RAMAPO COLLEGE OF NEW JERSEY PHASE II HOUSING REHABILITATION C 2012

Size: px
Start display at page:

Download "RAMAPO COLLEGE OF NEW JERSEY PHASE II HOUSING REHABILITATION C 2012"

Transcription

1 SECTION LOUVERS AND VENTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes the following: 1. Fixed metal wall louvers. B. Related Sections: The following Sections contain requirements that relate to this Section: 1. Division 7 Section "Joint Sealants" for sealants installed in perimeter joints between louver frames and adjoining construction. 2. Division 15 Section for ductwork connected to metal wall louvers. 1.3 DEFINITIONS A. Louver Terminology: Refer to Air Movement and Control Association (AMCA) 501 for definitions of terms for metal louvers not otherwise defined in this Section or in referenced standards. 1.4 PERFORMANCE REQUIREMENTS A. Structural Performance: Engineer, fabricate, and install exterior metal wall louvers to withstand the effects of loads and stresses from wind and normal thermal movement without evidencing permanent deformation of louver components including blades, frames, and supports; noise or metal fatigue caused by louver blade rattle or flutter; or permanent damage to fasteners and anchors. 1. Wind Load: Uniform pressure (velocity pressure) of 20 lbf per sq. ft. (960 Pa), acting inwards or outwards. 2. Normal thermal movement is defined as that resulting from the following maximum change (range) in ambient temperature. Base design calculations on actual surface temperatures of metals due to both solar heat gain and nighttime sky heat loss. a. Temperature Change (Range): 100 deg F (56 deg C). B. Air-Performance, Water-Penetration, and Air-Leakage Ratings: Provide louvers complying with performance requirements indicated as demonstrated by testing manufacturer's stock units of height and width indicated. Test units according to AMCA Perform testing on unpainted, cleaned, degreased units. 2. Perform water-penetration testing on louvers without screens. 3. Equivalent Air-Performance Ratings: Louvers having less free area than that specified or having a lower free area velocity at the static pressure loss specified may be considered for the Work provided their total air performance is equivalent to that specified. The burden of proof of equivalency is on the Contractor. For louvers to be considered equivalent, the product of their free area, for the size specified, and their free area velocity at the static pressure loss specified must be at least equal to the product of the specified free area and velocity. Also, their free area velocity at the static pressure loss specified must not result in water penetration of more than 0.01 oz. per sq. ft. (3.1 g/sq. m) of free area, and they must meet all other requirements. C. Airborne Sound Transmission Loss: Provide acoustical louvers complying with airborne sound transmission loss ratings indicated, as demonstrated by testing manufacturer's stock units according to ASTM E SUBMITTALS A. General: Submit each item in this Article according to the Conditions of the Contract and Division 1 Specification Sections. LOUVERS AND VENTS Page 1 of 5

2 B. Product data for each type of product specified. C. Shop drawings of louver units and accessories. Include plans, elevations, sections, and details showing profiles, angles, and spacing of louver blades; unit dimensions related to wall openings and construction; free areas for each size indicated; profiles of frames at jambs, heads, and sills; and anchorage details and locations. 1. For installed products indicated to comply with certain design loadings, include structural analysis data sealed and signed by the qualified professional engineer who was responsible for their preparation. D. Samples for initial selection in the form of manufacturer's color charts showing the full range of colors available for units with factory-applied color finishes. E. Samples for verification of each type of metal finish required, prepared on samples of same thickness and material indicated for final unit of Work. Where finishes involve normal color and texture variations, include sample sets showing the full range of variations expected. F. Product test reports evidencing compliance of units with performance requirements indicated. G. Product certificates signed by louver manufacturers certifying that their products comply with the specified requirements and are licensed to bear the AMCA seal based on tests made according to AMCA 500 and complying with the AMCA Certified Ratings Program. H. Qualification data for firms and persons specified in the "Quality Assurance" Article to demonstrate their capabilities and experience. 1.6 QUALITY ASSURANCE A. Single-Source Responsibility: Obtain louvers and vents from one source and by a single manufacturer where alike in one or more respects regarding type, design, and factory-applied color finish. B. Welding Standards: Comply with applicable provisions of D1.3 "Structural Welding Code--Sheet Steel." 1. Certify that each welder has satisfactorily passed AWS qualification tests for welding processes involved and, if pertinent, has undergone recertification. C. Engineer Qualifications: A professional engineer legally authorized to practice in the jurisdiction where the Project is located and experienced in providing engineering services of the kind indicated that have resulted in the installation of louvers similar to this Project in material, design, and extent and that have a record of successful in-service performance. D. SMACNA Standard: Comply with SMACNA "Architectural Sheet Metal Manual" recommendations for fabrication, construction details, and installation procedures. 1.7 PROJECT CONDITIONS A. Field Measurements: Check actual louver openings by accurate field measurements before fabrication, and show recorded measurements on final shop drawings. Coordinate fabrication schedule with construction progress to avoid delaying the Work. 1. Where field measurements cannot be made without delaying the Work, guarantee opening dimensions and proceed with fabricating louvers without field measurements. Coordinate construction to ensure that actual opening dimensions correspond to guaranteed dimensions. PART 2 - PRODUCTS 2.1 MATERIALS A. Galvanized-Steel Sheet: ASTM A 526 or ASTM A 527, G90 zinc coating, mill phosphatized. B. Stainless-Steel Sheet: ASTM A 167, Type 302 or 304. LOUVERS AND VENTS Page 2 of 5

3 C. Fasteners: 300 series stainless steel. 1. Use stainless steel tamper-proof security flat-head screws for exposed fasteners. D. Anchors and Inserts: Of type, size, and material required for type of loading and installation indicated. Use stainless steel anchors and inserts for exterior installations and elsewhere as required for corrosion resistance. Use toothed steel or expansion bolt devices for drilled-in-place anchors. 2.2 FABRICATION, GENERAL A. General: Fabricate louvers and vents to comply with requirements indicated for design, dimensions, materials, joinery, and performance. B. Assemble louvers in shop to minimize field splicing and assembly. Disassemble units as necessary for shipping and handling limitations. Clearly mark units for reassembly and coordinated installation. C. Maintain equal louver blade spacing to produce uniform appearance. D. Fabricate frames, including integral sills, to fit in openings of sizes indicated, with allowances made for fabrication and installation tolerances of louvers, adjoining construction, and perimeter sealant joints. E. Include supports, anchorages, and accessories required for complete assembly. F. Provide vertical mullions of type and at spacings indicated but not more than recommended by manufacturer, or 72 inches (1830 mm) o.c., whichever is less. At horizontal joints between louver units, provide horizontal mullions except where continuous vertical assemblies are indicated. G. Provide sill extensions and loose sills made of same material as louvers where indicated or required for drainage to exterior and to prevent water penetrating to interior. H. Join frame members to one another and to fixed louver blades as follows, unless otherwise indicated or size of louver assembly makes bolted connections between frame members necessary: 1. With fillet welds, concealed from view. 2.3 FIXED, FORMED-METAL WALL LOUVERS A. Horizontal, Non-drainable, Fixed-Blade Louvers: Frames and louver blades fabricated from metal of kind and in form indicated below; complying with the following requirements: 1. Blade Metal and Thickness: Steel sheet, inch, unless otherwise indicated. 2. Frame Metal and Thickness: Same as louver blades, unless otherwise indicated. 3. Louver Depth: 12 inches, unless otherwise indicated. 4. Frame Type: As indicated. 5. Blade Profile: As indicated. 6. Blade Angle: 45 degrees, unless otherwise indicated. 7. Performance Requirements: As follows, determined by testing units 48 inches (1220 mm) wide by 48 inches (1220 mm) high per AMCA 500: a. Free Area: Not less than 6.40 sq. ft. (0.595 sq. m). b. Static Pressure Loss: Not more than 0.15 inch wg (37 Pa) at an airflow of 900 fpm (4.57 m/s) free area intake velocity. c. Water Penetration: Not more than 0.01 oz. per sq. ft. (3.1 g/sq. m) of free area at an airflow of 700 fpm (3.56 m/s) free area velocity when tested for 15 minutes. 8. AMCA Seal: Mark units with the AMCA Certified Ratings Seal. 2.4 LOUVER SCREENS A. General: Provide louvers with screens at locations indicated. B. General: Provide each exterior louver with louver screens complying with the following requirements: LOUVERS AND VENTS Page 3 of 5

4 1. Screen Location for Fixed Louvers: Interior face, unless otherwise indicated. 2. Screening Type: Insect screening where indicated. C. Secure screens to louver frames with tamper-proof security stainless-steel machine screws, spaced 2 inches maximum from each corner and 6 inches o.c. D. Louver Screen Frames: Fabricate screen frames with mitered corners to louver sizes indicated and to comply with the following requirements: 1. Metal: Same kind and form of metal as indicated for louver frames to which screens are attached. 2. Finish: Same finish as louver frames to which louver screens are attached. 3. Type: Non-rewireable, U-shaped frames for permanently securing screen mesh. E. Louver Screening for Galvanized-Steel Louvers: Fit galvanized-steel louver screen frames with screening and complying with the following requirements: 1. Insect Screening: 18-by-18 mesh formed with inch diameter stainless-steel wire. 2.5 BLANK-OFF PANELS A. General: Fabricate blank-off panels from materials and to sizes indicated and to comply with the following requirements: 1. Finish: Match finish applied to louvers with respect to coating type, color, and gloss. a. Color: As indicated. 2. Attach blank-off panels to back of louver frames with clips. 3. Attach blank-off panels to back of louver frames with tamper-proof security stainless-steel sheet-metal screws. B. Insulated, Blank-Off Panels: Laminated metal-faced panels consisting of insulating core surfaced on back and front with metal sheets, complying with the following requirements: 1. Thickness: 2 inches (50 mm). 2. Metal Facing Sheets: As indicated. 3. Insulating Core: Unfaced, rigid, glass-fiberboard insulation complying with ASTM C 612, Class 1 and Edge Treatment: Trim perimeter edges of blank-off panels with louver manufacturer's standard channel frames inch (2.06 mm) thick, with corners mitered and with same finish as panels. 5. Seal perimeter joints between panel faces and louver frames with 1/8-inch-by-l-inch (3.2-mmby-25-mm) polyvinyl chloride compression gaskets. 2.6 FINISHES, GENERAL A. Comply with NAAMM "Metal Finishes Manual" for recommendations relative to applying and designating finishes. 2.7 GALVANIZED-STEEL SHEET FINISHES A. Surface Preparation: Clean surfaces of dirt, grease, and other contaminants followed by a conversion coating of the type suited to the organic coating applied over it. Clean welds, mechanical connections, and abraded areas followed by an application of galvanizing repair paint to comply with ASTM A 780. B. Baked-Enamel Finish: Immediately after cleaning and pretreating, apply manufacturer's standard 2- coat, baked-enamel finish consisting of prime coat and thermosetting topcoat, with not less than a 1.0-mil (0.025-mm) dry film thickness for topcoat. Comply with paint manufacturer's instructions for applying and baking to achieve a minimum dry film thickness of 2.0 mils (0.051 mm). 1. Color and Gloss: As selected by Architect from manufacturer's full range of choices for color and gloss. Color to match cement fiber panels for each specific building color. LOUVERS AND VENTS Page 4 of 5

5 PART 3 - EXECUTION 3.1 PREPARATION A. Coordinate setting drawings, diagrams, templates, instructions, and directions for installation of anchorages that are to be embedded in concrete and masonry construction; or installed in prefabricated metal cells. Coordinate delivery of such items to Project site and the prefabrication plant. 3.2 INSTALLATION A. Locate and place louver units plumb, level, and at indicated alignment with adjacent work. B. Use concealed anchorages where possible. Provide stainless steel fitted to tamper-proof security screws where required to protect metal surfaces and to make a weathertight connection. C. Form closely fitted joints with exposed connections accurately located and secured. D. Provide perimeter reveals and openings of uniform width for sealants and joint fillers, as indicated. E. Repair finishes damaged by cutting, welding, soldering, and grinding operations required for fitting and jointing. Restore finishes so there is no evidence of corrective work. Return items that cannot be refinished in the field to the shop, make required alterations, and refinish entire unit, or provide new units. F. Protect galvanized- and nonferrous-metal surfaces from corrosion or galvanic action by applying a heavy coating of bituminous paint on surfaces that will be in contact with concrete, masonry, or dissimilar metals. G. Install concealed gaskets, flashings, joint fillers, and insulation, as louver installation progresses, where required to make louver joints weathertight. Comply with Division 7 Section "Joint Sealants" for sealants applied during installation of louver. 3.3 ADJUSTING AND PROTECTION A. Protect louvers and vents from damage of any kind during construction period including use of temporary protective coverings where needed and approved by louver manufacturer. Remove protective covering at time of Substantial Completion. B. Restore louvers and vents damaged during installation and construction period, so that no evidence remains of correction work. If results of restoration are unsuccessful, as judged by Architect, remove damaged units and replace with new units. 1. Clean and touch up minor abrasions in finishes with air-dried coating that matches color and gloss of, and is compatible with, factory-applied finish coating. C. Test operation of adjustable wall louvers and adjust as needed to produce fully functioning units that comply with requirements. 3.4 CLEANING A. Periodically clean exposed surfaces of louvers and vents that are not protected by temporary covering to remove fingerprints and soil during construction period. Do not let soil accumulate until final cleaning. B. Before final inspection, clean exposed surfaces with water and a mild soap or detergent not harmful to finishes. Rinse surfaces thoroughly and dry. END OF SECTION LOUVERS AND VENTS Page 5 of 5