2017 UNDERWATER BRIDGE INSPECTION REPORT. CEDAR (10TH) over MISS R; BNSF STS. Date of Inspection: Equipment Used: 07/07/2017

Size: px
Start display at page:

Download "2017 UNDERWATER BRIDGE INSPECTION REPORT. CEDAR (10TH) over MISS R; BNSF STS. Date of Inspection: Equipment Used: 07/07/2017"

Transcription

1 2017 UNDERWATER BRIDGE INSPECTION REPORT BRIDGE # 2796 CEDAR (10TH) over MISS R; BNSF STS DISTRICT: Metro COUNTY: Hennepin CITY/TOWNSHIP: Minneapolis STATE: Minnesota Date of Inspection: Equipment Used: 07/07/2017 Owner: City or Municipal Highway Agency Inspected By: Stuber, Cory Report Written By: Cory Stuber Report Reviewed By: Final Report Date:

2 TABLE OF CONTENTS PAGE NUMBER UNDERWATER SUMMARY 3 UNDERWATER INSPECTION 4 UNDERWATER INSPECTION PROCEDURES 6 STRUCTURE INVENTORY 7 ELEMENTS 8 PICTURES 13 DRAWINGS 17

3 UNDERWATER INSPECTION REPORT SUMMARY The substructure unit inspected at Bridge 2796, Pier 12, was in satisfactory condition below water with no structural significant defects observed. The channel consisted of tightly packed riprap and large concrete debris at the downstream nose. Gaps were observed in the steel sheeting at the east and west upstream quarter points along with a void between the horizontal C- channels and vertical sheathing. The steel sheeting was in fair condition with surface corrosion throughout and torch cut holes at random locations. The steel sheeting was slightly separated from the concrete. INSPECTION FINDINGS (A) The channel bottom material, within 10 feet of the substructure unit, typically consisted of tightly packed riprap from 1 foot to 3 feet in size. Along the downstream end, the channel sloped up at a steep angle and was located approximately 3 feet below the waterline, the downstream channel bottom material consisted of cobbles of less than 6 inches in size, riprap from 1 foot to 4 feet in size, and large concrete debris. (B) Gaps in the lines of construction (not at interlocks), were observed in the steel sheeting at the east and west upstream 1/4 points with maximum widths located at the channel bottom. The west gap measured 15 inches in width and had a maximum penetration of 6 inches. The east side gap measured 36 inches in width and had no penetration. (C) A void between the horizontal C-channels and the vertical sheeting was observed at the east side upstream 1/4 point of the pier at 3.0 feet below the waterline with a height of 2.5 feet and 3.5 feet of maximum penetration. (D) The steel sheeting was in fair condition with a uniform 1/8 inch layer of surface corrosion extending from the top of the sheeting to the channel bottom. Torch cut holes, 3 inches in diameter observed at random locations. (E) The steel sheet piling was slightly separated from the concrete around the base of the pier for a length of approximately 20 feet along the east and west sides. (F) The topside concrete surface within the sheeting was sound, however, gaps/cracks up to 1 foot maximum width were observed on both east and west sides of Pier 12. RECOMMENDATIONS (A) Reinspect the submerged substructure unit at the normal maximum recommended (NBIS) interval of sixty (60) months. Contractor: Contractor Job Number: Collins Engineers, Inc Page 3 of 19

4 UNDERWATER INSPECTION 1. BRIDGE DATA Bridge #: Feature Intersected: Facility Carried: District: County: 2796 MISS R; BNSF STS CEDAR (10TH) Metro Hennepin Bridge Description: The superstructure consists of an open-spandrel reinforced concrete arch supporting a reinforced concrete deck. The superstructure is supported on two reinforced concrete abutments and 19 reinforced piers numbered from the west end of the bridge. Only Pier 12 is located within the channel. The pier is supported on a rectangular footing supported by steel piles. 2. INSPECTION DATA Professional Engineer/Team Leader: Inspection Diver: Date of Underwater Inspection: Weather Conditions: Underwater Visibility (feet): Waterway Velocity (ft/sec): Garrett Owens Cory Stuber 07/07/2017 Sunny, 75 F SUBSTRUCTURE INSPECTION DATA Substructure(s) Inspected: Pier 12 General Shape: The pier consists of an oblong rectangular shaft with rounded ends. The base of the pier shaft is encased with steel sheet piling encasement (protection) system which is pointed at the upstream end and filled with concrete. Maximum Water Depth at Substructure(s) Inspected (feet): WATERLINE DATUM Water Level Reference: Waterline Elevation (feet): Description: The spring line at the downstream nose of Pier The waterline was approximately 10.8 feet below reference. 5. NBIS CODING INFORMATION (Minnesota specific codes are used for 92B and 113) Item 60: Substructure: Item 61: Channel and Channel Protection: Item 62: Culvert: Item 92B: Underwater Inspection: Code: Code: Code: Code: 5 6 Y 48 07/2017 Page 4 of 19

5 Item 113: Scour Critical Bridge: Code: P Bridge is scour critical because abutment or pier foundation is rated as unstable due to observed scour at bridge site. Yes X No (Mark your selection with an X) 6. STRUCTURAL ELEMENT CONDITION RATING Conditions ELEM # Element Description Quantity Unit CS1 CS2 CS3 CS4 210 Reinforced Concrete Pier Wall 110 LF Secondary Members (Substructure) 1 EA Scour 1 EA 1 Page 5 of 19

6 UNDERWATER INSPECTION INSPECTION PROCEDURES The routine underwater inspection of Bridge 2796 (10th Avenue over the Mississippi River) was completed on July 7, The underwater inspection was conducted from a 21 foot boat. The inspection was conducted by a team consisting of a PE-Diver with a valid MnDOT Team Leader certification, a backup diver and a dive tender. The inspection utilized commercial dive equipment and techniques (SSA and/or SCUBA) in accordance with OSHA regulations. Profiles were taken along the upstream and downstream faces of the bridge and around the periphery of substructure units to determine the presence, location and area of scour. The bridge elements inspected consisted of three reinforced concrete piers. According to the bridge inventory or design drawings, Pier 12 was supported by rectangular footing founded on steel H-piles. Inspection procedures followed FHWA guidance and the MnDOT Bridge and Structure Inspection Program Manual with channel bottom probing to search for foundations. The routing underwater inspection frequency is recommended to remain at a maximum of 60 months based on those findings and risk factors. Also, inspection procedures should continue to follow the above approach and standard guidance with 100% Level I and 10% Level II intensity efforts. Page 6 of 19

7 Bridge ID: 2796 Minnesota Structure Inventory Report CEDAR (10TH) over MISS R; BNSF STS Date: 07/12/ G E N E R A L + + R O A D W A Y + + I N S P E C T I O N + Agency Br. No Crew Bridge Match ID (TIS) 1 Userkey 173 District 05 County Hennepin Route Sys 05 - MSAS Number 328 Functionally Obsolete City Township Desc. Loc. Sect., Twp., Range Latitude ' '' Control Section (TH Only) Status Longitude ' Custodian Owner BMU Agreement Main Span Type 1 - Concrete Median Width On Bridge Main Span Design Main Span Detail Culvert Type Barrel Length Cantilever ID MAIN: 7 Main Span Length Structure Length 12 - Arch Appr. Guardrail 1 - MEETS STANDARDS V - OPEN SPANDREL ARCH + M I S C. B R I D G E D A T A + GR Termini 1 - MEETS STANDARDS Appr. Span Type 5 - Prestress or Precast Structure Flared Appr. Span Design Appr. Span Detail Skew 0 Number of Spans APPR: 14 TOTAL: ft. Field Conn. ID Abutment Foundation (Material/Type) Pier Foundation (Material/Type) Historic Status Deck Width (Out-to-Out) 68.1 ft. Year Painted 1975 Deck Material Wear Surf Type Wear Surf Install Year 2000 Wear Course/Fill Depth Deck Membrane Deck Rebars Deck Rebars Install Year Roadway Area (Curb-to-Curb) Sidewalk Width 50A. Lt No flare 01 - Beam Span Parallel Structure N - No parallel structure Structure Area (Out-to-Out) sq. ft. Curb Height Minneapolis 0.3 MI N OF WASH AVE Level of Service 1 - MAINLINE N - 24W Roadway Type 04 - City or Municipal Highway 04 - City or Municipal Highway Year Built 1929 Lt 1 - Concrete Cast-in-Place 4 - Low Slump Concrete 0.16 ft. 0 - None Maint. Area 3 - FTG PILE 1 - CONC 3 - FTG PILE 1 - On National Register + P A I N T + ft. Bridge Railing 1 - MEETS STANDARDS Underwater 60 Pinned Asbly. Spec. Feat. Drainage Area (sq. mi.) ft. Navigation Control sq. ft. Traffic ft. 50B. Rt ft. Rt Painted Area 0 - None + B R I D G E Posted Load ft. GR Transition 1 - CONC Frac. Critical 2 - Vehicle & Semi (Type R12-5) 1 - Speed Limit ft. Horizontal 0 - Not Required 0.00 ft. Vertical Roadway O/U Key '' Reference Point 2-2-way traffic Detour Length 1.0 mi. Lanes Route On Structure Roadway Name or Description 10th AVE SE On - Off System 1 - ON Roadway Width ft. Legislative District 59B Vertical Clearance ft. Potential ABC 2 - N/A Max. Vert. Clear. ft. Service On 5 - Highway-pedestrian Appr. Surface Width Service Under + S T R U C T U R E + HCADT MN Year Reconstructed 2001 Functional Class FHWA Year Reconstructed MN Temporary Status Bridge Plan Location Date Opened to Traffic 1 - CENTRAL 7/1/1976 If Divided + R D W Y Horizontal Clear. Lateral Clearance ON 4 UNDER ADT 8 - Highway-waterway-railroad Bridge Roadway Width YEAR ft. N - Not Applicable + I N + W A T E R W A Y + Waterway Opening (sf.) Pier Protection Unsound Paint % 10 Nav. Clr. (ft.) sq. ft. Nav. Vert. Lift Bridge Clear. (ft.) Posting Rating Date 8/25/ MEETS STANDARDS D E P T H I N S P. + Y/N Freq Date 07/07/ Nav. control on waterway 1 - Not required Vert Horiz. Primer Type 1 - Lead - non 3309 MN Scour Code P - STBL - Year 2015 Finish Type L - Other (Unknown) PROT INPL + C A P A C I T Y R A T I N G S + S I G N S + Structurally Deficient Sufficiency Rating 39.9 Routine Inspection Date 09/26/2016 Routine Inspection Frequency 12 Inspector Name Design Load 5 - HS 20 Operating Rating Stuber, Cory P - Posted for Load C O N D I T I O N Deck 6 Unsound Superstructure 4 Deck % 2 - HS TRUCK Inventory Rating 2 - HS TRUCK 12.2 VEH: 36 SEMI: 40 DBL: 40 Overweight Permit Codes R A T I N G S + Rail Type Lt 07 Rt 07 A N - N/A B N - N/A C N - N/A ADTT 16 - Urban - Minor Arterial ft. ft. ft. ft. + N B I Underclearances 4 Waterway Adequacy ft. ft. Approach Alignment 7 ft. 6 D I M E N S I O N S + NB-EB % SB-WB Substructure Channel 6 Culvert + N B I Structure Evaluation Deck Geometry 5 5 Y N N A P P R A I S A L R A T I N G S + N + S A F E T Y F E A T U R E S Page 7 of 19

8 07/17/2017 MINNESOTA BRIDGE INSPECTION REPORT BRIDGE 2796 County: City: Township: Hennepin Minneapolis Section: 24 Township: 029N Range: 24W Maint. Area: Span Type: 1 - Concrete 11 - Arch - Deck List: NBI Deck: 6 Super: 4 Sub: 5 Chan: 6 Culv: N Appraisal Ratings - Approach: Required Bridge Signs - Load Posting: CEDAR (10TH) OVER MISS R; BNSF STS 7 Waterway: 9 Horizntal: Location: Route: Control Section: 2 - Vehicle & Semi (Type R12-5) 0 - Not Required 0.3 MI N OF WASH AVE 05 - MSAS 328 Local Agency Bridge Nbr.: 4205 Open, Posted, Closed: MN Scour Code: Traffic: Vertical: Ref. Pt.: P - Posted for Load P - STBL - PROT INPL 1 - Speed Limit N - Not Applicable Length: Deck Width: Rdwy. Area/ Pct. Unsnd: sq. ft. / % Paint Area/ Pct. Unsnd: Culvert: N/A ft ft sq. ft. / 10% Postings: Unofficial Structurally Deficient Unofficial Functionally Obsolete Unofficial Sufficiency Rating 39.9 Y N ELEM NBR ELEMENT NAME REPORT TYPE INSP. DATE QUANTITY CS 1 CS 2 CS 3 CS 4 Reinforced Concrete Deck 07/12/ SF Underwater 02/28/ SF Notes: THERE ARE MANY TRANSVERSE CRACKS WITH EFFLORESCENCE. HEAVY RUST STAINS ABOVE CAPS AT LEAKING POURED JOINTS, WITH HEAVY DELAMINATION AND MANY LARGE SPALLS WITH REBAR EXPOSED. HEAVY SPALLS WITH REBAR EXPOSED TO SECOND MAT AROUND TWO UTILITY ACCESS MANHOLES Wearing Surfaces Underwater 07/12/ SF /28/ SF Notes: Low Slump Overlay with Uncoated Rebar Notes: DECK OVER STEEL AND CONCRETE GIRDERS. MANY FINE, MEDIUM TO LARGE SIZE LONGITUDINAL AND TRANSVERSE CRACKS THROUGHOUT. FEW PATCHES. Reinforced Concrete Slab 07/12/ SF Underwater 02/28/ SF Notes: THERE ARE MANY TRANSVERSE CRACKS WITH EFFLORESCENCE. HEAVY RUST STAINS ABOVE CAPS AT LEAKING POURED JOINTS, WITH HEAVY DELAMINATION AND MANY LARGE SPALLS WITH REBAR EXPOSED. HEAVY SPALLS WITH REBAR EXPOSED TO SECOND MAT AROUND TWO UTILITY ACCESS MANHOLES Wearing Surfaces Underwater 07/12/ SF /28/ SF Notes: Concrete Slab with Uncoated Rebar and Low Slump Overlay Notes: SLAB OVER ARCH SPAN. MANY FINE, MEDIUM TO LARGE SIZE LONGITUDINAL AND TRANSVERSE CRACKS THROUGHOUT. [2014]THREE FULL DEPTH PATCHES AT THE POURED JOINT AREAS. FALSE WORK STILL IN PLACE. 2' SAW CUT NOT FILLED. [2016] SPALL N. BIKE LANE AT POURED JOINT. Steel Open Girder/Beam 07/12/ LF Underwater 02/28/ LF Notes: THERE ARE AREAS OF MINOR PAINT PEELING DUE TO A FIRE ON THE BOTTOM OF THE SECOND AND THIRD GIRDERS ON THE S.W. IN SPAN #20.(LEAD PAINT) LOWER FLANGE HAS RUST SPOTS AND PAINT PEELING. HEAVY RUST AT THE JOINTS. [2014]LARGE AREAS OF PAINT FLAKING AT LOWER FLANGE AND WEB Steel Protective Coating Underwater 07/12/ SF /28/2017 Notes: [2016] LARGE AREA OF PAINT FAILURE LOWER FLANGE AND WEB. 109 Prestressed Concrete Open Underwater Girder/Beam SF /12/ LF /28/ LF Notes: THERE IS MINOR ACCIDENT DAMAGE TO THE FOURTH GIRDER FROM THE SOUTH OF SPAN #1. MANY ENDS OF THE GIRDERS ARE SPALLED WITH REBAR EXPOSED UNDER LEAKING JOINTS. LARGE SPALL AT THE BOTTOM OF 2ND GIRDER ABOVE THE BEARING OVER PIER 2. Page 8 of 19

9 BRIDGE 2796 CEDAR (10TH) OVER MISS R; BNSF STS ELEM NBR ELEMENT NAME REPORT TYPE INSP. DATE QUANTITY CS 1 CS 2 CS 3 CS 4 Reinforced Concrete Arch 07/12/ LF Underwater 02/28/ LF Notes: THE ARCHES HAVE MANY MEDIUM TO LARGE SIZE LONGITUDINAL AND TRANSVERSE CRACKS WITH RUST STAINS AND AREAS OF MAP CRACKING WITH LEACHING. THERE ARE MANY LARGE SPALLS WITH REBAR EXPOSED AND UNDERMINED. LARGE AREAS OF DELAMINATION AND RUST STAINS. LOOK AT SNOOPER INSPECTION FOR MORE DETAIL. Arch Spandrel Wall Notes: MODERATE DETERIORATION. THERE ARE MANY MEDIUM TO LARGE SIZE RANDOM CRACKS, MANY LARGE SIZE SPALLS WITH REBAR EXPOSED AND LARGE DELAMINATED AREAS WITH RUST STAINS. FEW SPALLS UNDERMINED REBAR. HEAVY SPALLING UNDER LEAKING JOINTS. MANY SPANDREL OUT OF PLUMB. FEW HAVE LARGE CRACKS IN THE MIDDLE OF THE FACE. MORE INFORMATION IN 2016 SNOOPER REPORT. Reinforced Concrete Column 07/12/ EA Underwater 02/28/ EA Notes: THREE COLUMNS ON PIER#5 HAVE 2'X1' SPALLS ON THE EAST SIDE WITH RUST STAINS. MANY FINE SIZE RANDOM CRACKS. WEST SIDE COLUMNS HAVE THREE SECURITY CAMERAS MOUNTED ON THE N. THERE IS GRAFFITI ON THE COLUMNS AND STRUTS. 3RD COLUMN FROM SOUTH ON PIER#2 HAS 3'X3' DELAMINATION. Reinforced Concrete Pier Wall 07/12/ LF Underwater 02/28/ LF Notes: THERE ARE MANY MODERATE CRACKS, LEACHING, STAINING AND MANY SMALL TO LARGE SIZE SPALLS WITH REBAR EXPOSED AND UNDERMINED REBARS. MINOR TO MODERATE DETERIORATION. WATER STAINS. Reinforced Concrete Abutment 07/12/ LF Underwater 02/28/ LF Notes: [2016] WEST ABUTMENT JOINT IS LEAKING SHOWING SEEPAGE WITH MANY CRACKS AND EFFLORESCENCE ON THE BACKWALLS. THE BREASTWALL HAS FINE SIZED FULL HEIGHT AND A FEW THAT ARE NOT FULL HEIGHT CRACKS. THERE IS MINOR MAP CRACKING ON THE NORTH. THE ELECTRICAL CONDUIT ON THE ABUTMENT SEAT IS RUSTING. THE EAST ABUTMENT HAS MANY FULL HEIGHT FINE SIZED CRACKS WITH RUST STAINS, LARGE SPALLS AND HEAVY DELAMINATION. THERE ARE MANY VERTICAL FINE SIZED CRACKS WITH EFFLORESCENCE ON THE BACKWALL. LARGE CRACK ON THE SHELF, SPALL AND DELAMINATION. MAP CRACKING AND RUST STAINS AROUND UTILITY BOX. Wingwall notes: MANY FINE TO MEDIUM SIZED VERTICAL CRACKS. MODERATE CRACKING, LEACHING AND STAINING. Reinforced Concrete Pier Cap 07/12/ LF Underwater 02/28/ LF Notes: MANY PIER CAPS HAVE HEAVY SEEPAGE WITH RUST STAINS, SMALL TO LARGE SPALLS WITH REBAR EXPOSED AT LEAKING JOINTS, DELAMINATION, AND MANY FINE TO MEDIUM SIZE RANDOM CRACKS. PIER #5 FIVE HAVE SPALLS WITH REBAR EXPOSED, STAINS AND DELAMINATION. CAMERA MOUNTED ON PIER CAP #1. PIER #2 HAVE LARGE DELAMINATION AREA, 3 LARGE SPALLS WITH REBAR EXPOSED UNDERSIDE OF CAP. (9' X 3', 2'X 1' AND 2' X 2') LARGE SPALL BETWEEN THE TWO SOUTH COLUMNS, WITH HEAVY DELAMINATION AND MAP CRACKING. 2 LIGHTS MOUNTED ON PIER #7 ARE BROKEN. Strip Seal Expansion Joint 07/12/ LF Underwater 02/28/ LF Notes: DIRT AND DEBRIS. MODERATE DETERIORATION AND MINOR LEAKAGE. ADJACENT DECK HAS MINOR SPALLING. HEAVY RUST AT THE JOINT ANCHORAGE. Pourable Joint Seal 07/12/ LF Underwater 02/28/ LF Notes: 20' OF THE JOINTS HAVE BEEN CONCRETE PATCHED. 20' OF THE SOUTH END OF LARGE POURED JOINT HAS LOSS ITS ADHESION AND SEPARATING. 7' OF THE JOINT LOST ADHESION AND LEAKING.THE REST OF THE JOINT HAS LITTLE DETERIORATION. ADJACENT DECK HAS MINOR CRACKING AND SPALLING. [2015] 1' MISSING WEST JOINT IN BIKE LANE. Compression Joint Seal 07/12/ LF Underwater Notes: JOINT AT WEST ABUTMENT. MAJOR DETERIORATION, 50% MISSING. 02/28/ LF Page 9 of 19

10 BRIDGE 2796 CEDAR (10TH) OVER MISS R; BNSF STS ELEM NBR ELEMENT NAME REPORT TYPE INSP. DATE QUANTITY CS 1 CS 2 CS 3 CS 4 Movable Bearing 07/12/ EA Underwater 02/28/ EA Notes: BEARING: (EAST AND WEST OF THE ARCHES) ON PIER #2 THE NORTH BOLT ON THE THIRD GIRDER FROM THE SOUTH AND THE NORTH AND SOUTH BOLTS ON THE FIRST AND SECOND GIRDERS FROM THE NORTH (WEST FACE) ARE NOT TIGHT. ON THE 8TH PIER THE BEARINGS HAVE LIGHT TO MODERATE RUST. ON THE 15TH PIER (WEST FACE) THERE IS LIGHT TO MODERATE RUST ON THE BEARING SHOES. ALL OF THE SHOES ON THE EAST ABUTMENT HAVE MODERATE TO HEAVY PAINT LOSS WITH RUST. MANY NUTS AND BOLTS HAVE HEAVY RUST. CITY CREWS LUBRICATED EXPANSION BEARINGS IN Fixed Bearing 07/12/ EA Underwater 02/28/ EA Notes: BEARINGS: (EAST AND WEST OF THE ARCHES) ON PIER #2 THE NORTH BOLT ON THE THIRD GIRDER FROM THE SOUTH AND THE NORTH AND SOUTH BOLTS ON THE FIRST AND SECOND GIRDERS FROM THE NORTH (WEST FACE) ARE NOT TIGHT. ON THE 8TH PIER THE BEARINGS HAVE LIGHT TO MODERATE RUST. ON THE 15TH PIER (WEST FACE) THERE IS LIGHT TO MODERATE RUST ON THE BEARING SHOES. ALL OF THE SHOES ON THE EAST ABUTMENT HAVE MODERATE TO HEAVY PAINT LOSS WITH RUST. Reinforced Concrete Approach Slab 07/12/ SF Underwater 02/28/ SF Notes: [2016] WEST BANK OF THE APPROACH HAS FINE TO MEDIUM SIZE RANDOM CRACKS. ONE LARGE, FULL LENGTH CRACK AT S.E. PANEL. SPALL AND MAP CRACKS AT SOUTH END OF EASTBOUND LANE. Metal Bridge Railing 07/12/ LF Underwater 02/28/ LF Notes: [2016] J- BARRIER WITH GALVANIZED PIPE RAIL AND 4' CHAIN LINK FENCE ON TOP UPSTREAM SIDE. RUST AT PIPE RAIL BASES. FENCE IS BROKEN AT N.E END OVER THE W. RAILROAD AND HELD BY PLASTIC TIES. THE SIDEWALK GALVANIZED RAIL HAS MINOR RUST AND OXIDIZING. FADING, CHIPPING AND SCRATCHES Steel Protective Coating Underwater 07/12/ SF /28/2017 Notes: [2016] PAINT IS CHIPPING, FADING MINOR RUST SPOTS SF Reinforced Concrete Bridge Railing 07/12/ LF Underwater 02/28/ LF Notes: [2016] J- BARRIER WITH GALVANIZED PIPE RAIL AND 4' CHAIN LINK FENCE ON TOP UPSTREAM SIDE. HEAVY MAP CRACKING AND SPALLS WITH REBAR EXPOSED, DELAMINATION ON THE BARRIER. RUST AT PIPE RAIL BASES. JOINT MATERIAL ON J- BARRIERS IS DETERIORATING AND SEPARATING IN MANY LOCATIONS. HEAVY STAINING UNDER LIGHTS. Critical Deficiencies or Safety Hazards 07/12/ EA Underwater Notes: NO CRITICAL FINDINGS. 02/28/ EA Concrete Decks - Cracking & Sealing 07/12/ LF Underwater 02/28/ LF Notes: MANY FINE, MEDIUM AND LARGE SIZE RANDOM CRACKS. CONCRETE WEARING SURFACE HAS CRACKS OF MODERATE SIZE AND DENSITY. Bituminous Approach Roadway 07/12/ EA Underwater Notes: EAST END. MINOR TRANSVERSE FINE SIZE CRACKING. 02/28/ EA Steel Hinge Assembly 07/12/ EA Underwater 02/28/ EA Notes: THE TWO OUTSIDE HINGES HAVE MODERATE DETERIORATION AND MODERATE RUST. THE REST HAVE MINOR DETERIORATION AND RUST. [2013]CITY CREW LUBRICATED HINGE BEARINGS. Page 10 of 19

11 BRIDGE 2796 CEDAR (10TH) OVER MISS R; BNSF STS ELEM NBR ELEMENT NAME REPORT TYPE INSP. DATE QUANTITY CS 1 CS 2 CS 3 CS 4 Secondary Members (Superstructure) 07/12/ EA Underwater 02/28/ EA Notes: STEEL DIAPHRAGMS: HEAVY PAINT PEELING AND LIGHT TO MODERATE RUST SPOTS AT THE JOINTS. CONCRETE DIAPHRAGMS: MANY LARGE SPALLS WITH REBAR EXPOSED AND DIAGONAL FINE SIZE CRACKS UNDER LEAKING JOINTS. SCOUR PROTECTION PIER 12: GOOD. Secondary Members (Substructure) 07/12/ EA Underwater Notes: [2017] Underwater Inspection - Element added for steel sheet piling at Pier 12. Steel piling has surface corrosion throughout and torch cut holes at random locations. Piling also had a C-channel member attachment at the upstream nose, above the waterline, which was moderately to severely bent out of plane, likely due to impact damage. Concrete Shear Cracking 07/12/ EA Underwater 02/28/ EA Notes: MINOR SHEAR CRACKING IS PRESENT ON 1ST GIRDER NORTH OF SPAN 8. GIRDER IS CRUSHING AGAINST ARCH PIER. Scour 07/12/ EA Underwater 02/28/ EA Notes: P - Stable due to protection. Inspect countermeasures. PIER 12: UNDER WATER INSPECTIONS DATED ON 10/29/2012 WERE DONE BY COLLINS ENGINEERS INC. CITY SCOUR MONITOR REPORT IN THE CHANNEL BOTTOM AROUND THE SUBSTRUCTURE UNITS IS PRESENTLY STABLE WITH NO EVIDENCE OF SIGNIFICANT SCOUR. NO RIP RAP AROUND PIER 13 ON THE EAST BANK. [2015]SCOUR SOUNDINGS. [2017] Underwater Inspection: No evidence of significant scour and channel bottom remained stable around Pier 12, moved from CS2 to CS Load Posting or Vertical Clearance Underwater Signing Notes: [2016] LOAD POSTING SIGN 36T-40T-40T INPLACE. 07/12/ EA /28/ EA Other Bridge Signing 07/12/ EA Underwater Notes: SPEED LIMIT SIGNS ARE IN PLACE. 02/28/ EA Slopes & Slope Protection 07/12/ EA Underwater 02/28/ EA Notes: SLOPES HAVE MINOR TO MODERATE EROSION AROUND PIERS. EAST CONCRETE SLOPE HAS LARGE CRACK UP TO SCUPPER AT NE. JOINT MATERIAL MISSING AT EAST ABUTMENT. Guardrail 07/12/ EA Underwater Notes: THERE IS GUARDRAIL ON THE N.E. GOOD. 02/28/ EA Deck & Approach Drainage 07/12/ EA Underwater Notes: DRAINAGE SYSTEM FUNCTIONING AS INTENDED. 02/28/ EA Sidewalk, Curb, & Median 07/12/ EA Underwater 02/28/ EA Notes: CURB: J- BARRIERS DOWNSTREAM. MANY FINE SIZE RANDOM CRACKS AND LARGE SPALLS. PLATE MISSING AT JOINT OVER RR, EAST BANK. HEAVY STAINING UNDER LIGHTS, WITH SPALLS AND LARGE CRACKS. SEPARATION OF JOINT MATERIAL IN FEW PLACES. SIDEWALK: SEALED AND UNSEALED FINE SIZE TRANSVERSE CRACKS. THE SW APPROACH SIDEWALK HAS A FINE SIZE FULL LENGTH SEALED CRACK AT THE RAIL LINE. SE CORNER OF SIDEWALK A ABUTMENT 1' X 1' SPALL FILLED WITH JOINT SEAL. Page 11 of 19

12 BRIDGE 2796 CEDAR (10TH) OVER MISS R; BNSF STS ELEM NBR ELEMENT NAME REPORT TYPE INSP. DATE QUANTITY CS 1 CS 2 CS 3 CS 4 Miscellaneous Items 07/12/ EA Underwater 02/28/ EA Notes: LIGHTING: BRIDGE LIGHT ON DECK THE BASES HAVE HEAVY FLAKING AND RUST. TOTAL SIX LIGHT BASES HAVE HOLES, TWO HAVE LARGE HOLES (3" X 1"). ONE LIGHT HAS BEEN REMOVED. ONE WIRE COVER MISSING. LIGHTS UNDER, TWO LIGHTS ON PIER 7 BROKEN, 4 LIGHTS ATTACHED TO STEEL GIRDERS SPAN 21 AND 3 POWER BOXES ATTACHED TO THE UNDERDECK. ONE COVER IS LOOSE. NAVIGATIONAL LIGHTS: GOOD. CAMERAS MOUNTED ON POLES. UTILITY ATTACHED UNDER THE BRIDGE: 54" WATERMAIN, HEAVY PAINT PEELING. 2-16" GAS PIPE AND 8-5" GALVANIZED PIPES WITH A CATWALK. CATWALK CABLE RUSTY AND LOOSE BOARDS. Protected Species 07/12/ EA Underwater Notes: NO PROTECTED SPECIES. 02/28/ EA General Notes: NOTE: THE BRIDGE WAS REMODELED IN THE STRUCTURE WAS REALIGNED IN BRIDGE DECK TO WATER IS 118' PLUS OR MINUS WITH THE ELEVATION OF THE RIVER. SHARED ROAD, TWO BIKE STRIPE LANES ADDED IN AREA UNDER: 1. FIRST ST SOUTH UNDER. (1ST SPAN) ROADWAY: ASPHALT, CURB: B624, SIDEWALK: 4' CONCRETE BOTH SIDES. LIGHTING: GOOD, PED. RAMPS IN PLACE. [2014]NEW DINKY GREENWAY BIKE TRAIL 2. WEST RIVER ROAD UNDER; (10TH SPAN) ROADWAY: ASPHALT GOOD. CURB: GOOD, SIDEWALK CONC. ON THE NORTH AND ASPHALT BIKE PATH NORTH AND SOUTH OF ROADWAY. 3. SERVICE RD. UNDER; (14TH SPAN) AT E. BANK WAS PAVED IN 2009, WITH TOE WALL AND CONDUIT. 4. BNSF RR AND SERVICE ROAD UNDER; (SPAN 16) ONE TRACK, THE OTHER 5 ARE CUT OFF. SERVICE ROAD 16' WIDE. VERTICAL CLEARANCE ND ST. S.E. UNDER; SECOND SPAN FROM EAST; ROADWAY: MANY FULL WIDTH TRANS. CRACKS IN ASPHALT AND ONE LARGE CRACK AT S. SIDE. CURB: B624, SIDEWALK: 6' ON EAST. LIGHTING: GOOD, 58. Deck NBI: 36A. Brdg Railings NBI: 36B. Transitions NBI: 36C. Appr Guardrail NBI: 36D. Appr Guardrail Terminal NBI: 59. Superstructure NBI: 60. Substructure NBI: 61. Channel NBI: CONCRETE GIRDERS HAVE LARGE SPALLS. CONCRETE ARCH AND CONCRETE SPANDREL WALLS HAVE LARGE LONGITUDINAL AND TRANSVERSE CRACKS, LARGE SPALLS WITH REBAR EXPOSED AND UNDERMINED, LARGE DELAMINATIONS, HEAVY SPALL UNDER LEAKING JOINTS AND MANY SPANDREL OUT OF PLUMB. (2015) THE CONCRETE ARCH HAS ADVANCED DETERIORATION. ADVANCED SCALING, CRACKING AND SPALLING. EXPOSED REINFORCEMENT HAS SIGNIFICANT SECTION LOSS. CONCRETE COLUMNS, CONCRETE PIER WALLS AND CONCRETE ABUTMENTS HAVE LARGE SPALLS WITH REBAR EXPOSED, DELAMINATIONS AND LARGE LONGITUDINAL AND TRANSVERSE CRACKS. 62. Culvert NBI: 71. Waterway Adeq NBI: 72. Appr Roadway Alignment NBI: Inspector's Signature Reviewer's Signature Page 12 of 19

13 Pictures Photo 1 - South Elevation, Looking North. Photo 2 - Span 13, Looking South. Page 13 of 19