1 Limited Asbestos Survey Loretto Abbey Secondary School 101 Mason Bouleva rd Toronto, Ontario G2S14780 Toronto Catholic School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 1/15/2015

2 Limited Asbestos Survey 101 Mason Boulevard, Toronto, Ontario G2S /15/2015 Material Asbestos Description Pipe Insulation (Aircell) Pipe Fittings (Paring Cement) Executive Summary The Site is occupied by Loretto Abbey Catholic Secondary School and Sisters Residence. The building is four stories plus basement and has an approximate footprint of 2,900 m 2 (31,215 ft 2 ) in area. The building was reportedly constructed in the early 1920 s. New teacher s offices were recently relocated to space formerly occupied by the Sisters Residence, located on the 2 nd and 3 rd floors. Several rooms on the ground floor, includingg the chapel, chapel reception and lunch room are now shared with the Sisters Residence. Toronto Catholic District School Board (TCDSB) provided G2S with a copy of a report entitled Asbestos-Containing Building Materials Assessment, Loretto Abbey Secondary School, 101 Mason Boulevard, Toronto, Ontario, prepared by Jacques Whitford, dated May 8, The 2008 survey did not include areas previously occupied primarily by the Sisters Residence. This survey was limited to areas of the building that were not included in the original asbestos survey completed by Jacques Whitford. Locations of the areas not included in this survey are illustrated on Drawings 1 and 2. The following areas were included in our survey: Basement hallway, boiler room and elevator mechanical; Ground floor chapel, chapel reception, lunchroom and adjacent hallway; 2 nd and 3 rd floor teachers offices; and, Stairwell #1 The purpose of this Asbestos Survey is to identify the location, type and condition of asbestos- containing materials (ACMs), for compliance with Ontario Regulation 278/05. G2S s conclusions and recommendations are summarized below. Recommendation Friable grey insulation (Aircell) containing 20% Chrysotile asbestos was identified on the LPR Steam line located within the shared basement hallway and boiler room. The LPR Steam line in the hallway was approximately 15 metres (m) in length andd approximately 20 m in length within the Boiler room. Both liness were observed to be in good condition at the time of our survey. The asbestos-containing insulation in the hallways is accessible to maintenance staff with a 4 foot step ladder. The asbestos- a lift or extensionn ladder. containing insulation in the boiler room is not accessible without Friable grey parging cement containing 15% Chrysotile asbestos was identified on the LPR Steam line pipe fitting located within the shared basement hallway. One (1) fitting, approximately 12 in diameter was observed to be in good conditionn at the time off our survey. The asbestos-containing insulation is accessible to maintenance staff with a 4 foot step ladder. i

3 Limited Asbestos Survey 101 Mason Boulevard, Toronto, Ontario G2S /15/2015 Material Description Recommendation Friable Asbestos-containing pipe insulation and parging cement located in the basement hallway and boiler room may be left in place and managed under an asbestos management plan in accordance with O. Reg. 278/05. Should the asbestos-containing materials require repair or removal, it shall be done in accordance with Type II or III specifications as per O. Reg. 278/ /05. Should suspect ACMs be uncovered during future renovations or demolition projects, the material should be assessed for asbestos content prior too disturbance. ii

4 Limited Asbestos Survey 101 Mason Boulevard, Toronto, Ontario G2S /15/2015 Table of Contents Executivee Summary i 1. Introduction Scope of Work Methodology Asbestos Building Description Findings Friable Materials... 3 Non-Friable Materials Conclusions and Recommendations Friable Asbestos... 5 Non-Friable Asbestos Qualifications of the Assessor Limitations Closing Remarks... 6 Appendices Appendix A: Appendix B: Appendix C: Photographs and Drawings Laboratory Analytical Results Asbestos Inventory Table & Condition Assessment and Action Table iii

5 Limited Asbestos Survey 101 Mason Boulevard, Toronto, Ontario G2S /15/ Introduction G2S Environmental Consulting Inc. (G2S) completedd a Limited Asbestos Survey for the property located at 101 Mason Boulevard in Toronto, Ontario, hereafter referred to as the Site. Authorization to proceed with the Asbestos Survey was provided by Ms. Kathleen Wilson of the TCDSB. The Site is occupied by Loretto Abbey Catholic Secondary School and Sisters Residence. The building is four stories plus basement and has an approximate footprint of 2,900 m 2 (31,215 ft 2 ) in area. The building was reportedly constructed in the early 1920 s. New teacher s offices were recently relocated to space formerly occupied by the Sisters Residence, located on the 2 nd and 3 rd floors. Several rooms on the ground floor, includingg the chapel, chapel reception and lunch room are now shared with the Sisters Residence. TCDSB provided G2S with a copy of a report entitled Asbestos-Containing Building Materials Assessment, Lorettoo Abbey Secondary School, 101 Mason Boulevard, Toronto, Ontario, prepared by Jacques Whitford, dated May 8, The 2008 survey did not include areas previously occupied primarily by the Sisters Residence. This survey was limited to areas of the building that were not included in the original asbestos survey completed by Jacques Whitford. Locations of the areas not included in this survey are illustrated on Drawings 1 and 2. The following areas were included in our survey: Basement hallway, boiler room and elevator mechanical; Ground floor chapel, chapel reception, lunchroom and adjacent hallway; 2 nd and 3 rd floor teachers offices; and, Stairwell #1 The Asbestos Survey was conducted on December 29, 2014 and was completed in accordance with the Occupationa al Health and Safety Act. 2. Scope of Work The scope of work for this Asbestos Survey included a visual inspection of the areas listed in Section 1.0 as well as sampling and analysis of potential ACMs. Concealed areas including wall, ceiling and bulkhead cavities were assessed as part of this investigation where accesss was attainable without destructive measures. Any suspect materials uncovered during the course of renovation or demolition should be assessed prior to disturbance. 1

6 Limited Asbestos Survey 101 Mason Boulevard, Toronto, Ontario G2S /15/ Methodology The following subsection describes the general characteristics, sampling and analytical methods of the suspected ACMs. 3.1 Asbestos Asbestoss is a generic term used to describe a naturally occurring silicate mineral with fibrous crystalline structure. There are six minerals defined ass asbestos, two of which are commonly found within some building materials used in Canada, chrysotile and amosite. Asbestos can be further defined as serpentine or amphibole. Chrysotile is the only asbestos mineral classified as serpentine, curly fibres occurring in a layered structure. Building materials often containing chrysotile asbestos include floor tiles, ceiling tiles, drywall compounds, plaster, texture coats (stucco), roofing materials, caulking, pipe insulation,, fireproofing, gaskets, fire doors, fire blankets, adhesives, brake pads and shoes, clutch plates and asbestos-cement siding, panels and pipes. Asbestoss minerals classified as amphibole include amosite, crocidolite, anthophyllite, tremolite and actinolite. The second most commonly used asbestos mineral, Amosite, can be found in asbestos-cement panels and pipes, thermal and chemical insulators (gaskets, lagging), insulationn boards and ceiling tiles. Samples of suspected ACMs were collected and submitted to EMLab P&K (EMLab) in Fort Lauderdale, Florida, an accredited laboratory under the National Voluntary Laboratory Accreditation Program (NVLAP) for asbestos analysiss using testt method EPA/600/R-93/116 (NVLAP # ). Samples were collected and analyzed in accordance with Ontario Regulation 278/ Building Description The Site is occupied by Loretto Abbey Catholic Secondary School and Sisters Residence. The building is four stories plus basement and has an approximate footprint of 2,900 m 2 (31,215 ft 2 ) in area. The building was reportedly constructed in the early 1920 s.. The building contains both TCDSB facilities and the Loretto Sisterss Residence. New teacher s offices were recently relocated to space formerly occupied by the Sisters Residence, located on the 2 nd and 3 rd floors. Several rooms on the ground floor, including the chapel, chapel reception and lunch room are now shared with the Sisters Residence. Interior flooring finishes were found to be constructed off wood, carpet, vinyl sheet, terrazzo and concrete. Walls were found to be constructed of drywall, plaster and concrete. Ceilings were found to be constructed of drywall, plaster, concrete, suspended and acoustic ceiling tiles. Exterior construction included brick, stone, and cement. 2

7 Limited Asbestos Survey 101 Mason Boulevard, Toronto, Ontario G2S /15/ Findings A total of 74 samples of suspected ACMs were collected and submitted for asbestos analysis. The table below detail the sample identification, material description, location of material and results of analytical testing completed during this survey. As per O. Reg. 278/ /05, materials containing less than 0.5% asbestos are not considered to be asbestos-containing materials. The following subsections present the findings of our visual inspection, sampling and analytical results. 5.1 Friable Materials Sample ID Material Description Location Asbestos Result AS001a-c VSF Blue/Grey colour Washroom, 2 ndd Floor AS002a Room 344, 2 nd Floor AS002b Room 342, 2 nd Floor AS002c Room 340, 2 nd Floor AS002d Drywall Joint Compound Room 337, 2 nd Floor AS002e Room 335, 2 nd Floor AS002f Room 336, 2 nd Floor AS002g Hallway, 2 nd Floor AS003a-c VSF Yellow colour Mastic Tan colour Room 342 (Closet), 2 nd Floor AS004a Room 447, 3 rdd Floor AS004b Room 444, 3 rd Floor AS004c Room 443, 3 rd Floor AS004d Drywall Joint Compound Room 440, 3 rd Floor AS004e Room 439, 3 rd Floor AS004f Room 438, 3 rd Floor AS004g Hallway, 3 rd Floor AS005a-c Plaster Chapel Reception 1 st Floor AS006a-g Plaster Chapel 1 st Floor AS007a-c Drywall Joint Compound Chapel (Back Room) 1 st Floor 3

8 Limited Asbestos Survey 101 Mason Boulevard, Toronto, Ontario G2S /15/2015 Sample ID Material Description Location Asbestos Result AS008a-e VSF Yellow/Brown colour Lunchroom 1 st Floor AS009a-e Plaster Lunchroom 1 st Floor AS010a-e SCT 2 x4, Small dots and fissures Lunchroom 1 st Floor AS011a-e ACT 1 x1, Smalls dots Lunchroom (Above SCT) 1 st Floor AS012a-c AS012d-g Plaster Stairwell 1 1 st Floor Stairwell 1 3 rdd Floor AS013a-e Plaster Hallway Basement AS014a-c Pipe straight insulation (Aircell) Hallway (LPR Steam Line) Basement 20% Chrysotile AS015a-c Pipe fitting insulation Hallway (LPR Steam Line) - Basement 15% Chrysotile AS016a-c Drywall Joint Compound Elevator Mechanical Room Basement SCT = Suspended Ceiling Tile ACT = Acoustic Ceiling Tile VSF = Vinyl Sheet Flooring = None Detected Bold = Asbestos-containing Material 5.2 Non-Friable Materials Non-friable materials were not observed at the time of our survey. 4

9 Limited Asbestos Survey 101 Mason Boulevard, Toronto, Ontario G2S /15/ Conclusions s and Recommendations 6.1 Friable Asbestos Material Asbestos Description Pipe Insulation (Aircell) Pipe Fittings (Paring Cement) Recommendation Friable grey insulation (Aircell) containing 20% Chrysotile asbestos was identified on the LPR Steam line located within the shared basement hallway and boiler room. The LPR Steam line in the hallway was approximately 15 metres (m) in length andd approximately 20 m in length within the Boiler room. Both liness were observed to be in good condition at the time of our survey. The asbestos-containing insulation in the hallways is accessible to maintenance staff with a 4 foot step ladder. The asbestos- a lift or extensionn ladder. containing insulation in the boiler room is not accessible without Friable grey parging cement containing 15% Chrysotile asbestos was identified on the LPR Steam line pipe fitting located within the shared basement hallway. One (1) fitting, approximately 12 in diameter was observed to be in good conditionn at the time off our survey. The asbestos-containing insulation is accessible to maintenance staff with a 4 foot step ladder. Friable Asbestos-containing pipe insulation and parging cement located in the basement hallway and boiler room may be left in place and managed under an asbestos management plan in accordance with O. Reg. 278/05. Should the asbestos-containing materials require repair or removal, it shall be done in accordance with Type II or III specifications as per O. Reg. 278/ /05. Should suspect ACMs be uncovered during future renovations or demolition projects, the material should be assessed for asbestos content prior too disturbance. 6.2 Non-Friable Asbestos Non-friable materials were not observed at the time of our survey. 7. Qualification ns of the Assessor This Asbestos Survey was conducted by Mr. Ryan Boyd. Mr. Boyd has over 6 years of environmental consulting experience, including Phasee I and II ESAs, hazardous materials management, contaminant hydrogeology, waste compliance audits, air quality, environmental monitoring and remediation of contaminated sites. Mr. Boyd is responsible for the successful completion of field work and reporting. Mr. Boyd has completed numerous projects on behalf of private and public sector clients for industrial, commercial and residential sites. This Asbestos Survey was reviewed by Mr. Geoff Bell, P. Geo. (limited). Mr. Bell has over 13 years of environmental consulting experience, including Phase I and II ESAs, hazardous materials management, contaminant hydrogeology, airr quality, environmental monitoring and remediation of contaminated sites. Mr. Bell is responsible for the overall management of projects, QA/QC, and health and safety, as well as acting as a technical lead on projects. Mr. Bell has managed numerous asbestos, designated substances and mould assessments, as well as remediation programs. 5

10 Limited Asbestos Survey 101 Mason Boulevard, Toronto, Ontario G2S /15/ Limitations The scope of work for this Asbestos Survey included a visual inspection of the building, as well as sampling and analysis of potential asbestos-containing materials (ACMs). Concealed areas including wall and ceiling cavities were not assessed as part of this investigation. The survey was limited to several recently shared spaces with the school and Sisters Residence. Thesee areas were previously occupiedd primarily by the Sisters Residence; thereforee were not included in the original asbestos survey. Exterior building and roofing materials were not sampledd at the time of our survey. This report has been prepared for the sole benefit of TCDSB and is intended to provide an Asbestoss Survey of the Site, 101 Mason Boulevard in Toronto, Ontario. The report may not be used by any other person or entity without the expressed written consent of TCDSB and G2S Environmental Consulting Inc. (G2S). Any use which a third party makes of this report, or any reliance on decisions made based on it, are the responsibilities of such third parties. G2S accepts no responsibility for damages, if any suffered by any third party as a result of decisions made or actions based on this report. The findings in this report are limited to the conditions at the Site att the time of this investigation (December 2014) as well as information provided byy the Site representatives as reported herein. Conclusions presented in this report should not be construed as legal advice. If Site conditions or applicable standards change or if any additional information becomes available at a future date, changes to the findings, conclusions and recommendations in this report may be necessary. 9. Closing Remarks We trust this report is satisfactory for your purposes. Should you have any questions, please do not hesitate to contact this office. Yours truly, G2S Environmental Consulting Inc. Ryan Boyd, Dipl.T. Senior Environmental Techniciann Geoff Bell, P. Geo. (Limited) Seniorr Project Manager 6

11 Appendix A Photographs and Drawings

12 G2S14780 Appendix A- Site Photographs 101 Mason Boulevard, Toronto Picture and Description January 2015 Photo #1: Pipe insulation (Aircell), located in the Boiler room against the ceiling. Photo #2: Typical layout of the 2 nd and 3 rd floor hallways. Photo# #3: Typical office layout, within the 2 and 3 rd floor teacher s offices. nd Photo #4: Typical constructionn of the Chapel Reception room. Photo #5: Typical construction inside the Chapel. Photo #6: Typical constructionn inside the floor, lunchroom. 1 st

13 G2S14780 Appendix A- Site Photographs 101 Mason Boulevard, Toronto Picture and Description January 2015 Photo #7: Typical construction in the basement Boiler room. Photo #8: Hot water storage tanks, with Non- ACM fibreglass insulation. Photo# #9: Typical construction within Stairwell. Photo #10: Typical construction above drywall ceiling on the 2 nd and 3 rd floors.

14

15

16

17

18 Appendix B Laboratory Analytical Results

19 Report for: Mr. Ryan Boyd G2S Environmental Consulting, Inc Dundas St. W, Ste. 201 Mississauga, ON L5C 1E6 Canada Regarding: Project: G2S 14780; Loretto Abbey EML ID: Approved by: Dates of Analysis: Asbestos PLM: Approved Signatory Baluswamy Krishnan Service SOPs: Asbestos PLM (EPA Methods 600/R-93/116 & 600/M , SOP EM-AS-S-1267) All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the items tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested. EMLab P&K ("the Company") shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor. EMLab P&K, LLC EMLab ID: , Page 1 of 19

20 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS001a, VSF-Blue & Grey Pattern Lab ID-Version : Blue-Green Sheet Flooring Composite Non-: 10% Nylon Location: AS001b, VSF-Blue & Grey Pattern Lab ID-Version : Blue-Green Sheet Flooring Composite Non-: 10% Nylon 2% Glass Fibers Location: AS001c, VSF-Blue & Grey Pattern Lab ID-Version : Blue-Green Sheet Flooring Composite Non-: 10% Nylon 2% Glass Fibers Location: AS002a, Drywall Joint Compound Lab ID-Version : The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 2 of 19

21 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS002b, Drywall Joint Compound Lab ID-Version : Location: AS002c, Drywall Joint Compound Lab ID-Version : Location: AS002d, Drywall Joint Compound Lab ID-Version : Location: AS002e, Drywall Joint Compound Lab ID-Version : Cream Tape Composite Non-: 10% Cellulose The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 3 of 19

22 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS002f, Drywall Joint Compound Lab ID-Version : Location: AS002g, Drywall Joint Compound Lab ID-Version : Location: AS003a, VSF-Yellow Pattern Lab ID-Version : Yellow Sheet Flooring Tan Mastic Location: AS003b, VSF-Yellow Pattern Lab ID-Version : Yellow Sheet Flooring Tan Mastic The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 4 of 19

23 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS003c, VSF-Yellow Pattern Lab ID-Version : Yellow Sheet Flooring Tan Mastic Composite Non-: < 1% Cellulose Location: AS004a, Drywall Joint Compound Lab ID-Version : Location: AS004b, Drywall Joint Compound Lab ID-Version : Location: AS004c, Drywall Joint Compound Lab ID-Version : The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 5 of 19

24 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS004d, Drywall Joint Compound Lab ID-Version : Location: AS004e, Drywall Joint Compound Lab ID-Version : Location: AS004f, Drywall Joint Compound Lab ID-Version : Location: AS004g, Drywall Joint Compound Lab ID-Version : The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 6 of 19

25 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS005a, Plaster Lab ID-Version : Gray Plaster /Paint Location: AS005b, Plaster Lab ID-Version : Gray Plaster /Paint Location: AS005c, Plaster Lab ID-Version : Gray Plaster /Paint Location: AS006a, Plaster Lab ID-Version : Gray Plaster /Paint The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 7 of 19

26 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS006b, Plaster Lab ID-Version : Gray Plaster /Paint Location: AS006c, Plaster Lab ID-Version : Gray Plaster /Paint Location: AS006d, Plaster Lab ID-Version : Gray Plaster /Paint Location: AS006e, Plaster Lab ID-Version : Gray Plaster /Paint The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 8 of 19

27 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS006f, Plaster Lab ID-Version : Gray Plaster /Paint Location: AS006g, Plaster Lab ID-Version : Gray Plaster /Paint Location: AS007a, Drywall Joint Compound Lab ID-Version : Location: AS007b, Drywall Joint Compound Lab ID-Version : The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 9 of 19

28 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS007c, Drywall Joint Compound Lab ID-Version : Location: AS008a, VSF-Brown/ Yellow Pattern Lab ID-Version : Brown Sheet Flooring with Fibrous Backing Composite Non-: 20% Cellulose Location: AS008b, VSF-Brown/ Yellow Pattern Lab ID-Version : Brown Sheet Flooring with Fibrous Backing Composite Non-: 20% Cellulose Location: AS008c, VSF-Brown/ Yellow Pattern Lab ID-Version : Brown Sheet Flooring with Fibrous Backing Composite Non-: 20% Cellulose The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 10 of 19

29 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS008d, VSF-Brown/ Yellow Pattern Lab ID-Version : Brown Sheet Flooring with Fibrous Backing Composite Non-: 20% Cellulose Location: AS008e, VSF-Brown/ Yellow Pattern Lab ID-Version : Brown Sheet Flooring with Fibrous Backing Composite Non-: 20% Cellulose Location: AS009a, Plaster Lab ID-Version : White Plaster Location: AS009b, Plaster Lab ID-Version : White Plaster The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 11 of 19

30 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS009c, Plaster Lab ID-Version : White Plaster Location: AS009d, Plaster Lab ID-Version : White Plaster Location: AS009e, Plaster Lab ID-Version : White Plaster Location: AS010a, SCT, 2'x4' Small Dots & Fissures Lab ID-Version : Gray Ceiling Tile with White Surface Composite Non-: 20% Mineral Wool 15% Cellulose The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 12 of 19

31 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS010b, SCT, 2'x4' Small Dots & Fissures Lab ID-Version : Gray Ceiling Tile with White Surface Composite Non-: 20% Mineral Wool 15% Cellulose Location: AS010c, SCT, 2'x4' Small Dots & Fissures Lab ID-Version : Gray Ceiling Tile with White Surface Composite Non-: 20% Mineral Wool 15% Cellulose Location: AS010d, SCT, 2'x4' Small Dots & Fissures Lab ID-Version : Gray Ceiling Tile with White Surface Composite Non-: 20% Mineral Wool 15% Cellulose Location: AS010e, SCT, 2'x4' Small Dots & Fissures Lab ID-Version : Gray Ceiling Tile with White Surface Composite Non-: 20% Mineral Wool 15% Cellulose The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 13 of 19

32 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS011a, ACT, 1'x1' Small Dots Lab ID-Version : Brown Ceiling Tile with White Surface Composite Non-: 85% Cellulose Location: AS011b, ACT, 1'x1' Small Dots Lab ID-Version : Brown Ceiling Tile with White Surface Composite Non-: 85% Cellulose Location: AS011c, ACT, 1'x1' Small Dots Lab ID-Version : Brown Ceiling Tile with White Surface Composite Non-: 85% Cellulose Location: AS011d, ACT, 1'x1' Small Dots Lab ID-Version : Brown Ceiling Tile with White Surface Composite Non-: 85% Cellulose The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 14 of 19

33 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS011e, ACT, 1'x1' Small Dots Lab ID-Version : Brown Ceiling Tile with White Surface Composite Non-: 85% Cellulose Location: AS012a, Plaster Lab ID-Version : Gray Plaster /Paint Location: AS012b, Plaster Lab ID-Version : Gray Plaster /Paint Location: AS012c, Plaster Lab ID-Version : Gray Plaster /Paint The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 15 of 19

34 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS012d, Plaster Lab ID-Version : Gray Plaster /Paint Location: AS012e, Plaster Lab ID-Version : Gray Plaster /Paint Location: AS012f, Plaster Lab ID-Version : Gray Plaster /Paint Location: AS012g, Plaster Lab ID-Version : Gray Plaster /Paint The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 16 of 19

35 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS013a, Plaster Lab ID-Version : White Plaster /Paint Location: AS013b, Plaster Lab ID-Version : White Plaster /Paint Location: AS013c, Plaster Lab ID-Version : White Plaster /Paint Location: AS013d, Plaster Lab ID-Version : White Plaster /Paint The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 17 of 19

36 Client: G2S Environmental Consulting, Inc. C/O: Mr. Ryan Boyd Re: G2S 14780; Loretto Abbey EMLab P&K 6301 NW 5th Way, Suite 2850, Ft. Lauderdale, FL (877) Fax (954) Date of Sampling: Date of Receipt: Date of Report: ASBESTOS PLM REPORT: EPA-600/M & EPA METHOD 600/R Location: AS013e, Plaster Lab ID-Version : White Plaster /Paint Location: AS014a, Pipe Straight Insulation Lab ID-Version : Gray Insulation 20% Chrysotile Comments: Samples 014B and 014C were not analyzed due to positive stop. Location: AS015a, Pipe Fitting Insulation Lab ID-Version : Gray Insulation 15% Chrysotile Comments: Samples 015B and 015C were not analyzed due to positive stop. Location: AS016a, Drywall Joint Compound Lab ID-Version : The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification. A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x". EMLab P&K, LLC EMLab ID: , Page 18 of 19