 Quantity 20 Photo1 Inside Room 233 TOILET ROOMS - STUDENTS Ceiling PLASTER: CRACKS/SPALLING Location/Instance Room 312 Quantity 10 Photo1 Room 312 Door(s) 5 - Poor Location/Instance Room 310, 312 Quantity 2 WOOD: DETERIORATED DOOR EACH MAINTENANCE PB/A&W Page 30 of 37

31 Building Assessment Survey Architectural Inspection TOILET ROOMS - STUDENTS Door(s) Photo1 Room 312 Floor Finish Stalls 5 - Poor BROKEN/MISSING Location/Instance Room 100/102, 112, 210, 310 Quantity 4 EACH Photo1 Room 310 Walls CERAMIC TILE: BROKEN/ MISSING Location/Instance Room 112, 122, 210 Quantity 20 PB/A&W Page 31 of 37

32 TOILET ROOMS - STUDENTS Walls Photo1 Building Assessment Survey Room 210 PLASTER: CRACKS/SPALLING Location/Instance Room 310 Quantity 10 Photo1 Room 310 LIFE SAFETY F.D. HOLDING AREA STEEL STAIRS SITE CONTAINERIZATION 5 - Poor FENCING MISSING Location/Instance 31st Road Quantity 600 INSTALL NEW Photo1 No photo recorded Location/Instance CONCRETE PAD MISSING 31st Road PB/A&W Page 32 of 37

33 Building Assessment Survey Architectural Inspection SITE CONTAINERIZATION Quantity 300 INSTALL NEW Photo1 No photo recorded CONTAINER DAMAGED Location/Instance 31st Road Quantity 3 EACH Photo1 31st Road Drainage System for Asphalt Catch Basins/Manhole - Surrounded by asphalt Culverts - Asphalt Covering Drainage System for Concrete Catch Basins/Manhole - Surrounded by concrete Culverts - Concrete Covering Drainage System for Soil DRINKING FOUNTAINS FENCES CONCRETE CURB: DAMAGED/DETERIORATED Location/Instance 31st Road Quantity 20 PB/A&W Page 33 of 37

34 SITE FENCES Photo1 Building Assessment Survey st Road CHAIN LINK: DAMAGED POST/RAIL Location/Instance 31st Road Quantity 20 L.F. Photo1 31st Road IRRIGATION SYSTEM PAVING Student Non-Use Gravel Exists? No Asphalt 3 - Fair CRACKS - MAJOR Location/Instance 31st Road Quantity 50 PB/A&W Page 34 of 37

35 SITE PAVING Student Non-Use Asphalt Photo1 Building Assessment Survey st Road Concrete Pavers Student Use Gravel Exists? No Asphalt Concrete Inaccessible Pavers Site Sidewalks & Walkways Asphalt Concrete 3 - Fair DAMAGED/DETERIORATED/MISSING SECTIONS Location/Instance Exit to 31st Drive Quantity 50 Photo1 Pavers DOT Sidewalk Asphalt Exit to 31st Drive PB/A&W Page 35 of 37

36 Building Assessment Survey Architectural Inspection SITE PAVING DOT Sidewalk Concrete 4 - Between Fair and Poor DAMAGED/DETERIORATED/MISSING SECTIONS Location/Instance 140th Street, 31st Drive, 31st Road Quantity 425 Photo1 140th Street HEAVING Location/Instance 140th Street Quantity 25 Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 140th Street DAMAGED CURBS Location/Instance 140th Street, 31st Drive, 31st Road Quantity 160 L.F. PB/A&W Page 36 of 37

37 SITE PAVING DOT Sidewalk Concrete Photo1 Building Assessment Survey st Road HEAVING Location/Instance 140th Street, 31st Drive Quantity 475 Photo1 Pavers PLAYGROUNDS Instance on 31st Drive - South Side PLAYING SURFACE RETAINING WALLS SEATING Benches Concrete Metal/Wood/Plastic Bleachers SITE WALLS (NOT RETAINING WALLS) STAIRS/RAMPS: EXTERIOR 140th Street Inaccessible Inaccessible PB/A&W Page 37 of 37