1 Architectural Inspection Building Assessment Survey Asset: RICHARD R GREEN HS OF TEACHING - M, 421 EAST 88 STREET, New York, Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior :46 PM :55 AM AA : Architectural - Associate :01 PM :44 PM Asset Data Was the building fully accessible for inspection Principal(s) Information Custodian Fireman Principal Name Organization Did you meet with this Principal? Did this Principal provide feedback? Summary of Principal's Feedback Answer Building Square Footage Comments on the Area Comments on the Stories (Floors) plus Basements 5+B Comments on the Number of Classrooms 31 Yes Samantha Kaplan P.S Manhattan (Yorkville Community School) No Yes The Principal returned the questionnaire with the following comments: The school's air conditioning system does not sufficiently cool the building. Darko Krsulic (TC) Samuel Rodriguez None Comments on the Year Built 1907 Student Population 514 Staff Population 80 Weather Facade Photo Fair East 88th Street - Northwest view PB/A&W Page 1 of 43

2 Main Entrance Photo Building Assessment Survey Roof Photo Facade A - East 88th Street Roof 1 - Northwest view Have any Systems/Major Building Components been upgraded? Have there been any New Building Additions? Tandem Schools? Leased Space? Yes Systems: Limited Flooring replacement; limited Stairwell Glass replacement Year: Systems: All Student Toilet Rooms except 1st Floor Boys Toilet Room Year: Systems: Modernization project including complete Windows and Exterior Guards (except at Basement Boiler Room), Vault Doors, Exterior Stairs and Railings, Areaway Gratings, and Roof Flashing replacement; Exterior HC Ramp installation; limited Areaway, Bulkhead and Exterior Masonry repairs; Foundation Waterproofing; limited Exterior Door, Transom and Sidelight replacement; Library and Cafeteria upgrades. Year: No No No Priority PB/A&W Page 2 of 43

3 Building Assessment Survey Architectural Inspection Priority Exist Last Year? Priority Category Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage Yes Protruding Elements Rusted metal railing with sharp edges is a protruding elements safety hazard. LIFE SAFETY STEEL STAIRS West Play Yard egress stair Samuel Rodriguez Fireman Structural Engineer Required Structural Type Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No condition recorded Accessibility Accessibility Status Is the primary or secondary entrance on an accessible route? Is the building a multi-story building? Are all floors of the building accessible through compliant means? Are SOME floors other than the 1st floor and basement accessible through compliant means? Do any of the following spaces exist on the First floor? Classroom, Art Room, Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs For the rooms that do exist, are SOME of them accessible on the 1st floor? Boys and Girls or Unisex accessible toilets exist on the 1st floor? Yes Yes No No Yes Yes Yes Physical Breakdown Structure Exists Complies Required FUNCTIONAL ACCESSIBILITY Exterior Routes Exterior Entrances & Exits Exterior H/C Lifts No No Exterior Ramps and Railings Yes Yes Interior Routes Corridor and Lobby H/C Lifts No No Interior Corridor Doors and Hardware Yes Yes Interior Corridors and Lobbies Interior Elevators Interior Lobby Doors and Hardware Interior Ramps Yes Yes Rooms & Spaces Art Rooms Auditorium Room 401 (Alternate Use for Science Lab) Cafeteria 1st Floor Yes No No Yes Yes Yes No Not on Accessible Route Classrooms None on Accessible Route No Not on Accessible Route Computer Rooms Gymnasium Room 301 No Not on Accessible Route Library Room 407 No Not on Accessible Route Main Office Room 208 No Not on Accessible Route PB/A&W Page 3 of 43 No

4 Building Assessment Survey Physical Breakdown Structure Exists Complies Required Rooms & Spaces Multi-purpose Room Nurse's Room Room 300A No Not on Accessible Route Pool Science Lab Room 401 (used as Art Room) No Not on Accessible Route Toilet Rooms (Boys) 1st Floor Yes Toilet Rooms (Girls) 1st Floor Yes Toilet Rooms (Staff) 1st Floor No Clear opening < 32" Turning Radius Water Closet Arrangement No No Building Template Inspection Architectural EXTERIOR AREAWAY Instance on AW1-AW7 Instance Instance Quantity 7 Instance EACH AWNINGS AND CANOPIES CHIMNEY Material Type(s) Masonry 3 - Fair BRICK: OPEN JOINTS PB/A&W Page 4 of 43

5 EXTERIOR CHIMNEY Building Assessment Survey Quantity 150 REPOINT Urgency of Action PRIORITY 4 Photo1 COPING Chimney TERRA COTTA: CRACKED/BROKEN PIECES Quantity 40 L.F. -IN-KIND PB/A&W Page 5 of 43

6 EXTERIOR COPING Photo1 Building Assessment Survey Façade A CAST STONE: CRACKED/BROKEN PIECES Quantity 15 L.F. -IN-KIND Photo1 CORNICE DOORS DOORS AND FRAMES Roof 1 - Facade C 5 - Poor METAL CLAD: DETERIORATED DOOR AND FRAME - MAJOR DETERIORATION PB/A&W Page 6 of 43

7 EXTERIOR DOORS DOORS AND FRAMES Building Assessment Survey Quantity 3 EACH Photo1 Façade G METAL: DETERIORATED DOOR AND FRAME - MAJOR DETERIORATION Quantity 3 EACH Photo1 DOOR HARDWARE No photo recorded 3 - Fair PB/A&W Page 7 of 43

8 EXTERIOR DOORS LINTELS TRANSOM/SIDE LIGHT Building Assessment Survey WOOD: EXCESSIVELY WEATHERED Quantity 5 Photo1 Facade G EXTERIOR WALLS Material Type(s) Masonry Replacement Quantity 36,500 Replacement Uom Instance on All Facades Instance Instance Quantity 36,500 Instance STONE: CHIPPED/SPALLED/BROKEN PIECES PB/A&W Page 8 of 43

9 EXTERIOR EXTERIOR WALLS Building Assessment Survey Elevation Quantity 5 REPAIR Photo1 Facade A EXTERIOR SOFFITS LOADING DOCK LOUVER PARAPETS Material Type(s) Masonry Replacement Quantity 6,800 Replacement Uom Instance on All Facades Instance C.F. 3 - Fair Instance Quantity 6,800 Instance PB/A&W Page 9 of 43 C.F.

10 EXTERIOR PARAPETS Building Assessment Survey BRICK: MAJOR DETERIORATION/CRACKS Quantity 40 REMOVE AND REBUILD Photo1 Facade D BRICK: EFFLORESCENCE Quantity 150 MAINTENANCE Urgency of Action PRIORITY 1 Purpose of Action LEVEL 1 PB/A&W Page 10 of 43

11 EXTERIOR PARAPETS Photo1 Building Assessment Survey Roof 1 PLAZA DECK ROOF Roofing Replacement Quantity 11,700 Replacement Uom ROOF HATCH/SMOKE HATCH LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS ROOF BARRIER ROOF CAGE ROOF FENCE ROOFING Instance on Built-Up: All Roofs Instance 3 - Fair Instance Quantity 11,700 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 1990 Source of Installation Yes Custodial Staff BUILT-UP: ROOFING: LOSS OF GRAVEL Quantity 50 Urgency of Action PRIORITY 4 INSTALL NEW GRAVEL PB/A&W Page 11 of 43

12 EXTERIOR ROOF Roofing ROOFING Photo1 Building Assessment Survey Roof 1 BUILT-UP: FLASHING: CAP FLASHING MISSING Quantity 5 L.F. INSTALL NEW Urgency of Action PRIORITY 4 Photo1 Roof 1 - Facade D Location/Instance Quantity 11,700 BUILT-UP: ROOFING: BEYOND USEFUL LIFE Built-Up: All Roofs Urgency of Action PRIORITY 1 Photo1 ROOFING WITH MAJOR EQUIPMENT REMOVAL No photo recorded PB/A&W Page 12 of 43

13 EXTERIOR ROOF Roofing ROOFING ROOFING DRAINS Building Assessment Survey Poor DETERIORATED Quantity 4 EACH Photo1 Specialties BULKHEAD/PENTHOUSE Roof Fair BULKHEAD/PENTHOUSE WALLS/INTERIOR: PLASTER CRACKS/SPALLING Quantity 20 PB/A&W Page 13 of 43

14 Building Assessment Survey Architectural Inspection EXTERIOR ROOF Specialties BULKHEAD/PENTHOUSE MAINTENANCE Photo1 BH3 BULKHEAD/PENTHOUSE WALLS/INTERIOR: GLAZED BLOCK CRACKS/SPALLING Quantity 8 Photo1 BH2 BULKHEAD/PENTHOUSE CEILING: PLASTER DAMAGED/DETERIORATED PB/A&W Page 14 of 43

15 EXTERIOR ROOF Specialties BULKHEAD/PENTHOUSE Building Assessment Survey Quantity 30 Photo1 BH2 CUPOLA/ SPIRES/ TOWERS DORMER DUNNAGE STEEL 3 - Fair HEIGHT LESS THAN 18" Quantity 66 L.F. Urgency of Action PRIORITY 1 Purpose of Action LEVEL 1 PB/A&W Page 15 of 43

16 EXTERIOR ROOF Specialties DUNNAGE STEEL Photo1 Building Assessment Survey SKYLIGHT/ROOF VENT ROOF/GRAVITY TANK STAIRS/RAMPS: EXTERIOR BUILDING CHEEK/FLANK WALLS Roof Fair STONE: DETERIORATED JOINTS AT COPING STONES Quantity 5 L.F. MAINTENANCE Urgency of Action PRIORITY 4 Photo1 Facade A - Ramp STONE: DETERIORATED COPING STONE PB/A&W Page 16 of 43

17 Building Assessment Survey Architectural Inspection EXTERIOR STAIRS/RAMPS: EXTERIOR BUILDING CHEEK/FLANK WALLS Quantity 10 Urgency of Action PRIORITY 4 Photo1 RAILINGS Facade A - Ramp (3 missing pieces) 3 - Fair DAMAGED Quantity 10 L.F. Urgency of Action PRIORITY 4 PB/A&W Page 17 of 43

18 EXTERIOR STAIRS/RAMPS: EXTERIOR RAILINGS Photo1 Building Assessment Survey STAIRS/RAMPS Facade G 3 - Fair STONE: CRACKS, SPALLING Quantity 12 Urgency of Action PRIORITY 4 Photo1 Facade G CONCRETE: CRACKS/SPALLING - MAJOR PB/A&W Page 18 of 43

19 EXTERIOR STAIRS/RAMPS: EXTERIOR STAIRS/RAMPS Building Assessment Survey Quantity 10 Urgency of Action PRIORITY 4 Photo1 Facade C WINDOWS Replacement Quantity 7,200 Replacement Uom EXTERIOR GUARDS LINTELS WINDOWS Material Type(s) Solid Wood, Aluminum Instance on Aluminum - Double Hung: All Facades except B and H Instance 4 - Between Fair and Poor Instance Quantity 7,100 Instance Installation Year 2010 Source of Installation Custodial Staff ALUMINUM - DOUBLE HUNG: INOPERABLE PB/A&W Page 19 of 43

20 EXTERIOR WINDOWS WINDOWS Building Assessment Survey Elevation Quantity 1,800 WINDOW Urgency of Action PRIORITY 4 Photo1 No photo recorded ALUMINUM - DOUBLE HUNG: INOPERABLE BALANCE Elevation Quantity 120 PB/A&W Page 20 of 43

21 Building Assessment Survey Architectural Inspection EXTERIOR WINDOWS WINDOWS EACH BALANCES Urgency of Action PRIORITY 4 Photo1 No photo recorded Instance on Wood: Basement Instance 3 - Fair Instance Quantity 100 Instance Installation Year 1970 Source of Installation Custodial Staff WOOD: DETERIORATED Elevation Quantity 20 WINDOW Photo1 Boiler Room PB/A&W Page 21 of 43

22 EXTERIOR WINDOWS WINDOWS Building Assessment Survey WOOD: BEYOND USEFUL LIFE Location/Instance Wood: Basement Quantity 100 Urgency of Action PRIORITY 1 Photo1 No photo recorded INTERIOR POOLS STRUCTURAL COLUMNS/BEAMS/BEARING WALLS Location/Instance Quantity Poor STEEL COLUMNS/BEAMS: DETERIORATED/MISSING PLASTER FIREPROOFING Gas Meter Room, Boiler Room Purpose of Action LEVEL 5 Photo1 Gas Meter Room Location/Instance Quantity 25 STEEL COLUMNS/BEAMS: DETERIORATED MASONRY FIREPROOFING Boiler Room Urgency of Action PRIORITY 4 Purpose of Action LEVEL 5 PB/A&W Page 22 of 43

23 Building Assessment Survey Architectural Inspection INTERIOR STRUCTURAL COLUMNS/BEAMS/BEARING WALLS Photo1 Boiler Room - both sides FLOOR STRUCTURE 4 - Between Fair and Poor CONCRETE SLAB ON GRADE: MINOR CRACKS Location/Instance Boiler Room Quantity 90 REPAIR Purpose of Action LEVEL 5 Photo1 Boiler Room CONCRETE SLAB ON GRADE: THRU CRACKS Location/Instance Boiler Room Quantity 40 Purpose of Action LEVEL 5 Photo1 PB/A&W Page 23 of 43

24 INTERIOR STRUCTURAL FLOOR STRUCTURE Building Assessment Survey Boiler Room FOUNDATION WALLS Material Type(s) Masonry 4 - Between Fair and Poor BRICK: CRACKED/SPALLED Location/Instance Gas Meter Room, Boiler Room, Oil Tank Room Quantity 500 RESTITCH Purpose of Action LEVEL 5 Photo1 Gas Meter Room ROOF STRUCTURE VAULTS-BUNKERS Foundation Walls Slab Structure Vault/Ash Hoist Doors and Framing Location/Instance Quantity Fair DETERIORATED/DAMAGED VAULT/ASH HOIST DOORS AND FRAMING East 88th Street Favade EACH PB/A&W Page 24 of 43

25 Building Assessment Survey Architectural Inspection INTERIOR STRUCTURAL VAULTS-BUNKERS Vault/Ash Hoist Doors and Framing Photo1 WATER INFILTRATION Location/Instance Ash Hoist Vault Quantity 10 REPAIR Urgency of Action PRIORITY 5 Photo1 No photo recorded AUDITORIUM CAFETERIA Instance on 1st Floor Ceiling Instance on 1st Floor Door(s) Instance on 1st Floor Fixed Equipment Instance on 1st Floor Floor Finish Instance on 1st Floor VINYL TILES: DETERIORATED SUBSTRATE Location/Instance Near Entrance, near columns Quantity 50 PB/A&W Page 25 of 43

26 INTERIOR CAFETERIA Floor Finish Photo1 Building Assessment Survey Near Entrance Sliding-folding Partition Instance on 1st Floor Stage Instance on 1st Floor Stage Instance on 1st Floor Stage Curtain Rigging Instance on 1st Floor Stage Curtains Instance on 1st Floor Walls Instance on 1st Floor Window Curtains/Shades/Blinds Instance on 1st Floor CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling PLASTER: CRACKS/SPALLING Location/Instance Rooms 205, 305, 506 Quantity 50 PB/A&W Page 26 of 43

27 Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling Photo1 Room 305 PLASTER: CRACKS/SPALLING - ACTIVE LEAK Location/Instance Rooms 509, 409, 309, 209 Quantity 40 Urgency of Action PRIORITY 5 Photo1 Room 509 Door(s) 3 - Fair WOOD: DETERIORATED DOOR Location/Instance Rooms 205,506 Quantity 2 EACH MAINTENANCE Photo1 PB/A&W Page 27 of 43

28 Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Door(s) Room 205 Floor Finish TERRAZZO: CRACKS Location/Instance 1st Floor Exit 4 Vestibule Quantity 10 Photo1 1st Floor Exit 4 Vestibule CERAMIC TILE: BROKEN/MISSING TILES Location/Instance Room 506A Quantity 10 Photo1 Room 506A Location/Instance Quantity 300 VINYL TILES: DETERIORATED SUBSTRATE Rooms 300A, 304, 402, 508, Corridor near Stair DE/1, and others PB/A&W Page 28 of 43

29 Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Floor Finish Photo1 Room 508 Location/Instance Quantity 400 VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Custodian Office, PTA Office, Rooms 304A, 400A, Corridor near Room 207, and others Photo1 Custodian Office Walls BRICK: CRACKS/SPALLING Location/Instance 1st Floor Exit 6 Vestibule Quantity 10 PB/A&W Page 29 of 43

30 Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Walls Photo1 1st Floor Exit 6 Vestibule CERAMIC TILE: BROKEN/ MISSING Location/Instance 2nd Floor Exit 10 Vestibule, 1st Floor Exit 4 Vestibule, 1st Floor Exit 1 Vestibule Quantity 30 Photo1 2nd Floor Exit 10 Vestibule PLASTER: CRACKS/SPALLING Location/Instance Rooms 509, 500A, Corridor near Rooms 201,204,503, and others Quantity 100 Photo1 Room 509 PB/A&W Page 30 of 43

31 Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Walls Specialties GYMNASIUM Instance on Room 301 Ceiling Instance on Room 301 Door(s) Instance on Room Fair WOOD: DETERIORATED DOOR AND FRAME Location/Instance Entrance Quantity 1 EACH MAINTENANCE Photo1 Entrance Fixed Equipment Instance on Room 301 Floor Finish Instance on Room 301 Seating Instance on Room 301 Sliding-folding Partition Stage Walls Instance on Room 301 Instance on Room 301 Instance on Room 301 PB/A&W Page 31 of 43

32 Building Assessment Survey Architectural Inspection INTERIOR GYMNASIUM Window Curtains/Shades/Blinds Instance on Room 301 INTERIOR DOOR HARDWARE 3 - Fair INTERIOR GUARDS KITCHEN Instance on 1st Floor Ceiling Instance on 1st Floor Door(s) Instance on 1st Floor Floor Finish Instance on 1st Floor VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Location/Instance Near Toilet Quantity 10 Photo1 Near Toilet QUARRY TILE: BROKEN/MISSING TILES Location/Instance Near Entrance Quantity 20 PB/A&W Page 32 of 43

33 INTERIOR KITCHEN Floor Finish Photo1 Building Assessment Survey Near Entrance Walls Instance on 1st Floor PLASTER: CRACKS/SPALLING Location/Instance Storage Quantity 10 Photo1 LIBRARY Instance on Room 407 Built-in Furnishing Instance on Room 407 Ceiling Instance on Room 407 Door(s) Instance on Room 407 Floor Finish Instance on Room 407 Storage PB/A&W Page 33 of 43

34 Building Assessment Survey Architectural Inspection INTERIOR LIBRARY Floor Finish Walls Instance on Room 407 LOCKER ROOM MULTI-PURPOSE ROOM SCIENCE DEMO ROOM SCIENCE LAB Instance on Room 401 Alternative use Yes Fixed Equipment Instance on Room 401 CABINETRY: MISSING/DAMAGED Location/Instance Near Entrance Quantity 2 L.F. Photo1 Near Entrance SCIENCE PREP ROOM Instance on Room 402 Alternative use Fixed Equipment Instance on Room 402 SHOWER ROOM STAIRS/RAMPS: INTERIOR Ceiling Do Letter Stair Signs Exist? Door(s) Yes Yes PB/A&W Page 34 of Fair

35 Building Assessment Survey Architectural Inspection INTERIOR STAIRS/RAMPS: INTERIOR Door(s) METAL CLAD WOOD: DETERIORATED DOOR Location/Instance Stair AB/3 Quantity 1 EACH MAINTENANCE Photo1 Stair AB/3 Partition 3 - Fair GLASS PANEL: DAMAGED/DETERIORATED Location/Instance Stairs AB/2,4, DE/2,3,4,5 Quantity 50 Photo1 Stair DE/5 Railings Stairs and Landings Location/Instance Stair C/4 Quantity 10 CONCRETE: WORN-OUT TREAD/NOSINGS PB/A&W Page 35 of 43

36 Building Assessment Survey Architectural Inspection INTERIOR STAIRS/RAMPS: INTERIOR Stairs and Landings Photo1 Stair C/4 VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Location/Instance Stairs AB/1,2, DE/2, C/2 Quantity 100 Photo1 Stair DE/2 CONCRETE: CRACKS/SPALLING - MAJOR Location/Instance Stair C/bulkhead Quantity 20 PB/A&W Page 36 of 43

37 INTERIOR STAIRS/RAMPS: INTERIOR Stairs and Landings Photo1 Building Assessment Survey Stair C/bulkhead Walls CERAMIC TILE: BROKEN/ MISSING Location/Instance Stairs AB/2,3,4,5, C/2 Quantity 50 Photo1 Stair AB/4 TOILET ROOMS - STAFF Ceiling PLASTER: CRACKS/SPALLING Location/Instance 2nd Floor Staff Quantity 10 PB/A&W Page 37 of 43

38 INTERIOR TOILET ROOMS - STAFF Ceiling Photo1 Building Assessment Survey nd Floor Staff Door(s) 5 - Poor WOOD: DETERIORATED DOOR Location/Instance 4th Floor Staff Quantity 1 EACH MAINTENANCE Photo1 4th Floor Staff Floor Finish STONE: BROKEN/MISSING TILES Location/Instance In the Room 500A Quantity 10 PB/A&W Page 38 of 43

39 INTERIOR TOILET ROOMS - STAFF Floor Finish Photo1 Building Assessment Survey In the Room 500A Stalls Walls TOILET ROOMS - STUDENTS Ceiling Door(s) 5 - Poor METAL: DAMAGED LOUVER Location/Instance 1st Floor Boys, 2nd Floor Girls Quantity 2 EACH MAINTENANCE Photo1 1st Floor Boys Floor Finish Location/Instance Quantity 10 CERAMIC TILE: BROKEN/MISSING TILES 1st Floor Boys, 2nd Floor Boys East PB/A&W Page 39 of 43

40 Building Assessment Survey Architectural Inspection INTERIOR TOILET ROOMS - STUDENTS Floor Finish Photo1 2nd Floor Boys East Stalls Walls PLASTER: CRACKS/SPALLING Location/Instance 1st Floor Girls, 2nd Floor Boys East Quantity 10 Photo1 2nd Floor Boys East LIFE SAFETY F.D. HOLDING AREA STEEL STAIRS Location/Instance Quantity Poor DAMAGED Facade D - West Play Yard Urgency of Action PRIORITY 5 PB/A&W Page 40 of 43

41 Building Assessment Survey Architectural Inspection LIFE SAFETY STEEL STAIRS Purpose of Action LEVEL 6 Photo1 Facade D - West Play Yard MAJOR RUSTING Location/Instance Facade D - West Play Yard Quantity 200 Urgency of Action PRIORITY 4 Photo1 SITE CONTAINERIZATION Drainage System for Asphalt Drainage System for Concrete Catch Basins/Manhole - Surrounded by concrete Culverts - Concrete Covering Drainage System for Soil DRINKING FOUNTAINS FENCES IRRIGATION SYSTEM PAVING Student Non-Use Student Use Gravel Exists? Site Sidewalks & Walkways Facade D - West Play Yard No PB/A&W Page 41 of 43

42 Building Assessment Survey Architectural Inspection SITE PAVING DOT Sidewalk Asphalt Concrete DAMAGED/DETERIORATED/MISSING SECTIONS Location/Instance East 88th Street Quantity 25 Photo1 Pavers PLAYGROUNDS Instance on Courtyard East Instance on Courtyard West Benches Instance on Courtyard East Instance on Courtyard West Fence Instance on Courtyard East Instance on Courtyard West Pavement Instance on Courtyard West Instance on Courtyard East Play Equipment Instance on Courtyard East Instance on Courtyard West Safety Surfacing Instance on Courtyard West Instance on Courtyard East Unpaved Area Instance on Courtyard West East 88th Street PB/A&W Page 42 of 43

43 Building Assessment Survey Architectural Inspection SITE PLAYGROUNDS Unpaved Area Instance on Courtyard East PLAYING SURFACE RETAINING WALLS SEATING SITE WALLS (NOT RETAINING WALLS) STAIRS/RAMPS: EXTERIOR PB/A&W Page 43 of 43