1 Architectural Inspection Building Assessment Survey Asset: P.S QUEENS, 180 BEACH 35 STREET, New York, Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior :27 PM :18 PM AA : Architectural - Associate :41 PM :35 PM Asset Data Was the building fully accessible for inspection Principal(s) Information Custodian Fireman Principal Name Organization Did you meet with this Principal? Did this Principal provide feedback? Summary of Principal's Feedback Answer Building Square Footage 23,000 Comments on the Area Comments on the Stories (Floors) plus Basements 3+B Comments on the Number of Classrooms 13 Yes Rachelle Legions P.S Queens No Yes The Principal returned the questionnaire with the following comments: 1. There is no space for physical education. Students use the Cafeteria for physical education. 2. The building is not accessible for people with disabilities. They have to climb many stairs to enter the Main Entrance lobby. There is no elevator. Patrick O'Sullivan Rupert Palmer None Comments on the Year Built 1931 Student Population 210 Staff Population 49 Weather Facade Photo Fair Beach 35 Street - Northeast View PB/A&W Page 1 of 34

2 Main Entrance Photo Building Assessment Survey Roof Photo Facade A - Beach 35 Street Roof 1 - North View Have any Systems/Major Building Components been upgraded? Yes Systems: New Running Track, Playground (Play Equipment and Safety Surfacing), Paving/Student Use - Asphalt, Site Benches, Walkway - Asphalt near TCUs; Limited Fencing replacement; Exterior Stair repairs at Exits 2 and 4 Year: 2017 Systems: Flood Elimination Project; Structural Beams and Columns Fireproofing repairs; Partial Exterior Wall repointing; Areaway restoration; Areaway Grating replacement; Exterior Doors replacement; Basement Windows replacement; Basement Louvers replacement; Basement Transportable Flood Barriers Rack; Skylight and Roof Ventilation repair; Student Toilet Rooms upgrade (1st Floor) Year: 2016 Systems: Exterior Wall repointing and Partial repair; Parapets repointing; Roof Barriers, Coping replacement Year: 2009 Systems: Basement Flood Elimination Project including Waterproofing injection to Foundation Walls Year: 2008 Systems: Partial Exterior Doors replacement Year: 2005 PB/A&W Page 2 of 34

3 Have there been any New Building Additions? Tandem Schools? Leased Space? Priority Building Assessment Survey Systems: Windows, Window Guards and Shades replacement except the Basement Year: 2000 No No No Priority Exist Last Year? Priority Category Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No condition recorded Structural Engineer Required Structural Type Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No condition recorded Accessibility Accessibility Status Is the primary or secondary entrance on an accessible route? No Physical Breakdown Structure Exists Complies Required FUNCTIONAL ACCESSIBILITY Exterior Routes Exterior Entrances & Exits No Saddle height > 1/2" Exterior H/C Lifts No No Exterior Ramps and Railings No Yes Interior Routes Corridor and Lobby H/C Lifts No Yes Interior Corridor Doors and Hardware Yes Yes Interior Corridors and Lobbies No Change in Elevation Interior Elevators No Interior Lobby Doors and Hardware Yes Interior Ramps No Rooms & Spaces Art Rooms Auditorium No No Cafeteria 1st Floor No Not on Accessible Route Classrooms None on Accessible Route No Not on Accessible Route Computer Rooms Room 316 No Not on Accessible Route Gymnasium Library No No Main Office Room 211 No Not on Accessible Route Multi-purpose Room 1st Floor No Not on Accessible Route Nurse's Room Room 323 No Not on Accessible Route Pool Science Lab No No Toilet Rooms (Boys) None on Accessible Route No Not on Accessible Route Toilet Rooms (Girls) None on Accessible Route No Not on Accessible Route Toilet Rooms (Staff) None on Accessible Route No Not on Accessible Route PB/A&W Page 3 of 34

4 Building Assessment Survey Physical Breakdown Structure Exists Complies Required Building Template Inspection Architectural EXTERIOR AREAWAY Instance on AW1 - AW2 Instance Instance Quantity 2 Instance AWNINGS AND CANOPIES CHIMNEY Material Type(s) COPING CORNICE DOORS DOORS AND FRAMES DOOR HARDWARE LINTELS EACH Masonry 1 - Good PB/A&W Page 4 of 34

5 Building Assessment Survey Architectural Inspection EXTERIOR DOORS LINTELS TRANSOM/SIDE LIGHT EXTERIOR WALLS Material Type(s) Masonry Replacement Quantity 7,500 Replacement Uom Instance on All Facades Instance Instance Quantity 7,500 Instance BRICK: EFFLORESCENCE Roof Plan reference Elevation Quantity 20 MAINTENANCE Urgency of Action PRIORITY 1 Purpose of Action LEVEL 1 Photo1 No photo recorded STONE: CHIPPED/SPALLED/BROKEN PIECES PB/A&W Page 5 of 34

6 EXTERIOR EXTERIOR WALLS Roof Plan reference Building Assessment Survey Elevation Quantity 30 REPAIR Urgency of Action PRIORITY 4 Photo1 Roof Plan reference Facade A BRICK: MINOR CRACKS AND SPALLING PB/A&W Page 6 of 34

7 EXTERIOR EXTERIOR WALLS Elevation Building Assessment Survey Quantity 30 RESTITCH Photo1 Roof Plan reference Facade C BRICK: MAJOR / THRU CRACKS Elevation Quantity 40 REMOVE AND REBUILD PB/A&W Page 7 of 34

8 Building Assessment Survey Architectural Inspection EXTERIOR EXTERIOR WALLS Urgency of Action PRIORITY 4 Photo1 Facade C - Near Exit 2 EXTERIOR SOFFITS LOADING DOCK LOUVER PARAPETS Material Type(s) Masonry Replacement Quantity 3,500 Replacement Uom C.F. Instance on All Facades Instance Instance Quantity 3,500 Instance C.F. BRICK: EFFLORESCENCE Roof Plan reference Quantity 20 MAINTENANCE Urgency of Action PRIORITY 1 Purpose of Action LEVEL 1 Photo1 No photo recorded PLAZA DECK ROOF Roofing PB/A&W Page 8 of 34

9 Building Assessment Survey Architectural Inspection EXTERIOR ROOF Roofing Replacement Quantity 7,500 Replacement Uom ROOF HATCH/SMOKE HATCH LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS ROOF BARRIER RAILINGS/PANELS: DETERIORATED, MINOR RUSTING Roof Plan reference Quantity 10 MAINTENANCE Photo1 ROOF CAGE ROOF FENCE ROOFING Instance on Built-Up: Roof 1 Instance No photo recorded 3 - Fair Instance Quantity 7,340 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 1995 Source of Installation No Documented BUILT-UP: FLASHING: DRIP EDGE/GRAVEL STOP DAMAGED PB/A&W Page 9 of 34

10 EXTERIOR ROOF Roofing ROOFING Roof Plan reference Building Assessment Survey Quantity 10 L.F. Urgency of Action PRIORITY 4 Photo1 Roof Plan reference Roof 1 - Bulkhead BUILT-UP: FLASHING: DRIP EDGE/GRAVEL STOP DAMAGED Quantity 10 L.F. Urgency of Action PRIORITY 4 PB/A&W Page 10 of 34

11 EXTERIOR ROOF Roofing ROOFING Photo1 Building Assessment Survey Roof Plan reference Roof 1 - Bulkhead BUILT-UP: FLASHING: CAP FLASHING DAMAGED Quantity 10 L.F. Urgency of Action PRIORITY 4 Photo1 Roof 1 - Facade A BUILT-UP: FLASHING: CAP FLASHING DAMAGED PB/A&W Page 11 of 34

12 EXTERIOR ROOF Roofing ROOFING Roof Plan reference Building Assessment Survey Quantity 10 L.F. Urgency of Action PRIORITY 4 Photo1 Roof Plan reference Roof 1 - Facade A BUILT-UP: ROOFING: MINOR LEAKAGE Quantity 10 REPAIR Urgency of Action PRIORITY 5 PB/A&W Page 12 of 34

13 EXTERIOR ROOF Roofing ROOFING Photo1 Building Assessment Survey Room 316 at Roof 1 Location/Instance Built-Up: Roof 1 Quantity 7,340 BUILT-UP: ROOFING: BEYOND USEFUL LIFE Urgency of Action PRIORITY 1 Photo1 Instance on Modified Bitumen: Roofs 2, 3 Instance Instance Quantity 160 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? No photo recorded 5 - Poor Installation Year 1995 Source of Installation Roof Plan reference No Documented MODIFIED BITUMEN: ROOFING: MAJOR ACTIVE ROOF LEAKS IN INSTRUCTIONAL SPACE Quantity 50 Urgency of Action PRIORITY 5 ROOFING WITHOUT MAJOR EQUIPMENT REMOVAL PB/A&W Page 13 of 34

14 EXTERIOR ROOF Roofing ROOFING Photo1 Building Assessment Survey ROOFING DRAINS Specialties BULKHEAD/PENTHOUSE Roof Plan reference Stair A/Vestibule (Exit 2)at Roof 3 BULKHEAD/PENTHOUSE CEILING: PLASTER DAMAGED/DETERIORATED Quantity 10 Photo1 CUPOLA/ SPIRES/ TOWERS Stair B/Bulkhead PB/A&W Page 14 of 34

15 Building Assessment Survey Architectural Inspection EXTERIOR ROOF Specialties DORMER DUNNAGE STEEL SKYLIGHT/ROOF VENT Material Type(s) Glass ROOF/GRAVITY TANK STAIRS/RAMPS: EXTERIOR BUILDING CHEEK/FLANK WALLS 3 - Fair BRICK: CRACKS/SPALLING - MAJOR Roof Plan reference Quantity 15 Urgency of Action PRIORITY 4 Photo1 RAILINGS Facade C - Near Exit Between Fair and Poor RUST - MAJOR PB/A&W Page 15 of 34

16 EXTERIOR STAIRS/RAMPS: EXTERIOR RAILINGS Roof Plan reference Building Assessment Survey Quantity 20 L.F. Urgency of Action PRIORITY 4 Photo1 Facade A - Main Entrance STAIRS/RAMPS WINDOWS Replacement Quantity 4,120 Replacement Uom EXTERIOR GUARDS LINTELS WINDOWS Material Type(s) Instance on Aluminum - Double Hung: All Facades (except Basement) Instance Aluminum 3 - Fair Instance Quantity 4,000 Instance Installation Year 2000 Source of Installation Documented PB/A&W Page 16 of 34

17 Building Assessment Survey Architectural Inspection EXTERIOR WINDOWS WINDOWS Instance on Aluminum - Double Hung: All Facades (Basement) Instance 1 - Good Instance Quantity 120 Instance Installation Year 2016 Source of Installation Documented INTERIOR POOLS STRUCTURAL COLUMNS/BEAMS/BEARING WALLS Location/Instance Quantity Fair STEEL COLUMNS/BEAMS: DETERIORATED MASONRY FIREPROOFING Basement - Boiler Room Urgency of Action PRIORITY 4 Purpose of Action LEVEL 5 Photo1 Basement - Boiler Room Location/Instance Quantity 50 STEEL COLUMNS/BEAMS: DETERIORATED CONCRETE FIREPROOFING Basement - Boiler Room, near Vault adjacent to Electrical Room, Storage on North side Urgency of Action PRIORITY 4 Purpose of Action LEVEL 5 PB/A&W Page 17 of 34

18 Building Assessment Survey Architectural Inspection INTERIOR STRUCTURAL COLUMNS/BEAMS/BEARING WALLS Photo1 Storage on North side of Basement FLOOR STRUCTURE 3 - Fair CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED Location/Instance Basement - Boiler Room Quantity 15 REPAIR Purpose of Action LEVEL 5 Photo1 Boiler Room Location/Instance Quantity 30 Urgency of Action PRIORITY 5 Purpose of Action LEVEL 5 CONCRETE SLAB ON GRADE: WATER INFILTRATION IN NON- INSTRUCTIONAL SPACE Basement - near Storage on North side of Boiler Room, Corridor on South side of Boiler Room INSTALL WATERPROOFING PB/A&W Page 18 of 34

19 INTERIOR STRUCTURAL FLOOR STRUCTURE Photo1 Building Assessment Survey Near Storage on North side of Boiler Room H FOUNDATION WALLS Material Type(s) Concrete, Masonry ROOF STRUCTURE VAULTS-BUNKERS Foundation Walls Slab Structure Vault/Ash Hoist Doors and Framing AUDITORIUM CAFETERIA Ceiling Door(s) 5 - Poor WOOD: DETERIORATED DOOR Location/Instance North and South Entrance Quantity 3 EACH MAINTENANCE PB/A&W Page 19 of 34

20 INTERIOR CAFETERIA Door(s) Photo1 Building Assessment Survey North Entrance Fixed Equipment Floor Finish 3 - Fair VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Location/Instance Center Quantity 125 Photo1 Center Sliding-folding Partition Stage Walls Window Curtains/Shades/Blinds CLASSROOMS/CORRIDORS/ADMIN SPACES PB/A&W Page 20 of 34

21 Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling PLASTER: CRACKS/SPALLING - ACTIVE LEAK Location/Instance Rooms 112, 316 Quantity 15 Urgency of Action PRIORITY 5 Photo1 Room 112 Door(s) 5 - Poor METAL CLAD WOOD: DETERIORATED DOOR Location/Instance Room 323 Quantity 1 EACH MAINTENANCE Photo1 Room 323 WOOD: DETERIORATED DOOR Location/Instance Rooms 211, 217, 316 Quantity 3 EACH MAINTENANCE PB/A&W Page 21 of 34

22 Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Door(s) Photo1 Room 211 Floor Finish 3 - Fair VINYL TILES: DETERIORATED SUBSTRATE Location/Instance Room 223, Corridor near Room 319, 315, 215, 121 and others Quantity 650 Photo1 Corridor near Room 315 Walls Specialties GYMNASIUM INTERIOR DOOR HARDWARE INTERIOR GUARDS KITCHEN Ceiling 3 - Fair PB/A&W Page 22 of 34

23 Building Assessment Survey Architectural Inspection INTERIOR KITCHEN Ceiling Door(s) Floor Finish Walls SALT GLAZED BRICK: CRACKS/SPALLING Location/Instance Near Windows Quantity 10 Photo1 LIBRARY LOCKER ROOM MULTI-PURPOSE ROOM Ceiling Door(s) Fixed Equipment Floor Finish Sliding-folding Partition Near Windows PB/A&W Page 23 of 34

24 Building Assessment Survey Architectural Inspection INTERIOR MULTI-PURPOSE ROOM Sliding-folding Partition Stage Stage Stage Curtain Rigging Stage Curtains Walls Window Curtains/Shades/Blinds SCIENCE DEMO ROOM SCIENCE LAB SCIENCE PREP ROOM SHOWER ROOM STAIRS/RAMPS: INTERIOR Do Letter Stair Signs Exist? Yes Ceiling 3 - Fair PLASTER: CRACKS/SPALLING Location/Instance Stair B/1 Quantity 25 Photo1 No photo recorded PLASTER: CRACKS/SPALLING - ACTIVE LEAK Location/Instance Stair A/1 Exit 2 Vestibule Quantity 25 Urgency of Action PRIORITY 5 PB/A&W Page 24 of 34

25 INTERIOR STAIRS/RAMPS: INTERIOR Ceiling Photo1 Building Assessment Survey Stair A/1 Exit 2 Vestibule Door(s) Partition Railings Stairs and Landings 5 - Poor STONE: BROKEN/MISSING Location/Instance Main Entrance Quantity 70 Photo1 Main Entrance Location/Instance Quantity 650 ROLLED ASPHALT: CRACKS Stair A/Basement,3, B/Basement, Bulkhead PB/A&W Page 25 of 34

26 INTERIOR STAIRS/RAMPS: INTERIOR Stairs and Landings Photo1 Building Assessment Survey Stair B/Bulkhead VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Location/Instance Stair A/3, B/1,2,3 Quantity 90 Photo1 Stair A/3 TERRAZZO: CRACKS Location/Instance Stair A/1 Quantity 30 Photo1 Stair A/1 PB/A&W Page 26 of 34

27 Building Assessment Survey Architectural Inspection INTERIOR STAIRS/RAMPS: INTERIOR Walls GLAZED BLOCK: CRACKS/SPALLING Location/Instance Stair A/1 Exit 2 Vestibule Quantity 15 Photo1 Stair A/1 Exit 2 Vestibule PLASTER: CRACKS/SPALLING - ACTIVE LEAK Location/Instance Stair A/1 Exit 2 Vestibule Quantity 25 Urgency of Action PRIORITY 5 Photo1 Stair A/1 Exit 2 Vestibule STONE MOLDINGS: CRACKS/SPALLING Location/Instance Stair A/2 Quantity 10 L.F. PB/A&W Page 27 of 34

28 INTERIOR STAIRS/RAMPS: INTERIOR Walls Photo1 Building Assessment Survey Stair A/2 PLASTER: CRACKS/SPALLING Location/Instance Stair B/1 Exit 4 Vestibule, B/3 Quantity 45 Photo1 Stair B/1 Exit 4 Vestibule TOILET ROOMS - STAFF Ceiling PLASTER: CRACKS/SPALLING Location/Instance Room 308 Quantity 10 PB/A&W Page 28 of 34

29 INTERIOR TOILET ROOMS - STAFF Ceiling Photo1 Building Assessment Survey Room 308 Door(s) Floor Finish 5 - Poor CERAMIC TILE: BROKEN/MISSING TILES Location/Instance Rooms at Stair A/2, B/2 Quantity 50 Photo1 Stalls Walls TOILET ROOMS - STUDENTS Ceiling Door(s) Room at Stair A/2 1 - Good PB/A&W Page 29 of 34

30 Building Assessment Survey Architectural Inspection INTERIOR TOILET ROOMS - STUDENTS Floor Finish 1 - Good Stalls 1 - Good Walls 1 - Good LIFE SAFETY F.D. HOLDING AREA STEEL STAIRS SITE CONTAINERIZATION 5 - Poor CONTAINER DAMAGED Location/Instance Along Beach 34th Street Quantity 5 EACH Photo1 Drainage System for Asphalt Catch Basins/Manhole - Surrounded by asphalt Culverts - Asphalt Covering Drainage System for Concrete Drainage System for Soil Catch Basins/Manhole - Surrounded by Soil Culverts - Soil Covering DRINKING FOUNTAINS FENCES Along Beach 34th Street 3 - Fair PB/A&W Page 30 of 34

31 Building Assessment Survey Architectural Inspection SITE FENCES CHAIN LINK: DAMAGED POST/RAIL Location/Instance Beach 35th Street Quantity 20 L.F. Photo1 Beach 35th Street WROUGHT IRON: DAMAGED/DETERIORATED Location/Instance Beach 35th Street Quantity 120 Photo1 Beach 35th Street IRRIGATION SYSTEM PAVING Student Non-Use Gravel Exists? Asphalt Concrete Pavers Student Use No 1 - Good PB/A&W Page 31 of 34

32 Building Assessment Survey Architectural Inspection SITE PAVING Student Use Gravel Exists? No Asphalt 1 - Good Concrete Pavers Site Sidewalks & Walkways Asphalt 1 - Good Concrete 3 - Fair CRACKS - MAJOR Location/Instance Near Exit 2, North of Building Quantity 50 Photo1 Near Exit 2 Pavers DOT Sidewalk Asphalt Concrete 4 - Between Fair and Poor DAMAGED CURBS Location/Instance Beach 34th Street, Beach 35th Street Quantity 70 L.F. PB/A&W Page 32 of 34

33 SITE PAVING DOT Sidewalk Concrete Photo1 Building Assessment Survey Beach 34th Street DAMAGED/DETERIORATED/MISSING SECTIONS Location/Instance Beach 35th Street, Beach 34th Street Quantity 450 Photo1 Beach 35th Street Pavers PLAYGROUNDS Benches Fence Pavement Instance on Schoolyard Instance on Schoolyard Instance on Schoolyard Instance on Schoolyard Play Equipment Instance on Schoolyard Safety Surfacing Instance on Schoolyard 1 - Good 1 - Good PB/A&W Page 33 of 34

34 Building Assessment Survey Architectural Inspection SITE PLAYGROUNDS Unpaved Area Instance on Schoolyard PLAYING SURFACE Playing Field Running Track Instance on Schoolyard Instance 1 - Good RETAINING WALLS SEATING Benches Concrete Metal/Wood/Plastic 1 - Good Bleachers SITE WALLS (NOT RETAINING WALLS) CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR Location/Instance Schoolyard Quantity 15 Photo1 STAIRS/RAMPS: EXTERIOR Schoolyard PB/A&W Page 34 of 34