Single Wythe CMU Meeting the Energy Code

Size: px
Start display at page:

Download "Single Wythe CMU Meeting the Energy Code"

Transcription

1 Single Wythe CMU Meeting the Energy Code

2 Conventional CMUs

3 Architectural CMUs

4 A and H CMUs

5 Hi-R and Hi-R H CMUs

6 Specialty CMUs

7 Code ASHRAE Compliance Effective date September 20, 2017

8 Code Compliance ASHRAE Compliance

9 Climate Zones 2009 IECC, Figure 301.1

10 Compliance Options Prescriptive Path

11 Climate Zone 5 ASHRAE Compliance Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080

12 Climate Zone 5 ASHRAE Compliance Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080

13 Climate Zone 5 ASHRAE Compliance Zone 5: Slab-on-Grade Floors and Opaque Doors

14 Slab on Grade Floors

15 Climate Zone 5 ASHRAE Compliance Zone 5: Fenestration

16 NCMA Thermal Catalog

17 NCMA Thermal Calculator NCMA Thermal Calculator

18 Single Wythe CMU

19 NCMA Thermal Calculator Exposed Both Faces 12 CMU Density, pcf t fs,in. t w,in. Grout spacing, in. U factor Conventional 135 (normal wt) Architectural A block Conventional 105 (medium wt) H block A block 105 (medium wt) Hi-R Fully Grouted Hi-R H Fully Grouted Specialty # Specialty #

20 Climate Zones U max = U max = U max = U max = U max = U max = U max = IECC, Figure 301.1

21 NCMA Thermal Catalog Single Wythe CMU (conventional & architectural) Three (3) web block Assembly 1-1: foamed cells (U factor > U max =0.090) Assembly 1-5: HD polyisocyanurate c.i.

22 Single Wythe CMU Assembly 1-5

23 Single Wythe CMU Assembly 1-5: Continuous polyisocyanurate heavy duty (HD) attached directly to masonry, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Thickness of HD polyisocyanurate: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) 2 in. (R-14.4) (0.059) (0.061) 2-1/2 in. (R-17.8) (0.049) (0.050) 3 in. (R-21.2) (0.042) (0.043) 3-1/2 in. (R-24.6) (0.037) (0.037) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080

24 Exposed Single Wythe CMU DOW THERMAX Insulation

25 Exposed Single Wythe CMU DOW THERMAX Heavy Duty Insulation

26 Non-Continuous Insulation Example: Airport Hangar U=0.047 < U max = U=0.177 > U max = U = (15/37)*0.177+(22/37)*0.047 U = 0.099

27 Single Wythe CMU vs Precast Versatility Architectural effects (limitless) Variety of unit sizes, shapes, textures, finishes, and colors Banding and integrated patterns Pigmented mortar Curb appeal (making a statement)

28 Single Wythe CMU vs Precast LEED Masonry manufactured locally support Michigan

29 Single Wythe CMU vs Precast Structural Panel weight on foundation New system design software RAM Elements NCMA SMDS Direct Design 3DiQ BIM interfacing

30 Single Wythe CMU vs Precast Structural Masonry bearing pockets (less eccentricity) vs. Precast loadbearing connection (greater eccentricity) Masonry wall can be designed as a pinned or fixed base Internal wall bracing (fixed base) Precast panel typically designed as a pinned base Masonry wall can be designed as partially reinforced and insulated

31 Single Wythe CMU vs Precast Initial Construction Cost Comparison Caulking of precast concrete panel joints (interior and exterior)

32 Single Wythe CMU vs Precast Construction Masonry productivity Electrical conduits easier to account for in lieu of casting in precast concrete Interior joints struck flush behind insulation No cell fill Moisture management (IWR) Flashing Tolerances for masonry wall vs. precast concrete panel

33 Single Wythe CMU vs Precast Flexibility of Masonry Last minute design changes and corrections are easier Variation in footing elevation Openings

34 Single Wythe CMU vs Precast Schedule Precast concrete panel lead time Time required for the temporary shoring of the joists and girders Speed of construction

35 Single Wythe CMU vs Precast Maintenance Cost Caulking of precast concrete panel joints time consuming and prone to failure due to panel movement, especially at the corners Painting precast concrete panels Staining precast concrete panels Pigmented masonry requires no exterior/interior painting or wallpaper

36 Compliance Options Building Envelope Trade Off Option

37 Compliance Options

38 Single Wythe CMU

39 Single Wythe CMU

40 Single Wythe CMU Example Courtesy and permission from Dixon Architecture

41 Single Wythe CMU Example Courtesy and permission from Dixon Architecture

42 Single Wythe CMU Example Courtesy and permission from Dixon Architecture

43 Single Wythe CMU Example Courtesy and permission from Dixon Architecture

44 Single Wythe CMU Example Courtesy and permission from Dixon Architecture

45 Single Wythe CMU Example Courtesy and permission from Dixon Architecture

46 Single Wythe CMU Example Courtesy and permission from Dixon Architecture

47 NCMA Thermal Catalog

48 NCMA Thermal Catalog 3 Web/2 Cell

49 Single Wythe CMU Assembly 1-3

50 Single Wythe CMU Assembly 1-3: 1-in. continuous closed-cell spray polyurethane foam (SPF) interior insulation, metal furring with additional SPF insulation between the furring, and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Thickness of SPF Insulation between furring: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) 1 in. (R-6.8) (0.075) (0.078) 2 in. (R-13) (0.069) (0.071) 3 in. (R-19) (0.066) (0.068) 3-1/2 in. (R-22) (0.065) (0.068) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080

51 Single Wythe CMU Assembly 1-4

52 Single Wythe CMU Assembly 1-4: Continuous rigid interior insulation 1-1/2 in. metal furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Rigid Insulation type and thickness: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) Polyisocyanurate, 1 in. (R-6.7) (0.086) (0.090) Polyisocyanurate, 1-1/2 in. (R-10.5) (0.065) (0.067) Polyisocyanurate, 2 in. (R-14.4) (0.052) (0.053) Polyisocyanurate, 2-1/2 in. (R-17.8) (0.044) (0.045) Polyisocyanurate, 3 in. (R-21.2) (0.038) (0.039) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080

53 Single Wythe CMU Assembly 1-5

54 Exposed Single Wythe CMU DOW THERMAX Heavy Duty Insulation

55 Exposed Single Wythe CMU DOW THERMAX Insulation

56 Single Wythe CMU Assembly 1-6

57 Single Wythe CMU Assembly 1-6: Metal furring at 24 in. o.c. with batt insulation between furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Insulation type: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) R-19 Batt (0.086) (0.090) R-21 Batt (0.083) (0.087) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080

58 Single Wythe CMU WOOD Assembly 1-7

59 Single Wythe CMU Assembly 1-7: Wood furring at 24 in. o.c. with insulation between furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Insulation type and thickness: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) Polyisocyanurate, 1-1/2 in. (R-10.5) (0.077) (0.080) R-11 Batt (0.073) (0.076) R-13 Batt (0.068) (0.071) R-15 Batt (0.064) (0.066) R-19 Batt (0.054) (0.056) R-21 Batt (0.051) (0.052) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080

60 NCMA Thermal Catalog 2 Web/1 Cell

61 Single Wythe CMU Assembly 2-3

62 Single Wythe CMU Assembly 2-3: 1-in. continuous closed-cell spray polyurethane foam (SPF) interior insulation, metal furring with additional SPF insulation between the furring, and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Thickness of SPF Insulation between furring: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) 1 in. (R-6.8) (0.076) (0.078) 2 in. (R-13) (0.069) (0.077) 3 in. (R-19) (0.066) (0.069) 3-1/2 in. (R-22) (0.066) (0.068) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080

63 Single Wythe CMU Assembly 2-4

64 Single Wythe CMU Assembly 2-4: Continuous rigid interior insulation 1-1/2 in. metal furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Rigid Insulation type and thickness: Extruded Polysytrene, 1-1/2 in. (R- 7.5) Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) (0.090) Extruded Polysytrene, 2 in. (R-10) (0.073) (0.076) Extruded Polysytrene, 2-1/2 in. (R- 12.5) (0.062) (0.064) Extruded Polysytrene, 3 in. (R-15) (0.054) (0.055) Polyisocyanurate, 1 in. (R-6.7) (0.086) (0.090) Polyisocyanurate, 1-1/2 in. (R-10.5) (0.065) (0.067) Polyisocyanurate, 2 in. (R-14.4) (0.052) (0.053) Polyisocyanurate, 2-1/2 in. (R-17.8) (0.044) (0.045) Polyisocyanurate, 3 in. (R-21.2) (0.038) (0.039)

65 Single Wythe CMU Assembly 2-5

66 Single Wythe CMU Assembly 2-5: Continuous polyisocyanurate heavy duty (HD) attached directly to masonry, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Thickness of HD polyisocyanurate: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) 2 in. (R-14.4) (0.059) (0.061) 2-1/2 in. (R-17.8) (0.049) (0.050) 3 in. (R-21.2) (0.042) (0.043) 3-1/2 in. (R-24.6) (0.037) (0.037) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080

67 Single Wythe CMU Assembly 2-6

68 Single Wythe CMU Assembly 2-6: Metal furring at 24 in. o.c. with batt insulation between furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Insulation type: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) R-19 Batt (0.086) (0.090) R-21 Batt (0.083) (0.087) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080

69 Single Wythe CMU Assembly 2-7

70 Single Wythe CMU Assembly 2-7: Wood furring at 24 in. o.c. with insulation between furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Insulation type and thickness: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) Polyisocyanurate, 1-1/2 in. (R-10.5) (0.078) (0.081) R-11 Batt (0.074) (0.077) R-13 Batt (0.069) (0.071) R-15 Batt (0.065) (0.067) R-19 Batt (0.055) (0.056) R-21 Batt (0.051) (0.052) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080

71 NCMA Thermal Catalog 1 Web/No Cell

72 Single Wythe CMU Assembly 3-3

73 Single Wythe CMU Assembly 3-3: 1-in. continuous closed-cell spray polyurethane foam (SPF) interior insulation, metal furring with additional SPF insulation between the furring, and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Thickness of SPF Insulation between furring: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) 1 in. (R-6.8) (0.076) (0.078) 2 in. (R-13) (0.069) (0.071) 3 in. (R-19) (0.067) (0.069) 3-1/2 in. (R-22) (0.066) (0.068) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080

74 Single Wythe CMU Assembly 3-4

75 Single Wythe CMU Assembly 3-4: Continuous rigid interior insulation 1-1/2 in. metal furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Rigid Insulation type and thickness: Extruded Polysytrene, 1-1/2 in. (R- 7.5) Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) (0.090) Extruded Polysytrene, 2 in. (R-10) (0.073) (0.076) Extruded Polysytrene, 2-1/2 in. (R- 12.5) (0.062) (0.064) Extruded Polysytrene, 3 in. (R-15) (0.054) (0.055) Polyisocyanurate, 1 in. (R-6.7) (0.087) (0.090) Polyisocyanurate, 1-1/2 in. (R-10.5) (0.065) (0.067) Polyisocyanurate, 2 in. (R-14.4) (0.052) (0.053) Polyisocyanurate, 2-1/2 in. (R-17.8) (0.044) (0.045) Polyisocyanurate, 3 in. (R-21.2) (0.038) (0.039)

76 Single Wythe CMU Assembly 3-5

77 Single Wythe CMU Assembly 3-5: Continuous polyisocyanurate heavy duty (HD) attached directly to masonry, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Thickness of HD polyisocyanurate: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) 2 in. (R-14.4) (0.059) (0.061) 2-1/2 in. (R-17.8) (0.049) (0.050) 3 in. (R-21.2) (0.042) (0.043) 3-1/2 in. (R-24.6) (0.037) (0.037) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080

78 Single Wythe CMU Assembly 3-6

79 Single Wythe CMU Assembly 3-6: Metal furring at 24 in. o.c. with batt insulation between furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Insulation type: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) R-19 Batt (0.086) (0.090) R-21 Batt (0.084) (0.087) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080

80 Single Wythe CMU Assembly 2-7

81 Single Wythe CMU Assembly 3-7: Wood furring at 24 in. o.c. with insulation between furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Insulation type and thickness: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) Polyisocyanurate, 1-1/2 in. (R-10.5) (0.077) (0.080) R-11 Batt (0.074) (0.076) R-13 Batt (0.069) (0.071) R-15 Batt (0.065) (0.066) R-19 Batt (0.054) (0.056) R-21 Batt (0.051) (0.052) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080

82 Concrete Products Group

83 Hi-R Thermal Properties: Korfil Hi-R, Spec-Brik Hi-R, and Hi-R H Construction Best Practices

84 Hi-R Thermal Properties: Korfil Hi-R, Spec-Brik Hi-R, and Hi-R H Construction Best Practices

85 Hi-R H Thermal Properties: Korfil Hi-R, Spec-Brik Hi-R, and Hi-R H Construction Best Practices

86 Hi-R H Thermal Properties: Korfil Hi-R, Spec-Brik Hi-R, and Hi-R H Construction Best Practices