HAMILTON TOWNSHIP MUNICIPAL UTILITIES AUTHORITY

Size: px
Start display at page:

Download "HAMILTON TOWNSHIP MUNICIPAL UTILITIES AUTHORITY"

Transcription

1 HEIGHT TO REMOVE STRAINER ELEMENT D C G I E B H F J A Operating Characteristics Meter Normal Operating Range* AWWA Low Flow Maximum Accuracy (±1.5%) Accuracy Intermittent Flow Rate 4" 3/4 to 1200 US gpm 2 to 700 US gpm 3/8 US gpm 1500 US gpm to m 3 /h 0.45 to 159 m 3 /h 0.09 m 3 /h m 3 /h 6" 1 1 /2 to 2500 US gpm 4 to 1600 US gpm 3/4 US gpm 3100 US gpm 0.34 to m 3 /h 0.91 to 363 m 3 /h 0.17 m 3 /h m 3 /h 8" 2 to 4000 US gpm 7 to 2800 US gpm 1 US gpm 5000 US gpm 0.45 to m 3 /h 1.6 to 636 m 3 /h 0.23 m 3 /h m 3 /h 10" 2 to 6500 US gpm 12 to 4400 US gpm 1 US gpm 8000 US gpm 0.45 to m 3 /h 2.7 to 999 m 3 /h 0.23 m 3 /h 1817 m 3 /h Registration Registration Disc Side Turbine Side (per sweep hand revolution) 1" 1 1 /2" 2" 4" 6" 8" & 10" 1,000 US Gallons 100 Gallons 100 Cubic Feet 10 US Gallons 10 Cubic Feet 1 Cubic Foot 10 Cubic Metres 1 Cubic Metre 0.1 Cubic Metre Register Capacity Disc Side Turbine Side (6 active wheel odometer) 1" 1 1 /2 " 2" 4" 6" 8" & 10" 1,000,000,000 Gallons 100,000,000 Gallons 100,000,000 Cubic Feet 10,000,000 Gallons 10,000,000 Cubic Feet 10,000,000 Cubic Metres 1,000,000 Cubic Metres 1,000,000 Cubic Feet 100,000 Cubic Metres Dimensions Meter A B C D E F G H I J Weight Size in/mm in/mm in/mm in/mm in/mm in/mm in/mm in/mm in/mm in/mm lbs/kg 4Ó / / /4 6 3 / Ó / / / /2 9 1 / Ó / / / / / / Ó / / / / / Guarantee Systems Capability All HP Protectus III Fire Service meters are guaranteed adaptable to our ARB V, ProRead AutoDetect, TRICON /S, TRICON/E3, and Neptune meter reading systems without removing the meter from service. Specifications Application: cold water measurement of flow in one direction Maximum operating pressure: 175 psi (1206 kpa) Register: direct reading, center sweep, roll-sealed magnetic drive with low-flow indicator Measuring element: AWWA Class II Turbine, hydrodynamically balanced rotor, nutating disc Flanges: round flanged ends per AWWA C207, Class D Options Sizes: 4, 6, 8, and 10 Units of measure: U.S. gallons, imperial gallons, cubic feet, cubic metres Register types: - Direct reading: Bronze box and cover (standard) - Remote reading systems*: ARB, ProRead AutoDetect Absolute Encoder, TRICON/S, TRICON/E3 - Reclaim Companion flanges: - Cast iron - Bronze (4 only) * Consult factory for meter performance specifications when fitted with ARB. HTMUA DRAWING #3A 4",6",8" & 10" FIRE SERVICE METER NEPTUNE TECHNOLOGY

2 HTMUA DRAWING #3B 4",6",8" & 10" FIRE SERVICE METER NEPTUNE TECHNOLOGY

3 4'-6" MIN. 2'-6" MUELLER SUPER CENTURION FIRE HYDRANT WITH TWO HOSE CONNECTIONS AND PUMPER CONNECTION HYDRANT SHALL BE ADJUSTABLE TO GRADE FROM STREET 1'-6" MIN. VALVE BOX LID MARKED "WATER" ADJUSTABLE VALVE BOX, MUELLER H OR EQUAL 4'-0" MIN. CONCRETE THRUST BLOCK 6" SPOOL PIECE WITH RESTRAINING RODS FOR FULL LENGTH 6" SHORT BODY GATE VALVE MECH. JOINT WATER MAIN UNDISTURBED EARTH COURSE GRAVEL OR BROKEN STONE & COURSE SAND HAND COMPACTED FILL TEE WITH 6" OUTLET CONCRETE THRUST BLOCK FIRE HYDRANT & VALVE DETAIL N.T.S. NOTE: THREADS ON FIRE HYDRANT OUTLETS SHALL BE AMERICAN NATIONAL FIRE HOSE CONNECTION SCREW THREADS HTMUA DRAWING #4 FIRE HYDRANT CONNECTION

4 METER PIT DETAIL 3/4" TO 1" SERVICE N.T.S. HTMUA DRAWING #6 3/4" TO 1" SERVICE

5 METER PIT DETAIL 1.5"-2" SERVICE N.T.S. HTMUA DRAWING #6 1.5"-2" SERVICE

6 VARRIES NOTE: R900 WATER RF PIT MIV NOT SHOWN MUELLER/ HUNT 18-INCH DIA. COIL SINGLE METER PIT FOR 1-INCH METER (#330CS1848FSAS) HTMUA DRAWING #6A 1-INCH METER

7 VARRIES NOTE: R900 WATER RF PIT MIV NOT SHOWN MUELLER/ HUNT 18-INCH DIA. COIL SINGLE METER PIT FOR 3/4-INCH METER (#330CS1848FSAS) HTMUA DRAWING #6B 3/4-INCH METER

8 " 24" 24" VARRIES NOTE: R900 WATER RF PIT MIV NOT SHOWN MUELLER/ HUNT 24-INCH DIA. COIL SINGLE METER PIT FOR 1.5-INCH METER HTMUA DRAWING #6C 1.5-INCH METER

9 2" 2" 18" 27" 27" 2" 2" VARIES 2" 2" 2" NOTE: R900 WATER RF PIT MIV NOT SHOWN MUELLER/ HUNT 27-INCH DIA. COIL SINGLE METER PIT FOR 2-INCH METER HTMUA DRAWING #6D 2-INCH METER

10 Operating Characteristics Meter Normal Operating Range AWWA Low Flow Accuracy (±1.5%) 95% Accuracy 5/8" 1/2 to 20 US gpm 1 to 20 US gpm 1/8 US gpm 0.11 to 4.55 m 3 /h 0.23 to 4.5 m 3 /h 0.03 m 3 /h 3/4" 3/4 to 30 US gpm 2 to 30 US gpm 1/4 US gpm 0.17 to 6.82 m 3 /h 0.45 to 6.8 m 3 /h 0.06 m 3 /h 1" 1 to 50 US gpm 3 to 50 US gpm 3/8 US gpm 0.23 to m 3 /h 0.68 to 11.4 m 3 /h 0.09 m 3 /h Specifications Certification: ANSI/NSF 61 Application: cold water measurement of flow in one direction Maximum operating pressure: 150 psi (1034 kpa) Maximum operating temperature: 80 F Measuring chamber: nutating disc technology design made from proprietary synthetic polymer Registration Registration (per sweep hand revolution) 5/8" 3/4" & 1" 10 US Gallons 10 Imperial Gallons 1 Cubic Foot 0.1 Cubic Metre 0.01 Cubic Metre IN B Register Capacity (6-wheel odometer) 5/8" 3/4" & 1" 10,000,000 US Gallons 10,000,000 Imperial Gallons F D C 1,000,000 Cubic Feet 100,000 Cubic Metres 10,000 Cubic Metres E Dimensions Meter A B C-Std. C-ARB D-Threads D-OD E F Weight Size in/mm in/mm in/mm in/mm per inch in/mm in/mm in/mm lbs/kg 5/8" 7 1 /2 3 5 /8 4 7 /8 5 3 / /8 2 1 /2 3 3 / /8"x 3 /4" 7 1 /2 3 5 /8 4 7 /8 5 3 / / /8 2 5 / /4" /8 5 1 / / / /8 2 5 / /4"SL 7 1 /2 4 3 /8 5 1 / / / /8 2 5 /8 5 1 / /4"x1" /8 5 1 / / / /8 2 3 /4 6 1 / " 10 3 /4 6 1 /2 6 3 /8 6 5 / / /8 2 3 /4 9 3 / "x1 1 /4" 10 3 /4 6 1 /2 6 3 /8 6 5 / / / / / A Options Sizes: - 5/8", 5/8" x 3/4" - 3/4", 3/4" SL, 3/4" x 1" - 1", 1" x 1 1/4" Units of measure: U.S. gallons, imperial gallons, cubic feet, cubic metres Register types: - Direct reading: Bronze box and cover (standard) - Remote reading: ProRead AutoDetect Absolute Encoder, TRICON/S, TRICON/E3 - Reclaim Bottom caps: - Synthetic polymer (5/8" only) - Cast iron - EnviroBrass II, ductile iron Connections: EnviroBrass II, straight or bent Guaranteed Systems Compatibility All T-10 water meters are guaranteed adaptable to our ARB V, ProRead AutoDetect, TRICON /S, TRICON/E3, and Neptune meter reading systems without removing the meter from service. HTMUA DRAWING #6E 5/8"- 3/4"-1" T-10 WATER METER NEPTUNE TECHNOLOGY

11 Operating Characteristics Meter Normal Operating Range AWWA Low Flow Accuracy (±1.5%) 95% Accuracy 1 1/2" 2 to 100 US gpm 5 to 100 US gpm 3/4 US gpm 0.46 to m 3 /h 1.1 to 22.7 m 3 /h 0.17 m 3 /h 2" 2 1/2 to 160 US gpm 8 to 160 US gpm 1 US gpm 0.57 to m 3 /h 1.8 to 36.3 m 3 /h 0.23 m 3 /h Guaranteed Systems Compatibility All T-10 meters are guaranteed adaptable to our ARB V, ProRead AutoDetect, TRICON /S, TRICON/E3, and Neptune meter reading systems without removing the meter from service. Options Sizes: -1 12" flanged or threaded end - 2" flanged or threaded end E Units of measure: U.S. gallons, imperial gallons, cubic feet, cubic metres Register types: - Direct reading: Bronze box and cover (standard) - Remote reading: ProRead AutoDetect Absolute Encoder, TRICON/S, TRICON/E3 -Reclaim EMeasuring chamber: synthetic polymer Companion flanges: cast iron or EnviroBrass II C Registration Registration (per sweep hand revolution) 1 1 /2" 2" 100 US Gallons E A 100 Imperial Gallons 10 Cubic Feet 1 Cubic Metre 0.1 Cubic Metre B D Register Capacity (6-wheel odometer) 1 1 /2" 2" 100,000,000 US Gallons 100,000,000 Imperial Gallons 10,000,000 Cubic Feet 1,000,000 Cubic Metres 100,000 Cubic Metres Dimensions Meter A B C-Std. C-ARB D-Threads D-Thread E Weight Size in/mm in/mm in/mm in/mm per inch Type in/mm lbs/kg 1 1 /2" 12 5 /8 8 1 / /8 8 9 / /2 1 1 /2" 2 9 /16 31 Screw End NPT /2" / /8 8 9 /16 2 9/16 35 Flanged End " 15 1 /4 9 7 / / / /2 2" 3 1 /8 40 Screw End NPT " / / /4 3 1 /8 44 Flanged End Specifications Certification:ANSI/ NSF 61 Application: cold water measurement of flow in one direction Maximum operating pressure: 150 psi (1034 kpa) Maximum operating temperature: 80 F Measuring chamber: nutating disc technology design made from proprietary synthetic polymer HTMUA DRAWING #6F 1.5" - 2" T-10 WATER METER NEPTUNE TECHNOLOGY

12 1.25 in in in in in..88 in in. 4 in in..44 in in. Technical Specifications Electrical Specifications: - Power: Lithium battery Transmitter Specifications: -Transmit Period: 4 seconds -Transmitter Channels: 50 - Channel Frequency: 910 to 920 MHz spread spectrum - Output Power: Meets FCC part FCC Verification: Part Encoder Register Interface: -Two Available Wire Lengths: 6 feet and 25 feet Enviromental Conditions: - Operating Temperature: -22º to 149ºF (-30º to 65ºC) - Storage Temperature: -40º to 158ºF (-40º to 70ºC) - Operating Humidity: 0 to 100% Functional Specifications: - Register Reading -MIU ID NEPTUNE TECHNOLOGY R900 PIT MIU AND DRIVE-BY DATA COLLECTION SYSTEM HTMUA DRAWING #6G R900 MIU DATA COLLECTOR

13 HTMUA DRAWING #6H 1.5" METER SETTER

14 HTMUA DRAWING #6I 2" METER SETTER

15 HTMUA DRAWING #6J 1.5" METER YOKE

16 HTMUA DRAWING #6K 2" METER YOKE

17 HTMUA DRAWING #6L 18" TO 27" METER BOX SETTER LIDS

18 HTMUA DRAWING #6M 27" METER BOX SETTER LIDS

19 HTMUA DRAWING #6N 1.5" STOPS AND FITTINGS

20 HTMUA DRAWING #6O 2" STOPS AND FITTINGS

21 SIDEWALK FINISHED GRADE CAST IRON NO-HUB WITH CURB PAVING SURFACE LENGTH OF 4" PVC RISER PIPE TO VARY AS REQUIRED-NOT MORE THAN TWO SECTIONS AND NOT TO EXCEED 5'-0" MIN. 2' BEHIND CURB LINE OR EDGE OF PAVING JOINTS SHALL BE RUBBER GASKET TYPE OR APPROVED EQUAL PVC SANITARY "Y" AND L/S BEND COMBINATION FLOW SECTION CLEANOUT PVC SDR-35 OR APPROVED EQUAL 2'-0" CUT "H" IN TOP OF CURB STANDARD COUPLING CLEANOUT (TYP. WHERE CURB EXISTS) H SANITARY SEWER MAIN 4" 45 㠀 WYE OR TEE 4" PIPE 4" 45 㠀 BEND CURB OR CURB LINE LATERAL SHALL BE PLACED ON UNDISTURBED EARTH OR STONE CONCRETE CRADLE NOTES: 1. ANY COMBINATION OF 4" PIPE MUST BE CONNECTED BY APPROVED ADAPTER 2. ALL CLEAN-OUTS SHALL BE FITTED WITH A METALLIC CAP (OR A NONMETALLIC CAP FITTED WITH A METALLIC PLUG) THAT CAN BE LOCATED WITH A METAL DETECTOR (BRASS IS NOT SUITABLE). 3. LOCATION OF CLEANOUT TO BE IN PLANTER AREA OR 1 FOOT ON RESIDENT'S SIDE OF PROPOSED SIDEWALK AND NEVER OUTSIDE OF STREET R.O.W. 4. NO CONNECTION WILL BE BACKFILLED UNTIL WRITTEN APPROVAL IS MADE BY THE MUNICIPAL UTILITIES AUTHORITY. 5. NO DEVIATION FROM THESE SPECIFICATIONS SHALL BE MADE WITHOUT APPROVAL OF THE MUNICIPAL UTILITIES AUTHORITY. 6. VIOLATORS WILL BE REQUIRED TO EXPOSE THE WORK FOR INSPECTION BEFORE APPROVAL WILL BE GRANTED. 7. MATERIALS SHALL BE 4" SDR-35 PVC PIPE. 8. ALL ABOVE MATERIALS MUST BE APPROVED BY HAMILTON TOWNSHIP M.U.A. TYPICAL 4" HOUSE CONNECTION N.T.S HTMUA DRAWING #8 4" HOUSE CONNECTION (SEWER)

22 EXTENDED BELL DEPTH ON 90 낮 RISER BEND TO COMPENSATE FOR SETTLEMENT. INSTALL RISER PIPE IN SEWER MAIN FITTING AND CUT TO APPROPRIATE LENTH. (2" ABOVE CASING CAP.) CASING CAP 4" OR 6" SERVICE LATERAL PIPE 4" OR 6" RISER PIPE (ASTM D-3034) CASING PIPE (AWWA C-900) CASING SHOE (DUCTILE IRON) SEWER MAIN PIPE SEWER MAIN FITTING (WYE, TEE WYE, OR TEE) (ENCASE IN CRUSHED STONE) DEEP SEWER ASSEMBLY CONNECTION DETAIL N.T.S NOTES: 1) PROVIDE 3/4" CRUSHED STONE (#57) 9" THICK AT SEWER MAIN FITTING. 2) PLACE CASING SHOE OVER SEWER MAIN OUTLET. 3) MAKE SQUARE CUTS ON CASING PIPE - INSTALL IN SHOE AND CUT TO PROPER ELEVATION. ( SHORT SEGMENTS WITH COUPLINGS FOR CONVENIENCE IS PERMITTED.) INSTALL CASING CAP. HTMUA DRAWING #9 DEEP SEWER CONNECTION DETAIL

23 HTMUA PICKHOLES PLAN VIEW 34" 31 3/4" 1 3/8" 30" 10" 41" 49" SECTION VIEW STANDARD MANHOLE FRAME & COVER NOT TO SCALE NOTES: A. COVER SHALL BE SUPPLIED WITH SPECIAL NON-PENETRATING WATERTIGHT PICKHOLES. B. BEARING SURFACE OR FRAME AND COVER SHALL BE MACHINED. C. COVER SHALL BE SUPPLIED WITH 1 1/2" HIGH BLOCK LETTERING, RAISED. D. CAMPBELL FOUNDRY PATTERN NUMBER 1206 OR APPROVED EQUAL. HTMUA DRAWING #10 STANDARD MANHOLE FRAME AND COVER

24 WATERTIGHT MANHOLE SEWER GUARD OR EQUAL MANHOLE RIM 2" ABOVE FINISHED GRADE OF TOPSOIL 8" C REINFORCED CONCRETE SLAB 5-1/2" FRAME TO BE SET IN FULL BED OF MORTAR ADJUST TO GRADE WITH COARSES OF BRICK OR CONCRETE GRADING RINGS, (12" MAX.) PARGE INSIDE AND OUTSIDE OF BRICKS DURA PLATE 100 LINER OR EQUAL TWO SEPARATE COATS OF APPROVED BLACK BITUMASTIC WATERPROOFING COMPOUND APPLIED PER MANUFACTURER'S SPECIFICATIONS GROUT INSIDE AND OUTSIDE FACE OF MANHOLE WALL AT JOINT. REAPPLY BITUMASTIC WATERPROOFING OVER GROUTED AREAS ON OUTSIDE OF WALLS 6" MIN. 60" 5" JOINT CAN BE SEALED USING BUTYL RUBBER OR D-LOK RUBBER GASKET 30"x48" PRECAST MANHOLE CONE OR FLAT SLAB AS REQUIRED 48" INSIDE DIA. BY 5" THICK WALL PRECAST CONCRETE MANHOLE CONSTRUCTED AND REINFORCED IN ACCORDANCE WITH ASTM SPEC. C-478 ROUND RUBBER GASKET JOINT IN ACCORDANCE WITH ASTM SPEC. C-361, (TYP) 3/4" CRUSHED STONE FOUNDATION (12" THICK) UNDISTURBED SUBGRADE SMOOTH CONCRETE CHANNEL WITH DEPTH EQUAL TO 0.80 TIMES THE DIA. OF THE PIPE, (8" DIA. PIPE) SEAL INSIDE AND OUTSIDE FACE OF WALLS WITH GROUT AT PIPE TO MANHOLE CONNECTION TYPICAL MANHOLE DETAIL - PVC LINED NO SCALE HTMUA DRAWING #11 STANDARD MANHOLE

25 FINISHED GRADE MANHOLE FRAME & COVER WITH 2" RAISED LETTERS (SEE DETAIL) FRAME TO BE BEDDED IN MORTAR ALUM. MANHOLE STEPS AT 12"O.C. 30" ADJUST TO GRADE WITH SOLID BRICK AND MORTAR AS REQUIRED (3 COURSES MAX.) SEAL WATERTIGHT WITH TWO COATS OF ASPHALTIC PITCH 3 FT. PRECAST CONCRETE ECCENTRIC CONE FLEXIBLE WATERTIGHT RUBBER GASKET JOINT BACKFILL MATERIAL 48" 6"THICK WALLS (MIN.) PRECAST REINF. CONCRETE MANHOLE RISERS AT 1',2' OR 3' LENGTHS AS REQUIRED TWO (2) COATS MIN. BLACK BITUMASTIC WATERPROOFING CAST IN PLACE CONCRETE CHANNEL CLASS C CONCRETE 6"THICK (MIN) CLASS C CONCRETE FOUNDATION 6" 3 FT. PRECAST REINF. CONCRETE BASE FIRM SUB-GRADE CRUSHED STONE BASE TO FIRM GROUND OR COURSE AGGREGATE (8"THICK) NOTE: THE MANHOLE SHALL CONFIRM TO ASTM SPECIFICATION C-478 PRECAST CONCRETE MANHOLE DETAIL (SANITARY SEWER) NOT TO SCALE HTMUA DRAWING #11A STANDARD MANHOLE

26 S=1:1 CONSTRUCT NEW CHANNEL DIRECTED TOWARDS DOWNSTREAM PIPE SMOOTH CONCRETE CHANNEL A A FORCE MAIN GRAVITY SEWER PIPE MANHOLE RIM 2" ABOVE FINISHED GRADE OF TOPSOIL IN LAWN AREA OF FLUSH ON PAVEMENT AREA. 8" SECTION B - B 5-1/2" REINFORCED CONCRETE SLAB FRAME TO BE SET IN FULL BED OF MORTAR ADJUST TO GRADE WITH COARSES OF BRICK OR CONCRETE GRADING RINGS, (12" MAX.) PARGE INSIDE AND OUTSIDE OF BRICKS JOINT CAN BE SEALED USING BUTYL RUBBER OR D-LOK RUBBER GASKET DURA PLATE 100 P.V.C. LINER OR EQUAL 60" 5" DRILL 1" HOLE IN TOP OF WYE CONNECTION CAP END B C B WYE CONNECTION INSTALL STAINLESS STEEL BANDS FORCE MAIN PIPE 10" 90 ELBOW DIRECTED TOWARDS DOWNSTREAM PIPE 18" GRAVITY SEWER PIPE SECTION A - A CLASS "C" CONCRETE FILL AS NEEDED TO CONSTRUCT CHANNEL PVC LINED FORCE MAIN DISCHARGE MANHOLE NO SCALE HTMUA DRAWING #12 STANDARD DROP MANHOLE

27 STANDARD MANHOLE FRAME FRAME & COVER (SEE DETAIL) FINISHED GRADE FRAME TO BE BEDDED IN MORTAR ALUM. MANHOLE STEPS AT 12"O.C. 30" 36" ADJUST TO GRADE WITH SOLID BRICK AND MORTAR AS REQUIRED (3 COURSES MAX.) SEAL WATERTIGHT WITH TWO COATS OF ASPHALTIC PITCH 3 FT. PRECAST CONCRETE ECCENTRIC CONE FLEXIBLE WATERTIGHT RUBBER GASKET JOINT BACKFILL MATERIAL TWO (2) COATS MIN. BLACK BITUMASTIC WATERPROOFING 48" VARIES 5" 5" PRECAST REINF. CONCRETE MANHOLE RISERS AT 1',2' OR 3' LENGTHS AS REQUIRED STONE BEDDING FOR PIPE SOLID COLLAR 6" OR 12" HIGH STANDARD REINFORCED CONC. MANHOLE WITH EXTENDED BASE AND RUBBER GASKETS AT JOINTS 6"THICK (MIN) CLASS C CONCRETE FOUNDATION 6" 6"THICK WALLS (MIN.) U-SHAPED COLLAR 12", 24" OR 36" CONCRETE ENCASEMENT TO UNDISTURBED MATERIAL FIRM SUB-GRADE CRUSHED STONE BASE TO FIRM GROUND OR COURSE AGGREGATE (8"THICK) NOTE: THE MANHOLE SHALL CONFIRM TO ASTM SPECIFICATION C-478 PRECAST CONCRETE DROP MANHOLE DETAIL (SANITARY SEWER) NOT TO SCALE HTMUA DRAWING #12A STANDARD DROP MANHOLE

28 NOTE: MANHOLE CHUTE CONNECTION TO INCLUDE A DURA PLATE 100 P.V.C. LINER HTMUA DRAWING #13 MANHOLE CHUTE

29 HTMUA DRAWING #14 MANHOLE STUB AND HOUSE LATERAL DETAIL

30 HTMUA DRAWING #15 ALUMINUM STEP

31 HTMUA DRAWING #16 CONNECTION TO EXISTING MANHOLE

32 HTMUA DRAWING #17 DETAIL OF MANHOLE BARREL & FOUNDATION