1 Single Wythe CMU Meeting the Energy Code
2 Conventional CMUs
3 Architectural CMUs
4 A and H CMUs
5 Hi-R and Hi-R H CMUs
6 Specialty CMUs
7 Code ASHRAE Compliance Effective date September 20, 2017
8 Code Compliance ASHRAE Compliance
9 Climate Zones 2009 IECC, Figure 301.1
10 Compliance Options Prescriptive Path
11 Climate Zone 5 ASHRAE Compliance Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080
12 Climate Zone 5 ASHRAE Compliance Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080
13 Climate Zone 5 ASHRAE Compliance Zone 5: Slab-on-Grade Floors and Opaque Doors
14 Slab on Grade Floors
15 Climate Zone 5 ASHRAE Compliance Zone 5: Fenestration
16 NCMA Thermal Catalog
17 NCMA Thermal Calculator NCMA Thermal Calculator
18 Single Wythe CMU
19 NCMA Thermal Calculator Exposed Both Faces 12 CMU Density, pcf t fs,in. t w,in. Grout spacing, in. U factor Conventional 135 (normal wt) Architectural A block Conventional 105 (medium wt) H block A block 105 (medium wt) Hi-R Fully Grouted Hi-R H Fully Grouted Specialty # Specialty #
20 Climate Zones U max = U max = U max = U max = U max = U max = U max = IECC, Figure 301.1
21 NCMA Thermal Catalog Single Wythe CMU (conventional & architectural) Three (3) web block Assembly 1-1: foamed cells (U factor > U max =0.090) Assembly 1-5: HD polyisocyanurate c.i.
22 Single Wythe CMU Assembly 1-5
23 Single Wythe CMU Assembly 1-5: Continuous polyisocyanurate heavy duty (HD) attached directly to masonry, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Thickness of HD polyisocyanurate: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) 2 in. (R-14.4) (0.059) (0.061) 2-1/2 in. (R-17.8) (0.049) (0.050) 3 in. (R-21.2) (0.042) (0.043) 3-1/2 in. (R-24.6) (0.037) (0.037) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080
24 Exposed Single Wythe CMU DOW THERMAX Insulation
25 Exposed Single Wythe CMU DOW THERMAX Heavy Duty Insulation
26 Non-Continuous Insulation Example: Airport Hangar U=0.047 < U max = U=0.177 > U max = U = (15/37)*0.177+(22/37)*0.047 U = 0.099
27 Single Wythe CMU vs Precast Versatility Architectural effects (limitless) Variety of unit sizes, shapes, textures, finishes, and colors Banding and integrated patterns Pigmented mortar Curb appeal (making a statement)
28 Single Wythe CMU vs Precast LEED Masonry manufactured locally support Michigan
29 Single Wythe CMU vs Precast Structural Panel weight on foundation New system design software RAM Elements NCMA SMDS Direct Design 3DiQ BIM interfacing
30 Single Wythe CMU vs Precast Structural Masonry bearing pockets (less eccentricity) vs. Precast loadbearing connection (greater eccentricity) Masonry wall can be designed as a pinned or fixed base Internal wall bracing (fixed base) Precast panel typically designed as a pinned base Masonry wall can be designed as partially reinforced and insulated
31 Single Wythe CMU vs Precast Initial Construction Cost Comparison Caulking of precast concrete panel joints (interior and exterior)
32 Single Wythe CMU vs Precast Construction Masonry productivity Electrical conduits easier to account for in lieu of casting in precast concrete Interior joints struck flush behind insulation No cell fill Moisture management (IWR) Flashing Tolerances for masonry wall vs. precast concrete panel
33 Single Wythe CMU vs Precast Flexibility of Masonry Last minute design changes and corrections are easier Variation in footing elevation Openings
34 Single Wythe CMU vs Precast Schedule Precast concrete panel lead time Time required for the temporary shoring of the joists and girders Speed of construction
35 Single Wythe CMU vs Precast Maintenance Cost Caulking of precast concrete panel joints time consuming and prone to failure due to panel movement, especially at the corners Painting precast concrete panels Staining precast concrete panels Pigmented masonry requires no exterior/interior painting or wallpaper
36 Compliance Options Building Envelope Trade Off Option
37 Compliance Options
38 Single Wythe CMU
39 Single Wythe CMU
40 Single Wythe CMU Example Courtesy and permission from Dixon Architecture
41 Single Wythe CMU Example Courtesy and permission from Dixon Architecture
42 Single Wythe CMU Example Courtesy and permission from Dixon Architecture
43 Single Wythe CMU Example Courtesy and permission from Dixon Architecture
44 Single Wythe CMU Example Courtesy and permission from Dixon Architecture
45 Single Wythe CMU Example Courtesy and permission from Dixon Architecture
46 Single Wythe CMU Example Courtesy and permission from Dixon Architecture
47 NCMA Thermal Catalog
48 NCMA Thermal Catalog 3 Web/2 Cell
49 Single Wythe CMU Assembly 1-3
50 Single Wythe CMU Assembly 1-3: 1-in. continuous closed-cell spray polyurethane foam (SPF) interior insulation, metal furring with additional SPF insulation between the furring, and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Thickness of SPF Insulation between furring: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) 1 in. (R-6.8) (0.075) (0.078) 2 in. (R-13) (0.069) (0.071) 3 in. (R-19) (0.066) (0.068) 3-1/2 in. (R-22) (0.065) (0.068) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080
51 Single Wythe CMU Assembly 1-4
52 Single Wythe CMU Assembly 1-4: Continuous rigid interior insulation 1-1/2 in. metal furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Rigid Insulation type and thickness: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) Polyisocyanurate, 1 in. (R-6.7) (0.086) (0.090) Polyisocyanurate, 1-1/2 in. (R-10.5) (0.065) (0.067) Polyisocyanurate, 2 in. (R-14.4) (0.052) (0.053) Polyisocyanurate, 2-1/2 in. (R-17.8) (0.044) (0.045) Polyisocyanurate, 3 in. (R-21.2) (0.038) (0.039) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080
53 Single Wythe CMU Assembly 1-5
54 Exposed Single Wythe CMU DOW THERMAX Heavy Duty Insulation
55 Exposed Single Wythe CMU DOW THERMAX Insulation
56 Single Wythe CMU Assembly 1-6
57 Single Wythe CMU Assembly 1-6: Metal furring at 24 in. o.c. with batt insulation between furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Insulation type: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) R-19 Batt (0.086) (0.090) R-21 Batt (0.083) (0.087) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080
58 Single Wythe CMU WOOD Assembly 1-7
59 Single Wythe CMU Assembly 1-7: Wood furring at 24 in. o.c. with insulation between furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Insulation type and thickness: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) Polyisocyanurate, 1-1/2 in. (R-10.5) (0.077) (0.080) R-11 Batt (0.073) (0.076) R-13 Batt (0.068) (0.071) R-15 Batt (0.064) (0.066) R-19 Batt (0.054) (0.056) R-21 Batt (0.051) (0.052) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080
60 NCMA Thermal Catalog 2 Web/1 Cell
61 Single Wythe CMU Assembly 2-3
62 Single Wythe CMU Assembly 2-3: 1-in. continuous closed-cell spray polyurethane foam (SPF) interior insulation, metal furring with additional SPF insulation between the furring, and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Thickness of SPF Insulation between furring: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) 1 in. (R-6.8) (0.076) (0.078) 2 in. (R-13) (0.069) (0.077) 3 in. (R-19) (0.066) (0.069) 3-1/2 in. (R-22) (0.066) (0.068) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080
63 Single Wythe CMU Assembly 2-4
64 Single Wythe CMU Assembly 2-4: Continuous rigid interior insulation 1-1/2 in. metal furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Rigid Insulation type and thickness: Extruded Polysytrene, 1-1/2 in. (R- 7.5) Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) (0.090) Extruded Polysytrene, 2 in. (R-10) (0.073) (0.076) Extruded Polysytrene, 2-1/2 in. (R- 12.5) (0.062) (0.064) Extruded Polysytrene, 3 in. (R-15) (0.054) (0.055) Polyisocyanurate, 1 in. (R-6.7) (0.086) (0.090) Polyisocyanurate, 1-1/2 in. (R-10.5) (0.065) (0.067) Polyisocyanurate, 2 in. (R-14.4) (0.052) (0.053) Polyisocyanurate, 2-1/2 in. (R-17.8) (0.044) (0.045) Polyisocyanurate, 3 in. (R-21.2) (0.038) (0.039)
65 Single Wythe CMU Assembly 2-5
66 Single Wythe CMU Assembly 2-5: Continuous polyisocyanurate heavy duty (HD) attached directly to masonry, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Thickness of HD polyisocyanurate: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) 2 in. (R-14.4) (0.059) (0.061) 2-1/2 in. (R-17.8) (0.049) (0.050) 3 in. (R-21.2) (0.042) (0.043) 3-1/2 in. (R-24.6) (0.037) (0.037) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080
67 Single Wythe CMU Assembly 2-6
68 Single Wythe CMU Assembly 2-6: Metal furring at 24 in. o.c. with batt insulation between furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Insulation type: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) R-19 Batt (0.086) (0.090) R-21 Batt (0.083) (0.087) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080
69 Single Wythe CMU Assembly 2-7
70 Single Wythe CMU Assembly 2-7: Wood furring at 24 in. o.c. with insulation between furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Insulation type and thickness: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) Polyisocyanurate, 1-1/2 in. (R-10.5) (0.078) (0.081) R-11 Batt (0.074) (0.077) R-13 Batt (0.069) (0.071) R-15 Batt (0.065) (0.067) R-19 Batt (0.055) (0.056) R-21 Batt (0.051) (0.052) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080
71 NCMA Thermal Catalog 1 Web/No Cell
72 Single Wythe CMU Assembly 3-3
73 Single Wythe CMU Assembly 3-3: 1-in. continuous closed-cell spray polyurethane foam (SPF) interior insulation, metal furring with additional SPF insulation between the furring, and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Thickness of SPF Insulation between furring: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) 1 in. (R-6.8) (0.076) (0.078) 2 in. (R-13) (0.069) (0.071) 3 in. (R-19) (0.067) (0.069) 3-1/2 in. (R-22) (0.066) (0.068) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080
74 Single Wythe CMU Assembly 3-4
75 Single Wythe CMU Assembly 3-4: Continuous rigid interior insulation 1-1/2 in. metal furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Rigid Insulation type and thickness: Extruded Polysytrene, 1-1/2 in. (R- 7.5) Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) (0.090) Extruded Polysytrene, 2 in. (R-10) (0.073) (0.076) Extruded Polysytrene, 2-1/2 in. (R- 12.5) (0.062) (0.064) Extruded Polysytrene, 3 in. (R-15) (0.054) (0.055) Polyisocyanurate, 1 in. (R-6.7) (0.087) (0.090) Polyisocyanurate, 1-1/2 in. (R-10.5) (0.065) (0.067) Polyisocyanurate, 2 in. (R-14.4) (0.052) (0.053) Polyisocyanurate, 2-1/2 in. (R-17.8) (0.044) (0.045) Polyisocyanurate, 3 in. (R-21.2) (0.038) (0.039)
76 Single Wythe CMU Assembly 3-5
77 Single Wythe CMU Assembly 3-5: Continuous polyisocyanurate heavy duty (HD) attached directly to masonry, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Thickness of HD polyisocyanurate: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) 2 in. (R-14.4) (0.059) (0.061) 2-1/2 in. (R-17.8) (0.049) (0.050) 3 in. (R-21.2) (0.042) (0.043) 3-1/2 in. (R-24.6) (0.037) (0.037) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080
78 Single Wythe CMU Assembly 3-6
79 Single Wythe CMU Assembly 3-6: Metal furring at 24 in. o.c. with batt insulation between furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Insulation type: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) R-19 Batt (0.086) (0.090) R-21 Batt (0.084) (0.087) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080
80 Single Wythe CMU Assembly 2-7
81 Single Wythe CMU Assembly 3-7: Wood furring at 24 in. o.c. with insulation between furring and 1/2 in. gypsum wallboard on interior, exposed exterior masonry Concrete Masonry Assembly R-Values (hr-ft 2 - o F/Btu) and U-Factors (Btu/hr-ft 2 - o F) Insulation type and thickness: Density of CMU, PCF 12-in. Concrete Masonry Lightly Reinforced, R (U) Polyisocyanurate, 1-1/2 in. (R-10.5) (0.077) (0.080) R-11 Batt (0.074) (0.076) R-13 Batt (0.069) (0.071) R-15 Batt (0.065) (0.066) R-19 Batt (0.054) (0.056) R-21 Batt (0.051) (0.052) Zone 5: R min = 11.4, U max =0.090 Zone 6: R min = 13.3, U max =0.080
82 Concrete Products Group
83 Hi-R Thermal Properties: Korfil Hi-R, Spec-Brik Hi-R, and Hi-R H Construction Best Practices
84 Hi-R Thermal Properties: Korfil Hi-R, Spec-Brik Hi-R, and Hi-R H Construction Best Practices
85 Hi-R H Thermal Properties: Korfil Hi-R, Spec-Brik Hi-R, and Hi-R H Construction Best Practices
86 Hi-R H Thermal Properties: Korfil Hi-R, Spec-Brik Hi-R, and Hi-R H Construction Best Practices