Rate (Rs.) Description Unit Qty PART I : REMOVING & RESHIFTING OF EXISTING. Amount (Rs.) INSTALLATION

Size: px
Start display at page:

Download "Rate (Rs.) Description Unit Qty PART I : REMOVING & RESHIFTING OF EXISTING. Amount (Rs.) INSTALLATION"

Transcription

1 REVISED BOQ FOR ELECTRICAL WORK FOR ESTABLISHMENT OF MUSEUM AT BANK'S BUILDING AT 70/80, M.G. ROAD, FORT, MUMBAI Note : The rates quoted shall include supply, installation, testing, commissioning of complete individual system to consultant/client's satisfaction & preparation, submission & approval from consultant, of Shop drawings, AS-BUILT drawings. Sr. No. Description Unit Qty PART I : REMOVING & RESHIFTING OF EXISTING INSTALLATION 1 Removing of Existing lighting points Nos Reshifting & utilising existing lighting points Nos. 20 Removing & shifting existing smoke detectors in Nos ceiling Adding & removing of MCCB/ MCB from main Nos. 4 4 panel Removing & reconnecting the existing armoured Nos. 4 5 cables from main panel Laying of fire alarm cable from existing fire alarm Mtrs panel Nos Removing & shifting existing speakers in ceiling 8 Removing & shifting existing raceways in flooring Mtrs. 200 along with junction boxes PART - I TOTAL CARRIED TO SUMMARY PART II : LIGHTING & SMALL POWER INSTALLATION 1 CIRCUIT WIRING Mtrs Light Point/ Bell point wiring with 2 x 2.5 sqmm + 1 x 1.5 sqmm (green)(approved make) solid multistrand FRLS cu conductor 1100 V ISI marked PVC insulated wires in medium guage PVC conduits (cost of conduits included), surface type on the slab ceiling, recessed in wall/partitions,complete with all conduit accessories including cost of 6A switch & modular type switchbox consisting of concealed /surface M.S. box,grid plate, front-plate etc. as directed by architects/consultants, as per specifications and layout drawings attached. 2 POINT WIRING FOR LIGHTING & SMALL POWER Note: 1.The rate for primary lighting point should include wiring with 2 x 1.5 sqmm + 1 x 1.5 sqmm (green) wires from switch box to 1st primary light point. Rate (Rs.) Amount (Rs.)

2 Note: 2. The maximum circuit length of primary light point from LDB shall be 10.0 meters. & The maximum circuit length of secondary light point from primary light point will be 3.0 meters. 2.1 Normal Lighting points Primary Light Point Nos Secondary Light Point Nos Supply & Installation of the following complete with Recessed type metal boxes & 16A Switch Socket Outlet with shuttered type Nos Supply & installation of following sizes of heavy duty PVC conduits including all accessories laid surface on celing/concealed in walls/partitions for wiring other than item 1.0 & its subitems (Emergency Backup units,data/ Voice wiring in false ceiling/ducts/ partitions etc.,security systems wiring etc.) mm dia Rigid Mtr mm dia. Rigid Mtr mm dia flexible Mtr mm dia flexible Mtr. 80 PART - II TOTAL CARRIED TO SUMMARY PART III : LIGHTING FIXTURES 1 Supply,installation,testing & commissioning of following surface/recessed type fluorescent tube lighting fixtures complete with lamps,control gear & low loss Electronics ballasts & PF improvement capacitor with Trulite/ Osram lumilux TL'D lamps,all accessories(approved make) Note : All Light fixture wil be procured after approval by Architect/ Consultant 1.1 1x28W T5 Light fixture (FOR BACK PANEL & COVE No. 390 LIGHT) 1.2 No. 75 2x18W CFL recesse type lighting fixture with glass 1.3 Track lighting with halogen lights mtr 52 PART III TOTAL CARRIED TO SUMMARY PART IV : DISTRIBUTION BOARDS

3 1 Supply,installation, testing and commissioning of the following totally enclosed,floor/wall mounting cubicle type panels/smdbs/dbs, fabricated with 16 SWG CRCA sheet steel epoxy + polyester powder coated after seven tank process,having dust-proof and vermin proof neoprene gaskets and hinged doors with all accessories,complete with internal wiring & internal accessories such as DIN rails,neutral links,earth bar, earthing lugs etc. housing following switchgears,as per technical specifications and schematic drawings enclosed. Note : 1) Neutral bars & Earth bars shall have 2 spare ways for each phase 2) All MCBs will be C curve type unless & otherwise mentioned. 3) All MCCBs will have thermo-magnetic release & will be provided with operating handles. 4) All MCCBs will be provided with one set of auxiliary NO/NC contact & shunt trip coil 1.1 Distribution Board with 1 No. 32/63A TPN MCB incomer,3 Nos. 40A 300mA DP ELCB's,set of 100A 4Pole Copper Busbars,Brass Neutral Bars,Brass Earth Bars,indicating lamps, Outgoings SP MCBs of suitable ratings as specified Way TPN DB with 18 Nos. 10A SP MCBs No.s Emergency Lighting Distribution Board with 1 No.32 / 40A DP MCB incomer, 1 Nos. 40A 300mA DP ELCB, set of 100A 2 Pole Copper Busbars, Brass Neutral Bars, Brass Earth Bars, indicating llamps, Outgoings SP MCBs of suitable ratings as specified Way SPN DB with 12 Nos. 10 A SP MCBs Nos. 1

4 2 Supply,installation,testing & commissioning of the following in M.S. enclosure fabricated with 16 SWG CRCA sheet steel epoxy powder coated after seven tank process,having dust-proof and vermin proof gaskets and hinged doors with all accessories, complete with internal wiring & internal accessories such as DIN rails,neutral links,earthing lugs etc. & mounting brackets,housing following switchgears,as per technical specifications A TPN MCB In W/P enclosure No.s 2 PART IV TOTAL CARRIED TO SUMMARY PART V : CABLING, EARTHING & MISC. 1 Supply,Installation,Testing & commissioning of 1100V,solid multi-stranded copper/aluminium conductor,xlpe/pvc insulated,pvc sheathed cables confirming to IS 1554(Part-I)latest,cables cleated to wall/ceiling or within cable risers etc. including supply & fixing at aluminium clamps, aluminium cable tags at every 15Mtrs. hardware etc. complete as per specifications C 6 sq.mm CU PVC Armoured Mtr C - 10 sq.mm YWY Armoured Mtr C - 6 sq.mm Cu PVC Armoured Mtr End Termination of the following sizes of 1100V grade aluminium/copper conductor,pvc insulated and sheathed cables with single compression brass glands & crimping type copper lugs with earthing of glands C 6 sq.mm CU PVC Armoured No.s C - 10 sq.mm YWY Armoured No.s C - 6 sq.mm Cu PVC Armoured No.s 4 3 Supply & Installation of the following earth conductor including earthing Clamps, terminal lugs etc SWG hard drawn bare copper wire Mtr SWG hard drawn bare copper wire Mtr SWG hard drawn bare copper wire Mtr 20 Safe earth bar consisting of 25 X 3 mm 300 mm long copper strip mounted on insulated supports, 3.4 in M.S. enclosure. No.s 2

5 4 Supply, fabrication & installation of M.S. support structures of M.S. channels/angles/plates for panels, DBs,cable trays as required,complete with one coat of red oxide primer & 2 coats of black enamel paint,with all fixing accessories etc. Kg 10 5 Supply & lnstallation of following sizes of heavy guage UPVC conduit on already provided M.S. supports,surface walls,ceiling,partitions with all accessories like clamps,bends,ts,jbs,glands etc mm dia PVC Rigid Mtr JOB L.S. Obtaining all the requisite approvals from Chief Electrical Inspector,PWD,for the complete electrical installation work.(statutory fees to be paid by the client) IF REQUIRED PART V TOTAL CARRIED TO SUMMARY PART VI : COMPUTER POWER WIRING, TELEPHONE & T.V. SYSTEM WIRING. 1 Supply,Laying,termination, of following unarmoured cat6 data cables in underfloor/ surface raceways/m.s./pvc conduits(measured separately)- termination at workstation side as well as server rack side with ferruling and including certification pair cat6 enhanced for data Mtr Supply & Installation of the following wiring accessories complete with recessed/surface type metal boxes, modular gridplate, faceplate in walls/partitions/work tables 2.1 RJ45 data outlet including termination with No.s 10 provision for labling on faceplate. 2.2 RJ11 Telephone outlet including termination with No.s 6 provision for labling on faceplate. 3 Supply & Installation of RG-6 Coaxial Cable. finolex Mtrs. 100 make. 4 Supply & Installation of TV Outlet Nos. 4 5 Supply,laying and termination of following sizes jelly filled armoured cable pair mtr 50 6 Supply,installation, testing & commissioning of following sizes krone boxes in M.S enclosure pair Nos. 2 PART VI- TOTAL CARRIED TO SUMMARY

6 I II III IV V VI SUMMARY OF PRICES REMOVING & RESHIFTING OF EXISTING INSTALLATION LIGHTING & SMALL POWER INSTALLATION LIGHTING FIXTURES DISTRIBUTION BOARDS. CABLING, EARTHING & MISC. COMPUTER POWER WIRING, TELEPHONE & T.V. SYSTEM WIRING. TOTAL