Submit shop drawings in accordance with Vale Specification SPEC

Size: px
Start display at page:

Download "Submit shop drawings in accordance with Vale Specification SPEC"

Transcription

1 017/03/3 1/8 1.0 PURPOSE This specification describes the minimum requirements for Vertical Lift Doors. The latest standards, codes and regulations apply to all other requirements not specifically mentioned. In case of a conflict Vale will furnish a written interpretation..0 DRAWINGS The following drawings form part of this specification: B Vertical Lift Operated Doors Plans, Elevations and Details 3.0 GENERAL 3.1 SHOP DRAWINGS Submit shop drawings in accordance with Vale Specification SPEC Include schedule identifying each unit, with door marks and numbers relating to numbering on drawings and door schedule if any. The drawings will clearly show thickness of materials, construction details, attachments and reinforcing for hardware and other pertinent information. For power operated doors the above will also include electrical schematic drawings. Indicate mortises, reinforcements, anchorages, locations of exposed fasteners, openings (glazed, paneled or louvered) and arrangement of standard hardware. Units will not be ordered until the respective drawings have been approved. Verify all dimensions with job conditions before fabricating. Submit shop drawings well in advance of required fabrication to avoid construction delay. 3. DELIVERY AND STORAGE Deliver, store and handle units so as to prevent twisting, warping and damage. Do not remove units from crates of other protective covering until ready for installation. Supply and install hardware in accordance with the approved shop drawings. 3.3 DESIGN CRITERIA Design vertical lift door curtain and assembly to withstand the wind load as per the Building code. A minimum design wind load of 0 psf within door opening area, unless noted

2 017/03/3 /8 higher on the project drawings or higher value is calculated as per the Building Code. The door design shall be such that the jambs, weight box, guides and drive mechanism form a column required to carry and transfer the entire weight of the door and counterbalancing mechanism down to the floor. At the same time, transferring lintel wind load to the jambs. All roller chain sprockets shall be heavy duty, all steel type. Roller chains and cables shall have a safety factor of 7: MATERIALS Vertical lift doors to be industrial quality single or multi-leaf type, (see contract job drawings for type), each leaf operating on its individual vertical part of guides, and counterweights shall be balanced. All mounting hardware, operators, counter-weights and other necessary hardware to be supplied by the door manufacturer. Where required, welding must be concealed as much as possible. All welded joints to be ground smooth. All welding must conform to the latest CSA specifications using arc, mig and or spot welding for distortion free finished product. 4.1 DOOR LEAVES Each leaf to be constructed of structural steel channel frame, reinforced at approximately 4'-0 maximum centers faced on exterior surface with 16 gauge, "paint grip" galvanized steel, insulated and covered on inside with 0 gauge minimum "paint grip" galvanized steel sheet. 4. GLASS OPENINGS - VISION LITES Openings for glass to be 18" wide x 9" high x 1/4" thick polished wire glass. 4.3 GUIDES All leaves to ride in angle guides, guides mounted on 1 gauge minimum steel plate reinforced with " x " x 3/16" angles at 4'-0 vertical centers. Guide assembly to be mounted on 1/4" thick base plate for anchoring to the floor. Heavy duty spreader I beam joining guides at top. The weight box must have full height removable cover for easy access to weights and for future repairs.

3 017/03/3 3/8 4.4 COUNTERBALANCING MECHANISM Positive friction free drive achieved by use of machined cable sheaves and steel sprockets mounted on solid cold rolled steel cross-header shaft. Shaft to ride on heavy duty, regreaseable, self-aligning flange bearings mounted on heavy drive housing. Bottom driving blade must be connected to counterweight by roller chains running over steel sprockets. All other blades to be connected to individual counterweight by galvanized aircraft cables running over machined idler sheaves. Each door blade must be provided with cable or roller chain adjustable tensioning which will ensure that when bottom blade will rise, picking up the second blade and succeeding blades, the door shall open effortlessly. For maximum safety, horizontal weatherstripping must be made using full width combination steel and neoprene astragal. Rubber weatherstripping alone will not be permitted. This will make it impossible, in case of cable breakage, for the top blade to drop below the bottom blade. For additional safety, the top blade must be supplied with steel pick-up bumpers equipped with rubber silencers. 4.5 SAFETY MECHANISM Door must be equipped with failsafe device sufficient to withstand the free-fall of the door system, by means of safety dogs, chain driven on door bottom section. 4.6 WEATHERSTRIPPING Provide 1/4" foam rubber pad on door stopper angles for each angle guide. Use vinyl sealing gaskets for meeting edges of door leaves and Lintel closure. Install "brush type weatherseal" vertically on door guides to give a complete perimeter weatherseal. 4.7 FIRE RATING Fire-rated doors shall be provided for those openings requiring fire protection and temperature rise ratings, in accordance with the Building Code or as specified on the project drawings. Such products shall be listed for conformance with CAN4-S104. All fire-rated doors shall bear the label of, and be listed by a nationally recognized testing agency having a factory inspection service. Labeling shall be in accordance with NFPA 80, the listing authority's policies and label materials, and shall identify the manufacturer. Firerated doors shall be constructed as listed for labeling in the Follow-Up Service Procedures/Factory Inspection Manuals issued by the listing agency to individual manufacturers.

4 017/03/3 4/8 5.0 INSULATION Door leaves must be fully insulated with " thick semi-rigid AF-530 glass fibre. 6.0 PAINTING Paint system to be in accordance with Standard SPEC Epoxy System for Steel Heavy Industrial and Underground and to include S.S.P.C.-SP7 Brush Blast. Paint both sides, all metal exposed to sight. Final paint coat to be field applied upon completion of door installation. ("Paint-grip" galvanized sheeting not to be sandblasted) 7.0 ACCEPTABLE MANUFACTURERS Vertical lift door curtains as manufactured by: 1) Richards-Wilcox of Canada ) Accent Door Manufacturing Ltd. 3) Ridge Nassau Canada Ltd. 8.0 MANUAL OPERATOR Provide chain hoist with galvanized steel endless hand chain, with electric interlock. Include hand chain interlocked auxiliary operator to disconnect motor mechanically and electrically for emergency operation in case of power failure. This must consist of a manually operated control cable reaching to the floor and making possible the release of the brake and must also engage the hand chain wheel, thus actuating a limit switch to prevent flow of power to the motor operator in the event of sudden resumption of the power supply. Doors to be operated mechanically by means of reduction gear and chain. Hand chain to be #50 min. galvanized. Reduction to be calculated to reduce pull on hand chain to not over 30 lb. Provide oil lubricated reducer. 9.0 ELECTRIC OPERATOR The operator to be guide mounted on the drive side of door mechanism. Electric door operator to be CSA and UL approved, extra heavy duty gearhead type c/w prewired, number-coded, wall-mounted control cabinet.

5 017/03/3 5/8 9.1 MOTORS Motors shall be IEEE 841 Certified (1 HP or higher). Allow for the following door speeds: DOOR OPENING MAXIMUM DOOR SPEED up to 150 sq. ft. 4 per second sq. ft. 18 per second sq. ft. 1 per second sq. ft. 10 per second 9. CONTROL PANEL WIRING Power wiring must be a minimum of 14 AWG stranded copper. Control wiring to be a minimum of 16 AWG stranded copper. Provide 600 volt insulated single conductor, stranded (seven strands minimum) copper heat and flame retardant wiring rated 105 deg. C. Provide extra flexible wires for door mounted items. Provide wiring in continuous lengths, without splices between connection points, installed in channels or neatly tied and clamped to panel. Terminate all wiring on terminal blocks if not terminated on devices. No more than one (1) wire at any one terminal is acceptable. Identify all wires at both ends with permanent sleeve type wire markers, with wire numbers as shown on the manufacturer s control schematic drawings. 9.3 ENCLOSURE Panel enclosure must be rated EEMAC-1 unless otherwise specified. Door to be hinged with provision for padlock. A warning sign stating the highest voltage to be encountered within the panel must be prominently displayed on the door. 9.4 FUSIBLE DISCONNECTING MEANS Disconnecting means must be an EEMAC rated flange operated visible-blade disconnect switch. Flange mounted operating handle must be interlocked with the enclosure door such that the door cannot be opened with the switch in the closed position unless a defeater is deliberately operated.

6 017/03/3 6/8 Motor circuit fuses shall be Class C. 9.5 CONTACTORS Contactors must be EEMAC rated and a minimum of size 1. Coils must operate on 10 volts AC and to be electrically and mechanically interlocked to prevent energization of up and down contactors simultaneously. 9.6 OVERLOAD PROTECTION An overload relay must be provided complete with 3 heater elements appropriately sized to protect the motor from thermal damage. 9.7 GROUNDING Green insulated bonding conductors must be provided between the enclosure, the back panel, and the door. Provide terminals for connection of bonding conductors from cables entering the panel. 9.8 ENTRAPMENT PROTECTION Door operation and external entrapment protection shall comply with UL Standard 35 Door, Drapery, Gate, Louver, and Window Operators and Systems. 9.9 ACCEPTABLE MANUFACTURERS Acceptable manufacturers of electric operators are as follows: Manaras Canada Door Lec Canada Sprocketing for door and operator shafts to be connected by #50 ANSI chain and sprocketing and shall allow for the door speeds as described earlier in this section EXECUTION Examine all applicable drawings to determine structural steel framing and architectural details which will affect door installations, provisions for supports and connection for operators, track and mounting hardware. Examine completed work on which door installation is dependent. Determine whether sufficient headroom and clearances are provided.

7 017/03/3 7/8 Immediately report to the Vale representative discrepancies, if any, in the drawings or in field conditions which will affect the installation INSTALLATION Install the doors in strict accordance with the manufacturer's printed instructions. Erect and secure the units square and level, free from warp, twist or superimposed loads. Set and fasten the tracks and guide assembly, operator and counterbalance in correct alignment within safe tolerances which will ensure uniform bearing of the door rollers on the tracks along the full length of the tracks, and proper travel of the door sections without binding. The completed assembly must be placed in correct operating condition. When closed, the doors must make weathertight closure along all edges and joints. 1.0 WARRANTY The manufacturer must furnish a written warranty against defects in workmanship and materials for a period of five (5) year from date of acceptance of the installation. The warranty must be provided prior to release of final holdback payment REFERENCE DOCUMENTATION The following documents are related to this specification and shall be used to their latest revision: SPEC-0801 SPEC-1001 SPEC SPEC-1400 SPEC SPEC SPEC SPEC-1600 SPEC OBC CSA ANSI CGSB EEMAC UL SSPC Vendor, Fabrication, and Shop Drawing Requirements Masonry Requirements Cast-in-Place Concrete Structural Steel Quality Requirements Steelwork - Fabrication Steelwork Erection Epoxy System for Steel Heavy Industrial and Underground Caulking - Interior Sealants Building Code Canadian Standards Association American National Standards Institute Canadian General Standards Board Electrical and Electronic Manufacturers Association of Canada Underwriters Laboratories Steel Structures Painting Council

8 017/03/3 8/ REVISION AND TRANSITION NOTES Revision notes describe: what was changed, and if applicable, why it was changed, and the plan to implement the change, including whether changes are retroactive. Note: The revision notes are a summary of the changes and may not necessarily be a complete list. A risk code is entered for each revision and if applicable, the revision notes will describe how risk was addressed for the revision. Risk Code A Risk Category This revision is a minor change and/or introduces no risk. B C Risk has been addressed for this revision by the reviewer and approver. Low risk or no new hazards identified. For this revision, a PHR or other risk management tool has been used to address risk and minimize hazards. This risk assessment has been documented and is available through Central Engineering. Rev 1 Revision Notes Document format and number changed to suit updated Vale Engineering Document System. This specification replaces former standard Rev 017 Review Format updated Some minor corrections - No other changes Risk Code Approved by Reviewed by Issue Date YYYY/MM/DD --- A.A. A.A. 013/1/09 A A.Alaeddine M.Verrilli 017/03/3