NYC Department of Education

Size: px
Start display at page:

Download "NYC Department of Education"

Transcription

1 Architectural Inspection Building Assessment Survey Asset: I.S. 364 AX (POOL&GYM)-BROOKLYN, 1540 VAN SICLEN AVE, New York, Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior :19 AM :50 AM AA : Architectural - Associate :27 AM :19 PM Asset Data Was the building fully accessible for inspection Inspection Access Comment Principal(s) Information Custodian Fireman Principal Name Organization Did you meet with this Principal? Did this Principal provide feedback? Summary of Principal's Feedback Answer Building Square Footage 14,000 Comments on the Area Comments on the Stories (Floors) plus Basements 2+B Comments on the Number of Classrooms 0 Comments on the Year Built 1978 Student Population 354 Staff Population 0 Weather Facade Photo Foundation Walls, Pool Roof Structure, Basement Pool Mechanical Equipment Areas, MER HV-17. Nicole Fraser Edmund I.S. 364 Annex (Pool and Gymnasium) - Brooklyn The Principal had no specific concerns regarding the physical conditions of the building at this time. Was not present Frank Viscuso (Operations Manager) Approximately 100,000 SF Total Building (14,000 SF Leased) Fair Van Siclen Avenue - Southwest view PB/A&W Page 1 of 17

2 Main Entrance Photo Building Assessment Survey Roof Photo Facade A - Van Siclen Avenue Have any Systems/Major Building Components been upgraded? Roof 1 - West view Systems: Year: Systems: Complete Swimming Pool Room, Swimming Pools and Pool Equipment Room renovation 2017 (ongoing) Limited Roofing repairs; Limited Corridor Flooring replacement; Limited Gymnasium Doors replacement Year: 2015 Systems: Limited Swimming Pool upgrades including Pool Lining and Pool Walls Year: 2013 Systems: New Exterior Doors (main entrance) Year: 2011 Have there been any New Building Additions? Tandem Schools? Leased Space? Year Leased 1995 Inspection Partial Inspection Priority Priority Exist Last Year? Priority Category Description Component Affected Location Description Person(s) tified Person(s) Title PhotoImage PB/A&W Page 2 of 17

3 Last Year? condition recorded Structural Engineer Required Building Assessment Survey Structural Type Description Component Affected Location Description Person(s) tified Person(s) Title PhotoImage condition recorded Accessibility Accessibility Status Is the primary or secondary entrance on an accessible route? Is the building a multi-story building? Are all floors of the building accessible through compliant means? Accessible classrooms exists on each floor? Boys and Girls or Unisex accessible toilets exist on at least every other floor? If the following spaces exist, are they ALL accessible? Art Room, Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs Physical Breakdown Structure Exists Complies Required FUNCTIONAL ACCESSIBILITY Exterior Routes Exterior Entrances & Exits Exterior H/C Lifts Exterior Ramps and Railings Interior Routes Corridor and Lobby H/C Lifts Interior Corridor Doors and Hardware Interior Corridors and Lobbies Interior Elevators Interior Lobby Doors and Hardware Interior Ramps Rooms & Spaces Art Rooms Auditorium Cafeteria Classrooms Computer Rooms Gymnasium 1st Floor Library Main Office Multi-purpose Room Nurse's Room Pool 1st Floor - Main, 1st Floor - Training Science Lab Toilet Rooms (Boys) 1st Floor Toilet Rooms (Girls) 1st Floor Toilet Rooms (Staff) PB/A&W Page 3 of 17

4 Building Template Building Assessment Survey Inspection Architectural AREAWAY AWNINGS AND CANOPIES t Required 3 - Fair METAL: WATER PENETRATION Quantity 50 REPAIR Urgency of Action PRIORITY 5 Photo1 PB/A&W Page 4 of 17

5 AWNINGS AND CANOPIES CHIMNEY COPING Building Assessment Survey Facade A above the main entrance METAL: OPEN TRANSVERSE JOINTS WITH DAMAGED CAULKING Quantity 20 L.F. MAINTENANCE Photo1 CORNICE DOORS DOORS AND FRAMES Roof 2 at Facade A 4 - Between Fair and Poor METAL: DETERIORATED DOOR - MAJOR DETERIORATION PB/A&W Page 5 of 17

6 Building Assessment Survey Architectural Inspection DOORS DOORS AND FRAMES Quantity 2 EACH Urgency of Action PRIORITY 4 Photo1 Facade C METAL: DETERIORATED DOOR AND FRAME - MINOR DETERIORATION Quantity 2 EACH MAINTENANCE Photo1 photo recorded DOOR HARDWARE LINTELS 3 - Fair STEEL: MINOR RUSTING PB/A&W Page 6 of 17

7 DOORS LINTELS Building Assessment Survey Quantity 10 L.F. REPAIR Photo1 Roof 2 access door TRANSOM/SIDE LIGHT WALLS Material Type(s) Masonry Replacement Quantity 11,000 Replacement Uom Instance on All Leased Spaces Instance Instance Quantity 11,000 Instance BRICK: DETERIORATED MASONRY SILLS PB/A&W Page 7 of 17

8 WALLS Building Assessment Survey Elevation Quantity 10 L.F. REPAIR Photo1 Roof 2 SOFFITS LOADING DOCK LOUVER PARAPETS Material Type(s) t Required t Required Replacement Quantity 1,000 Replacement Uom Instance on Roofs 1-3 Instance Masonry, Metal C.F. Instance Quantity 1,000 Instance PB/A&W Page 8 of 17 C.F.

9 PARAPETS Building Assessment Survey METAL: RAILINGS: DETERIORATED Quantity 10 Urgency of Action PRIORITY 4 Photo1 Roof 2 parapet metal railing pitch pockets on top of metal coping PLAZA DECK ROOF Roofing Replacement Quantity 14,000 Replacement Uom ROOF HATCH/SMOKE HATCH LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS ROOF BARRIER ROOF CAGE ROOF FENCE ROOFING Instance on Built-Up: Built-up : Roof 1 Instance t Required 3 - Fair Instance Quantity 5,000 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 1978 Source of Installation Custodial Staff PB/A&W Page 9 of 17

10 Building Assessment Survey Architectural Inspection ROOF Roofing ROOFING BUILT-UP: ROOFING: BEYOND USEFUL LIFE Location/Instance Built-Up: Built-up : Roof 1 Quantity 5,000 Urgency of Action PRIORITY 1 Photo1 photo recorded Instance on Modified Bitumen: Modified Bitumen: Roofs 2 and 3 Instance Instance Quantity 2,000 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 1978 Source of Installation 4 - Between Fair and Poor Custodial Staff MODIFIED BITUMEN: ROOFING: DELAMINATION Quantity 70 ROOFING WITH MAJOR EQUIPMENT REMOVAL Urgency of Action PRIORITY 4 Photo1 Roof 2 MODIFIED BITUMEN: ROOFING: BEYOND USEFUL LIFE Location/Instance Modified Bitumen: Modified Bitumen: Roofs 2 and 3 PB/A&W Page 10 of 17

11 ROOF Roofing ROOFING Quantity 2,000 Urgency of Action PRIORITY 1 Photo1 Instance on Asphalt Shingle: Asphalt Shingle: Roofs 4 and 5 Instance ROOFING WITH MAJOR EQUIPMENT REMOVAL photo recorded 3 - Fair Instance Quantity 7,000 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 1978 Source of Installation Custodial Staff ASPHALT SHINGLE: ROOFING: BEYOND USEFUL LIFE Location/Instance Asphalt Shingle: Asphalt Shingle: Roofs 4 and 5 Quantity 7,000 Urgency of Action PRIORITY 1 Photo1 Building Assessment Survey photo recorded ROOFING DRAINS Specialties BULKHEAD/PENTHOUSE CUPOLA/ SPIRES/ TOWERS DORMER DUNNAGE STEEL t Required 3 - Fair MINOR RUSTING Quantity 20 PB/A&W Page 11 of 17 L.F.

12 Building Assessment Survey Architectural Inspection ROOF Specialties DUNNAGE STEEL MAINTENANCE Photo1 Roof 2 HEIGHT LESS THAN 18" Quantity 50 L.F. Urgency of Action PRIORITY 1 Purpose of Action LEVEL 1 Photo1 Roof 2 SKYLIGHT/ROOF VENT ROOF/GRAVITY TANK STAIRS/RAMPS: WINDOWS t Required Replacement Quantity 2,300 PB/A&W Page 12 of 17

13 Building Assessment Survey Architectural Inspection WINDOWS Replacement Uom GUARDS LINTELS WINDOWS Material Type(s) Aluminum Instance on Aluminum - Other: All Leased Facades Instance 3 - Fair Instance Quantity 2,300 Instance Installation Year 1978 Source of Installation Custodial Staff ALUMINUM - OTHER: BEYOND USEFUL LIFE Location/Instance Aluminum - Other: All Leased Facades Quantity 2,300 Urgency of Action PRIORITY 1 Photo1 photo recorded INTERIOR POOLS Instance Instance CEILING - Training - Main DECK/FLOOR - Training - Main DIVING BOARD - Main - Training POOL LINING - Training - Main ROOF STRUCTURE - Training - Main SEATING - Main - Training WALLS - Main 1st Floor - Training 1st Floor - Main Under Construction Under Construction Under Construction Under Construction Under Construction Under Construction Inaccessible Inaccessible Under Construction PB/A&W Page 13 of 17

14 INTERIOR POOLS WALLS - Training STRUCTURAL COLUMNS/BEAMS/BEARING WALLS FLOOR STRUCTURE FOUNDATION WALLS ROOF STRUCTURE Location/Instance Quantity 20 Under Construction Inaccessible STEEL COLUMNS/BEAMS: DETERIORATED/MISSING SPRAY-ON FIREPROOFING 2nd Floor Fan Room Purpose of Action LEVEL 5 Photo1 Building Assessment Survey VAULTS-BUNKERS AUDITORIUM CAFETERIA CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling Door(s) Floor Finish Walls Specialties Pool Fan Room PB/A&W Page 14 of 17

15 Building Assessment Survey Architectural Inspection INTERIOR GYMNASIUM Ceiling Door(s) 1 - Good Fixed Equipment Floor Finish Seating Sliding-folding Partition Stage Walls GYPSUM BOARD: DETERIORATED Location/Instance Near the Exit Vestibule Quantity 10 Photo1 Near the Exit Vestibule Location/Instance Quantity 140 WALL PADDING: DETERIORATED Perimeter walls PB/A&W Page 15 of 17

16 Building Assessment Survey Architectural Inspection INTERIOR GYMNASIUM Walls Photo1 Perimeter walls Window Curtains/Shades/Blinds INTERIOR DOOR HARDWARE 3 - Fair INTERIOR GUARDS KITCHEN LIBRARY LOCKER ROOM MULTI-PURPOSE ROOM SCIENCE DEMO ROOM SCIENCE LAB SCIENCE PREP ROOM SHOWER ROOM STAIRS/RAMPS: INTERIOR TOILET ROOMS - STAFF TOILET ROOMS - STUDENTS Ceiling 3 - Fair ACOUSTIC TILES: DAMAGED/MISSING Location/Instance Boys Toilet Room Quantity 20 PB/A&W Page 16 of 17

17 INTERIOR TOILET ROOMS - STUDENTS Ceiling Photo1 Building Assessment Survey Boys Toilet Room Door(s) Floor Finish Stalls Walls CERAMIC TILE: BROKEN/ MISSING Location/Instance Boys Toilet Room Quantity 10 Photo1 LIFE SAFETY F.D. HOLDING AREA STEEL STAIRS SITE Boys Toilet Room PB/A&W Page 17 of 17