NYC Department of Education

Size: px
Start display at page:

Download "NYC Department of Education"

Transcription

1 NYC Department of Education Architectural Inspection Building Assessment Survey Asset: P.S QUEENS, AVENUE, New York, Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior :46 AM :24 PM AA : Architectural - Associate :50 AM :08 PM Asset Data Was the building fully accessible for inspection Inspection Access Comment Principal(s) Information Custodian Fireman Principal Name Organization Did you meet with this Principal? Did this Principal provide feedback? Summary of Principal's Feedback Answer Building Square Footage Comments on the Area Comments on the Stories (Floors) plus Basements 4+B Comments on the Number of Classrooms 30 No Site/Paving/Student non-use/asphalt (due to construction) Dr. Samantha Maisonet P.S Queens No Yes The Principal returned the Principal naire with the following comments; 1. The air conditioning system throughout the school and primarily in the large assembly spaces is insufficient and needs to be upgraded since many student and community functions are held in these rooms. 2. There is currently no Intrusion Alarm system in the school and it needs to be installed. Dwight Woodly Rafael James None Comments on the Year Built 1931 Student Population 394 Staff Population 82 Weather Facade Photo Fair Corner of 31st Avenue and Hobart Street - North view PB/A&W Page 1 of 36

2 Architectural Inspection Main Entrance Photo NYC Department of Education Building Assessment Survey Roof Photo Facade A - 31st Avenue Roof 1 - West view Have any Systems/Major Building Components been upgraded? Yes Systems: External Modernization Project including Roofing Replacement, Chimney rebuilt, Parapets repointing, Copings, Roof Barriers, Roof Drain strainers; Exterior Walls repointing and Masonry Sills replaced; Foundation Waterproofing at Electric Meter Room Facade A; Also Foundation Waterproofing at Facades E, F and G; Partial Exterior Door Replacement; Partial Exterior Stair repair. Year: 2017 Systems: All Toilet Rooms renovated; Repairs to stalling concrete at Basement Tool Room; Repairs to exterior Stairs; Vault Hoist Doors replacement Year: 2016 Systems: Limited Repairs to exterior Stairs Year: 2015 Systems: Auditorium upgrade including new Seats & Flooring; Walls & Ceilings painting Year: 2014 Systems: 85% VCT Flooring replacement Year: 2008 Systems: Library upgrade including Flooring, Furniture and Lighting PB/A&W Page 2 of 36

3 Architectural Inspection Have there been any New Building Additions? Tandem Schools? Leased Space? Priority NYC Department of Education Building Assessment Survey Year: 2005 Systems: Gymnasium Flooring resurfaced Year: 2004 Systems: Exterior Modernization Project including New Windows, Guards, Shades, Roofing, Metal Coping at Roof 1, Exterior Doors and Areaway Gratings; Bulkhead Walls resurfaced; Roof Drains cleared and New Strainers installed; Chimney and 31st Street Wall repointing. Year: 2000 No No No Priority Exist Last Year? Priority Category Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No Tripping Hazard Missing handrail is a potential safety hazard. EXTERIOR STAIRS/RAMP S: EXTERIOR RAILINGS Exterior stair at Exit 2. Rafael James Fireman Yes Tripping Hazard Severely damaged safety surface is a potential tripping hazard SITE PLAYGROUN DS Safety Surfacing Center, North and South Side of playground Rafael James Fireman Structural Engineer Required Structural Type Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No condition recorded Accessibility Accessibility Status Is the primary or secondary entrance on an accessible route? Is the building a multi-story building? Are all floors of the building accessible through compliant means? Are SOME floors other than the 1st floor and basement accessible through compliant means? Do any of the following spaces exist on the First floor? Classroom, Art Room, Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs For the rooms that do exist, are SOME of them accessible on the 1st floor? Boys and Girls or Unisex accessible toilets exist on the 1st floor? Yes Yes No No Yes Yes No Physical Breakdown Structure Exists Complies Required FUNCTIONAL ACCESSIBILITY Exterior Routes Exterior Entrances & Exits Yes Exterior H/C Lifts No Yes Exterior Ramps and Railings No Yes Interior Routes PB/A&W Page 3 of 36

4 Architectural Inspection NYC Department of Education Building Assessment Survey Physical Breakdown Structure Exists Complies Required Interior Routes Corridor and Lobby H/C Lifts No Yes Interior Corridor Doors and Hardware Yes Yes Interior Corridors and Lobbies No Change in Elevation Interior Elevators Interior Lobby Doors and Hardware Interior Ramps Rooms & Spaces Art Rooms Room 403 No Not on Accessible Route Auditorium 1st Floor No No Stage Access Wheelchair Parking Cafeteria 1st Floor No Not on Accessible Route Classrooms None on Accessible Route No Not on Accessible Route Computer Rooms Room 405 No Not on Accessible Route Gymnasium 3rd Floor No Not on Accessible Route Library Room 103 No Not on Accessible Route Main Office Room 203 No Not on Accessible Route Multi-purpose Room Nurse's Room Room 262 No Not on Accessible Route Pool Science Lab Toilet Rooms (Boys) None on Accessible Route No Not on Accessible Route Toilet Rooms (Girls) None on Accessible Route No Not on Accessible Route Toilet Rooms (Staff) None on Accessible Route No Not on Accessible Route No No No No No Yes Building Template Inspection Architectural EXTERIOR PB/A&W Page 4 of 36

5 NYC Department of Education Building Assessment Survey Architectural Inspection EXTERIOR AREAWAY Instance on AW1-AW12 Instance 3 - Fair Instance Quantity 12 Instance EACH AREAWAY WALLS: CRACKS AND SPALLING Roof Plan reference Quantity 20 REPAIR Photo1 Roof Plan reference AW9 AREAWAY GRATINGS: MAJOR RUSTING / OR BROKEN Quantity 10 PB/A&W Page 5 of 36

6 Architectural Inspection EXTERIOR AREAWAY Photo1 NYC Department of Education Building Assessment Survey Roof Plan reference AW7 AREAWAY GRATINGS: MINOR RUSTING Quantity 40 MAINTENANCE Photo1 AWNINGS AND CANOPIES CHIMNEY Material Type(s) COPING CORNICE AW2 Masonry PB/A&W Page 6 of 36

7 Architectural Inspection EXTERIOR CORNICE DOORS DOORS AND FRAMES Roof Plan reference NYC Department of Education Building Assessment Survey Fair METAL: DETERIORATED DOOR AND FRAME - MINOR DETERIORATION Quantity 2 EACH MAINTENANCE Photo1 DOOR HARDWARE LINTELS TRANSOM/SIDE LIGHT Exit Fair METAL: DENTED, MINOR RUSTING PB/A&W Page 7 of 36

8 Architectural Inspection EXTERIOR DOORS TRANSOM/SIDE LIGHT Roof Plan reference NYC Department of Education Building Assessment Survey Quantity 10 MAINTENANCE Photo1 Exit 2 EXTERIOR WALLS Material Type(s) Masonry, Concrete Replacement Quantity 38,000 Replacement Uom Instance on All Facades Instance Instance Quantity 38,000 Instance BRICK: MINOR CRACKS AND SPALLING Roof Plan reference PB/A&W Page 8 of 36

9 Architectural Inspection EXTERIOR EXTERIOR WALLS Elevation NYC Department of Education Building Assessment Survey Quantity 50 RESTITCH Photo1 Roof Plan reference Facade H BRICK: OPEN JOINTS Elevation Quantity 200 REPOINT PB/A&W Page 9 of 36

10 NYC Department of Education Building Assessment Survey Architectural Inspection EXTERIOR EXTERIOR WALLS Photo1 Facade H EXTERIOR SOFFITS LOADING DOCK LOUVER PARAPETS Material Type(s) Masonry Replacement Quantity 5,200 Replacement Uom C.F. Instance on All Facades Instance Instance Quantity 5,200 Instance C.F. BRICK: MINOR CRACKS, SPALLING Roof Plan reference Quantity 30 REPAIR PB/A&W Page 10 of 36

11 Architectural Inspection EXTERIOR PARAPETS Photo1 NYC Department of Education Building Assessment Survey Roof 1 PLAZA DECK ROOF Roofing Replacement Quantity 18,000 Replacement Uom ROOF HATCH/SMOKE HATCH LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS ROOF BARRIER ROOF CAGE ROOF FENCE ROOFING Instance on Modified Bitumen: All Roofs Instance 1 - Good Instance Quantity 18,000 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 2017 Source of Installation Roof Plan reference No Custodial Staff MODIFIED BITUMEN: ROOFING: MAJOR ACTIVE ROOF LEAKS IN INSTRUCTIONAL SPACE Quantity 10 PB/A&W Page 11 of 36

12 NYC Department of Education Architectural Inspection EXTERIOR ROOF Roofing ROOFING Urgency of Action PRIORITY 5 Purpose of Action LEVEL 4 Photo1 Building Assessment Survey ROOFING WITHOUT MAJOR EQUIPMENT REMOVAL ROOFING DRAINS Specialties BULKHEAD/PENTHOUSE CUPOLA/ SPIRES/ TOWERS DORMER DUNNAGE STEEL SKYLIGHT/ROOF VENT ROOF/GRAVITY TANK STAIRS/RAMPS: EXTERIOR BUILDING CHEEK/FLANK WALLS RAILINGS Roof Plan reference Room H 1 - Good 3 - Fair MISSING RAILING Quantity 10 L.F. PB/A&W Page 12 of 36

13 NYC Department of Education Building Assessment Survey Architectural Inspection EXTERIOR STAIRS/RAMPS: EXTERIOR RAILINGS Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 Exit 2 STAIRS/RAMPS WINDOWS Replacement Quantity 12,000 Replacement Uom EXTERIOR GUARDS LINTELS WINDOWS Material Type(s) Aluminum Instance on Aluminum - Double Hung: All Facades Instance 3 - Fair Instance Quantity 12,000 Instance Installation Year 2000 Source of Installation Documented INTERIOR POOLS STRUCTURAL COLUMNS/BEAMS/BEARING WALLS FLOOR STRUCTURE FOUNDATION WALLS Material Type(s) Concrete, Masonry 3 - Fair PB/A&W Page 13 of 36

14 Architectural Inspection INTERIOR STRUCTURAL FOUNDATION WALLS Location/Instance Quantity 100 CONCRETE: WATER INFILTRATION IN ELECTRICAL PANEL ROOM Basement Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 Location/Instance Quantity 40 INSTALL WATERPROOFING No photo recorded CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONAL SPACE Basement Urgency of Action PRIORITY 5 Purpose of Action LEVEL 5 Photo1 NYC Department of Education Building Assessment Survey INSTALL WATERPROOFING Boiler Room ROOF STRUCTURE VAULTS-BUNKERS Foundation Walls Slab Structure Location/Instance Quantity Fair CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONAL SPACE Basement Urgency of Action PRIORITY 5 Purpose of Action LEVEL 5 INSTALL WATERPROOFING PB/A&W Page 14 of 36

15 Architectural Inspection INTERIOR STRUCTURAL VAULTS-BUNKERS Slab Structure Photo1 NYC Department of Education Building Assessment Survey Ash Hoist Vault Slab CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED Location/Instance Basement Quantity 20 REPAIR Purpose of Action LEVEL 5 Photo1 Ash Hoist Vault Slab Vault/Ash Hoist Doors and Framing AUDITORIUM Ceiling Instance on 1st Floor Seats Instance on 1st Floor Seats Door(s) Instance on 1st Floor Seats Location/Instance Quantity Good 4 - Between Fair and Poor WOOD: DETERIORATED DOOR AND FRAME Main Entrance EACH MAINTENANCE PB/A&W Page 15 of 36

16 NYC Department of Education Building Assessment Survey Architectural Inspection INTERIOR AUDITORIUM Door(s) Photo1 Fixed H/C Lift Instance on 1st Floor Seats Fixed Seating Instance on 1st Floor Seats Floor Finish Instance on 1st Floor Seats Sliding-folding Partition Instance on 1st Floor Seats Stage Instance on 1st Floor Seats Stage Instance on 1st Floor Seats Stage Curtain Rigging Instance on 1st Floor Seats Stage Curtains Instance on 1st Floor Seats Walls Instance on 1st Floor Seats Window Curtains/Shades/Blinds Instance on 1st Floor Seats Main Entrance 1 - Good PB/A&W Page 16 of 36

17 NYC Department of Education Building Assessment Survey Architectural Inspection INTERIOR CAFETERIA Instance on 1st Floor Ceiling Instance on 1st Floor Door(s) Instance on 1st Floor 4 - Between Fair and Poor WOOD: DETERIORATED DOOR Location/Instance Exit 2 Quantity 2 EACH MAINTENANCE Photo1 Exit 2 Fixed Equipment Instance on 1st Floor Floor Finish Instance on 1st Floor VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Location/Instance Near Entrance, Near Servery Quantity 20 PB/A&W Page 17 of 36

18 Architectural Inspection INTERIOR CAFETERIA Floor Finish Photo1 NYC Department of Education Building Assessment Survey Near Entrance Sliding-folding Partition Instance on 1st Floor Stage Instance on 1st Floor Walls Instance on 1st Floor CERAMIC TILE: BROKEN/ MISSING Location/Instance Near Servery Quantity 10 Photo1 Near Servery Window Curtains/Shades/Blinds Instance on 1st Floor CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling Location/Instance Room 419 Quantity 10 PLASTER: CRACKS/SPALLING - ACTIVE LEAK Urgency of Action PRIORITY 5 PB/A&W Page 18 of 36

19 NYC Department of Education Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling Purpose of Action LEVEL 4 Photo1 Room H Door(s) 5 - Poor WOOD: DETERIORATED DOOR Location/Instance Main Entrance, Rooms 417, 408, 255 Quantity 5 EACH MAINTENANCE Photo1 Room 417 Floor Finish VINYL TILES: DETERIORATED SUBSTRATE Location/Instance Room 417 Quantity 10 PB/A&W Page 19 of 36

20 NYC Department of Education Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Floor Finish Photo1 Room 417 WOOD: DAMAGED/DETERIORATED Location/Instance Room 217 Quantity 10 Photo1 Room 217 VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Location/Instance Rooms 415, 413, 360, 317, 254 and others Quantity 140 Photo1 Room 407 PB/A&W Page 20 of 36

21 NYC Department of Education Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Floor Finish TERRAZZO: CRACKS Location/Instance Main Entrance, Corridor near Room Quantity 75 Photo1 Main Entrance Walls STONE: CRACKS/SPALLING Location/Instance Corridor near Room 153 Quantity 10 Photo1 Corridor near Room 153 PLASTER: CRACKS/SPALLING - ACTIVE LEAK Location/Instance Room 419 Quantity 10 Urgency of Action PRIORITY 5 Purpose of Action LEVEL 4 PB/A&W Page 21 of 36

22 NYC Department of Education Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Walls Photo1 Room H Specialties GYMNASIUM Instance on 3rd Floor Ceiling Instance on 3rd Floor Door(s) Instance on 3rd Floor 4 - Between Fair and Poor WOOD: DETERIORATED DOOR Location/Instance Rooms 354, 352 Quantity 2 EACH MAINTENANCE Photo1 Fixed Equipment Instance on 3rd Floor Floor Finish Instance on 3rd Floor Room 354 PB/A&W Page 22 of 36

23 Architectural Inspection INTERIOR GYMNASIUM Seating Instance on 3rd Floor Sliding-folding Partition Instance on 3rd Floor Stage Instance on 3rd Floor Walls Instance on 3rd Floor Window Curtains/Shades/Blinds Instance on 3rd Floor INTERIOR DOOR HARDWARE INTERIOR GUARDS KITCHEN Instance on 1st Floor Ceiling Instance on 1st Floor Door(s) Instance on 1st Floor Floor Finish Instance on 1st Floor Walls Instance on 1st Floor LIBRARY Instance on Room 103 Built-in Furnishing Instance on Room 103 Ceiling Instance on Room 103 Door(s) Instance on Room 103 NYC Department of Education Building Assessment Survey PB/A&W Page 23 of 36

24 NYC Department of Education Building Assessment Survey Architectural Inspection INTERIOR LIBRARY Door(s) Floor Finish Instance on Room 103 Walls Instance on Room 103 LOCKER ROOM Instance on 4th Floor Alternative use Yes Instance on 3rd Floor Alternative use Yes Ceiling Instance on 3rd Floor PLASTER: CRACKS/SPALLING Location/Instance Center Quantity 10 Photo1 Door(s) Instance on 3rd Floor Instance on 4th Floor Floor Finish Instance on 4th Floor Center PB/A&W Page 24 of 36

25 Architectural Inspection INTERIOR LOCKER ROOM Floor Finish Instance on 3rd Floor Locker Room Lockers Instance on 3rd Floor Instance on 4th Floor Walls Instance on 3rd Floor Instance on 4th Floor MULTI-PURPOSE ROOM SCIENCE DEMO ROOM Instance on Room 309 Alternative use Fixed Equipment Instance on Room 309 SCIENCE LAB SCIENCE PREP ROOM SHOWER ROOM Instance on 4th Floor Alternative use Ceiling Instance on 4th Floor Door(s) Instance on 4th Floor Floor Finish Instance on 4th Floor Walls Instance on 4th Floor STAIRS/RAMPS: INTERIOR Do Letter Stair Signs Exist? Ceiling Door(s) NYC Department of Education Building Assessment Survey No Yes Partially 5 - Poor PB/A&W Page 25 of 36

26 NYC Department of Education Building Assessment Survey Architectural Inspection INTERIOR STAIRS/RAMPS: INTERIOR Door(s) WOOD: DETERIORATED DOOR Location/Instance Stair AB/1 Quantity 3 EACH MAINTENANCE Photo1 Stair AB/1 METAL CLAD WOOD: DETERIORATED DOOR Location/Instance Stair CD/2,3,4 Quantity 3 EACH MAINTENANCE Photo1 Stair CD/4 Partition Railings Stairs and Landings Location/Instance Quantity Between Fair and Poor TERRAZZO: CRACKS Stair CD/1 PB/A&W Page 26 of 36

27 NYC Department of Education Building Assessment Survey Architectural Inspection INTERIOR STAIRS/RAMPS: INTERIOR Stairs and Landings Photo1 Stair CD/1 ROLLED ASPHALT: CRACKS Location/Instance Stair AB/Bulkhead Quantity 75 Photo1 Stair AB/Bulkhead STONE: WORN-OUT TREAD/NOSINGS Location/Instance Stair CD/1 Quantity 75 PB/A&W Page 27 of 36

28 Architectural Inspection INTERIOR STAIRS/RAMPS: INTERIOR Stairs and Landings Photo1 NYC Department of Education Building Assessment Survey Stair CD/1 Walls BRICK: CRACKS/SPALLING Location/Instance Stair E/1 Exit 9 Vestibule Quantity 10 Photo1 Stair E/1 Exit 9 Vestibule PLASTER: CRACKS/SPALLING Location/Instance Stair E/4 Quantity 25 Photo1 PB/A&W Page 28 of 36

29 Architectural Inspection INTERIOR STAIRS/RAMPS: INTERIOR Walls NYC Department of Education Building Assessment Survey Stair E/4 TOILET ROOMS - STAFF Ceiling Door(s) Floor Finish Stalls Walls TOILET ROOMS - STUDENTS Ceiling PLASTER: CRACKS/SPALLING Location/Instance Room 358 Quantity 10 Photo1 Door(s) Floor Finish Stalls Room 358 PB/A&W Page 29 of 36

30 NYC Department of Education Building Assessment Survey Architectural Inspection INTERIOR TOILET ROOMS - STUDENTS Stalls Walls LIFE SAFETY F.D. HOLDING AREA STEEL STAIRS SITE CONTAINERIZATION 5 - Poor CONTAINER DAMAGED Location/Instance North side of Building Quantity 1 EACH Photo1 North side of Building Drainage System for Asphalt Catch Basins/Manhole - Surrounded by asphalt 5 - Poor BLOCKED Location/Instance Near Exit 9 Quantity 1 EACH MAINTENANCE Photo1 No photo recorded Culverts - Asphalt Covering Drainage System for Concrete Catch Basins/Manhole - Surrounded by concrete Culverts - Concrete Covering PB/A&W Page 30 of 36

31 NYC Department of Education Building Assessment Survey Architectural Inspection SITE Drainage System for Soil DRINKING FOUNTAINS FENCES 4 - Between Fair and Poor CONCRETE CURB: DAMAGED/DETERIORATED Location/Instance Hobart Street Quantity 20 Photo1 Hobart Street CHAIN LINK: DAMAGED POST/RAIL Location/Instance Hobart Street, 50th Street Quantity 80 L.F. Photo1 Hobart Street WROUGHT IRON: DAMAGED/DETERIORATED Location/Instance Hobart Street, 31st Avenue, 50th Street Quantity 720 PB/A&W Page 31 of 36

32 Architectural Inspection SITE FENCES Photo1 NYC Department of Education Building Assessment Survey Hobart Street IRRIGATION SYSTEM PAVING Student Non-Use Gravel Exists? Yes Asphalt Inaccessible Concrete 3 - Fair CRACKS - MAJOR Location/Instance 31st Avenue Quantity 50 Photo1 31st Avenue Pavers Student Use Gravel Exists? Asphalt Location/Instance Quantity 50 No 4 - Between Fair and Poor LOCALIZED SINK AREA Schoolyard REPAIR PB/A&W Page 32 of 36

33 NYC Department of Education Building Assessment Survey Architectural Inspection SITE PAVING Student Use Asphalt Photo1 Schoolyard CRACKS - MAJOR Location/Instance Schoolyard Quantity 500 Photo1 Schoolyard Concrete Pavers Site Sidewalks & Walkways Asphalt Location/Instance Quantity Fair CRACKS - MAJOR North side of Building PB/A&W Page 33 of 36

34 NYC Department of Education Building Assessment Survey Architectural Inspection SITE PAVING Site Sidewalks & Walkways Asphalt Photo1 North side of Building Concrete Pavers DOT Sidewalk Asphalt Concrete 4 - Between Fair and Poor HEAVING Location/Instance Hobart Street Quantity 50 Photo1 Hobart Street DAMAGED/DETERIORATED/MISSING SECTIONS Location/Instance Hobart Street, 31st Avenue, 50th Street Quantity 775 PB/A&W Page 34 of 36

35 Architectural Inspection SITE PAVING DOT Sidewalk Concrete Photo1 NYC Department of Education Building Assessment Survey Hobart Street Pavers PLAYGROUNDS Instance on Schoolyard Benches Instance on Schoolyard Fence Instance on Schoolyard Pavement Instance on Schoolyard Play Equipment Instance on Schoolyard Safety Surfacing Instance on Schoolyard 3 - Fair DETERIORATED/MISSING Location/Instance Center, North and South Side Quantity 180 Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 Center Unpaved Area PB/A&W Page 35 of 36

36 Architectural Inspection SITE PLAYGROUNDS Unpaved Area Instance on Schoolyard PLAYING SURFACE RETAINING WALLS Are there any Retaining Walls 6' OR higher facing public street/sidewalk? Location/Instance Quantity 10 No 3 - Fair CAST IN PLACE CONCRETE: DETERIORATED EXPANSION JOINT Schoolyard L.F. Photo1 NYC Department of Education Building Assessment Survey Schoolyard CAST IN PLACE CONCRETE: CRACKS/SPALLING - MINOR Location/Instance North side of Schoolyard Quantity 25 REPAIR Photo1 No photo recorded SEATING Benches Concrete Metal/Wood/Plastic Bleachers SITE WALLS (NOT RETAINING WALLS) STAIRS/RAMPS: EXTERIOR PB/A&W Page 36 of 36