1 REGULATORY INFORMATION REPORT The Fire Resistance Performance of Hilti CP606 protecting linear joints and gap seals in walls when tested in accordance with AS and assessed with AS EWFA Report No: RIR Report Sponsor: Hilti (Aust.) Pty Ltd 1G Homebush Bay Drive, Rhodes, NSW,2138 Australia & Hilti New Zealand Limited 600 Great South Road Ellerslie, Auckland 1051 New Zealand

2 Page 2 of 21 DOCUMENT REVISION STATUS Date Issued Issue No Description 24/07/2018 RIR Initial Issue 07/08/2018 RIR Typographical Amendments CONTACT INFORMATION Exova Warringtonfire Aus Pty Ltd - ABN NATA Registered Laboratory Unit 2, Hammond Road Dandenong Victoria 3175 Australia T: +61 (0) F: +61 (0) New South Wales Suite 802, Level Kent Street Sydney NSW 2000 Australia T: +61 (0) Perth Unit Railway Road Subiaco WA 6008 Australia T: +61 (0) Victoria Unit 2, Hammond Road Dandenong Victoria 3175 Australia T: +61 (0) F: +61 (0) Queensland T6. L Mary Street Brisbane QLD 4000 Australia T: +61 (0) F: +61 (0) Canberra 2/11 Murray Cres Griffith ACT 2603 Australia T: +61 (0)

3 Page 3 of 21 CONTENTS 1 INTRODUCTION 4 2 TESTED PROTOTYPES 4 3 VARIATION TO TESTED PROTOTYPES 4 4 REFERENCED TEST PROCEDURES 6 5 FORMAL ASSESSMENT SUMMARY 6 6 DIRECT FIELD OF APPLICATION 20 7 REQUIREMENTS 20 8 VALIDITY 20 9 AUTHORITY APPLICANT UNDERTAKINGS AND CONDITIONS OF USE GENERAL CONDITIONS OF USE AUTHORISATION ON BEHALF OF EXOVA WARRINGTONFIRE AUS PTY LTD DATE OF ISSUE EXPIRY DATE 21

4 Page 4 of 21 1 INTRODUCTION This report contains the minimum information sufficient for regulatory compliance and refers to the Assessment Report EWFA The referenced report presents an assessment of Hilti CP606 protecting linear joints and gap seals in walls when tested in accordance with AS and assessed with AS The tested prototypes described in Section 2 of this report, when subject to the proposed variations described in Section 3 and tested in accordance with the referenced test method described in Section 4. The conclusions of the report are summarised in Section 5. The validity of the referenced assessment is conditional on compliance with Sections 6, 7, 8 and 9 of this report. Summaries of the test data on which this assessment is based are provided in Appendix A together with a summary of the critical issues leading to the assessment conclusions including the main points of argument. 2 TESTED PROTOTYPES The referenced assessment report is based on reference test EWFA , being a test of a deflection head protected by Hilti CP606 fire resistant joint filter within a 128mm USG Fibrerock Aqua Tough Interior Panel Wall System on wall systems protected by Hilti Firestop Sealant CP 606 in accordance with AS respectively. The test was sponsored by Hilti (Aust.) Pty Ltd and was conducted by Exova Warringtonfire Aus Pty Ltd. Tests EWFA & EWFA being tests in accordance with AS of various control joints in a 90mm & 116mm thick non-load bearing CSR fire rated plasterboards protected by Hilti Firestop sealant CP606. Tests were sponsored by Hilti (Aust.) & Hilti (NZ) Ltd and were conducted by Exova Warringtonfire Aus Pty Ltd. Refer to Appendix A in the referenced assessment report for a full summary of the test data. 3 VARIATION TO TESTED PROTOTYPES The proposed construction for deflection heads and control joints in walls and floors shall be as tested in EWFA , EWFA & EWFA with conration of following variations as permitted within AS & AS Control joints and gap seals in single layer flexible walls Control joints and gap seals in multi-layered fire rated flexible walls Linear s and Gap Seals in Rigid Walls The use of timber framing in lieu of steel framing, only applicable for wall systems designed to achieve FRL -/60/60 or FRL 60/60/60 Use of various backing materials such as, Open Cell (PE) Polyethylene Foam Backing Rod, Closed Cell (PE) Polyethylene Foam Backing Rod & eral Wool or Stone Wool insulation and achieve the same FRL Reference to Test Report EWFA assess Service H to achieve -/120/120, by increasing the sealant depth from 20mm to 26mm Variation to the commercial brand name of plasterboard used. Assess different configurations for 1 hr, 2hr & 3 hr systems.

5 TABLE 1- SCHEDULE OF COMPONENTS FOR JOINTS AND CONTROL JOINTS IN WALLS Report No. RIR Page 5 of 21 Item Description s and Control s FRL -/60/60 or FRL 60/60/60 Plasterboard Walls Systems Dimensions The Shall be nominally 5-30mm wide Sealant Flexible Firestop Sealant (item 5) Backing Framing Wall framing material, Steel Stud & Steel Track or Timber for (Wall to Wall, Bottom of Wall & Top of Wall s) PE Foam Backing Rod (Open Cell or Closed Cell) or use of eral/stone wool imum framing width 64mm, Steel & Timber. Timber framed walls shall be designed and constructed as per system manufacturers instructions to achieve FRL 60/60/60 or -/60/60 FRL -/120/120 or FRL 120/120/120 Plasterboard Wall Systems Dimensions The shall be nominally 5-30mm wide Sealant Flexible Firestop Sealant (item 5) Backing Framing Steel Stud & Steel Track for (Wall to Wall, Bottom of Wall & Top of Wall s) PE Foam Backing Rod (Open Cell & Closed Cell) or use of eral Wool/Stone wool Steel FRL -/180/180 or FRL 180/180/180 Plasterboard Wall Systems Dimensions The shall be nominally 5-27mm wide Sealant Flexible Firestop Sealant (Item 5) Backing Framing Separating Element Product Name Item Name Steel Stud & Steel Track for (Wall to Wall, Bottom of Wall & Top of Wall s) PE Foam Backing rod (Open cell & Closed Cell) or use of eral/stone Wool Steel Plasterboard used in the construction shall include but not be limited to USG Boral Firestop, CSR Fyrcheck& Knauf Fireshield & GIB Fyreline. Also including other types and brands of fire-resistant grade plasterboard verified by the manufacturer. Wall Construction for 1- hour Applications Fire Rated Plasterboard lined wall 4 Size Specification Item Name imum Wall thickness 90mm imum Track width: 64 mm The wall system shall have a minimum thickness 90mm and comprise steel/timber stud framing lined on both faces with a minimum one layer of at least 13mm or 16mm thick fire resistant grade plasterboard that has been tested or otherwise assessed by the others to achieve FRL of -/60/60 or 60/60/60 Wall Construction for 2- hour Applications Fire Rated Plasterboard Lined Wall

6 Page 6 of 21 Size imum Wall thickness 116mm imum Track width: 64mm Specification Name Size The wall system must have a minimum thickness of 116mm and comprise steel stud framing lined on both faces with a minimum two at least 13mm or 16mm thick fire resistant grade plasterboard that has been tested or otherwise assessed by the others to achieve a FRL of -/120/120 or 120/120/120. Supporting Wall Construction for 3- hour Applications Fire Rated Plasterboard Lined Wall imum Wall thickness 128mm imum Track : 64mm Sealant 5 Specification Item Name Size Item Name Product Name Hilti CP 606 The wall system shall have a minimum thickness of 128mm and comprise of steel stud framing lined on both faces with a minimum two 16mm thick fire-resistant grade plasterboard that has been tested or otherwise assessed by others to achieve FRL of -/180/180 or 180/180/180. Support Rigid Wall Construction Masonry, Concrete, AAC imum Wall to achieve FRL of -/60/60: 90 mm imum Wall to achieve FRL of -/120/120: 116mm imum Wall to achieve FRL of -/180/180: 128mm Flexible Firestop Sealant 4 REFERENCED TEST PROCEDURES The referenced assessment report is prepared with reference to the requirements of AS and AS FORMAL ASSESSMENT SUMMARY On the basis of the discussion presented in the referenced assessment report, it is the opinion of this testing authority that if the tested prototype described in Section 2 had been varied as in Section 3, it will achieve the performance as stated below if tested in accordance with the test method referenced in section 4 and subject to the requirements of section 7.

7 Page 7 of 21 WALL TYPE: FLEXIBLE FRL:-/60/60 or 60/60/60 Figure 1- Wall to Wall - Top View Seal Type Expansion Wall Lining (mm) t 1 x 13mm or 16mm on each 1 x 13mm or 16mm on each Figure 2- Wall to Wall Expansion - Top of View Backfilling Steel Track or Timber Framing PE Foam Backing Rod or eral Wool Insulation Nominal (mm) W *Timber Framing maybe used in lieu of steel framing Depth of Sealant (mm) d Depth of Wall Lining Wall (mm) a Track/Stud (mm) s Figure FRL /60/60 20mm /60/60

8 Page 8 of 21 Figure 3- Top of Wall - End View Figure 4- Bottom of Wall - End View Seal Type Top Of Wall Wall Lining (mm) t 1 x 13mm or 16mm on Backfilling Steel Track or Timber framing Nominal (mm) W Depth of Sealant (mm) d Depth of Wall Lining Wall (mm) a Track/Stud (mm) s Figure FRL /60/60 Bottom Of Wall 1 x 13mm or 16mm on Steel Track or Timber framing *Steel Stud can be substituted for Timber framing Depth of Wall Lining /60/60

9 Page 9 of 21 WALL TYPE: FLEXIBLE FRL:-/120/120 or 120/120/120, -/180/180 or 180/180/180 Figure 1A- Wall to Wall - Top View Figure 1B- Wall to Wall - Top View Figure 1C-Wall to Wall - Top View

10 Page 10 of 21 Seal Type Wall Lining (mm) t 2 x 13mm or 2 x 13mm or 2 x 13mm or Backfilling Nominal (mm) W Steel Stud Steel Stud Steel Stud & 1st layer of plaster board Steel Stud 5-27 Steel Stud 5-27 Steel Stud & 1st layer of plaster board 5-27 Depth of Sealant (mm) d Depth of both plaster board Sealed to depth of inner lining only, covered by second layer of plaster board Sealed to depth of outer lining only, applied on top of 1st layer of plaster board Depth of both plaster board Sealed to depth of inner lining only, covered by second layer of plaster board Sealed to depth of outer lining only, applied on top of 1st layer of plaster board Wall (mm) a Track/Stud (mm) s Figure FRL A -/120/ B -/120/ C -/120/ A -/180/ B -/180/ C -/180/180

11 Page 11 of 21 WALL TYPE: FLEXIBLE FRL:-/120/120 OR 120/120/120, -/180/180 or 180/180/180 Figure 2A-Wall to Wall Expansion - Top View Figure 3A- Top of Wall -Side View Seal Type Expansion Expansion Top Of Wall Top Of Wall Wall Lining (mm) t 2 x 16mm on each 2 x 16mm on each 2 x 16mm on each 2 x 16mm on each Backfilling PE Backing Rod or eral Wool Insulation PE Backing Rod or eral Wool Insulation Nominal (mm) W Steel Stud 5-27 Steel Stud 5-27 Depth of Sealant (mm) d Depth of both plaster board Depth of both plaster board Depth of both plaster board Depth of both plaster board Wall (mm) a Track/Stud (mm) s Figure FRL A -/120/ A -/180/ A -/120/ A -/180/180

12 Page 12 of 21 WALL TYPE: FLEXIBLE FRL:-/120/120 or 120/120/120, -/180/180 or 180/180/180 Figure 4A-Bottom of Wall -End View Figure 4B-Bottom of Wall -End View Figure 4C-Bottom of Wall - End View

13 Page 13 of 21 Seal Type Bottom Of Wall (Both layers) Wall Lining (mm) t 2 x 13mm or 2 x 16mm on Backfilling Nominal (mm) W Steel Track 5-20 Depth of Sealant (mm) d Depth of both layers of plasterboard Wall (mm) a Track/Stud (mm) s Figure FRL A -/120/120 Bottom Of Wall (Inner Layer Only) 2 x 13mm or 2 x 16mm on Steel Track 5-20 Sealed to depth of inner lining only, covered by second layer of plasterboard B -/120/120 Bottom Of Wall (Outer Layer Only) 2 x 13mm or 2 x 16mm on Steel Stud & 1st Layer of plasterboard 5-20 Sealed to depth of outer lining only, applied on top of 1st layer of plaster board C -/120/120 Bottom Of Wall (Both layers) 2 x 16mm on each Steel Track 5-20 Depth of both layers of plasterboard A -/180/180 Bottom Of Wall (Inner Layer Only) 2 x 16mm on each Steel Track 5-20 Sealed to depth of inner lining only, covered by second layer of plaster board B -/180/180 Bottom Of Wall (Outer Layer Only) 2 x 16mm on each Steel Stud & 1st Layer of Plaster board 5-20 Sealed to depth of outer lining only, applied on top of 1st layer of plaster board C -/180/180

14 Page 14 of 21 WALL TYPE: FLEXIBLE FRL:-/120/120 or 120/120/120, -/180/180 or 180/180/180 Figure 8A- Wall to Wall Butt -Top View Figure 8B- Wall to Wall Butt -Top View Seal Type Wall Lining (mm) t Backfilling Nominal (mm) W Depth of Sealant (mm) d Wall (mm) a Track/Stud (mm) s Figure FRL Over Steel Stud (1st Layer Only) 2 x 13mm or 2 x 16mm on Steel Stud Sealed to depth of inner lining only, covered by second layer of plasterboard A -/120/120 Over Steel Stud (2nd Layer Only) 2 x 13mm or 2 x 16mm on Steel Stud & 1st Layer of plasterboard Sealed to depth of outer lining only, applied on top of 1st layer of plasterboard B -/120/120 Over Steel Stud (1st Layer Only) Steel Stud 5-27 Sealed to depth of inner lining only, covered by second layer of plasterboard A -/180/180 Over Steel Stud (2nd Layer Only) Steel Stud & 1st Layer of plasterboard 5-27 Sealed to depth of outer lining only, applied on top of 1st layer of plasterboard B -/180/180

15 Page 15 of 21 WALL TYPE: FLEXIBLE FRL:-/60/60 or 60/60/60, -/120/120 or 120/120/120, -/180/180 or 180/180/180 Figure 5-90-degree corner plasterboard Wall- Top of Wall and Vertical Seal Type 90 Degree Plaster Board Wall Corner Detail 90 Degree Plaster Board Wall Corner Detail 90 Degree Plaster Board Wall Corner Detail Wall Lining (mm) t 1 x 13mm or 16mm on 2 x 13mm or Backfilling Steel Track or PE Foam Backing Rod or eral Wool Insulation Steel Track or PE Foam Backing Rod or eral Wool Insulation Steel Track or PE Foam Backing Rod or eral Wool Insulation Nominal (mm) W 5-27 Depth of Sealant (mm) d Depth of Wall Lining Depth of both plasterboard Depth of both plasterboard *Only applicable for walls constructed from steel stud and track Wall (mm) a Track/Stud (mm) s Figure FRL /60/ /120/ /180/180

16 Page 16 of 21 Figure 6- Intersection T Plasterboard Wall- Top of Wall and Vertical Seal Type Wall Lining (mm) t Backfilling Nominal (mm) W Depth of Sealant (mm) d Wall (mm) a Track/Stud (mm) s Figure FRL Intersection (T) between two plaster board walls perpendicular to each other 1 x 13mm or 16mm on each Steel Track or PE Foam Backing Rod or eral Wool Insulation Depth of Wall Lining /60/60 Intersection (T) between two plaster board walls perpendicular to each other 2 x 13mm or 2 x 16mm on Steel Track or PE Foam Backing Rod or eral Wool Insulation Depth of both plaster board /120/120 Intersection (T) between two plaster board walls perpendicular to each other Steel Track or PE Foam Backing Rod or eral Wool Insulation 5-27 Depth of both plaster board *Only applicable for walls constructed from steel stud and track /180/180

17 Page 17 of 21 Seal Type Angled Corner Detail Angled Corner Detail Angled Corner Detail Wall Lining (mm) t 1 x 13mm or 16mm on each 2 x 13mm or 2 x 16mm each Figure 7: Angled Plasterboard Wall- Top of Wall and Vertical Backfilling Nominal (mm) W Steel Stud Steel Stud Steel Stud 5-27 Depth of Sealant (mm) d Depth of Wall Lining Depth of both plasterboard Depth of both plasterboard *Only applicable for walls constructed from steel stud and track Wall (mm) a Track/Stud (mm) s Figure FRL /60/ /120/ /180/180

18 Page 18 of 21 WALL TYPE: RIGID FRL:-/60/60 or 60/60/60, -/120/120 or 120/120/120, -/180/180 or 180/180/180 Figure 9- Wall to Wall Top View Figure 10- Vertical, Wall to Wall -Top View Figure 11- Wall to Wall T -Top View

19 Page 19 of 21 Seal Type Wall To wall Rigid Wall Type Concrete, Aerated Concrete & Masonry, Hollow Block or Solid Filled Backfilling PE Foam Backing Rod or eral Wool insulation Nominal (mm) W 5-27 Depth of Sealant (mm) d 13mm both s of wall 26mm both s of wall 32mm both s of wall Wall (mm) a Figure FRL /60/ /120/ /180/180 Top Of Wall Concrete, Aerated Concrete & Masonry, Hollow Block or Solid Filled PE Foam Backing Rod or eral Wool insulation mm both s of wall 26mm both s of wall 32mm both s of wall /60/ /120/ /180/180 Vertical - (T) Intersection Between two Rigid Walls Concrete, Aerated Concrete & Masonry, Hollow Block or Solid Filled PE Foam Backing Rod or eral Wool insulation mm both s of wall 26mm both s of wall 32mm both s of wall /60/ /120/ /180/180

20 Page 20 of 21 6 DIRECT FIELD OF APPLICATION The referenced assessment applies to penetrations in walls exposed to fire from either or from the stated and applies to penetrations in floors exposed to fire from under only. The results of the assessment report are based on actual test data and the scope is necessarily limited to the specifications indicated in section 3 and discussed in the Appendices of the assessment. 7 REQUIREMENTS The referenced assessment report details the methods of construction, test conditions and assessed results that would have been expected had the specific elements of construction described herein been tested in accordance with AS All services shall be supported in the manner in which they are assessed as described in Section 3. Any further variations with respect to size, constructional details, loads, stresses, edge or end conditions, other than those identified in this report, may invalidate the conclusions drawn in this report. 8 VALIDITY The referenced assessment report does not provide an endorsement by Exova Warringtonfire Aus Pty Ltd of the actual products supplied. The conclusions of the referenced assessment may be used to directly assess fire hazard, but it should be recognised that a single test method will not provide a full assessment of fire hazard under all conditions. Because of the nature of fire testing, and the consequent difficulty in quantifying the uncertainty of measurement, it is not possible to provide a stated degree of accuracy. The inherent variability in test procedures, materials and methods of construction, and installation may lead to variations in performance between elements of similar construction. The referenced assessment can therefore only relate only to the actual prototype test specimens, testing conditions, and methodology described in the supporting data, and does not imply any performance abilities of constructions of subsequent manufacture. The referenced assessment is based on information and experience available at the time of preparation. The published procedures for the conduct of tests and the assessment of test results are the subject of constant review and improvement and it is recommended that this report be reviewed on or, before, the stated expiry date. The information contained in this report shall not be used for the assessment of variations other than those stated in the conclusions above. The assessment is valid provided no modifications are made to the systems detailed in this report. All details of construction should be consistent with the requirements stated in the relevant test reports and all referenced documents.

21 Page 21 of 21 9 AUTHORITY 9.1 APPLICANT UNDERTAKINGS AND CONDITIONS OF USE By using this report as evidence of compliance or performance, the applicant(s) confirms that: to their knowledge the component or element of structure, which is the subject of this assessment, has not been subjected to a fire test to the Standard against which this assessment is being made, and they agree to withdraw this assessment from circulation should the component or element of structure be the subject of a fire test by a test authority in accordance with the Standard against which this assessment is being made and the results are not in agreement with this assessment, and they are not aware of any information that could adversely affect the conclusions of this assessment and if they subsequently become aware of any such information, agree to ask the assessing authority to withdraw the assessment. 9.2 GENERAL CONDITIONS OF USE This report may only be reproduced in full without modifications by the report sponsor. Copies, extracts or abridgments of this report in any form shall not be published by other organisations or individuals without the permission of Exova Warringtonfire Aus Pty Ltd. 9.3 AUTHORISATION ON BEHALF OF EXOVA WARRINGTONFIRE AUS PTY LTD Prepared by: Reviewed by: Mahmoud Akl Omar Saad 9.4 DATE OF ISSUE 7 August EXPIRY DATE 31 July 2023