New Jersey Chapters July NEC updates. The Association of Electrical and Medical Imaging Equipment Manufacturers

Size: px
Start display at page:

Download "New Jersey Chapters July NEC updates. The Association of Electrical and Medical Imaging Equipment Manufacturers"

Transcription

1 New Jersey Chapters July NEC updates The Association of Electrical and

2 2016 NFPA CAMs 43 NITMAM (Notice Intent To Make a Motion) Certified Amending Motions (CAMs) submitted for NFPA CAMs passed the Floor Vote The New Process of Inputs/Comments PI/PC led to First Drafts and Second Drafts: Rules and Regulations limit new language during this process due to lack of public review CMPs are restricted to the actions of the PCs and PIs. There may be PI and PC submitted by the Panels. TIAs are automatically submitted as inputs.

3 CAM Results of interest Failed - AFCI 2014 language remains (Results - AFCI System remains and no expansion ) (F) Passed - There was new language restricting the number of Feeders to sizes 1/0 or larger (Results - Taken out, all sizes are allowed to be considered ) (D) Passed - Language to require Service Disconnects Outside (removed requirement, previous language remains) Passed - requirement for increasing wire EGC was limited to Voltage Drop only when increasing ungrounded Conductors (all considerations, i.e. correction factors will require EGC to be increased)

4 CAM Results of interest (cont) Failed - Cablebus ampacities are now subject to ampacity tables and not Free Air tables ( Second Draft remains as-is) Passed - Tray Cable allowed in C1-D1 locations (removed) purview problems? 520.4(5) Cords on the Floor, language would have allowed BC and Feeder cables (art 400) to be on the ground (Removed language) Transcription correction All information on the meeting results on the Next Edition tab for NFPA 70

5 ARTICLE 300 HIGHLIGHTS Table burial depth for LV wiring as per instruction Table all Non-metallic raceways not suitable for direct buried EMT to provide Physical protection Conductors added to list of backfill requirements Spare raceways SEALED Sealing other with conductors must be compatible/ identified Expansion, Expansion/Deflection, deflection include a one for all product (B) Ducts Specifically Fabricated for Environmental Air

6 300.5(A) Burial Tables (LV) Footnote a to Table A lesser depth shall be permitted where specified in the installation instructions of a listed low voltage lighting system. Note 5 to Table Where solid rock prevents compliance with the cover depths specified in this table, the wiring shall be installed in a metal raceway, or a nonmetallic raceway permitted for direct burial. The raceways shall be covered by a minimum of 50 mm (2 in.) of concrete extending down to rock

7 300.5(B), Wet Locations Raceways and Enclosures (B) Wet Locations. The interior of enclosures or raceways installed underground shall be considered to be a wet location. Insulated conductors and cables installed in these enclosures or raceways in underground installations shall comply with (C). Any connections or splices in an underground installation shall be approved for wet locations. Already addressed in The requirement still exists!

8 300.5(D)(4) Protection from Damage EMT added to the list of protection Raceways or equiv. to provide physical protection

9 300.7(B) new Expansion/Deflection

10 300.5(F) Backfill Add Conductors to the list of products to consider damage to; Provide Sand, Sleeves, etc

11 300.5(G) Spare Raceways (Sealed) Conduits or raceways through which moisture may contact live parts shall be sealed or plugged at either or both ends. Spare or unused raceways shall also be sealed. Sealants shall be identified for use with the cable insulation, conductor insulation, bare conductor, shield, or other components.

12 300.22(B) Ducts: wiring methods (B) Ducts Specifically Fabricated for Environmental Air. Equipment, devices, and the wiring methods specified in this section shall be permitted within such ducts only if necessary for the direct action upon, or sensing of, the contained air. Where equipment or devices are installed and illumination is necessary to facilitate maintenance and repair, enclosed gasketed-type luminaires shall be permitted. Only wiring methods consisting of Type MI cable without an overall nonmetallic covering, Type MC cable employing a smooth or corrugated impervious metal sheath without an overall nonmetallic covering, electrical metallic tubing, flexible metallic tubing, intermediate metal conduit, or rigid metal conduit without an overall nonmetallic covering shall be installed in ducts specifically fabricated to transport environmental air. Flexible metal conduit shall be permitted, in lengths not to exceed 1.2 m (4 ft), to connect physically adjustable equipment and devices permitted to be in these fabricated ducts. The connectors used with flexible metal conduit shall effectively close any openings in the connection. Exception: Wiring methods and cabling systems, listed for use in other spaces used for environmental air (plenums), shall be permitted to be installed in ducts specifically fabricated for environmental air-handling purposes under the following conditions: (1) The wiring methods or cabling systems shall be permitted only if necessary to connect to equipment or devices associated with the direct action upon or sensing of the contained air, and (2) The total length of such wiring methods or cabling systems shall not exceed 1.2 m (4 ft).

13

14 300.22(C)(3) Equipment in Other Spaces (returns?) (3) Equipment. Electrical equipment with a metal enclosure, or electrical equipment with a nonmetallic enclosure listed for use within an air-handling space and having adequate fire-resistant and low-smoke-producing characteristics low smoke and heat release properties, and associated wiring material suitable for the ambient temperature shall be permitted to be installed in such other space unless prohibited elsewhere in this Code. Informational Note: One method to determine low smoke and heat release properties is that the equipment exhibits a maximum peak optical density of 0.50 or less, an average optical density of 0.15 or less, and a peak heat release rate of 100kW or less when tested in accordance with ANSI/UL , Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces. Exception: Integral fan systems shall be permitted where specifically identified for use within an air-handling space.

15 Article 590 Temporary Wiring Highlights Section SE Cable permitted uses Termination points GFCI protection on Generator Receptacles

16 590.4 (B) Temporary Installations Wiring methods Added SE and SER to the list of methods for wiring feeders and Branch circuits and allows SE in PVC underground. Feeders and Branch Ckts

17 Section 590.4(G) (box exclusions) splices Non-metallic cord or cable assemblies need not have a box for splices, Metallic Sheathed assemblies must have listed fittings w/o a box (G) Splices. A box, conduit body, or other enclosure, with a cover installed, shall be required for all splices except where: (1) The circuit conductors being spliced are all from nonmetallic multiconductor cord or cable assemblies, provided that the equipment grounding continuity is maintained with or without the box. (2) The circuit conductors being spliced are all from metal sheathed cable assemblies terminated in listed fittings that mechanically secure the cable sheath to maintain effective electrical continuity.

18 Section (A)(1) Generator Receptacle(TIA) (1) Receptacle Outlets Not Part of Permanent Wiring. All 125-volt, single-phase, 15-, 20-, and 30-ampere receptacle outlets that are not a part of the permanent wiring of the building or structure and that are in use by personnel shall have groundfault circuit-interrupter protection for personnel. Listed In addition to this required ground-fault circuit-interrupter protection for personnel, listed cord sets or devices incorporating listed ground-fault circuit-interrupter protection for personnel identified for portable use shall be permitted. (3) Generators older than Jan 1,, 2011 can use the Listed GFCI Cord Sets for portable use(less than 15kW)

19 312.5(C) cables, enclosures Number of Conductors and/or Cables // Cross Sectional Area (%) # % Over 2 40 Note 2: Table 1 applies only to complete conduit or tubing systems and is not intended to apply to sections of conduit or tubing used to protect exposed wiring from physical damage.

20 Section 312.5(C) Cabinets, Cutout Boxes, and Meter Socket Encl (C)Exc (g) Where installed as conduit or tubing, the cable fill does not exceed the amount that would be permitted for complete conduit or tubing systems by Table 1 of Chapter 9 of this Code and all applicable notes thereto. Chapter 9, Table 1, Note 2 does not apply to this condition. Informational Note: See Table 1 in Chapter 9, including Note 9, for allowable cable fill in circular raceways. See (B)(3) (a) for required ampacity reductions for multiple cables installed in a common raceway

21 312.6 (A) added Compact Aluminum to Deflection Table for width of Gutters

22 312.6 (A) Compact Aluminum

23 Section (Listed Equipment) 75% rule

24 Section Damp and Wet Locations

25 Section (A) Barriers (A) include Barriers in the way you calculate box fill Barriers take up space ½ in³ (metal) 1 in³ (plastic) Each space separate when calculating

26 Section Conductors entering Box NM/UF cable 1/4 in the METAL box No clear rule set for metal as is for Plastic

27 Section revised definition of receptacle (CMP 18)Changed how to interpret.27 The definition of receptacle was going through a change which drove the changes in 314 in the first draft. A contact device installed at the outlet for the connection of an attachment plug, or for the direct connection of electrical utilization equipment designed to mate with the corresponding contact device. A single receptacle is a single contact device with no other contact device on the same yoke. A multiple receptacle is two or more contact devices on the same yoke. (CMP-18)

28 Section (E) Separable Attachment Fittings (E) Separable Attachment Fittings. Outlet boxes required in shall be permitted to support listed locking support and mounting receptacles used in combination with compatible attachment fittings designed for the support of equipment covered within and subject to all weight and orientation limits contemplated by the listing. Where such fittings are used, the equipment mounted shall comply with (A) through (D) as applicable.. The combination shall be identified for the support of equipment within the weight and mounting orientation limits of the listing. Where the supporting receptacle is installed within a box, it shall be included in the fill calculation covered in (B)(4).

29

30 Section (A)(3) #4 AWG or larger Where the permitted combinations of conductors for which the box or conduit body has been listed are less than the maximum conduit or tubing fill permitted by Table 1 of Chapter 9, the box or conduit body shall be permanently marked with the maximum number and maximum size of conductors permitted. For other conductor sizes and combinations, the total cross-sectional area of the fill shall not exceed the crosssectional area of the conductors specified in the marking, based on the type of conductor identified as part of the product listing. Informational Note: Unless otherwise specified, the applicable product standards evaluate the fill markings covered here based on conductors with Type XHHW insulation.

31 Section (A)(3) #4 AWG or larger Any combination of wire must be calculated not to exceed the permitted fill with the max wires size on the conduit body All conductors must use XHHW insulation Values from Chapter 9

32 Section (E)(1) Power Distro Block suitable for the purpose (1) Installation. Power distribution blocks installed in boxes shall be listed. Power distribution blocks installed on the line side of the service equipment shall be listed and marked suitable for use on the line side of service equipment or equivalent. Some are not listed If they are they have to be marked as per QPQS

33 Section (E)(1)Power Distro Block Line Side Marking

34 Section Def. Outlet Box Hood. A housing shield intended to fit over a faceplate for flush-mounted wiring devices, or an integral component of an outlet box or of a faceplate for flushmounted wiring devices. The hood does not serve to complete the electrical enclosure; it reduces the risk of water coming in contact with electrical components within the hood, such as attachment plugs, current taps, surge protective devices, direct plug-in transformer units, or wiring devices. It is commonly known as a bubble cover.

35 406.3(E) Controlled Receptacles E) Controlled Receptacle Marking. All nonlocking-type, 125-volt, 15- and 20-ampere receptacles that are controlled by an automatic control device, or that incorporate control features that remove power from the receptacle for the purpose of energy management or building automation, shall be permanently marked with the symbol shown in Figure 406.3(E) and the word controlled. For receptacles controlled by an automatic control device, the marking shall be located on the receptacle face and visible after installation. In both cases where a multiple receptacle device is used, the required marking of the word controlled and symbol shall denote which contact device(s) are controlled.

36 406.3(E) Controlled Receptacles

37 Section 406.3(F) USB (F) Receptacle with USB Charger. A 125-volt 15- or 20-ampere receptacle that additionally provides Class 2 power shall be listed and constructed such that the Class 2 circuitry is integral with the receptacle. Supplement SF to the Standard 498, Receptacles

38 406.4(D) Replacements (4) Arc-Fault Circuit-Interrupter Protection. Where a receptacle outlet is located in any areas specified in (A) or (B), a replacement receptacle at this outlet shall be one of the following: 1) A listed outlet branch-circuit type arc-fault circuit-interrupter receptacle 2) A receptacle protected by a listed outlet branch-circuit type arc-fault circuitinterrupter type receptacle 3) A receptacle protected by a listed combination type arc-fault circuit-interrupter type circuit breaker Exception No. 1: Arc-fault circuit-interrupter protection shall not be required where all of the following apply: 1) The replacement complies with 406.4(D)(2)(b). 2) It is impracticable to provide an equipment grounding conductor as provided by (C). 3) A listed combination type arc-fault circuit-interrupter circuit breaker is not commercially available. FPE 4) GFCI/AFCI dual function receptacles are not commercially available. Exception No. 2: Section (B), Exception shall not apply to replacement of receptacles. (Dorms)

39 Dual Function Device AFCI/GFCI Available Now!

40 406.9(B) Rect. Wet Locations Exception: 15- and 20-ampere, 125- through 250-volt receptacles installed in a wet location and subject to routine high-pressure spray washing shall be permitted to have an enclosure that is weatherproof when the attachment plug is removed. All 15- and 20-ampere, 125- and 250-volt nonlocking-type receptacles shall be listed and so identified as the weatherresistant type. Informational Note No. 2: The configuration of weather-resistant receptacles covered by this requirement are identified as 5-15, 5-20, 6-15, and 6-20 in ANSI/NEMA WD , Standard for Dimensions of Attachment Plugs and Receptacles

41 TR Receptacles Dwelling units in all areas specified in and Guest rooms and guest suites of hotels and motels Child care facilities Preschools and elementary education facilities Business offices, corridors, waiting rooms and the like in clinics, medical and dental offices and outpatient facilities Subset of assembly occupancies described in Article to include places of waiting transportation, gymnasiums, skating rinks, and auditoriums Dormitories Informational Note: This requirement would include receptacles identified as 5-15, 5-20, 6-15, and 6-20 in ANSI/NEMA WD , Wiring Devices Dimensional Specifications. Exception to (1), (2), (3), (4), (5), (6), and (7): Receptacles in the following locations shall not be required to be tamper resistant: Receptacles located more than 1.7 m (5 1 2 ft) above the floor Receptacles that are part of a luminaire or appliance A single receptacle or a duplex receptacle for two appliances located within the dedicated space for each appliance that, in normal use, is not easily moved from one place to another and that is cord-and-plug-connected in accordance with (A)(6), (A)(7), or (A)(8) Nongrounding receptacles used for replacements as permitted in 406.4(D)(2)(a)

42 Article 404 Switches Section 404.2(C) Clarifies what rooms must be included in the list of areas to include a Grounded Circuit Conductor at the switch location. Includes a requirement to use the Grounded Wire for electronic switching and is addressed in Electronic Lighting Control Switches There will be a deadline for new products to be used in the field: January 1, 2020 This will allow the devices with a green wire to go through a product standard change and replace with a White Wire.

43 Electronic Lighting Control Switches. Electronic lighting control switches shall be listed. Electronic lighting control switches shall not introduce current on the equipment grounding conductor during normal operation. The requirement to not introduce current on the equipment grounding conductor shall take effect on January 1, Exception: Electronic lighting control switches that introduce current on the equipment grounding conductor shall be permitted for applications covered by 404.2(C), Exception. Electronic lighting control switches that introduce current on the equipment grounding conductor shall be listed and marked for use in replacement or retrofit applications only.

44 404.2(C) (C) Switches Controlling Lighting Loads. The grounded circuit conductor for the controlled lighting circuit shall be installed at the location where switches control lighting loads that are supplied by a grounded general-purpose branch circuit serving bathrooms, hallways, stairways, or rooms suitable for human habitation or occupancy as defined in the applicable building code. Where multiple switch locations control the same lighting load such that the entire floor area of the room or space is visible from the single or combined switch locations, the grounded circuit conductor shall only be required at one location. A grounded conductor shall not be required to be installed at lighting switch locations under any of the following conditions: Where conductors enter the box enclosing the switch through a raceway, provided that the raceway is large enough for all contained conductors, including a grounded conductor Where the box enclosing the switch is accessible for the installation of an additional or replacement cable without removing finish materials Where snap switches with integral enclosures comply with (E) Where lighting in the area is controlled by automatic means Where a switch controls a receptacle load The grounded conductor shall be extended to any switch location as necessary and shall be connected to switching devices that require line-to-neutral voltage to operate the electronics of the switch in the standby mode and shall meet the requirements of EX. cont

45 404.2(C) Ex. Exception: The connection requirement shall become effective on January 1, It shall not apply to replacement or retrofit switches installed in locations prior to local adoption of 404.2(C) and where the grounded conductor cannot be extended without removing finish materials. The number of electronic lighting control switches on a branch circuit shall not exceed five, and the number connected to any feeder on the load side of a system or main bonding jumper shall not exceed 25. For the purpose of this exception, a neutral busbar, in compliance with 200.2(B) and to which a main or system bonding jumper is connected shall not be limited as to the number of electronic lighting control switches connected. Informational Note: The provision for a (future) grounded conductor is to complete a circuit path for electronic lighting control devices.

46 NEW JERSEY IAEI, JULY 12, 2016 Thanks for your time

47

48