Transcription

1 GS6 Air Extractor System Installation and Operating Instructions 09/0

2 LEGAL NOTICES WARNING CONCEPT These instructions contain information for your personal safety and to prevent material damage. Information for your personal safety is denoted by a warning triangle. Information pertaining to material damage only has no warning triangle. The warnings are grouped according to these levels of risk: DANGER indicates that death or serious injury will result if proper precautions are not taken. WARNING indicates that death or serious injury can result if proper precautions are not taken. CAUTION with warning triangle denotes that minor injury can result if proper precautions are not taken. CAUTION without warning triangle denotes that material damage can result if proper precautions are not taken. BEWARE denotes that an undesirable event or state can result if the relevant advisory is not heeded. Should there be more than one level of risk, the warning for the highest level of risk is always used. A warning about personal injury with a warning triangle may also include a warning about material damage. NOTE denotes further, useful information. QUALIFIED PERSONNEL The unit/system may only be installed and operated in conjunction with this documentation. Installation, electrical connection and initial startup of the unit/system may only be performed by qualified personnel. Qualified personnel within the context of safety-related information in this documentation are those authorized to install, start up and identify equipment, systems and electrical circuits in accordance with safety engineering standards. INTENDED USE > WARNING When installing the equipment/system, observe the applicable building codes, fire protection regulations and accident prevention regulations of the Employer's Liability Insurance Association. Only use the equipment/system as intended for the applications described in this documentation and only in conjunction with the components recommended, approved and specified in this documentation by Öko-Haustechnik inventer GmbH. Changes and modifications to the equipment/system are not permitted. Trouble free and safe operation of the equipment/ system requires proper transportation, proper storage and assembly, as well as careful operation and maintenance. This documentation is part of the equipment/system and must be accessible at all times. Observe all safety regulations in this documentation. TRADEMARKS inventer is a registered trademark of ÖkoHaustechnik inventer GmbH. Other names used in this documentation may be trademarks whose use by third parties may infringe upon the rights of the owner. EXEMPTION FROM LIABILITY The content of this documentation has been reviewed for compliance with the hardware and software described. However, discrepancies cannot be ruled out and so liability cannot be assumed for full compliance. This documentation is updated regularly. Necessary corrections and appropriate additions are always included in subsequent versions. As of: 07/0 GS6 Air Extraction System Installation and Operating Instructions 09/0

3 TABLE OF CONTENTS System overview Description Features...7. Assembly...7 Operating conditions Telescopic tube...8. Flat duct (GS6-Corner)...8 Functional elements / interfaces GS6 PSU Installation Installation preparation PSU Telescopic tube Fitting the telescopic tube into the wall Protective hood Nonreturn valve Fan housing Inner baffle Flat duct (GS6-Corner) Dimensional drawings GS6 with protective hood GS6 with GS6-Corner Electrical connection Technical details GS6 air extraction system GS6 PSU Fan Telescopic tube Inner baffle Protective hood Flat duct Grate with sleeve Fan housing Nonreturn valve Deliverables, accessories and spare parts Deliverables Accessories Spare parts...7 GS6 Air Extraction System Installation and Operating Instructions 09/0

4 TABLE OF CONTENTS 9 Maintenance and repair Troubleshooting and disposal Troubleshooting GS6 air extraction system Functional modules Disposal... 9 Warranty and service Terms of warranty Service... 0 Legal notice GS6 Air Extraction System Installation and Operating Instructions 09/0

5 SYSTEM OVERVIEW SYSTEM OVERVIEW The GS6 was developed for the ventilation of rooms with outside windows in single and multiple occupancy houses, hotels and guest houses. It is an air extraction system that works without heat recovery and with direct current. Application areas The GS6 is fitted into the outside wall of a building and can be used for: Bathrooms / toilets Kitchens Utility rooms Hallways Variants The base element of every variant is the combination of wall mounting sleeve (), fan housing () with integrated fan () and the GS6 PSU. GS6 base element GS6 PSU The GS6 can optionally be connected to the following modules, offering extended functionality as compared to a standard On/Off switch* ) : R60 controller Delay switch Hygrostat Interior room side Note - The description and connection options of these modules are in additional, accompanying installation and operating instructions for the GS6 air extraction system. The ventilation system is covered by a baffle on the interior wall side. Inside baffles can be ordered: in colors white/silver/stainless/gold (material: is plastic, curved shape) in opaque glass (straight shape) as a frame for affixing a glass or ceramic tile (material: plastic, straight shape) *) The On/Off switch is not included in the delivery GS6 Air Extraction System Installation and Operating Instructions 09/0 5

6 SYSTEM OVERVIEW Exterior room side In the direction of the exterior room side, the ventilation system can be closed either with a protective hood (white/gray/bare ) ) or the GS6-Corner 500 / GS6-Corner 000, depending on preference and practical requirements The GS6-Corner is used mainly when a building is retrofitted with insulation as part of renovation measures. The air duct is embedded in the insulation and the airflow is directed out in the window reveal. The wall opening for the ventilation system must therefore be in close proximity to the window. The GS6-Corner 500 is used for a 50 50mm distance, the GS6-Corner 000 for a mm distance, between wall opening and window reveal. GS6 WITH PROTECTIVE HOOD GS6 WITH GS6-CORNER Validity The installation and operating instructions apply for these elements: COMPONENT DESCRIPTION FEATURES ORDER NO. GS GS6-Corner 500 Comprising flat duct (500mm), x wall brackets and moffit grate White GS6-Corner 000 Comprising flat duct (000mm), x wall brackets and moffit grate White part telescopic tube Extension (500mm) for standard telescopic tube GS6 protective hood High-grade steel, powder-coated White (RAL 906) Gray (RAL 70) High-grade steel, sanded Bare* ) Inside baffle Plastic (curved) White Stainless Gold** ) Silver ** ) Glass Opaque Frame Decor of tile R60 controller Fan speed regulator Delay timer Button with integrated delay controller Hygrostat Supports regulation of relative humidity *) Install only after coating (by customer) with Nano Set,included **) Not stock items (lead time on request) 6 GS6 Air Extraction System Installation and Operating Instructions 09/0

7 DESCRIPTION DESCRIPTION The GS6 air discharge system is used to expel old air from a room. The fan is preinstalled in the housing for ex works deliveries.. Features Low power consumption of fan (approx. 70% less than comparable AC fans) Use for wall thicknesses of mm, to 950mm with telescopic extension Hole for telescopic tube Ø 5mm Use for distance between wall opening and window reveal of mm (GS6-Corner) Combination of the base element with six inside baffles of different designs, shapes and colors, and with three protective hoods of different colors, or the GS6-Corner in white. Assembly GS6 WITH PROTECTIVE HOOD GS WITH GS6-CORNER Interior plaster Interior plaster Fan housing Fan housing Inside baffle Inside baffle Fan Fan 5 Nonreturn valve 5 Nonreturn valve 6 Telescopic tube, -part (sleeve with tube) 6 Telescopic tube, -part (sleeve with tube) 7 Protective hood rear panel 7 Window 8 Protective hood cover 8 Grate 9 Exterior plaster 9 Window ledge 0 Insulation 0 Duct Masonry Exterior plaster Insulation Masonry Figure : GS6 assembly GS6 Air Extraction System Installation and Operating Instructions 09/0 7

8 OPERATING CONDITIONS OPERATING CONDITIONS Caution - Only use the GS6 in rooms that are free of aggressive and caustic gases, and extreme dust exposure. This will ensure reliable functioning of the fan.. Telescopic tube Standard variant The length of the standard variant of the telescopic tube is 550mm, meaning it can be used for maximum wall thicknesses of 550mm. For wall thicknesses of mm, the telescopic tube is continuously adjustable. The sleeve can be shortened by a maximum of 50mm for wall thicknesses shorter than 5mm. Note - The minimum permitted wall thickness when using the standard variant of the telescopic tube is 50mm. The sleeve of the telescopic tube on the interior wall side is covered by the fan housing and an Inside baffle. Extension An extension is available as an option for walls having a thickness from 550mm to 000mm (maximum). The extension is a second telescopic tube without fan. The order number for the extension is under Validity in Section System overview. -part telescopic tube (extension) Fan housing Inside baffle Fan Nonreturn valve -part telescopic tube (sleeve with tube) Protective hood rear panel Protective hood cover Figure : GS6 assembly with two telescopic tubes (extension). Flat duct (GS6-Corner) The length of the flat duct (GS6-Corner 500) is 500mm, and so can be used for gaps between wall opening and window reveal of mm. If the gap between wall opening and window reveal is greater than 00mm, a flat duct 000mm in length can be ordered as an option (GS6-Corner 000). Note - The maximum permitted gap between wall opening and window reveal is 950mm. 8 GS6 Air Extraction System Installation and Operating Instructions 09/0

9 FUNCTIONAL ELEMENTS/INSTALLATION FUNCTIONAL ELEMENTS / INTERFACES. GS6 PSU Power supply (AC 0V, 50 Hz) Fan connector (-) Fan connector (+) or functional module (+) Figure : Connectors on GS6 PSU 5 INSTALLATION 5. Installation preparation Dimensions Name Comprising: Length (mm) LxW / diameter (mm) Hole for Wall thickness Ø 5 telescopic tube - (with insulation, interior/exterior plaster) Telescopic tube Sleeve 00 Ø 07 Tube 00 Ø 0 Extension Identical in design to combination Wall mounting sleeve / telescopic tube Flat duct x Opening for - 87 Ø 75 wall mounting box Wall mounting box - 87 Ø 7 Wall holes and cable laying Note - Keep a minimum distance of 00mm from the center of the wall mounting sleeve to walls, to components in the interior area as well as to fixtures and fittings. Danger - Make the opening for the wall mounting box outside protective areas 0 to of the room. This will ensure that no moisture can penetrate in.. Make two holes in the masonry - one (Ø75) for the wall mounting box and one (Ø5) for the telescopic tube. Ensure that the hole for the wall mounting sleeve of the GS6 is at an angle of - to the outside wall so that condensation is drained away reliably.. Lay the -wire connecting lead (red/white) for the wall mounting box in the cable duct such that the cable ends project out of each wall opening by at least 50mm. This ensures that the PSU and switch can be connected with terminal blocks. Note - The dimensional drawings for all holes are in Section Dimensional drawings. GS6 Air Extraction System Installation and Operating Instructions 09/0 9

10 INSTALLATION 5. PSU Danger - Before starting any work on electrical systems, disconnect all relevant equipment from the power supply. When wiring the power supply, observe the requirements of Safety Class II. GS6 PSU 5 Figure : Fitting the PSU 5 Cavity PSU Fan connector (terminal, -pin) Wall mounting box Cavity separating wall. Make two holes on the wall mounting box () - these must be in different cavities ().. Separately guide the cables for the PSU and the fan through one hole each and insert the wall mounting box.. Connect the fan cable to the PSU () using the -pin terminal ().. Ensure correct polarity connections are made. Information on this is in Section Electrical connection. Note - The wall mounting box must always be shut. GS6 PSU - Attach a standard or optionally available On/Off switch. Order number information is in Section Deliverables and accessories. 5. Telescopic tube GS6 with protective hood GS6 with GS6-Corner Exterior plaster Insulation Masonry Interior plaster Figure 5: Determining the wall thickness 0 GS6 Air Extraction System Installation and Operating Instructions 09/0

11 INSTALLATION GS6 with protective hood GS6 with GS6-Corner. Determine the exact wall thickness by. Determine the exact wall thickness by adding the thicknesses of exterior plaster, insulation, adding the thicknesses of masonry and masonry and interior plaster. interior plaster.. Add 5mm for the projection at the. Add 0mm for the projection at the outside plaster edge. The projection is required for masonry. The projection is required for correct correct installation of the protection hood. installation of the flat duct.. Shorten or extend the telescopic tube in line with the wall thickness determined. The following table shows an overview of the exact procedure. Standard telescopic tube telescopic tubes (extension) Wall thickness (mm) Wall thickness (mm) a) Shorten the sleeve to the wall thickness using a grinder or jigsaw. Keep pulling the telescopic tube out of the sleeve until the length corresponds to the wall thickness. Connect up the two telescopic tubes such that they overlap by at least 50mm. b) Subtract 0mm from the wall thickness and shorten the tube to the difference using a grinder or jigsaw. - Align the tube combination to the length corresponding to the wall thickness. c) - - Protect the tube combination using durable, watertight adhesive tape* ). Seal all the joints of the tube and sleeve with durable, watertight adhesive tape* ). This fuses together the joints. When condensation forms in the telescopic tube, the sealed joints prevent moisture from penetrating into the wall. *) Not included in the delivery. GS6 Air Extraction System Installation and Operating Instructions 09/0

12 INSTALLATION 5. Fitting the telescopic tube into the wall. Insert the telescopic tube () into the wall opening. Ensure that the fastening elements () for the protective hood are inserted horizontally. Masonry ca. 0 mm Free area between masonry and telescopic tube Telescopic tube Securing elements for protective hood Figure 6: Inserting the telescopic tube. Align the telescopic tube at an angle of - to the outside wall Use polystyrene or wood wedges for securing. Note - GS6 with protective hood: Ensure that the two elements for securing the protective hood () to the outer wall protrude no more than mm. GS6 with GS6-Corner: Ensure that the telescopic tube protrudes 0-5mm on the outside wall. This ensures that the flat duct can be fitted correctly. Before inserting the telescopic tube, turn the two brass sleeves upwards and affix the all-round sealing tape (included) at a distance of 8mm from the outer edge of the telescopic tube (see Figure : no. ). Use -component foam to fully foam the free area between the masonry and telescopic tube ().. Cut the installation foam inside and outside flush to the wall. 5. GS6 with GS6-Corner: Stick sealing tape all around the projection of the telescopic tube. Caution - The GS6 is not suitable for drying out buildings. Do not use the GS6 whilst construction work is being carried out in the building. Close the telescopic tube to protect the fan. This safeguards reliable functioning of the GS6 following completion of building work. GS6 Air Extraction System Installation and Operating Instructions 09/0

13 INSTALLATION 5.5 Protective hood Protective hood rear panel Sealing tape Holes for securing the rear panel to the telescopic tube Figure 7: Protective hood rear panel. Apply the sealing tape (included) on the rear panel as in Figure 7. Ensure to keep a gap of approx. 7mm on the left and right from the outer edge for sliding on the protective hood.. Turn the board over. The sealing tape is facing the facade. Protective hood cover Sealing tape Figure 8: Protective hood cover. Use the two screws (included) to attach the rear panel of the protective hood to the two fastening elements of the telescopic tube. Seal the protective hood at the top edge as in Figure 8 5. Slide the protective hood* ) onto the rear panel from above Note: Remove the polystyrene spacer from the telescopic tube before fitting the protective hood *) Use of the GS6-Blank protective hood only after coating (by customer) with Nano Set included GS6 Air Extraction System Installation and Operating Instructions 09/0

14 INSTALLATION 5.6 Nonreturn valve Fan housing with fan Nonreturn valve Figure 9: Nonreturn valve and fan housing. Insert the nonreturn valve () into the rear of the fan housing (). Allow the four attachment hooks to audibly click into place 5.7 Fan housing 6 Housing screen 5 7 Housing cover Fan housing Hole for cable feedthrough (PSU connection) 8 5 Nonreturn valve 6 Telescopic tube Connector cable (-wire) position from the masonry for fan and PSU connection Masonry Hole for wall attachment ( x) Figure 0: Fan housing installation on interior room side GS6 Air Extraction System Installation and Operating Instructions 09/0

15 INSTALLATION Note: The polystyrene spacer, if still in, and any dirt residue must be removed from the telescopic tube before the fan housing is fitted. Also, the -wire cable for connecting the fan to the PSU must be wired at the designated place (7).. Remove the housing screen () and housing cover () from the fan housing (). Undo the two screws to remove the housing cover. The housing screen is clipped on.. Before final installation, drill four holes (Ø 6mm) in the wall for the wall attachment (9). To do this, position the fan housing into the telescopic tube (6) from the interior wall side, align it and mark the places for drilling at the four external holes for wall attachment (9) of the fan housing. Remove the fan housing, drill the wall holes and insert the dowels (included).. Position the fan housing (), including nonreturn valve (5), into the telescopic tube (6) from the interior wall side. Before pushing the housing all the way to the wall, route the -wire cable for the fan and PSU connection through the cable feedthrough hole (7).. Push the fan housing all the way to the wall and attach it to the masonry using the four screws (included) at the four external holes for wall attachment (9). 5. Connect the cable in the fan housing to the connectors provided. Information on this is in Section Electrical connection on Page. 6. Refit the housing screen () and housing cover (). GS6 Air Extraction System Installation and Operating Instructions 09/0 5

16 INSTALLATION 5.8 Inside baffle Fan housing Inside baffle Mounting elements (x ) Figure 9: Fitting the Inside baffle. Put the Inside baffle () onto the fan housing () - as seen from the inside panel.. Allow the four mounting elements () to audibly click into place Figure 0: (from left to right) inside baffle (curved plastic), glass inside baffle, tile inside baffle 6 GS6 Air Extraction System Installation and Operating Instructions 09/0

17 INSTALLATION 5.9 Flat duct (GS6-Corner) The flat duct is mounted onto the telescopic tube instead of the outer hood. Note - Ensure that sealing tape is applied all around the telescopic tube. Make sure that the flat duct is mounted at an angle of - towards the window reveal so that any condensation is reliably drained away ( ) Masonry 8 Interior plaster 9 Exterior plaster Sleeve (reveal grate) Telescopic tube 0 Insulation 5 inside baffle Wall bracket (x ) Fan housing Flat duct* ) 6 Window Wall hole break-out (left/right) 7 Window frame Sealing tape * ) Use the 500mm flat duct when the maximum value of y+z = 50mm. Use the 000mm flat duct when y+z is between 5mm and 950mm. Figure 0: Fitting the flat duct (complete unit). Add y and z.. Subtract 5mm from this value for the end position of the duct.. Shorten the flat duct on the side opposite the hole for the telescopic tube down to the length determined: overall length of flat duct = 70mm + (y+z) - 5mm. GS6 Air Extraction System Installation and Operating Instructions 09/0 7

18 INSTALLATION Telescopic tube sealing tape Wall bracket (x ) Window reveal Wall holder fixing fixing screws (x ) Insulation Exterior plaster Telescopic tube Masonry Figure : Fitting of wall brackets. Use the fixing screws () to attach the two wall brackets () to the outer wall. Flat duct Wall bracket (x ) Grate Sleeve Figure : Fitting of sleeve and grate. Push the circular opening on the flat duct onto the telescopic tube and secure it at the wall brackets ().. Push the sleeve () for attaching the grate onto the flat duct.. Push the grate () onto the sleeve until it audible clicks into place (additional securing with acrylic as required). 5.0 Dimensional drawings 5.0. GS6 with protective hood Wall opening Ø5 50 Protective hood (outline) Exterior side element (e.g. window, door) Shown in the drawing is the situation most aesthetic visually - the top edge of the protective hood is flush with the top edge of the structural element or with the lower edge of the soffit on the lintel. Figure : Wall opening dimensional drawing, GS6 telescopic tube with protective hood (exterior view) Note - Keep to the minimum distance of 50mm away from other components on the exterior. 8 GS6 Air Extraction System Installation and Operating Instructions 09/0

19 INSTALLATION Air extraction system (as a complete assembly) Figure : Dimensional drawing for GS6 with protective hood Telescopic tube (extension) 00 Ø07 Ø Figure 5: Dimensional drawing for -part telescopic tube (extension) Wall mounting box 6 7 Ø7 Figure 6: Dimensional drawing for wall mounting box Protective hood Figure 7: Dimensional drawing for GS6 protective hood GS6 Air Extraction System Installation and Operating Instructions 09/0 9

20 INSTALLATION Inside baffle Figure 8: Dimension drawing from left to right GS inside baffle (white, stainless, gold and silver), glass, tile 5.0. GS6 with GS6-Corner Note - The dimensional drawings for these components are in Section Dimensional drawings for GS6 with protective hood - telescopic tube (extension), wall mounting box and inside baffle Wall opening 50 Flat duct (outline) * Ø5 Lower edge of soffit (lintel)* Outer edge of reveal (masonry) *) Take into consideration insulation thickness and any roller shutters Figure 9: Wall opening dimensional drawing, GS6 telescopic tube with GS6-Corner (exterior view) 0 GS6 Air Extraction System Installation and Operating Instructions 09/0

21 INSTALLATION Air extraction system (as a complete assembly) Figure 0: Dimensional drawing for GS6 with GS6-Corner Flat duct Figure : Dimensional drawing for flat duct (500mm/000mm) Reveal grate Figure : Dimensional drawing for grate with sleeve GS6 Air Extraction System Installation and Operating Instructions 09/0

22 OPERATION 6 ELECTRICAL CONNECTION Danger - Before working on electrical systems, disconnect all relevant equipment from the power supply. AC 0 V, 50 Hz N L 5 A B - + ) ) A B ) ) AC 0 V, 50 Hz 6 A B A DC 5 V ) ) B Fan A Connector A ) Red Hygrostat* ) B Connector B ) Black Delay timer* ) N Neutral ) White R60 controller* ) L Conductor On-off switch** ) GS6 PSU *) Functional module (optional) **) optional Figure : GS6 connection example Note - The GS6 PSU is not disconnected from the power but remains continually in standby mode (except when using the on/off switch). The descriptions and connection options for the functional modules are in additional, accompanying installation and operating instructions for the GS6 air extraction system. GS6 Air Extraction System Installation and Operating Instructions 09/0

23 INSTALLATION PSU (DC V) ) ) ) ) Fan housing ) Red ) Black ) White Figure : Fan connection Note - The position of the cable (to connect the fan and PSU) should be set to o'clock on the telescopic tube panel. The cable is then directly at the intended cable feedthrough of the fan housing and can be routed straight into the housing. Information on this is in Section Installation > Fan housing. GS6 Air Extraction System Installation and Operating Instructions 09/0

24 TECHNICALDETAILS 7 TECHNICAL DETAILS 7. GS6 air extractor system Airflow GS6 with protective hood (telescopic tube 500mm) GS6 with GS6-Corner 500 GS6 with GS6-Corner Pa 66m³/h 5% lower (basis for comparison: airflow with protective hood) 5% lower (basis for comparison: airflow with protective hood) Power consumption of fan GS6 PSU 5.W /.5V Airflow The output voltage is.5v. Pressure difference [Pa] Volume flow [m³/h] PSU / voltage steady (.5V) Diagram: GS6 airflow with protective hood GS6 Air Extraction System Installation and Operating Instructions 09/0

25 TECHNICALDETAILS 7. GS6 PSU Protection class II Transformer type Safety transformer to DIN EN 6558 (VDE 0570) Short-circuit strength Conditional with temperature switch, 00 C Input voltage AC 0V (internal: DC 5V) Power consumption 5. VA at.5v Frequency 50 Hz Dimensions (mm) Height: 7 Width: 50 Depth: Weight (g) Fan Approvals Input voltage Power consumption VDE / UL / CSA / CE DC V.W for V Dimensions (mm) Depth: Diameter: 98 Weight (g) 8 Noise 7 db(a) Airflow 80m³/h to 0 Pa 70m³/h to 0 Pa Pressure build-up (max.): 58 Pa Operational temperature C range 7. Telescopic tube Sleeve Tube Extension Dimensions (mm) Length: 00mm Diameter: 0mm Weight (g) Dimensions (mm) Length: 00mm Diameter: 07mm Weight (g) 50 Identical construction to sleeve and tube GS6 Air Extraction System Installation and Operating Instructions 09/0 5

26 TECHNICALDETAILS 7.5 Inside baffle Dimensions (mm) Height: 60 Width: 60 Depth: 8.5 (white, stainless, gold, silver) Weight (g) 68 Glass Tile Dimensions (mm) Height: 6 Width: 6 Depth: 6.0 Weight (g) 0 Dimensions (mm) Height: 60 Width: 60 Depth: 6.0 Weight (g) Protective hood Dimensions (mm) Height: 57 Width: 5 Depth: 6 Weight (g) 7.7 Flat duct GS6-Corner 500 Dimensions (mm) Height: 0 Width: 500 Depth: 60 Weight (g) 668 GS6-Corner 000 Dimensions (mm) Height: 0 Width: 000 Depth: 60 Weight (g) Grate with sleeve Dimensions (mm) Height: Width: 9 Depth: 76 Weight (g) Fan housing Dimensions (mm) Height: 7 Width: 7 Depth: 85 Weight (g) Nonreturn valve Dimensions (mm) Height: 00 Width: 00 Depth: 7 Weight (g) 5 6 GS6 Air Extraction System Installation and Operating Instructions 09/0

27 DELIVERABLES/ACCESSORIES/SPARE PARTS 8 DELIVERABLES, ACCESSORIES AND SPARE PARTS 8. Deliverables Fan housing with fan Nonreturn valve Telescopic tube Protective hood* ) or GS6-Corner inside baffle Wall mounting box PSU 0m cable, -wire ( x Ø 0.5mm, red/white) Sealing tape Dowels and screws Installation and operating instructions 8. Accessories Name Order number On/Off switch Adhesive tape component foam**) part telescopic tube (extension) Spare parts Spare part Order number GS6 fan GS6/60 flush mounted PSU ZZ00 nonreturn valve Grate for duct *) A Nano Set is provided with the GS6-Blank protective hood for surface coating. Nano Set is enough to coat at least 0 GS6-blank protective hoods **) Only for commercial customers GS6 Air Extraction System Installation and Operating Instructions 09/0 7

28 MAINTENANCEANDREPAIR 9 MAINTENANCE AND REPAIR The GS6 air extraction system is virtually maintenance-free. The table lists all maintenance measures. Danger - Prior to any maintenance and repair work, disconnect all relevant equipment from the power supply. System Maintenance measure module GS6 Protective hood inside baffle Telescopic tube Flat duct Fan Regularly clean the surface of the module with a damp cloth. Check the telescopic tube every 6 months for dirt. Remove dirt and use a damp cloth to clean it.. Every 6 months, use a brush to clean the fan blades from the accessible side. R60 controller Delay time Regularly clean the surface of the module with a damp cloth. Hygrostat Caution - So as not to damage the surface sealing, never use any cleaning agents containing sand, soda, acid or especially chlorine. 8 GS6 Air Extraction System Installation and Operating Instructions 09/0

29 TROUBLESHOOTINGANDDISPOSAL 0 TROUBLESHOOTING AND DISPOSAL 0. Troubleshooting The table contains an overview of potential faults, causes and rectification instructions. If the problem persists, please contact your factory representative. Information on this is in the section Warranty and \Service. 0.. GS6 air extraction system Fault Cause Rectification Fan failure No electrical voltage Switch thegrid voltage off and back on. Installation fault Fan motor defective. Check the polarity of all cables to ensure they are connected correctly. Check the switches/ buttons connected for proper function. Replace the fan, including housing. Noise Foreign body in the fan Remove the foreign body from the fan and clean the GS6 air extraction system. Fan blades dirtied Clean the fan blades with a brush. 0.. Functional modules 0. Disposal Note - An overview for R60 controller, delay timer and hygrostat module fault rectification is in the additional, accompanying installation and operating instructions for the GS6. Dispose of the product in line with applicable national regulations. The products described in these installation and operating instructions are broadly recyclable given their ecologically compatible manufacturing processes. Please contact a waste management center for electronic equipment for environmentally sustainable recycling and disposal of your old system. Refer to the overview for disposal recommendations. Product Material Disposal Protective hood High-grade steel Collection point for electronic equipment Fan PSU PBTP / PA Iron / copper Telescopic tube / flat duct PVC Recycling inside baffle PVC / glass / metal GS6 Air Extraction System Installation and Operating Instructions 09/0 9

30 GUARANTEEANDSERVICE WARRANTY AND SERVICE. Terms of warranty Note - The terms of warranty of the country in which the system was sold apply outside Germany. Please contact the dealer in your country. GS6 air extractor system The manufacturer assumes a warranty of two years for the GS6 air extraction system. The warranty becomes void if damage due to improper or inappropriate treatment and use, or damage due to failure to comply with the installation and operating instructions, occurs, supplementary or accessory components are used that are not approved by the manufacturer of the system modifications and/or alterations to the GS6 are made, spare parts that are not original spare parts from the manufacturer of the GS6 are used, damage is caused by the impact of force majeure or environmental factors, or damage attributable to chemical and/or electrochemical effects of liquids and gases occurs. Complaints On receipt, use the delivery note to check the delivery for completeness and damage during transit. Report missing items within four weeks. Documentation This documentation describes the functionality of the standard version. For reasons of clarity, the documentation does not contain all detailed information about all variants of the product and cannot cover every conceivable installation, mounting, operation, maintenance and repair scenario. The figures in the documentation may differ slightly from the design of the product you purchased. Functional equivalence is maintained despite any variance in detail.. Service Contact your supplier, business representatives or our service technicians for technical advice. Germany Phone +9 (0)67 / 9-0 Fax +9 (0)67 / 9- Internet info@inventer.de 0 GS6 Air Extraction System Installation and Operating Instructions 09/0

31 LEGALNOTICE LEGAL NOTICE Publisher: Öko-Haustechnik inventer GmbH Ortsstraße a 0775 Löberschütz Germany Phone: +9 (0)67 / 9-0 Fax: +9 (0)67 / 9- info@inventer.de Homepage: CEO: Peter Moser VAT no.: DE 867 District court Jena, company reg. no Images: Öko-Haustechnik inventer GmbH 0 Rights to all content: Öko-Haustechnik inventer GmbH 0 Subject to changes. All information provided "as is". No liability assumed for printing errors. GS6 Air Extraction System Installation and Operating Instructions 09/0