FIRESTOP GUIDE 2016 SAVING LIVES THROUGH INNOVATION AND EDUCATION.

Size: px
Start display at page:

Download "FIRESTOP GUIDE 2016 SAVING LIVES THROUGH INNOVATION AND EDUCATION."

Transcription

1 FIRESTOP GUIDE 2016 SAVING LIVES THROUGH INNOVATION AND EDUCATION. Hilti. Outperform. Outlast.

2 Available nearby. WITH YOU EVERY STEP OF THE WAY. At Hilti, our people and products are with you every step of the way. From design to construction, we help make your team more productive every day with expert technical advice, reliable products, prompt delivery, ongoing research and development, and outstanding service. Fire Protection Specialists offer firestop consultation and training Fire Protection Engineers works directly with architects and engineers to provide technical assistance and on-site problem solving Engineering Back-office provides solutions and Engineering Judgments for unique and complex applications Project References Hilti firestop systems are used continuously worldwide in various types of projects. Please contact your local firestop specialist or Hilti center for international or local project references. Engineering Judgement Hilti has performed extensive testing in both through penetration and constructio joint applications. However, dueto variations in construction through out the phases of a project, it is not possible to test every application that may been countered. For these situations, Hilti has developed a process for creating custom drawings to accommodateparticular applications. Hilti custom drawings, or Engineering Judgements, are developed through the careful and restricted application of accepted engineering principles and fire protection guidelines set forth by the IFC (International Firestop Council). Please contact your local Hilti firestop specialist ifyou require an Engineering Judgement solution. Sample Written Specifications Sample written specifications for firestop are available in accordance to various international standards. It includes allrequired specification details on firestop expertly laid out forspecifiers and designers. Please contact your local Hilti Firestop specialist for a copy of firestop sample specifications according to BS standard, ASTM standard, or to any otherinternational standards. MSDS Material Safety Data Sheets for all Hilti firestop systems are available if required. Please contact your local Hiltirepresentative for details. Test reports and approvals Test reports and approvals according to ASTM E814 UL1479, UL2079, EN 1366, DIN 4102, or any other international standard, or local approvals are available upon request. Please contactyour local Hilti Firestop specialis for further details. Support Firestop Design Center Support Call 800-HILTI (44584) Hilti Online E: ae.contactus@hilti.com 1

3 Hilti Firestop Systems Contents About Hilti Firestop Hilti and the Environment Problems and Hilti Solutions Firestop Application Review Firestop approvals & testings Additional Attributes Product Information and Installation Instructions Firestop joint spray CFS-SP WB Flexible firestop sealant CP Elastomeric silicone sealant CP 601S High-performance intumescent firestop sealant FS-ONE MAX Firestop foam CP Firestop foam CP Firestop mortar CP Firestop mortar CP Firestop coating CP Firestop block CFS-BL Firestop plug CFS-PL Firestop speed sleeve CP Drop-in device CFS-DID Cast-In Firestop Device CP Firestop wrap strip CP 648-E (endless) Firestop wrap strip CP 648-S (single) Firestop collar CP 643 N Firestop collar CP Firestop putty pad CP Firestop cable coating CP Firestop cable coating (ablative) CP 679 A Dispenser foam CF Filling foam CF-F Insulating foam CF-I Smoke and acoustic sealant CP Accessories Estimating Tables Engineering Judgments Legislation Hilti Firestop Save lives, protect assets and improve building performance. Hilti. Outperform. Outlast. 1

4 Dedicated to Life Safety 2 Visit the local website for more information on products and services.

5 Hilti Firestop Systems Hilti and the Environment. Hilti supplies the construction industry worldwide with technologically superior products, systems and services. We help our customers to be successful by identifying future needs and developing innovative solutions with outstanding added value. All Hilti products are designed for exceptionally high performance and long life. In early product development we use ecological guidelines to select both recyclable materials to be used in their manufacture and environmentally friendly packaging materials. As one of the worldís largest manufacturers of power tools, high performance consumables (including protection systems) and integrated services, Hilti recognises the value of designing buildings to meet green building standards. A great number of Hilti products and services help to comply with green building standards around the globe such as BREEAM, HQE, DGNB and LEED. Green Building Overview The building sector is one of the major contributors to increasing global CO2 emissions. Green building is one important means to meet the challenge of climate change while also owners. Green building is a globally visible trend to increase the resource the comfort and well-being for their occupants. Green building is the with which buildings use resources - energy, water, and materials - while reducing building impacts on human health and the environment during the building s lifecycle, through better site management, design, construction, operation, maintenance, and removal. Positive effects of green building are related to: 8-9 % decrease in operating costs 7.5 % increase in building values 6.6 % improvement in return on investment 3.5 % increase in occupancy 3 % rent increase Healthier and more motivated employees Fire Safety & Green Building bad for the environment. As well as combustion products such as carbon dioxide and sulphur oxides, the risk of land contamination from that may contain heavy metals. In addition, there are environmental structures and, in some cases, of relocating key services - such as added car travel if a local school is safety and sustainable development communities have a common interest in making sure that there are as cause as little damage as possible. The sustainability of sites can be air sealing products by supporting the following important characteristics of a building: movement capability, Movement capability allows the tracing of building movement. Firestop properties of Hilti products are tested to various worldwide standards to during the building phase. Water tightness aids in avoiding jobsite damage due to water penetration, 3

6 The designer s Problem Visit the local website for more information on products and services.

7 Hilti Solution 5

8 Firestop and Fire Protection Systems Firestop Sealants, Sprays Firestop joint spray CFS-SP WB Page Flexible firestop sealant CP 606 Page Elastomeric silicone sealant CP 601S Page High-performance intumescent firestop sealant FS-ONE MAX Page Firestop Foams Firestop foam CP 620 Page Firestop foam CP 660 Page Firestop Coating Systems and Mortars Firestop mortar CP 636 Page Firestop mortar CP 637 Page Firestop coating CP 670 Page Firestop Block and Plug Systems Firestop block CFS-BL Page Firestop plug CFS-PL Page Firestop Cast-In and Sleeve Devices Firestop speed sleeve CP 653 Drop-in device CFS-DID Cast-In Firestop Device CP 680-P and CP 680-M Page Page Page Firestop Collars and Wraps Firestop wrap strip CP 648-E (endless) Page Firestop wrap strip CP 648-S (single) Page Firestop collar CP 643 N Page Firestop collar CP 644 Page Firestop Putties Firestop putty pad CP 617 Page Cable Protection Firestop cable coating CP 678 Firestop cable coating (ablative) CP 679 A Page Page Visit the local website for more information on products and services.

9 u9+ 12oeoo Product Information Firestop Systems Application Review Application Metal pipes Plastic/glass pipes Cables/cable trays Insulated metal pipes Metal ducts Multiple penetrations Joints Page Description Features 12 Firestop Joint Spray (CFS-SP WB) mastic for construction joints where higher movement is expected Sprayable or apply by brush Paintable Quick and easy installation with the Titan 600 or 1100 Sprayers Meets 500 cycle Contains no halogens, solvents or asbestos so it is safe to use and won t harm the environment Water based formulation so spills and over-spray clean up quickly and easily 14 Flexible Firestop Sealant (CP 606) sealant for joint and through penetration applications Acrylic based formula Can be painted Available in foil pack (580 ml) Tested up to 33% movement with 500 cycles in accordance to UL 2079 and ASTM 1966 Fast and easy clean-up with water appearance Fast and easy dispensing Elastomeric Firestop Sealant (CP 601S) A single component for joint and through penetration applications FS-ONE MAX High Performance Intumescent Firestop Sealant A water-based sealant, designed to expand when exposed to heat Silicone based formula 1/4" depth systems Available in foil pack (600 ml) Meets 500 cycle requirements in joint applications (ASTM E 1966 and UL 2079) UL Listings for various penetrating items Several 1/4" depth systems Available in foil pack (600 ml) Allows for movement and vibration Cost effective solutions Fast and easy dispensing Smoke, fume and water resistant Meets Class I W Rating requirements One product to specify, purchase or inspect for most applications Low cost per penetration Quick and simple installation procedure 20 CP 620 Brandschutzbeschichtung sodfm,ev ijdjfiwhriuh. N owe 4i5kirdwiloi4jtf- x-.vbvbvh, ireiv Fire Foam (CP 620) solution for common construction materials. Can also be used in conjunction with CP 648E Wrap Strip One stop application Virtually impervious to smoke Fully cures in approximately 1 minute No additional materials required High yield One solution for various applications reach applications Excellent mold resistance Meets Class I W Rating requirements CP 660 High Performance Expanding Sealant A water-based sealant, designed to expand when exposed to heat CP 636 Firestop Mortar Fire resistant cementbased mortar with thermal insulating properties for large openings BS approvals for various penetrating items Suitable for openings up to 300 x 300mm Available in foil pack One side application Good thermal insulating properties A cementitious mortar with perlite One product to specify, purchase or inspect for most applications Low cost penetrations Quick and easy installation procedure Good for congested openings Suitable for wall applications High yield Good adhesion to seal, concrete and masonry Paintable 7

10 Firestop Systems Application Review Application Metal pipes Plastic/glass pipes Cables/cable trays Insulated metal pipes Metal ducts Multiple penetrations Joints Page Description Features 26 Firestop Mortar Some applications require (CP 637) minimum 2-1/2" depth A dry powder, when Cleans up with water mixed with water forms a pourable, trowelable be used in conjunction with CP 648E Wrap Strip Economical and simple to use Fast and easy clean-up 28 CP 670 Firestop Board with Accessories Ready to use Firestop Board designed for large openings with cable trays and multiple penetrations Lightweight design Variety of tested systems Easy to install; can be cut without power tools Solutions for low and high penetrated openings Solutions for congested areas 30 Firestop Block (CFS-BL) An innovative and simple designed to expand when exposed to heat Easy to cut and shape User friendly UL systems One-sided wall systems available Non-curing Easy to install, reuse and repenetrate around penetrating items Reduces need for extra labor, tools and parts Easiest solution for large openings with multiple penetrations 32 Firestop Plug (CFS-PL) A pre-sized, intumescent openings and cable penetrations Soft Flexible Design Versatile in use Non-curing Fast and cost effective installation Provides temporary or Reusable 34 Speed Sleeve (CP 653) Re-penetrable cable management device for electrical and telecom professionals Fast installation Low L-ratings Can be installed in wall and Easy penetration and re-penetration Withstands the rigors of usage and time 36 Firestop Drop-In Device (CFS-DID) Integrated moisture and smoke seal Quick and simple installation inspectors Solution for renovation/ for a variety of pipe materials and diameters construction Buy American compliant 8 Visit the local website for more information on products and services.

11 Firestop Systems Application Review Application Metal pipes Plastic/glass pipes Cables/cable trays Insulated metal pipes Metal ducts Multiple penetrations Joints Page Description Features 38 Cast-In Firestop Quick and simple installation Device Integrated moisture and (CP 680-P) smoke seal A one-step cast-in thicknesses from 2-1/2" variety of pipe materials (63 mm) and diameters Innovative adapter for metal deck applications 38 Cast-In Firestop Quick and simple installation Device Integrated moisture and (CP 680-M) smoke seal device for a wide variety thicknesses from 2-1/2" of non-combustible pipe (63 mm) materials and diameters Innovative adapter for metal deck applications 40 Firestop Wrap Strip May be continuously (CP 648E) wrapped Flexible Versatile and insulated pipe penetrations CP 648 Brandschutzmansch. sodfm,ev ijdjfiwhriuh. N owe Z8Z23aw p3i4 0288u27Āuze 4i5kirdwiloi4jtf- x-.vbvbvh, ireiv u9+ 12oeoo Ready to use no additional caulk required Easy to specify, install and inspect Cost effective solution Ready to use no additional caulk required Easy to specify, install and inspect Cost effective solution No need to measure each layer for multi-wrap applications Easy to use May be used inside the annular space or outside of the substrate 42 Firestop Wrap Strip (CP 648S) pipe penetrations Pre-measured no cutting required Integrated fastening tape No special tools required Easy installation User friendly Saves time and labor costs 44 Firestop Collar (CP 643N) device designed to collapse plastic pipe penetrations when Ready-to-use out of package Adjustable mounting tabs Simple and quick installation Flexibility in positioning of collar Allows for correct installation in tight areas 46 Firestop Collar (CP 644) device designed to collapse plastic pipe penetrations when Ready-to-use out of package Adjustable mounting tabs Simple and quick installation Flexibility in positioning of collar Allows for correct installation in tight areas 48 Firestop Putty Pad (CP 617, CP 617 L and CP 617 XL) A moldable putty sheet designed to help protect electrical outlet boxes Pad sizes 6" x 7", 7" x 7" or 9" x 9" 1 and 2 hour systems Tested for wood and steel studs Fits most common electrical boxes (refer to UL listings) Only one pad to stock and install Can be used for commercial and residential applications 9

12 Approvals and Testings Firestop products Approvals and Testing CPS - SP-WB FM EN EN APPROVED CP 606 FM APPROVED EN EN CP 601S FM APPROVED EN FS ONE MAX FM APPROVED CP 620 FM APPROVED EN CP 660 EN CP 636 FM EN SPECIFICATION TESTED CP 637 EN CP 670 FM EN SPECIFICATION TESTED CFS -BL FM EN APPROVED CFS -PL FM APPROVED EN CP 653 FM EN APPROVED CFS -DID CFS -680 CP 648-E FM APPROVED FM APPROVED FM APPROVED EN EN CP 648-S FM EN APPROVED CF 643 N CF 644 CF 617 CF 678 CF 679 A FM APPROVED FM APPROVED FM APPROVED FM APPROVED FM APPROVED EN EN EN IEC IEC Visit the local website for more information on products and services.

13 Additional Attributes Protecting against more than just fire. Improving building performance tested and certified. In addition to their superior behavior in passive fire protection, Hilti high-quality firestop systems enhance the performance and quality factor of a building in many more areas. They meet the requirements in building technology which continue to gain significance for designers and building owners. Improving seismic performance Hilti firestop products are tested for their performance in seismic events and help to reduce the risk of post-earthquake impacts. Avoiding the risk of mold and mildew Hilti firestop products are fungus resistant, thus alleviating the effects of surface moisture on the building. Improving acoustics Sound insulation is of great importance to the health and well-being of the occupants of a building. Hilti firestop products are tested for this purpose and individually tailored to the requirements of the installation and building structure. Electrical resistance Hilti has had the surface resistance and volume resistivity of fully cured and hardened firestop products tested for high electrical resistance in order to ensure that the firestop seal presents no hazards to the persons concerned. Chemical Resistance Hilti Firestop products have excellent resistance against chemicals. Chemical resistance is very important when working in environment were accidental spillage or concern of firestops coming in contact of chemicals is expected. Thermal Insulation Hilti Firestop products are also tested and can act as thermal barrier between compartments. Thermal Insulation is an important part when it comes to areas/compartments with variable temperature. Smoke and Gas Tightness Hilti Firestop products are Smoke and Gas tight. The smoke and gas-tightness of firestop products is of decisive importance in the event of fire as it may save lives. The requirements to be complied with in terms of smoke and gas-tightness are laid down in various laws and regulations. Water resistance Water resistance is an important ancillary element of firestop systems. Hilti firestop systems are not merely tested and approved in accordance with international firestop requirements, but have also been tested for their water-resistant properties according to the valid national and international standards. Explosion resistance Many building materials, building elements and penetration seals are significantly less endangered to static loads than to short-termed dynamic loads. Hilti Products were tested against the more critical type of load, which is the quick impact load similar to a detonation The tests to evaluate explosion resistant building components and building component sealing were conducted according to pren DIN and pren DIN Supporting green building standards Hilti products meet stringent environmental requirements, thereby supporting environmentally friendly building construction. Health, safety and environment profiles are available with references to LEED and BREEAM standards. 11

14 Firestop Joint Spray (CFS-SP WB) Product description maximum movement is required Areas of application Top-of-wall joints Curtain wall/edge of slab Expansion joints For use with Concrete, masonry and gypsum wall assemblies Examples Where a gypsum wall assembly meets the underside of a metal or concrete deck wall (concrete, glass, etc.) Product features Sprayable or apply by brush or trowel Approval) (ASTM E 1966 and UL 2079) Quick and easy installation with the Titan 600 or 1100 Sprayers can help save you time and money Contains no halogens, solvents or asbestos Water based formulation so spills and over-spray clean up quickly and easily Paintable Meets LEED requirements for indoor environmental quality credit 4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paints and Coatings Technical Data* CFS-SP WB Density Approx lb/gal (1.3 g/cm 3 ) Color Application temperature Temperature resistance Consistency Chemical basis Curing time Average volume shrinkage (ASTM C1241) Available in red, white and gray** 39 F to 104 F (4 C to 40 C) -40 F to 176 F (-40 C to 80 C) Sprayable liquid Acrylic-water-based-dispersion Approx F, 50% humidity for 1/8" (3mm) depth 51.1% Ph-value Approx. 8-9 Movement capability Up to 50% Surface burning characteristics (CAN/ULC-S102) Flame spread: 15 Smoke development: 10 Shelf life 1) LEED VOC 12 Months 73 g/l 59 (ASTM E 90-99) (per tested construction type) Tested in accordance with UL 2079 ASTM E 1966 ASTM E 84 ASTM E 2837 UL 1479 ASTM E 814 ASTM E 2307 Internationally Tested and approved *At 73 F (23 C) and 50% relative humidity **Gray color requires six (6) weeks lead time FM APPROVED EN EN Visit the local website for more information on products and services.

15 Ordering designation Volume per unit Sales pack Item number quantity CFS-SP WB red ml 1 pc CFS-SP WB white ml 1 pc Installation instructions for Firestop Joint Spray CFS-SP WB Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines always refer to the applicable drawing in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information Opening 1. Clean the opening. Surfaces to which Firestop Joint Spray will be applied should be cleaned of loose debris, dirt, oil, wax and grease. The surface should be moisture and frost free. Application of Firestop Joint Spray 2. Mineral wool packing: Install the prescribed back filling material type and depth to obtain desired rating. 3. Application of Firestop Joint Spray: Apply Firestop Joint Spray to the required depth in order to obtain the desired rating. Make sure Firestop Joint Spray contacts all surfaces and overlaps beyond all surrounding surfaces (Refer to UL System). Titan Sprayers have been successful in applying Firestop Joint Spray. Hilti recommends the use of the Titan 600 (for application temperatures above 50 F) or Firestop Joint Spray may also be brushed on with a paint brush. Contact Hilti Technical Support for more information. 4. Curing time: Allow approx. 24 hours for typical application thickness (@ 73 F / 23 C) 50% humidity for 1/8" depth for the Firestop Joint Spray to fully cure. 5. Identification: For maintenance reasons all Firestop Joint Spray applications can be permanently marked with an identification plate and fastened in a visible position next to the seal. Not for use In areas immersed in water On hot surfaces (above 176 F) (80 C) Storage Store only in the original packaging at temperatures 39 F to 77 F (4 C to 25 C) Observe expiration date on package 1. Clean opening 2. Pack in mineral wool compressed per UL System 3. Spray or brush on Firestop Spray 4. Allow Firestop Spray to cure (if required) 13

16 Flexible Firestop Sealant (CP 606) Product description applications Areas of application Sealing construction/expansion joints Top-of-wall joints Metal pipes Cable bundles HVAC penetrations For use with Various base materials such as masonry, concrete, gypsum, etc. Examples Where a gypsum wall assembly meets the underside of a metal or concrete deck toxic fumes Product features Silicone free Halogen, asbestos and solvent free Paintable Tested up to 33% movement with 500 cycles in accordance to UL 2079 and ASTM 1966 Smoke and fume resistant Easy clean up with water Single component systems available Meets LEED requirements for indoor environmental quality credit 4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paints and Coatings Technical Data* CP 606 Chemical basis Color Acrylic based firestop sealant Available in red, white and gray Application temperature 40 F to 104 F (5 C to 40 C) Skin-forming time Approx. 15 min Curing time Approx. 3 mm / 3 days Average volume shrinkage 22.2% (ASTM C1241) Movement capability Approx. 10% Temperature resistance 22 F to 176 F ( 30 C to 80 C) Surface burning characteristics (ASTM E 84-96) Flame Spread: 10 Smoke Development: 0 Sound transmission classification 56 (ASTM E 90-99) (Relates to specific construction) Shelf life 1) LEED VOC Base materials 24 Months 75 g/l Concrete, Masonry, Drywall, Steel Tested in accordance with UL 2079 ASTM E 814 ASTM E 1966 ASTM E 84 UL 1479 ASTM G21 *At 73 F (23 C) and 50% relative humidity Internationally Tested and approved FM APPROVED EN EN Visit the local website for more information on products and services.

17 Ordering designation Content per can/cartridge Volume per unit Sales pack Item number quantity CP ml white 310 ml 310 ml 1 pc CP ml INT grey 310 ml 310 ml 1 pc CP ml white 580 ml 580 ml 1 pc CP 606 5GAL white ml ml 1 pc Related Products Dispensers CP 670 Collars CP 643, CP 644 Wraps CP 648-S, CP 648-E page no 56 page no 28 page no page no Installation instructions for CP 606 Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines always refer to the applicable drawing in the UL Fire for complete installation information The use of backing material is recommended to control the sealant depth and help ensure assembly seal is complete Opening 1. Clean the opening. Surfaces to which CP 606 will be applied should be cleaned of loose debris, dirt, oil, wax and grease. The surface should be moisture and frost free. 4. Smooth firestop sealant with a trowel before the skin forms. Once cured, CP 606 can only be removed mechanically. 5. For maintenance reasons, a penetration seal can be permanently marked with an identification plate and fastened in a visible position next to the seal. Not for use On areas immersed in water Storage Store only in the original packaging in a location protected from moisture at a temperature of 40 F to 77 F (5 C to 25 C) Observe expiration date on package Application of firestop 2. Insert fill of mineral wool or backer rod (as required). 3. Apply firestop over backer rod. JOINT Firestop System 1. Clean opening 2. Insert backing material compressed per UL System 3. Apply CP Smooth CP 606 plate (if required) DUCT Firestop System 1. Clean opening 2. Insert backing material 3. Apply CP Smooth CP 606 plate (if required) 15

18 Elastomeric Firestop Sealant (CP 601S) Product description applications Areas of application Sealing construction/expansion joints Top-of-wall joints Metal pipes Cable bundles HVAC penetrations For use with Various base materials such as masonry, concrete, metal, glass, etc. Examples Where a gypsum wall assembly meets the underside of a metal or concrete deck toxic fumes Product features Halogen and solvent free Asbestos free Simple to use and apply Good adhesion without use of a primer Smoke, fume, water and UV resistant Excellent movement capability, meets 500 cycle requirements (ASTM E 1966 and UL 2079) Meets Class I W-rating requirements Meets LEED requirements for indoor environmental quality credit 4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paints and Coatings Technical Data* CP 601S Chemical basis Neutral elastic silicone Density Approx g/cm 3 Color Available in White, Gray Application temperature 40 F to 104 F (5 C to 40 C) Skin-forming time Approx. 15 min. Curing time Approx. 2 mm / 3 days Volume shrinkage Approx. 0 5% Movement capability Approx. 25% Temperature resistance 40 F to 320 F ( 40 C to 160 C) LEED VOC 3 g/l Shelf life 1) Surface burning characteristics (ASTM E84-96) 12 Months Flame spread: 0 Smoke development: 30 (ASTM E 90-97) Tested in accordance with UL 2079 ASTM E 814 ASTM E 1966 ASTM C 920 UL 1479 ASTM E 84 ASTM G21 *At 73 F (23 C) and 50% relative humidity Internationally Tested and approved FM APPROVED EN Visit the local website for more information on products and services.

19 Ordering designation Content per can/cartridge Volume per unit Sales pack Item number quantity CP 601S 310ML white 310 ml 310 ml 1 pc CP 601S 310ML grey 310 ml 310 ml 1 pc CP 601S 310ML red 310 ml 310 ml 1 pc CP 601S 600ML grey 600 ml 600 ml 1 pc Related Products Dispensers page no 56 Installation instructions for CP 601S Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines always refer to the applicable drawing in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information Opening 1. Clean the opening. Surfaces to which CP 601S will be applied should be cleaned of loose debris, dirt, oil, wax and grease. The surface should be moisture and frost free. Application of firestop 2. Insert fill of mineral wool (or backer as required). 3. Apply firestop over backer. 4. Smooth firestop sealant with a trowel before the skin forms. Once cured, CP 601S can only be removed mechanically. 5. For maintenance reasons, a penetration seal can be permanently marked with an identification plate and fastened in a visible position next to the seal. Chemical resistance At room temperature the cured silicone sealant is resistant for a short time to diluted (15%) acids and lyes/alkalis as well as most commercially available cleaning agents and disinfectants (except those containing iodine) Concentrated acids and lyes/alkalis destroy silicone rubber over time. Solvents and mineral oils cause cured silicone to swell. Consequently, proper functioning of the sealant should be checked after exposure to a solvent or mineral oil. Please contact your local sales representative or the nearest Hilti center if special requirements for chemical resistance have to be met. Not for use In areas immersed in water Not to be painted Storage Store only in the original packaging in a location protected from moisture at a temperature of 40 F to 77 F (5 C to 25 C) Observe expiration date on package JOINT Firestop System 1. Clean opening 2. Insert backing material compressed per UL System 3. Apply CP 601S 4. Smooth CP 601S plate (if required) DUCT Firestop System 1. Clean opening 2. Insert backing material 3. Apply CP 601S 4. Smooth CP 601S plate (if required) 17

20 High performance intumescent firestop sealant FS-ONE MAX Product description helps protect combustible and non-combustible penetrations for up to 4 hours fire rating Advantages One product for a variety of common through penetrations Cost-effective and easy-to-use solution W-rated systems available Ethylene glycol-free Industry leading VOC results Areas of application Steel, copper and EMT pipes Insulated steel and copper pipes Cable bundles Closed or vented plastic pipes HVAC penetrations For use with Examples construction construction Product features Smoke, gas and water resistant after material has cured Contains no halogen, solvents or asbestos Water based, easy to clean Paintable Single component systems available Meets LEED requirements for indoor environmental quality credit 4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paints and Coatings Technical Data* FS-ONE Chemical basis Water-based intumescent acrylic dispersion Color Red Application temperature 40 F to 104 F (5 C to 40 C) Skin forming time Approx min. Curing time Approx. 4 mm / 3 days Average volume shrinkage 24.1% (ASTM C1241) Movement capability Approx. 5% Expansion rate (unrestricted) Up to 3-5 times original volume Intumescent activation Approx. 302 F (150 C) Temperature resistance (cured) Shelf life 1) LEED VOC Surface burning characteristics (ASTM E 84-96) 40 F to 212 F ( 40 C to 100 C) 18 Months 9 g/l Flame Spread: 0 Smoke Development: 5 (ASTM E 90-99) Tested in accordance with UL 1479 ASTM E 814 ASTM E 84 ASTM G21 *At 73 F (23 C) and 50% relative humidity Internationally Tested and approved FM APPROVED 18 Visit the local website for more information on products and services.

21 Firestop System Firestop System Product Information Ordering designation Content per can/cartridge Volume per unit Sales pack Item number quantity FS-ONE MAX 10.1OZ CART 300 ml 300 ml 1 pc FS-ONE MAX 20.0OZ FOIL 592 ml 592 ml 1 pc FS-ONE MAX 5GAL PAIL ml ml 1 pc Related Products Dispensers Collars CP 643, CP 644 Wraps CP 648-S, CP 648-E page no 56 page no page no CFS-BL page no 30 CFS-PL page no 32 Installation instructions for FS-ONE MAX Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines always refer to the applicable drawing in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information Opening 1. Clean the opening. Surfaces to which FS-ONE will be applied should be cleaned of loose debris, dirt, oil, moisture, frost and wax. Structures supporting penetrating items must be installed in compliance with local building and electrical standards. Application of firestop sealant 2. Install the prescribed backfilling material type and depth to obtain the desired rating (if required). Leave sufficient depth for applying FS-ONE. 3. Application of firestop sealant: Apply FS-ONE to the required depth in order to obtain the desired fire rating. Make sure FS-ONE contacts all surfaces to provide maximum adhesion. For application of FS-ONE use a standard caulking gun, foil pack gun, bulk loader and bulk gun. With FS-ONE buckets, Graco type sealant pumps may be used. (Contact pump manufacturer for proper selection). 4. Smoothing of firestop sealant: To complete the seal, tool immediately to give a smooth appearance. Excess sealant, prior to curing, can be cleaned away from adjacent surfaces and tools with water. 5. Leave completed seal undisturbed for 48 hours. 6. For maintenance reasons, a penetration seal could be permanently marked with an identification plate. In such a case, mark the identification plate and fasten it in a visible position next to the seal. Not for use High movement expansion joints Underwater On materials where oil, plasticizers or solvents may bleed i.e. impregnated wood, oil based seals, green or partially vulcanized rubber In any penetration other than those specifically described in this manual or the test reports Storage Store only in the original packaging in a location protected from moisture at temperatures between 40 F (5 C) and 77 F (25 C) Observe expiration date on the package CABLE Firestop System 1. Clean opening. 2. Pack mineral wool. (If required) 3. Apply FS-ONE. 4. Smooth FS-ONE. 5. Leave completed seal undisturbed for 48 hours. 6. plate (if required). PIPE 1. Clean opening. 2. Pack mineral wool. (If required) 3. Apply FS-ONE. 4. Smooth FS-ONE. 5. Leave completed seal undisturbed for 48 hours. 6. plate (if required). 19

22 Fire Foam (CP 620) Product description Areas of application Sealing small to medium size openings Cables and cable trays Non-combustible pipes Combustible pipes when used in conjunction with Hilti Wrap Strips Where cables, steel, copper, cast iron or plastic pipes all pass through the same opening Concrete, drywall and masonry Examples Multiple penetrations Insulated metal pipes Product features Up to 6 times expansion of can yield Repenetrable Cures within 60 seconds Paintable Virtually impervious to smoke Mold resistant No additional materials required Execllent water vapor resistance Meets LEED requirements for indoor environmental quality credit 4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paints and Coatings Technical Data* CP 620 Chemical basis Color Fire foam yield Application temperature Two component polyurethane Red 3 Up to 110 in (1.8 litre) Substrate: 32 F to 104 F (0 C to 40 C) Product: 50 F to 104 F (10 C to 40 C) Curing time* Non-tacky after Approx. 35 seconds Ready to cut after Approx. 1 minute Thermal insulation (R-value) Temperature resistance of cured foam per inch of thickness 22 F to 212 F ( 30 C to 100 C) Shelf life 1) LEED VOC 9 Months 1.3 g/l (ASTM E90-97) Expansion rate (unrestricted) Surface burning characteristics (ASTM E84-01) Tested in accordance with UL 1479 ASTM E 814 ASTM E 84 ASTM G21 CAN/ULC-S115 *At 73 F (23 C) and 50% relative humidity Up to times original volume Intumescent activation Approx. 482 F (250 C) Flame spread: 0 Smoke development: 15 Internationally Tested and approved FM APPROVED EN Visit the local website for more information on products and services.

23 Ordering designation Content per can/cartridge Package contents Sales pack Item number quantity CP 620 US 300 ml 1x Cartridge, 2x Mixer, 1x Extension tube 1 pc Kit DSC kit 300 ml 1000x Dispenser DSC, 1000x Case, 4000x Firestop foam CP 620 GB-D-F-NL 1 pc assy, 8000x Mixer, 4000x Extension tube Related Products Dispensers page no 56 CFS-BL page no 30 CFS-PL page no 32 Installation instructions for CP 620 Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines always refer to the applicable drawing in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information Application 1-4. Prepare dispenser and cartridges as shown below. The Fire Foam from the first few strokes of the dispenser should be discarded until the Fire Foam in the mixer has a consistent red color. 5. Apply the CP 620 Fire Foam in the opening. Begin applying CP 620 Fire Foam at the back of the opening and work toward the front. Fill the opening completely with CP 620 Fire Foam. When dispensed slowly, the Fire Foam can be easily built up. When dispensed quickly, the consistency of the Fire Foam is more liquid allowing it to flow better between the cables. Note: The CP 620 Fire Foam becomes warm for a short time after application. 6. For maintenance reasons, the application can be permanently marked with an installation plate. Mark the installation plate and fasten it in a visible position next to the seal. Re-installing cables or pipes Additional cables or pipes can be installed later without difficulty. Use a suitable tool to create an opening. Push the cable or pipe through and then seal the remaining opening carefully with CP 620 Fire Foam. Notes The CP 620 Fire Foam can be cut back to no less than the minimum specified installation depth (see applicable UL systems for depths). Pieces of cured excess CP 620 Fire Foam which have been cut off can be laid in the next opening and fresh CP 620 Fire Foam can be applied around these. Not for use Exposed to weather Exposed to UV Storage Store only in the original packaging in a dry place at a temperature of 40 F to 77 F (5 C to 25 C). See technical data for application and substrate temperatures. Partly-used cartridges can be stored with mixer attached until they are required again. When re-using a partially used cartridge, simply attach a new mixer and dispense accordingly. Ausf hrungsschild 1. Hold the cartridge in the upright position and unscrew the cap. 2. Fit the mixer and screw in a clockwise motion until secure. 3. Release the dispenser and pull back the piston rod. 4. Insert the cartridge in the dispenser. 5. Apply CP 620 Fire Foam, building up a seal by working from the back towards the front. 6. Attach the installation plate (if required). 21

24 CP 660 Product description An innovative expanding product offering firestopping solutions for complex applications in small to medium sized openings. Applications: Permanent firestop seals in small and medium-sized openings (optimum size range:100 x 100 mm to 300 x 300 mm) Cable trays,bunched and single cables Openings accommodating pipes and cables Plastic pipes (can also be installed as a system in conjunction with Hilti firestop jackets and firestop wrap) Metal pipes (uninsulated or with flammable or non-flammable insulation) (National approvals must be observed.) Product Features Foam can be easily shaped during the curing process Neat and tidy application Very quick and easy to install and provides a reliable firestop seal with only one product Maintenance and retrofitting of cables is very easy Single-sided installation possible Smoketightness and firestopping with one system Paintable Technical data Chemical basis Base materials Approvals CP 660 Two component polyurethane Concrete, Masonry, Drywall ETA-10/0109 Fire foam Yield Repenetration Approx. tack-free time (at 23 C / 50% rel. humidity) Approx. curing time 1) 2.1 Litre Easy 5 min 10 min Application temperature range C Temperature resistance range C Expansion rate (unrestricted) Up to 2 times original volume Intumescent activation Approx. 482 F (250 C) LEED VOC Shelf life 1) 20 g/l 9 Months Storage and transportation 5-25 C temperature range Required dispenser HDM 330, HDE 500 Content per can / cartridge 1) at 75 F / 24 C, 50% relative humidity 325 ml Internationally Tested and approved EN Visit the local website for more information on products and services.

25 Ordering designation Content per can/cartridge Package contents Sales pack Item number quantity CP 660 INT 325 ml 1x Firestop foam CP 660 Internat. 1 pc Related Products Dispensers page no 56 Installation instructions for CP 660 Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Application of firestop 1. Clean the opening to be sealed free from dust or grease. 2. Slide the foil pack into the holder. 3. Remove the cap. Screw the mixing nozzle all the way onto the foil pack and tighten it securely. 4. Insert the holder containing the foil pack into the dispenser: 5. Discard the unevenly mixed initial quantity The mixed components of the foam react and begin to expand approx. 30 seconds after application (at including gaps between individual cables, etc. 7. The foam can be shaped or smoothed by hand (if necessary) after approx. 5 minutes (at 23 C). Wear protective gloves! After approx. 10 minutes (at 23 C) the foam becomes hard and it can then be cut. correctly sealed opening. 9. Additional cables or pipes can be installed in the approved maximum number and size of cables or pipes. The cable or pipe may be pushed directly through the foam. Where necessary, use a suitable tool (screwdriver or drill bit, etc.) to make a hole in the foam before pushing the cable or pipe through. Seal any remaining caps carefully with CP 660 Storage Store in a cool, dry, dark place at a temperature of +5 C to +25 C / +41 F to +77 F. 10min (@23 C) 23

26 Firestop mortar (suitable for walls) CP 636 Product description A fire resistant, cement based mortar with thermal insulating properties for sealing small to large sized openings where further penetrations may be required. Providing integrity of up to 4 hours. Areas of application Cables and cable trays Ductwork dampers Metal pipes Base materials Concrete Porous Concrete Masonry Product features Suitable for wall applications Excellent pot life / working time High yield Stiff (forms not always required) Contains no asbestos, phenol, or halogen constituents. Good adhesion to steel, concrete, and masonry Simple application by trowel paintable Technical data CP 636 Fire rating Base materials Chemical basis Up to 4 hours Concrete, Concrete (porous block), Masonry Concrete mortar with perlite Application temperature range 5 C - 40 C LEED VOC Acoustics performance Air Leakage Rating 1 g/l Up to 59dB m 3 /h (min) Gypsum based no Yield (20Kg Bag) Litres depending on mix ratio Internationally Tested and approved FM SPECIFICATION TESTED EN Visit the local website for more information on products and services.

27 Ordering designation Weight Sales pack Item number quantity CP KG 20 kg 1 pc Related Products CP 606 page no 14 Collars CP 643, CP 644 Wraps CP 648-S, CP 648-E page no page no CFS-BL page no 30 Mixers page no 56 Installation instructions for CP 636 Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines Application 1. Preparation of the opening Clean and pre-moisten the opening sides. Cables and cable trays must be dry and free from dust, oil or grease. Cables must be laid and secured as stated in the respective standard. 2. Mixing the firestop mortar Mix CP 636 firestop mortar in the mortar-towater ratio of about 3:1 by volume. It is important that first water then CP 636 is poured into the bucket. Thoroughly mix small quantities using a drilling machine and mixer. It is important that no further binding agents or additives are used. 3. Application of firestop mortar Forms should be placed on one or both sides of large openings. Openings in floors must have forming on the underside. Ready-mixed mortar should be applied with a trowel or pump and then compacted. Make sure that gaps, voids and remaining openings are completely closed and sealed. Smooth the surface like ordinary concrete. 4. Follow-up installation/reworking CFS-BL firestop bricks and CP 606 A intumescent mastic can be installed in the fire seal, while keeping in mind the maximum allowable size of the opening. Care must be taken to completely close any gaps, voids or remaining openings. 5. Identification plate Some countries require the cable fire seal to be marked with a lasting identification plate. This plate must be given the appropriate wording and then fastened next to the cable fire seal in a clearly visible position. CP 636 Ausführungsschild Clean opening, moisten surfaces Mix CP 636 mortar (by adding mortar to water) Put mortar into place Optional: add CFS-BL for future cable changes Fasten installation plate in place (if required) Re-installation: lay cables and close remaining opening 25

28 Firestop Mortar (CP 637) Product description Product features Areas of application Sealing medium size to large openings with non-combustible pipes or cable trays pipes For use with Concrete and masonry assemblies Examples Large openings containing multiple steel, conduit and EMT pipes Large openings with single or multiple cable tray applications Quick-setting forms can be removed in as little as 2 hours Superior working properties Can be used in horizontal or vertical applications Saves time Versatile Simple mixing Paintable Technical Data* CP 637 Color Light red, Light Grey Application temperature 40 F to 110 F (5 C to 43 C) Form removal Approx. 2 hours (depending on consistency) Chemical Basis Density (dry) Gypsum Based Mortar Approx pcf (650 kg/m 3 ) Expansion on setting (approx.) 0.08% Compressive strength 24 hrs. after casting After full cure Pourable 508 psi (3.5 N/mm 2 ) 725 psi (5.0 N/mm 2 ) Trowelable 870 psi (6.0 N/mm 2 ) 1784 psi (12.3 N/mm 2 ) Shelf life 1) LEED VOC 12 Months 0 g/l Surface burning characteristics (ASTM E84-01) Yield (20Kg Bag) Flame spread: 5 Smoke development: Litres depending on mix ratio Tested in accordance with ASTM E 814 UL 1479 ASTM E 84 ASTM G21 *At 75 F (25 C) and 50% relative humidity Internationally Tested and approved EN Visit the local website for more information on products and services.

29 Ordering designation Weight Sales pack Item number quantity CP 637 FS 13.6 kg 1 pc CP 637 FS GB 20 kg 1 pc Related Products CP 606 page no 14 Collars CP 643, CP 644 Wraps CP 648-S, CP 648-E page no page no CFS-BL page no 30 Mixers page no 56 Installation instructions for CP 637 Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines Application 1. Preparation of the opening Clean and pre-moisten the opening sides. Cables and cable trays must be dry and free from dust, oil or grease. Cables must be laid and secured as stated in the respective standard. 2. Mixing the firestop mortar It is important that first water then CP 637 is poured into the bucket. Thoroughly mix small quantities using a drilling machine and mixer. It is important that no further binding agents or additives are used. 3. Application of firestop mortar Forms should be placed on one or both sides of large openings. Openings in floors must have forming on the underside. Ready-mixed mortar should be applied with a trowel or pump and then compacted. Make sure that gaps, voids and remaining openings are completely closed and sealed. Smooth the surface like ordinary concrete. 4. Follow-up installation/reworking CFS-BL firestop bricks and CP 606 A intumescent mastic can be installed in the fire seal, while keeping in mind the maximum allowable size of the opening. Care must be taken to completely close any gaps, voids or remaining openings. 5. Identification plate Some countries require the cable fire seal to be marked with a lasting identification plate. This plate must be given the appropriate wording and then fastened next to the cable fire seal in a clearly visible position. Mix ratio (recommended, mortar to water): Trowelable 30 lb (13.6 kg) : 2 U.S. gal (8 L) Pourable 30 lb (13.6 kg) : 2.5 U.S. gal (9.5 L) CP 637 Ausführungsschild Clean opening, moisten surfaces Mix CP 637 mortar (by adding mortar to water) Put mortar into place Optional: add CFS-BL for future cable changes Fasten installation plate in place (if required) Re-installation: lay cables and close remaining opening 27

30 Firestop coated board system CP670 Product description Hilti CP670 is an innovative system for fast, reliable and cost effective firestopping of wall and floor openings especially large ones. Areas of application Extended approvals for large diameter cables, dampered penetrations and double board usage Single cables, cable bundles, cable tray air ducts and pipes Combustible and non combustible pipes Large penetrations possible up to 5 meters high by any length Base materials Drywall, Masonry, Concrete Storage Store only in the original packaging in a location protected from moisture and direct sunlight at a temperature of 5 C to 37 C. Observe expiry date on packaging. Product features Pre-coated board Odourless and solvent free Less prone to damage due to pliancy of the material and the resilient elastic coating Approved for a wide range of applications Technical data CP 670 Fire rating Up to 4 hours Base materials Concrete, Masonry, Drywall Application temperature range 5 C - 40 C 1) Shelf life (Coating) 15 Months 1) Shelf life (Board) N/A LEED VOC Acoustics performance Density (coating) Density (board) Coating Thickness Colour Approx. curing time 2) Skin forming time (at 23 C/50% r.h) 38 g/l Up to 62dB 1470 kg/m³ 160 kg/m³ 0.7mm dry (1.1mm wet) White 3 mm/day 7 hours (CP 670 Coating) 1) at 77 F/25 C and 50% relative humidity; from date of manufacture 2) at 75 F/24 C, 50% relative humidity Internationally Tested and approved FM SPECIFICATION TESTED EN Visit the local website for more information on products and services.

31 Ordering designation Weight Sales pack quantity Item number CP ,5kg (coating) 17.5 kg 1 pc CP x600x50 white (board) 16 pc Related Products CP 606 page no 14 Collars CP 643, CP 644 Wraps CP 648-S, CP 648-E page no page no Installation instructions for CP 670 coated board system Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines Application of Coated Board 1. Clean the opening. Do not pre-moisten opening surfaces. Cables and cable supporting structures must be dry andclean from dust, grease or oil, and installed in compliance with local building and electrical standards. 2 Cut the Hilti CP 670 Firestop board to size. In case of services cut out required space.coat cut edges with Hilti CP 606 Firestop Sealant. 3. Coat the surface of the opening with Hilti CP 606 Firestop Sealant (refer to relevant reports for specific details). Insert the mineral wool panel flush with the opening edge. 4. Pack any larger gaps with loose mineral wool. Seal between cables with Hilti CP 606 Firestop Sealant. Fill gaps with Hilti CP 606 Firestop Sealant. 5. Thoroughly stir Hilti CP 670 Fire Safety Coating Apply Hilti CP 670 Fire Safety Coating to the cables and cable trays on all surfaces over the required length. It can be applied using a brush, roller or airless spray gun (recommendation: a nozzle diameter, spray angle 40 ). To achieve the dry coating of 0.7 mm, a wet film thickness of ca. 1.1 mm is required. Fasten installation plate (if required) Note Instead of using a Hilti CP 670 Firestop board Hilti CP 670 Fire Safety Coating can be either sprayed or painted on the jobsite prior or during installation, respectively in advance. To achieve the dry coating of 0.7 mm, a wet film thickness of ca. 1.1 mm is required. Hilti CP 670 Fire Safety Coating can be used where cutting has caused exposed mineral wool to appear. In addition, the coating can be applied if mineral wool is used to pack gaps. Storage Store only in the original packaging in a location protected from moisture and direct sunlight Clean the opening Coat mineral wool panel with CP 670 Coat cut edges with CP 606 Fit mineral wool panel Fill gaps with CP 606 Fasten installation (if required) 29

32 Firestop Block (CFS-BL) Product description medium to large size openings Areas of application Sealing single or multiple penetrations in small to large openings Temporary or permanent sealing of cables and cable tray penetrations Temporary or permanent sealing of insulated and non-insulated metallic pipes and combustible pipe penetrations For use with Walls UL tested up to max. opening 72 " x 36" (1.8m x 0.9m) Floors UL tested up to max. opening 72" x 36" (1.8m x 0.9m) Concrete, porous concrete, masonry and gypsum wall assemblies Wall assemblies rated up to 4 hours Floor assemblies rated up to 3 hours Examples installations are frequently used (ie: computer centers, hospitals, laboratories, etc.) New buildings in the construction phase and during renovation Large openings containing multiple penetrations as found in production bays, warehouses, hospitals etc. Product features Integrated Grid-Tech increases Annular Space up to 12 Suitable for re-penetration or new penetrations Economical to use with short installation times Easy installation no special tools required One sided wall systems available Halogen, asbestos and solvent free Operational immediately after installation Smoke resistant Paintable Technical Data* CFS-BL Color Red Chemical basis Two component polyurethane Application temperature 40 F to 104 F (5 C to 40 C) Temperature resistance 5 F to 140 F (-15 C to 60 C) Intumescent activation Approx. 392 F (200 C) Expansion ratio (unrestricted) Up to 1:3 Surface burning characteristics (ASTM E 84-10b) Flame Spread Index: 10 Smoke Development Index: 15 Shelf life 1) LEED VOC (ASTM E 90) Tested in accordance with UL 1479 ASTM E 814 ASTM E 84 N/A 5.4 g/l STC Rating: 52 *At 73 F (23 C) and 50% relative humidity Internationally Tested and approved FM APPROVED EN Visit the local website for more information on products and services.

33 Ordering designation Package contents Sales pack Item number quantity CFS-BL 1x Firestop block CFS-BL (200 x 130 x 50 mm) 1 pc Related Products FS-One Max page no 18 CP 620 page no 20 Installation instructions for Firestop Block CFS-BL Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines always refer to the applicable drawing in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information Opening 1. Clean the opening. Penetration and penetration supporting structures must be installed in compliance with local building and electrical standards. Application of Firestop Blocks 2a.If no penetrations are located, build up Firestop Block CFS-BL, firmly seated, within opening. 2b.If penetrations are located, build up Firestop Block CFS-BL, firmly seated, while cutting blocks with a knife to suit the placed penetrations. 3. Finish building up Firestop Blocks until entire opening is filled. 4. Completely fill cable spaces, gaps between blocks and pipes, and joints with FS-ONE Firestop Sealant (as required). 5. For maintenance reasons, a penetration seal could be permanently marked with an identification plate. In such a case, mark the identification plate and fasten it in a visible position next to the seal. Re-installing cables or other penetrations Remove or cut the block from the seal. Install the penetrant and re-lay the block in compliance with the approval. Fill gaps and spaces with FS-ONE Firestop Sealant (as required). Single cables can be run through joints between blocks or a hole can be drilled through a block using a sharpened piece of metal pipe or tubing. Not for use In wet rooms, outdoors or exposed to the weather or UV radiation (can be done only after applying an additional silicone coating, i.e. CP 601S). Storage Store only in the original packaging in a location protected from moisture and direct sunlight 1. Clean opening. 2a. Build up blocks 2b. Cut blocks to size for penetrations in place 3. Build up blocks 4. Fill gaps with FS-ONE, CP 617 or CP 618 putty (as required). plate in place (If required) 31

34 Firestop Plug (CFS-PL) Product description Ready-to-use intumescent and reusable plug for small openings Areas of application Temporary or permanent sealing of cables single or bundled cables Examples are frequently changed such as computer centers, hospitals and laboratories New buildings in the construction phase and during renovation Product features Fast and easy installation no special tools required, helps reduce installation time and costs Immediately functional after installation Suitable for laying new cables later Versatile in use (temporary or permanent protection) Smoke resistant One-sided installation wall systems available Halogen and solvent free Paintable Technical Data* CFS-PL Density Approx g/cm 3 Chemical basis Two component polyurethane Color Red Application temperature 40 F to 104 F (5 C to 40 C) Temperature resistance 5 F to 140 F (-15 C to 60 C) Intumescent activation Approx. 392 F (200 C) Expansion ratio (unrestricted) Approx. 1:3 Shelf life 1) N/A LEED VOC 4.9 g/l Surface burning characteristics (ASTM E 84-10b) Flame Spread Index: 10 Smoke Development Index: 15 STC Rating: 55 (ASTM E 90) Tested in accordance with UL 1479 ASTM E 814 ASTM E 84 ASTM E 90 CAN/ULC S115 *At 73 F (23 C) and 50% relative humidity Internationally Tested and approved FM APPROVED EN Visit the local website for more information on products and services.

35 Ordering designation Package contents Sales pack Item number quantity CFS-PL 2 1x Firestop plug CFS-PL 2 10 pc CFS-PL 4 1x Firestop plug CFS-PL 4 6 pc Related Products FS-One Max page no 18 CP 620 page no 20 Installation instructions for Firestop Plug CFS-PL Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines always refer to the applicable drawing in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information Opening 1. Clean the opening. surfaces Firestop Plug CFS-PL will be in contact with, should be cleaned of loose debris, dirt, oil, moisture, frost and wax. Application of firestop plug 2. If there are no penetrations, install Firestop Plug CFS-PL within opening and bead with Hilti CP 618 Putty Stick where firestop plug interfaces with inside of sleeve (when required). 3a. If there are penetrations, cut Firestop Plug CFS-PL to fit around cables. 3b. Insert firestop plug into sleeve. Optional: seal cables by forcing CP 618 into interstices of cables. 4. For maintenance reasons, a penetration seal can be permenantly marked with an identification plate and fastened in a visible position next to the seal. Re-installing cables Remove firestop plug from opening Install the penetrant and re-install the firestop plug in compliance with the appropriate UL system. If single cables are installed, a hole can be drilled through the firestop plug and a cable passed through. Not for use In wet rooms or outdoors exposed to the weather or UV radiation Storage Store only in the original packaging in a location protected from moisture and direct sunlight Firestop System 1. Clean opening 2. Blank opening: Install plug and CP 618 Putty Stick 3a. With cables: Cut plug to 3b. Install plug around cables (optional: CP 618 Putty Stick forced into interstices of cables) 4. Fasten installation plate in place (if required) 33

36 Speed Sleeve (CP 653) Product description Re-penetrable cable management device for electrical and telecom professionals Areas of application Cable and cable bundles For use with Gypsum walls rated up to 4 hours Examples Electrical wiring Premise wiring Low voltage and datacom Product features Fast installation Easy penetration and re-penetration Low L-ratings Withstands the rigors of usage and time Technical Data CP 653 2" (50 mm) 4" (102 mm) OD (device only) 2.3" (60 mm) 4.3" (110 mm) 4.7" (120 mm) 6.7" (170 mm) ID 1.7" (48 mm) 3.6" (92 mm) Total length 12.4" (315 mm) 12.4" (315 mm) 1.5 lbs 2.6 lbs Temperature resistance 22 F to 212 F (-6 C to 100 C) Intumescent activation Approx. 320 F (160 C) Expansion ratio (unrestricted) 1:40 Shelf life 1) LEED VOC Metal Plastic Fabric Tested in accordance with UL 1479 ASTM E 814 N/A 7.6 g/l Steel with zinc coating ABS Internationally Tested and approved FM APPROVED EN Visit the local website for more information on products and services.

37 Ordering designation Outside diameter (flange) Core bit diameter Sales pack Item number quantity CP BA 120 mm 63 mm 1 pc CP mm 63 mm 1 pc CP BA 170 mm 113 mm 1 pc CP mm 113 mm 1 pc Related Products CP 606 page no 14 FS-One Max page no 18 Installation instructions for CP 653 Notice Always refer to the MSDS before use and the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information. Instructions for use 1. Use hole saw to create the appropriate hole. 2. Insert the sleeve. 3. Seal the gap with firestop sealant to impede smoke and gas migration. Repeat on other side of the wall 4. Spin the flange clockwise onto the device. Repeat on other side of the wall. 5. To open the device: (a) On one side of the wall, press the clip closures inward. (b) Twist the device counterclockwise and pull the red housing outwards to eliminate the bunching of the smoke seal fabric. A yellow label will be visible to indicate that the device is open. 6. To close the device: (a) On the same side of the wall, press the clip closures inward. (b) Twist the device clockwise until finger-tight, allowing it to engage with a click. For repenetration of cables, repeat steps 5 and 6. For installation options not presented here, consult your local Hilti representative for other rated firestop systems. 4 CFS-S ACR Open Close 3 x x 9 12 Aushrungsschi l d 35

38 Firestop Drop-In Device (CFS-DID) Product description diameters Helps reduce labor costs and increase productivity Ready-to-use out of box Internationally tested and approved by UL Areas of application For use in concrete, hollow core, and metal deck slab thicknesses ranging from 2-1/2" to 12-1/2" cored or sleeved holes Installation complete with several fastening options including gas actuated fasteners, metal hit anchors, and kwik con screw anchor systems Product features Integrated moisture and smoke seal Simple, quick error free installation Technical Data CFS-DID Expansion temperature ~ 356 F (~ 180 C) Expansion rate 1:15 load expansion, load = 5g/cm 3 1:40 free expansion Shelf life 1) N/A LEED VOC Temperature resistance Storage temperature Tested in accordance with ASTM E814 UL g/l -4 up to 190 F (20 up to 88 C) 23 up to 122 F (-5 up to 50 C) Internationally Tested and approved FM APPROVED 36 Visit the local website for more information on products and services.

39 Ordering designation Sales pack Item number quantity CFS-DID 2 C 1 pc CFS-DID 3 C 1 pc CFS-DID 4 C 1 pc CFS-DID 6 C 1 pc CFS-DID 2 MD 1 pc CFS-DID 3 MD 1 pc CFS-DID 4 MD 1 pc Related Products Installation instructions for CFS-DID Notice Always refer to the MSDS before use and the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information. 37

40 Cast-In Firestop Devices (CP 680-P and CP 680-M) For use in centers and laboratories Product description and diameters Helps reduce labor costs and increase productivity Ready-to-use out of the package Internationally tested and approved by UL and FM Reduces the chance of project delays due to failed inspections Installation and applications or concrete over metal deck CP 680-M: - Insulated and non-insulated metal pipes - EMT and electrical conduits - Cable bundles - Multiple pipes CP 680-P: Addresses all applications for CP 680-M as well as the following: - Plastic pipes such as PVC, CPVC, ABS, ENT and FRPP - Fresh and waste water pipes Not suited for Areas with high condensation Outdoor areas Wall applications Product features Quick and simple installation SpeedLine Alignment system promotes faster layout QuickTurn System creates fast, simple vertical connections Integrated moisture and smoke seal Innovative adapter for metal deck applications Technical Data CP 680-P and CP 680-M ID Footprint Opening required thru metal deck 2" (50mm) 95mm x 114mm 89mm diameter 3" (75mm) 120mm x 143mm 114mm diameter 4" (100mm) 162mm x 171mm 140mm diameter 6" (150mm) 228mm x 241mm 184mm diameter Expansion temperature 392 F (200 C) Expansion rate 1:50 (unrestrained) 1:30 (Load expansion, Load = 20g/cm 3 ) Shelf life 1) LEED VOC Standard height Temperature resistance Color Tested in accordance with UL 1479 ASTM E 814 ASTM G21 Internationally tested and approved N/A 1.4 g/l 8" (200mm) Maximum 212 F (100 C) CP 680-P: red CP 680-M: black Internationally Tested and approved FM APPROVED EN Visit the local website for more information on products and services.

41 Ordering designation CP 680-P 2" Cast-In Device CP 680-P 3" Cast-In Device CP 680-P 4" Cast-In Device CP 680-P 6" Cast-In Device CP 680-M 2" Cast-In Device CP 680-M 3" Cast-In Device CP 680-M 4" Cast-In Device CP 680-M 6" Cast-In Device for Combustible Penetrations for Combustible Penetrations for Combustible Penetrations for Combustible Penetrations for Metallic Penetrations for Metallic Penetrations for Metallic Penetrations for Metallic Penetrations Color Sales pack quantity Red 1 Red Red Red Black Black Black Black Item number Related Products Installation instructions for CP 680 N Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Installation instructions for concrete slabs available Concrete floor with metal decking For applications, use the correct size CP 680 Metal Deck Adapter for installed cast-in device and follow the illustrations. 1. Create the opening in the metal-deck Use the correct size CP 680 Metal Deck Adaptor with the installed castin device. Size the hole with the plastic extension, and cut the metal deck. 2. Assemble the metal-deck Adaptor. Remove the underside plastic protective cap. Fix the plastic extension and the two metal plates on the CP 680 cast-in firestop device. 3. Fix the CP 680 cast-in firestop device Position the CP 680 at the right place ensuring that the plastic extension has been well positioned in the hole. Screw the two metal plates on the metal deck with the device using Hilti self drilling srews. Before pouring the concrete, make sure the top cap is in place thereby preventing the flow of concrete into the cast-in device. 4. Pour the concrete slab to the required thickness 5. Clean the pipe. The flexible sealing membrane ensures the water tightness of the device once the pipe has been passed through. Very dirty pipes with remains of mortar for example, may lead to a loss of the tight seal by damaging this membrane. Very dirty pipes can also disturb expansion of the intumescent material and lead to delays in the closing action during fire. Badly soiled pipes should, therefore, be cleaned. 6. Install the pipe. Pipes can be installed from the top or from the bottom. Remove the plastic protective caps and pass through the pipe breaking the white membrane. If insulation is required pass the pipe through first followed by the insulation. Installation is finished and firestop functional at this stage. 1 2 Concrete floor 1 2 Installation option Follow the illustrations if CP 680 has to be cut to slab thickness before installation, or when riser clamps are used

42 Firestop Wrap Strip (CP 648-E) CP 648 Brandschutzmansch. sodfm,ev ijdjfiwhriuh. N owe Z8Z23aw p3i4e 0288u27Āuze 4i5kirdwiloi4jtf- x-.vbvbvh, ireiv u9+ 12oeoo Product description insulated pipe penetrations Areas of application Firestopping combustible pipe penetrations Penetrations through concrete over metal deck Plastic and insulated penetrations using PVC, CPVC, PPR, ABS, FRPP and PEX For use with Examples Waste water pipes Fresh water pipes Decking penetrations Product features Highly Intumescent Long length avoids waste Can be continuously wrapped Cost effective Quick and easy closure without tools Ideal for very tight installations Technical Data* CP 648-E Density Approx g/cm 3 Dimensions (approximate) 3/16" (5mm) x 1" (25mm) x 33 ft (10m) 3/16" (5mm) x 1-3/4" (45mm) x 33 ft (10m) Color Black with foil backing Temperature resistance 40 F to 212 F ( 40 C to 100 C) Intumescent activation Approx. 210 C Shelf life 1) N/A LEED VOC Height 3.1 g/l 5 mm Expansion ratio (unrestricted) 1:19 Tested in accordance with UL 1479 ASTM E 814 ASTM G21 *At 73 F (23 C) and 50% relative humidity Internationally Tested and approved FM APPROVED EN Visit the local website for more information on products and services.

43 Ordering designation Sales pack Item number quantity CP 648-E 1 x 33 1 pc CP 648-E 1,75 x 33 1 pc Related Products CP ER page no 56 CP 606 page no 14 FS-One Max page no 18 Installation instructions for CP 648-E Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines always refer to the applicable drawing in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information Opening 1. Clean the plastic or insulated pipe penetration. Expansion of the intumescent material during a fire closes the plastic or insulated pipe penetration. Very dirty pipes (ie: with remains of mortar) may lead to a delay in this closing action. Soiled plastic pipes or insulated pipe penetrations should, therefore, be cleaned in the area where the CP 648-E Firestop Wrap Strip is to be installed. Application of firestop system 2. Tightly wrap the required number of strips continuously around the penetrant, and hold in place with tape. 3. Push the Hilti Wrap Strip into the opening until it is flush with the substrate surface unless otherwise required by the UL system. It may be required by the UL system to clamp, wire or use a Hilti Retaining Collar to secure the wrap strip in place for some applications. 4. If the UL system requires a cold smoke seal, then apply the proper amount of Hilti FS-ONE sealant in the opening over the wrap strip. 5. For maintenance reasons, a penetration seal can be permanently marked with an identification plate and fastened in a visible position next to the seal. Not for use In highly corrosive surroundings With unapproved retaining collars, anchors/fasteners Outdoors Storage Store only in the original packaging in a location protected from moisture at temperatures between 23 F and 86 F ( 5 C and 30 C). Firestop System 1. Clean penetration 2. Wrap strips around of times 3. Push Wrap Strips into hole 4. Seal penetration against smoke with FS-ONE 5. Fasten installation plate (If required) 41

44 Firestop Wrap Strip (CP 648-S) Product description plastic and insulated pipe penetrations Areas of application Firestopping combustible pipe penetrations Penetrations through concrete over metal deck Suitable for the following plastic pipe materials: PVC, CPVC, ABS, FRPP For use with Examples Waste water pipes Fresh water pipes Decking penetrations Product features Highly intumescent Pre-measured no cutting required Integrated fastening tape Cost effective Quick and easy closure without tools Ideal for very tight installations Technical Data* CP 648-S Density Approx g/cm 3 Dimension (approximate) (thkns" x width" x length") 1.5": 3/16" x 1" x 6-3/4" 2": 3/16" x 1" x 8-1/4" 3": 3/16" x 1-3/4" x 11-1/2" 4": 3/8" x 1-3/4" x 15" 6": 1/2" x 1-3/4" x 22-1/4" Black with foil backing N/A 3.1 g/l 4 F to 212 F ( 20 C to 100 C) Color Shelf life 1) LEED VOC Temperature resistance Intumescent activation Approx. 210 C Expansion ratio (unrestricted) 1:19 Tested in accordance with UL 1479 ASTM E 814 ASTM G21 *At 73 F (23 C) and 50% relative humidity Internationally Tested and approved FM APPROVED EN Visit the local website for more information on products and services.

45 Ordering designation Dimensions (LxWxH) Sales pack Item number quantity CP 648-S-2 US 202 x 25 x 5 mm 10 pc CP 648-S-3 US 291 x 45 x 5 mm 10 pc CP 648-S-4 US 383 x 45 x 9 mm 10 pc CP 648-S-6 US 569 x 45 x 14 mm 6 pc Related Products CP 606 page no 14 FS-One Max page no 18 Installation instructions for CP 648-S Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines always refer to the applicable drawing in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information Installation 1. Clean the plastic or insulated pipe penetration. Expansion of the intumescent material during a fire closes the plastic pipe. Very dirty pipes (ie: with remains of mortar) may lead to a delay in the closing action. Soiled plastic or insulated pipes should, therefore, be cleaned in the area where the CP 648-S Firestop Wrap Strip is to be installed. 2. Install Wrap Strip. First check the annular space to ensure compatibility with the appropriate UL System. Use the CP 648-S Firestop Wrap Strip corresponding to the diameter of the pipe to be installed. Wrap the CP 648-S strip around the pipe and fasten it tightly using the integrated adhesive strip. Push the CP 648-S Firestop Wrap Strip into the annular space in accordance with the UL listing. 3. Seal against smoke and gas. Seal the remaining gap with Hilti FS-ONE sealant. 4. For maintenance reasons, a penetration seal can be permanently marked with an identification plate and fastened in a visible position next to the seal. Not for use In highly corrosive surroundings Outdoors Storage Store only in the original packaging in a location protected from moisture at temperatures between 23 F and 86 F ( 5 C and 30 C). 1. Clean penetration 2A. Wrap the CP 648-S Wrap Strip around the pipe and fasten it tightly with the adhesive strip. 2B. Push the CP 648-S Wrap Strip along the pipe and into the annular space as indicated above. 3. Seal penetration against smoke with FS-ONE sealant. 4. Fasten installation plate (If required) 43

46 Firestop Collar (CP 643N) Product description Areas of application Firestopping combustible pipes up to 6" diameter in penetrations Suitable for the following pipe materials: PVC, CPVC, ABS, PVDF, PP and FRPP For use with Types of installation Wall: two collars, one on each side Floor: one collar on underside (bottom) Example Waste water pipes Fresh water pipes Product features Ready-to-use collar No construction required Fast installation time Adjustable mounting tabs Technical Data Description Pipe outside dia (in.) CP 643N Collar Collar No. of outside Height hooks and dia. (in.) (in.) fasteners CP /1.5"N CP /2"N CP /3"N CP /4"N CP /6"N Temperature resistance -4 F to 212 F ( 20 C to 100 C) Shelf life 1) N/A LEED VOC 7.6 g/l Intumescent activation Approx. 250 C Expansion ratio (unrestricted) Up to 1:17 Tested in accordance with UL 1479 ASTM E 814 ASTM G21 1) at 77 F/25 C and 50% relative humidity; from date of manufacture Internationally Tested and approved FM APPROVED EN Visit the local website for more information on products and services.

47 Ordering designation Outside diameter Pipe diameter - range Sales pack Item number quantity CP /1.5 N 67 mm mm 1 pc CP /2 N 82 mm mm 1 pc CP /3 N 116 mm mm 1 pc CP /4 N 146 mm mm 1 pc CP /5 N 166 mm mm 1 pc CP /6 N 236 mm mm 1 pc Related Products CP 606 page no 14 FS-One Max page no 18 Installation instructions for CP 643N Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines always refer to the applicable drawing in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information Opening 1. Clean the plastic pipes. Expansion of the intumescent material during a fire acts to close the plastic pipe. Very dirty pipes (ie: with remains of mortar) may lead to a delay in this closing action. Soiled plastic pipes should, therefore, be cleaned in the area where the CP 643N Firestop Collar is to be installed. Application of firestop system 2. Seal the opening if required. Gaps may be closed with FS-ONE. The approved methods vary and are given in the specific UL system. 3. Close the CP 643N Firestop Collar. Place the CP 643N Firestop Collar around the plastic pipe and lock the closure by applying firm pressure until it latches. 4. Attach fastening hooks. The fastening hooks can be attached to various points on the metal hous ing. This allows the fastening points to be made to suit the space available in each case. The hooks must be positioned as symmetrically as possible. The required number of fastening hooks is indicated on the packaging. 5. Fastening the CP 643N Firestop Collar. Only when fastened properly can CP 643N offer protection against fire. a. Mark the fastening points. b. Drill holes with a Hilti rotary hammer drill (i.e. TE 4-A18) or, depending on base material, fasten using Hilti powder-actuated tool. c. To secure the CP 643N Firestop Collar, use Hilti anchors/fasteners. d. For maintenance reasons, a penetration can be permanently marked with an identification plate and fastened in a visible position next to the seal. Not for use With metal pipes In highly corrosive surroundings With unapproved anchors/fasteners Storage Store only in the original packaging in a location protected from moisture 1. Clean plastic pipe. 2. Close remaining gap to provide smoke and gas resistant seal. 3. Close collar. 4. Attach fastening hooks. 5. Fasten collar and (if required). 45

48 Firestop Collar (CP 644) Product description Areas of application Sealing of penetrations for combustible pipes from 8" to 10" in diameter Vented or closed pipe PVC or CPVC pipe For use with Concrete, masonry, and gypsum walls Types of installation Wall: two collars, one on each side Floor: one collar on underside (bottom) Examples Waste water pipes Fresh water pipes Product features Ready-to-use collar No construction required Fast installation time Adjustable/moveable fastening tabs Technical Data CP 644 Pipe Collar Collar No. of outside outside Height hooks and Description dia (in.) dia. (in.) (in.) fasteners CP /8" CP /10" Temperature resistance -4 F to 212 F ( 20 C to 100 C) Shelf life 1) N/A LEED VOC 7.6 g/l Intumescent Activation Approx. 210 C Expansion ratio (unrestricted) Up to 1:17 Tested in accordance with UL 1479 ASTM E 814 ASTM G21 1) at 77 F/25 C and 50% relative humidity; from date of manufacture Internationally Tested and approved FM APPROVED EN Visit the local website for more information on products and services.

49 Ordering designation Outside diameter Pipe diameter - range Sales pack Item number quantity CP / mm mm 1 pc CP /2 82 mm mm 1 pc CP / mm mm 1 pc CP /3 117 mm mm 1 pc CP /4 146 mm mm 1 pc CP /5 166 mm mm 1 pc CP /7 228 mm 1 pc CP /6 236 mm mm 1 pc CP /8 US 257 mm 1 pc CP /9 289 mm 1 pc CP / mm 1 pc Related Products CP 606 page no 14 FS-One Max page no 18 Installation instructions for CP 644 Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines always refer to the applicable drawing in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information Opening 1. Clean the plastic pipes. Expansion of the intumescent material during a fire acts to close the plastic pipe. Very dirty pipes, (ie: with remains of mortar) may lead to a delay in this closing action. Soiled plastic pipes should, therefore, be cleaned in the area where the CP 644 Firestop Collar is to be installed. Application of firestop system 2. Seal the opening. Gaps must be closed with FS- ONE. The approved methods vary and are given in the specific UL system. 3. Close the CP 644 Firestop Collar. Place the CP 644 Firestop Collar around the plastic pipe and lock the closure by applying firm pressure until it latches. 4. Attach fastening hooks. The fastening hooks can be attached to various points on the metal hous ing. This allows the fastening points to be made to suit the space available in each case. The hooks must be positioned as symmetrically as possible. The required number of fastening hooks is indicated on the packaging. 5. Fastening the CP 644 Firestop Collar. Only when fastened properly can CP 644 offer protection against fire passing through. a. Mark the fastening points. b. Drill holes with a Hilti rotary hammer drill (i.e. TE 4-A18) or, depending on base material, fasten using Hilti powder-actuated tool. c. To secure the CP 644 Firestop Collar, use Hilti anchors/fasteners. d. For maintenance reasons, a penetration can be permanently marked with an identification plate and fastened in a visible position next to the seal. Not for use With metal pipes In highly corrosive surroundings With unapproved anchors/fasteners Storage Store only in the original packaging in a location protected from moisture 1. Clean plastic pipe 2. Close remaining gap to provide smoke and gas resistant seal 3. Close collar 4. Attach fastening hooks 5. Fasten collar and required) 47

50 Firestop Putty Pad (CP 617, CP 617L and CP 617XL) Product description boxes Areas of application Protection of electrical outlet boxes For use with Gypsum wall assemblies with wood or metal studs Examples Where two outlets are within a single stud/cavity or within 24" Product features Applied by hand Fast installation Technical Data* CP 617 Dimensions (LxWxH) Consistency Color Application temperature CP 617: 6" x 7" x 1/8" (15 x 18 x 0.3 cm) CP 617L: 7" x 7" x 1/8" (18 x 18 x 0.3 cm) CP 617XL: 9" x 9" x 1/8" (23 x 23 x 0.3 cm) Moldable putty Red 32 F (0 C) to 104 F (40 C) Storage temperature 23 F (-5 C) to 104 F (40 C) Temperature resistance range C Curing time Non-curing Density 1.48 g/cm 3 Intumescent activation Approx. 220 F to 250 F (104 C to 121 C) Shelf life 1) N/A LEED VOC 4.35 g/l Volatile solvents Surface burning characteristics (ASTM E 84-96) None None Flame Spread: 15 Smoke development: 10 (ASTM E 90-97) Tested in accordance with UL 263 ASTM E 84 ASTM G21 *At 73 F (23 C) and 50% relative humidity Internationally Tested and approved FM APPROVED EN Visit the local website for more information on products and services.

51 Ordering designation Dimensions (LxWxH) Package contents Sales pack Item number quantity CP x7 152 x 178 x 3 mm 1x Firestop putty pad CP x7 20 pc CP 617 L 7 x7 178 x 178 x 3 mm 1x Firestop putty pad CP 617L 7 x7 20 pc CP 617 XL 9 x9 229 x 229 x 3 mm 1x Firestop putty pad CP 617XL 9 x9 20 pc Related Products Installation instructions for CP 617 Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines always refer to the applicable listing (CLIV) in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information Application of firestop putty 1. After ensuring box is cleaned of loose debris, dirt, oil, moisture, frost and wax, remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad is required. Exposed side of pad is placed against box. 2. CP 617 Firestop Putty Pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud) and completely seal against the stud within the stud cavity. 3. Reshape CP 617 to fit around conduit or cables. 4. Press CP 617 to all sides of electrical box. 5. Remove other side of label. Not for use In areas exposed to water Storage Store only in the original packaging in a location at temperatures 40 F (5 C) to 104 F (40 C) 1. Remove label from one side of CP Adhere CP 617 to outlet box around box 4. Press CP 617 to all sides of outlet box 5. Remove other side of label 49

52 Firestop cable coating CP 678 Product description Hilti CP 678 is a ready to use, water based, intumescent cable coating, which can be applied by brush or airless spray to prevent the propagation of fires along internal electrical cables. Cables coated with CP 678 will exhibit increased protection in the event of a fire. Also suitable for protecting against spread of flame on timber panels. Main applications Power plants. Telecommunication complexes. Industrial plants. Petrochemical plants. Paper mills. Factories and production facilities. Product features Water soluble, odourless and solvent free. Rapid drying. Remains flexible when dry. Intumescent. Free of fibres, or as asbestos. No derating effect on cables. Compatible with the sheathing of electrical cables. Chemical basis CP 678 Vinyl Acetate Approx. curing time 2) 24 h Intumescent. Yes LEED VOC Temperature resistance of cured coating 60 g/l 30 C to 80 C Application of second layer Consistency electric surface resistance per DIN VDE 0472/05.85 Transport Temperature: Viscosity: 1) at 77 F/25 C and 50% relative humidity; from date of manufacture 2) at 75 F/24 C, 50% relative humidity After 2 to 4 hours can be applied by paint brush or sprayed 1,1 x C to +25 C approx mpas Internationally Tested and approved FM APPROVED IEC Visit the local website for more information on products and services.

53 Ordering designation Package contents Sales pack Item number quantity CP KG 1x Firestop cable coating CP 678 kpl. 1 pc Consumption of CP 678 cable coating depends upon the application for which it is being used. The following application rates apply for the different standards: Test Standard Dry film thickness Wet film thickness Aprox. Requirement IEC mm coating 1. 4 mm coating 1.8 kg/m (1. 4 liters/m ) Germanischer Lloyd (based on IEC ) 0.5 mm coating 0.7 mm coating 0.9 kg/m (0.7 liters/m ) Factory Mutual Approval 1.6 mm 2.2 mm 2.86 kg/m (2.2 liters/m ) * Each 20 kilogram container of CP 678 contains approximately 15.4 liters. Installation instructions for CP 678 Opening Clean the cables. The cables and cable supporting structures must be dry and free from dust, grease or oil and installed in compliance with local building and electrical standards. Prepare the cable coating. Thoroughly mix the CP 678 coating. Any separated water in the container must also be mixed in. Do not add water. Apply CP 678 cable coating to all areas of the cables and cable run over the required length. This can be done using a paint brush, roller or airless spray gun with the recommended nozzle and 40 spray angle. Each application will achieve a dry film thickness of approx. 0.5 mm. To meet IEC 332 requirements, the dry film thickness must be at least 0.5 mm. For Factory Mutual requirements the dry film thickness must reach 1.6 mm. Coverage On a flat surface coverage will be approximately 650 gm per m 2 (at 0.5 mm DFT). On cable bundles and cable trays allow 1 to 1.5 kg per m 2 (at 0.5 mm DFT) depending on volume of cables, method of application and wastage (ie. over spray). Do not Paint over the coating. Use outside or in damp rooms. Apply to uninsulated cables. Safety precautions Keep out of the reach of children. Observe the safety data sheet. Wear suitable gloves and eye protection. Storage Store only in the original packaging in a location protected from moisture. Observe expiry date on bucket. Store at temperatures between 5 C and 37 C Ø 1 = 5-40 C F 5a 5b 5c 6 2-4h x = (Ø 2 - Ø 1 ) / 2 5a 5b 5c Ø 2 = FM: x = 1.6 mm (0.07") GL (IEC ): x = 0.5 mm (0.02") 1x = ca. 0.5 mm 24h* 51

54 Ablative firestop cable coating CP 679A Product description CP 679A is a solvent and chlorine-free dispersion with flame retarding pigments ablations coating compound. Asbestos and halogen free. CP 679A is an ablation product, which undergoes an endothermic reaction when subjected to fire. This means that evaporation of the water released by the heat has a crucial effect on the spreading of the fire. Product Features Viscoelastic, remains elastic even in thick coats. Impermeable to water. Resistant to oil and petrol spills. Weatherproof, virtually odourless and Environmental friendly. Paintable Fields of applications CP 679A is a universal fire retardant coating used on cables laid horizontally or vertically. It can be used both for indoor or outdoor applications. Offshore exploration, production & refining Oil & Gas Power Plants Chemical basis Ablative CP 679A Acrylate Yes Dust dry 3 h LEED VOC Temperature resistance of cured coating Thickness of layer 60 g/l -30 C to +80 C One single layer can achieve 1 mm dry coating thickness approx. 1.7 kg/m amount of coating Thickness of layer: wet dry 1,5 mm wet 1,0 mm dry 2,2 mm wet 1,6 mm dry Application of 2nd layer Consistency Transport temperature after 24 hours. (23 C/50% humidity) can be applied by paint brush, roller or sprayed + 5 C to +25 C * at 23 C and 50% relative humidity Internationally Tested and approved FM APPROVED IEC Visit the local website for more information on products and services.

55 Ordering designation Sales pack Item number quantity CP 679 A 20KG 1 pc Consumption of CP 679A cable coating depends upon the application for which it is being used. The following application rates applying for the different standards: Test Standard Dry film thickness Wet film thickness Aprox. Requirement IEC mm coating 1.5 mm coating Flat surface: 1.7 kg/m (1.3 liters/m ) Factory Mutual Approval 1.6 mm Cable bundles and cable trays : kg/m ( liters/m ) 2.2 mm Flat surface: 2.5 kg/m (1.9 liters/m ) Cable bundles and cable trays: kg/m ( liters/m ) Installation instructions for CP 679A Opening Clean the cables. The cables and cable supporting structures must be dry and free from dust, grease or oil, and installed in compliance with local building and electrical standards. Prepare the cable coating. Thoroughly mix the CP 679A coating. Any separated water in the container must also be mixed in. Do not add water. CP 679A should be applied at its original viscosity. Apply CP 679A cable coating to all areas of the cables and cable run over the required length. CP 679A can be applied with conventional brush, roller or with airless spraying equipment. It is advisable to use nozzle openings 0.58 to 0.63 mm or to inch. CP 679A can also be applied in several thinner coats, each of them being allowed to dry before recoating. A single coat can achieve a dry film thickness (DFT) of approx. 1.0 mm (0.04 in.). Please note that a 1.0 mm (0.04 in.) DFT is required to meet ABS (American Bureau of Shipping) and/or DNV (Det Norske Veritas) rules. Coverage On bunched cables the coverage rate of CP 679A will be approximately 1.7 kg per m2 (at 1.0 mm DFT). Do not Dilute with water. Apply to uninsulated cables. Safety precautions CP 679A has no toxic additives and therefore only requires such measures as are to be adopted when applying paints. Remove splashes arising during application immediately with water. Keep out of the reach of children. Observe the material safety data sheet. Wear suitable gloves and eye protection. Storage Store only in the original packaging in a dry location protected from moisture. Observe expiry date on bucket. Store at room temperature, free from frost. Clean cables Mix coating Apply coating 53

56 Dispenser foam CF Technical data Application temperature range Foam yield (up to) Shelf life 1) Colour 5-30 C 50 l 15 Months Manila Key applications and advantages Insulating gaps around window frames, cooling equipment and pipes, heating pipes, baths, wood floors, air-conditioning equipment, air ducts High yield Stop-and-go controlled dispensing 1) at 77 F/25 C and 50% relative humidity; from date of manufacture Ordering designation Sales pack Item number quantity CF ML 1 pc Filling foam CF-F 750 Technical data Application temperature range Foam yield (up to) Shelf life 1) Colour 5-30 C 35 l 12 Months Manila Key applications and advantages Gaps and cracks Drywall voids Cavities around electrical fittings Easy to use - finger dispensing High adhesive strength 1) at 77 F/25 C and 50% relative humidity; from date of manufacture Ordering designation Sales pack Item number quantity CF-F pc Insulating foam CF-I 750 Technical data Application temperature range Foam yield (up to) Shelf life 1) Colour 5-30 C 50 l 15 Months Manila Key applications and advantages Insulating window joints, attics, drywall General-purpose construction foam Filling - wall openings, pipe penetrations, panels, risers, ducts and prefabricated sections Suitable for universal use HFC-free 1) at 77 F/25 C and 50% relative humidity; from date of manufacture Ordering designation Sales pack Item number quantity CF-I pc Visit the local website for more information on products and services.

57 Smoke and Acoustic Sealant (CP 506) Applications Sealing construction joints and through-penetration openings in Advantages Easy to dispense, apply and tool Excellent airborne sound insulation properties Low shrinkage after curing Easy cleaning with water Paintable Tested/evaluated in accordance with: ASTM E 90 ASTM C 834 ASTM E 84 ASTM C 919 Technical Data CP 506 Color Chemical basis Storage and transport temperature range Curing time (73 F / 50% relative humidity) Skin-forming time (73 F / 50% relative humidity) white acrylic 40 F to 77 F (5 C to 25 C) approx. 3 mm / 3 days approx. 15 min Application temperature range 40 F to 104 F (5 C to 40 C) Shelf life (ASTM E 90) 24 months from date of manufacture STC 63 (per tested construction type) Movement capability (ISO 11600) approx. 12.5% Mold and mildew (ASTM G 21) Surface burning characteristics (ASTM E 84-08) mold resistant Flame spread: 10 Smoke development: 10 Air leakage L-Rating at Ambient = Less than 1 CFM / Lin Ft. L-Rating at 400ºF = Less than 1 CFM / Lin Ft. Ordering designation Volume per unit Sales pack Item number quantity CP ml 580 ml 1 pc Installation instructions for CP 506 Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines always refer to the product label, applicable product test reports and/or architect requirements Opening 1. Clean the opening. Surfaces to which CP 506 will be applied should be cleaned of loose debris, dirt, oil, wax, grease, and other contaminants. The surface should be moisture and frost free. Application of sealant 2. Apply sealant in opening at required depth 3. Smooth sealant with a trowel before the skin forms. Once cured, CP 506 can only be removed mechanically Not for use In areas immersed in water Storage Store only in the original packaging in a location protected from moisture at a temperature of 40 F to 77 F (5 C to 25 C) Observe expiration date on package 1. Clean opening 2. Apply CP Tool CP

58 Accessories Dispensers Dispensers Ordering designation Package Contents Sales pack quantity Item number Dispenser CFS-DISP for 300ml cartridge 1x Dispenser CFS-DISP 1 pc Dispenser CS 270-P1 for 600ml foil pack 1x Dispenser CS 270-P1 1 pc Foil Dispenser Replacement Nut Foil Dispenser Nozzles pc 10 pc Dispenser DSC box for CP 620 1x Dispenser DSC 1 pc Dispenser DSC cas 1x Dispenser DSC, 1x Case 1 pc Extension tube CP 620-EXT 1x Extension tube 12 pc Mixer CP 620-M 1x Mixer 12 pc Foam dispenser CF-DS1 Ordering designation Sales pack Item number quantity Dispenser gun CF DS-1 1 pc Foam accessories CF Ordering designation Package contents Sales pack Item number quantity Grip adapter CF-GA1 1x Adapter CF-GA1 12 pc Finger adapter CF-FA1 1x Finger adapter CF-FA1 12 pc Cleaner CFR 1/CF 100 Ordering designation Sales pack Item number quantity Cleaner CFR1 500ML 1 pc Construction chemicals accessories Ordering designation Sales pack Item number quantity Mixing paddle stnls. 1 pc Retaining collar CP 648-ER Key applications and advantages For use with CP 648-E firestop wrap Holds CP 648-E firestop wrap in place Ordering designation Sales pack Item number quantity Retaining collar CP 648-ER 1.75 x 25 1 pc Visit the local website for more information on products and services.

59 Estimating Tables Estimating Tables CP 620 Expanding Fire Seal Foam installation thickness: Surface area of Diameter of Seal Seal (mm x mm) mm No. of CP 620 cartridges Cable loading (as % of opening size) 0% 10% 30% 60% ø90 50 x ø x ø x ø x ø x ø x ø x ø x ø x ø x ø x ø x ø x ø x ø x x x Unit Conversion Table 1 = 25.4 mm 1 ft = mm 1sq in = 6.45 sq cm = sqm 1 in 3 = ml 1 oz. = 29.5 ml 1 gallon = 3.78 litre CP 636 Firestop Mortar 20 kg bags yield 22.2 litres a = opening depth in cm b = opening length in cm c = opening width in cm Blank opening b c Number of bags required = a x b x c 22,000 a e.g. 100 mm thick floor with 1 meter x 1 meter opening: Therefore number of bags required = 10 x 100 x 100 = 5 bags 22,000 Opening with 30% cross sectional area of services Number of bags required = a x b x c x ,000 Opening with 50% cross sectional area of services Number of bags required = a x b x c x ,000 Hilti CP 670 Ablative Firestop Coated Board System Degree of Load Opening Size (m 2 ) L x w (mm) 100x x x x x x x2000 0% CP 670 (kg) % CP 670 (kg) % CP 670 (kg) % CP 670 (kg) Note 57

60 Estimating Tables Estimating tables for through-penetrations How to estimate amount of Firestop needed for pipe penetrations Single pipe, circular opening Single pipe, rectangular opening For multiple pipes in an opening Use the Estimation Chart (Table 3) found on page 59. Find the pipe size across the top of the table and match it with the hole diameter found along the side of the chart. The value from the table represents the volume of 1. Calculate the area of the pipe. For schedule 40 steel pipe, use the Calculation Chart For Pipe Areas (Table 1) found on page 59. Find the pipe size that is used and note the Area located in the far right column OR calculate the total crosssectional area of the penetration using the following formula (note: all values should be in units of inches): 2 A P = (r P ) x 3.14 A P = total area of penetrating pipe r P = outside radius of penetrating pipe = diameter 2 Use the methods stated previously, but add all of the penetration areas (A p ) together before subtracting from the total area of the opening (A o ). 2. Calculate the area of the opening (all values in units of inches): A o = length x width A o = area of opening Circular Opening: A o = (r P2 ) x Subtract the area of the penetrating pipe from the area of the opening and multiply o - A P ) x F D F D penetration. For wall systems requiring 2. Sample Problem System C-AJ-1226 (1/4" depth FS-ONE) A o = 8" diameter in 2 A P = 6" diameter in in 2 x 1/4" = 4.0 in 3 of FS-ONE MAX = 65.5ml of FS-ONE MAX 58 Visit the local website for more information on products and services.

61 Estimating Tables Estimating tables for through-penetrations TABLE 1 Calculation chart for pipe areas Nominal pipe size Pipe O.D. Area (sq. in.) 1/2" " /2" " " " " " " " Pipe O.D. based on schedule 40 steel pipe and plastic pipe TABLE 3 TABLE 2 General estimation table for CP 648-E (Length of Wrap Strip required for different pipe diameters) Nominal Pipe Size Length of CP 648-E Wrap Strips (3/16" thick) Required* (Number of layers of Wrap Strips) /2" 8" 16" 26" 37" 2" 9" 20" 31" 43" 3" 12" 27" 41" 58" 4" - 30" 50" 70" 6" " 97" 8" " 10" " 12" " Estimations based upon Schedule 40 PVC Plastic Pipe. * Estimated quantities are approximate. No allowance has been made for waste. between the O.D. of a penetrating pipe and the I.D. of the opening through which it passes. 3 Unit Conversion Table 1 = 25.4 mm 1 ft = mm 1sq in = 6.45 sq cm = sqm 1 in 3 = ml 1 oz. = 29.5 ml 1 gallon = 3.78 litre Opening diameter Actual pipe diameter (in.) (O.D.*) Nominal pipe size (I.D.) 1/2 3/ / / / / Coverages are based on the outside diameter of schedule 40 steel pipe. * For insulated pipes, use the outside diameter of the insulation. For 1/4" depth, divide above number by 2. For 1" depth, multiply above number by 2. For 5/8" depth, multiply above number by For 1-1/4" depth, multiply above number by 2.5. For 3/4" depth, multiply above number by Estimate only. Assumes no waste. TABLE 4 FS ONE volume Approximate # of 10.1 Oz.Tubes required Collar length Pipe I.D. (in.) Pipe O.D. (in.) Collar I.D. (in.) required (cu. in.) required** (in.) * Applies to Hilti listed systems using retaining colllars refer to system(s) for details. Volumes are approximate, and assumes no waste. ** Collar length assumes the ends overlap 1". Volume of FS-ONE calculated with retaining collar item no s 59

62 Estimating Tables Estimating tables for joints TABLE 1 Top of wall joint estimation table for CP 601S, CP 606 and CP 506 (Fluted deck only deck ribs perpendicular to wall), table is based on a 1/2" joint and there would be no overspray with sealants. Joint Width 1-1/2" 2" 3" 1.2 lineal feet/10.5 oz. tube 1.1 lineal feet/10.5 oz. tube 0.82 lineal feet/10.5 oz. tube 1/2" 2.2 lineal feet/600 ml foil pack 2.1 lineal feet/600 ml foil pack 1.5 lineal feet/600 ml foil pack 14.1 lineal feet/gallon 13.5 lineal feet/gallon 10.0 lineal feet/gallon Estimations based upon 1/2" product depth on both sides of the wall. For 1/4" depth, multiply values by 2. Estimates may vary depending on deck type. All estimates are approximate, and TABLE 2 to wall) Joint Width 1-1/2" 2" 3" 1.9 lineal feet/10.5 oz. tube 2.1 lineal feet/10.5 oz. tube 1.9 lineal feet/10.5 oz. tube 1/2" 3.5 lineal feet/600 ml foil pack 4.0 lineal feet/600 ml foil pack 3.6 lineal feet/600 ml foil pack 23.2 lineal feet/gallon 26.1 lineal feet/gallon 23.6 lineal feet/gallon Estimations based upon 5/8" product depth on both sides of the wall. For 1-1/4" depth, divide values by 2. Estimates may vary depending on deck type. All estimates are approximate, and assume no waste. TABLE 3 a 1/2" joint and there would be no overspray with sealants. Lineal Feet/10.5 oz. Tube Lineal Feet/600 ml Foil Pack Lineal Feet/Gallon Sealant Depth (in.) Sealant Depth (in.) Sealant Depth (in.) Joint Width 1/4 1/2 5/8 1-1/4 1/4 1/2 5/8 1-1/4 1/4 1/2 5/8 1-1/4 1/4" /2" /4" " /4" * * * * * * 1-1/2" * * * * * * 2" * * * * * * 2-1/2" * * * * * * 3" * * * * * * 3-1/2" * * * * * * 6" * * * * 12 6 * * 7" * * * * * * 8" * * * * * * For wall to wall and top of wall joints, values shown are for one side of the wall only. Divide values by 2 to estimate for both sides of wall. Estimates may vary depending on deck type. TABLE 4 Joint Width 1-1/2" 2" 3" 1/4" 38.5 lineal feet/gallon 34.2 lineal feet/gallon 28.0 lineal feet/gallon 1/2" 34.2 lineal feet/gallon 30.8 lineal feet/gallon 25.6 lineal feet/gallon 3/4" 30.8 lineal feet/gallon 28.0 lineal feet/gallon 23.6 lineal feet/gallon 1" 28.0 lineal feet/gallon 25.6 lineal feet/gallon 22.0 lineal feet/gallon 1-1/2" 23.6 lineal feet/gallon 22.0 lineal feet/gallon 19.2 lineal feet/gallon 2" 20.5 lineal feet/gallon 19.3 lineal feet/gallon 17.1 lineal feet/gallon 2-1/2" 18.1 lineal feet/gallon 17.1 lineal feet/gallon 15.4 lineal feet/gallon 3" 16.2 lineal feet/gallon 15.4 lineal feet/gallon 14.0 lineal feet/gallon 3-1/2" 14.6 lineal feet/gallon 14.0 lineal feet/gallon 12.8 lineal feet/gallon Estimations based upon 1/8" product depth with 1/2" overlap and installation on both sides of the wall. For 1/4" depth, divide values by 2. may vary depending on deck type. All estimates are approximate, and assume no waste. 60 Visit the local website for more information on products and services.

63 Estimating Tables Estimating tables for joints TABLE 5 General joint estimation table for CFS-SP WB Firestop Joint Spray, and wall, top of wall, curtain wall) Joint Width Joint Width plus overlap Lineal Feet/ Gallon 1/2" 1-1/2" 102 3/4" 1-3/4" 88 1" 2" /2" 2-1/2" 61 2" 3" 51 3" 4" 38 4" 5" 30 5" 6" 26 6" 7" 22 8" 9" 17 Estimations based upon 1/8" product depth, with 1/2" overlap. For 1/4" depth, divide values by 2. For wall to wall and top of wall joints, divide values by 2 to estimate for both sides of wall. All estimates are approximate and assume no waste. Unit Conversion Table 1 = 25.4 mm 1 ft = mm 1sq in = 6.45 sq cm = sqm 1 in 3 = ml 1 oz. = 29.5 ml 1 gallon = 3.78 litre 61

64 Engineering Judgment Process Engineering Judgment Process Hilti has performed extensive testing in both through-penetration and construction joint applications. However, due to variations in construction throughout the phases of a project, it is not possible to test every application that may be encountered. For these situations, Hilti has developed a process for creating custom drawings to accommodate particular applications. Hilti custom drawings, or Engineering Judgments, are developed through the careful and restricted application of accepted fire protection engineering principles and guidelines set forth by the IFC. Test data of like systems are analyzed and applied toward similar applications that do not exactly meet the criteria of a current UL Listed System. If the systems listed in this guide do not accommodate a particular application, please photocopy, complete, and submit the appropriate form(s) to request an Engineering Judgment on the following page. Once received, the requested information will be evaluated and an Engineering Judgment will be created, if possible. Support Firestop Design Center Support Call 800-HILTI (44584) Hilti Online E: ae.contactus@hilti.com Hilti. Outperform. Outlast Visit the local website for more information on products and services.

65 Hilti. Outperform. Outlast. Remarks 63

66 Legislation The UL Fire resistance nomenclature directory The Fire resistance Directory utilizes an alpha-numeric numbering system: Basic number system = ALPHA-ALPHA-NUMERIC Through Penetrations The first letter represents what is being penetrated: F = FLOOR W = WALLS C = FLOORS OR WALLS (COMBINED) The second letter(s) provide more information about the floor or wall: A = CONCRETE FLOORS 5 INCHES THICK OR LESS B = CONCRETE FLOORS GREATERE THAN 5 INCHES THICK C = FRAMED FLOORS FLOOR/CEILING ASSEMBLIES D = STEEL DECK CONSTRUCTION E THRU I = NOT USED AT THE PRESENT TIME J = CONCRETE OR MANSONRY WALLS 8 INCHES THICK K = CONCRETE WALLS GREATER THAN 8 INCHES THICK L = FRAMED WALLS - GYPSUM WALLBOARD ASSEMBLIES M = BULKHEADS N THRU Z = NOT USED AT THE PRESENT TIME The four digit number describes the penetrating item(s): BLANK OPENINGS METAL PIPE CONDUIT OR TUBING NONMETALLIC PIPE CONDUIT OR TUBING CABLES CABLE TRAYS INSULATED PIPES MISCELLANEOUS ELECTRICAL (BUSWAY) MISCELLANEOUS MECHANICAL MIXED PENETRATING ITEMS RESERVED FOR FUTURE USE EXAMPLE: CAJ1150 C = FLOOR OR WALL PENETRATION A = CONCRETE FLOORS 5 OR LESS J = CONCRETE OR MANSONRY WALLS 8 OR LESS 1150 = METAL PIPE, CONDUIT OR TUBING Joint Systems The first letters indentify the type or joint: FF = FLOOR-TO-FLOOR WW = WALL-TO-WALL FW = FLOOR-TO-WALL HW = HEAD-TO-WALL CG = WALL-TO WALL JOINTS INTENDED AS CORNER GUARDS BW = BOTTOM OF WALL The third letter signifies the movement capabilities of the joint system: S = NO MOVEMENT (STATIC) D = ALLOWS MOVEMENT (DYNAMIC) The four digit number describes the nominal joint width: LESS THAN OR EQUAL TO GREATER THAN 2 AND LESS THAN OR EQUAL TO GREATER THAN 6 AND LESS THAN OR EQUAL TO GREATER THAN 12 AND LESS THAN OR EQUAL TO GREATER THAN 24 EXAMPLE: HWD0042 HW D = HEAD-OF-WALL = ALLOWS MOVEMENT (DYNAMIC) 0042 = LESS THAN OR EQUAL TO 2 Perimeter Fire Containment Systems The first letters identify the perimeter fire containment system: The third letter signifies the movement capabilities of the joint system: The four digit number describes the nominal joint width: CW = CURTAIN WALL S D = NO MOVEMENT (STATIC) = ALLOWS MOVEMENT (DYNAMIC) LESS THAN OR EQUAL TO GREATER THAN 2 AND LESS THAN OR EQUAL TO GREATER THAN 6 AND LESS THAN OR EQUAL TO Visit the local website for more information on products and services.

67 Legislation Building regulations (United States of America) Code References Building Code Through Membrane Construction Joints Curtain Wall (Year) Penetrations Penetrations IBC (2000) IBC (2003) IBC (2006) IBC (2009) NFPA 101 (2000) A A A A A NFPA 101 (2006) NFPA 70 National Electrical Code International Building Code (IBC) Penetrations (Sec. 712) Fire resistance rated walls Hilti Interpretation 65

68 Accessories Legislation Hilti Interpretation Fire Resistant Joint Systems (Sec.713) Hilti Interpretation Hilti Interpretation Hilti Interpretation E NFPA Life Safety Code (NFPA 101) Construction and Compartmentation (Sec. 8.2) Section Hilti Interpretation Visit the local website for more information on products and services.

69 Legislation Section A Hilti Interpretation Section Hilti Interpretation Section A Hilti Interpretation ASTM E814 Methods for Fire Tests of Through-Penetration Fire Stops, Methods for Fire Tests of Through-Penetration Fire Stops. Section A Exception No. 3 Hilti Interpretation Section Hilti Interpretation Section A Hilti Interpretation Penetrations and Miscellaneous Openings in Fire Barriers ( ) Section Hilti Interpretation

70 Accessories Legislation Section A Standard Methods of Tests of Fire Endurance of Building Construction and Materials, with ASTM E814, Methods for Fire Tests of Through- Penetration Fire Stops. Hilti Interpretation 2006 NFPA Life Safety Code (NFPA 101) Firestop Systems and Devices Required. Standard Test Method for Fire Tests Through- Penetration Firestops, or UL 1479, Standard for Fire Tests of Through- Penetration Firestops, Hilti Interpretation Membrane Penetrations through Standard Test Method for Fire Tests Through- Penetration Firestops, or UL 1479, Standard for Fire Tests of Through-Penetration Firestops, Hilti Interpretation Visit the local website for more information on products and services.

71 Legislation 69

72 Accessories Legislation European Technical Approval (ETA). European Technical Approval is harmonised test standard based on Independent Testing based on EN Standards. It symbolises that product is in conformity with essential requirements of the Construction Product Directive (CPD) and the product has been subjected to appropriate conformity Introduction Hilti Firestop systems for penetration seals of pipes, cables and construction joints within fire rated walls and floors will be sold with a European Technical Approval (ETA) and therefore be provided with a CE mark from January This will lead to more transparency, higher quality and improved safety. Difference between ETA and National Approvals European Technical Approval All regulated properties related to the essential requirements are assessed. Not only fire. Assessment of durability and servicability. 3rd party control. Must be accepted throughout Europe. National Approvals Only resistance to fire is assessed. No full assessment of the product properties. Not required. No 3rd party control. Not accepted in other countries (only in case of mutual agreement). Advantages of ETA Safety More comparable results based on strict and demanding testing Higher building performance through additional testing according to official standards More realistic results - products tested for essential performance criteria, not only fire. - Health and Environment - Mechanical Resistance - Movement - Durability and Servicability Transparency Independent testing and certification according to specified test programme - easy product comparison Harmonised tests throughout Europe The Firestop Products are covered according to common guidelines (ETAG 026) which enables customers to act according to a harmonised International Standard Reliability and Quality Higher quality of products - third party approval Production quality control monitored by approved third party CE marking for the Firestop Products to indicate ETA and third party approval with Certificate of Conformity. 70 Visit the local website for more information on products and services.

73 Estimating Tables Hilti CFS-DM Firestop Documentation Manager FOR PEACE OF MIND. It s never been easier to plan and document every Firestop Documentation Manager. This comprehensive software application allows planners, building owners and installations, as well as produce compliant installation Documentation Manager. Hilti firestop documentation compliant, simple and efficient. and installers and demands considerable administrative work. In order to project participants including the building owner, general contractor, as well as supervisory authorities. Hilti CFS-DM Firestop Documentation Manager this task becomes almost trivial application. documentation - all from one single software application. 71

74 Accessories Simplicity itself. Professional firestop documentation management in just 3 easy steps. 1 Prepare the project The project is planned using the user-friendly application. plans of the building integrated as necessary and all necessary data set out. 2 Record the fire seal are recorded on the spot using a smartphone or tablet computer. This data is transferred straight to the database label carrying the corresponding QR code. 3 Create a report After completion of the project, or in an intermediate step, all data from the project is retrieved and a report then produced auto matically. Information about the project can be supplemented at any time. The report can also be in a list and subsequently processed. All reports created are saved automatically. 72 Visit the local website for more information on products and services.

75 Estimating Tables Firestop Documentation To learn more about how CFS-DM can be implemented in your facility, visit Get started in 5 easy steps Download the free app from itunes or Google Play Buy your full license online or call 800-Hilti (44584) for full enrollment. Receive a welcome with a username and password Create a project and start documenting The CFS-DM software program offers following package options: Standard (# ) Unlimited Users Multiple reports 2D Plan Integration Upload technical documents Basic (# ) Unlimited Users Multiple reports 2D Plan Integration Upload technical documents Premium (# ) Unlimited Users Multiple reports 2D Plan Integration Upload technical documents Permanently save the documentation for up to 500 penetrations Permanently save the documentation for up to 5000 penetrations Permanently save the documentation for up to 20,000 penetrations Barcodes and Stickers # Identification sticker small 500 per roll # Identification sticker small 2000 per roll Extension options 10,000 penetrations 20,000 penetrations 50,000 penetrations System requirements Hilti CFS-DM is a web-based application that can be accessed through the internet using a standard browser utilizing Microsoft Internet Explorer TM, Google Chrome TM and Mozilla Firefox TM The mobile application is available for devices running Apple ios 6 or higher (Apple iphone TM and ipad TM ), Android TM 2.3 or higher. Hilti. Outperform. Outlast. Hilti Emirates L.L.C Dubai UAE Toll Free 800-Hilti (44584)