1 210 WEST 27TH STREET

2

3 BUILDING DEPARTMENT NOTES (FILED UNDER NEW DECEMBER 31, 2014 NYC CODE) 1. THE OWNER SHALL ENGAGE THE SERVICES OF AN AGENCY APPROVED BY THE NYC DEPARTMENT OF BUILDINGS TO PERFORM ALL REQUIRED SPECIAL INSPECTIONS (BC 1704) AND PROGRESS INSPECTIONS (BC 110). SPECIAL AND PROGRESS INSPECTIONS SHALL BE PAID FOR BY THE OWNER. THE FOLLOWING ITEMS REQUIRE SPECIAL INSPECTION (CODE REFERENCES ARE TO THE DECEMBER 31, 2014 CODE): MECHANICAL SYSTEMS BC FIRESTOP, DRAFTSTOP AND FIREBLOCK SYSTEMS BC ENERGY CODE COMPLIANCE INSPECTIONS BC FINAL AND BC AND DIRECTIVE 14 OF 1975 THE FOLLOWING ITEMS REQUIRE PROGRESS INSPECTIONS: ENERGY CODE COMPLIANCE BC FINAL INSPECTION AND BC UPON COMPLETION OF THE WORK, A TEST SHALL BE CONDUCTED IN THE PRESENCE AND UNDER DIRECTION OF A LICENSED PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT, RETAINED BY THE CONTRACTOR QUALIFIED TO CONDUCT SUCH TESTS. THE TEST SHALL SHOW COMPLIANCE WITH THE CODE REQUIREMENTS FOR VENTILATION AND THE PROPER FUNCTIONING OF ALL OPERATING DEVICES, BEFORE THE SYSTEM IS APPROVED (BC 1704). 3. ALL INSPECTIONS AND TESTS WILL BE MADE IN COMPLIANCE WITH BC CERTIFICATES OF COMPLIANCE (BC AND ) SHALL BE OBTAINED AND PAID FOR BY THE CONTRACTOR. 5. ALL HVAC SYSTEMS AND EQUIPMENT COMPLY WITH THE REQUIREMENTS OF THE ENERGY CONSERVATION CONSTRUCTION CODE OF THE STATE OF NEW YORK (MC 301.2). 6. THE FOLLOWING WORK ITEMS, COMPONENTS, MATERIALS, CAPACITIES, ETC. SHALL COMPLY WITH THE FOLLOWING CODE REFERENCES: WORK ITEM/MATERIALS CODE SECTION A. ELECTRIC WIRING & EQUIPMENT -MC B. CONTROLS MC 405 C. NOISE CRITERIA LEVELS BC 1207 D. PIPING INSULATION MC 1204 E. SAFETY CODE FOR MECHANICAL REFRIGERATION MC 1101 THRU 1109 F. FIELD TEST PROCEDURES FOR MECHANICAL LIQUID CHILLING UNITS MC EQUIPMENT SHALL BE LISTED AND APPROVED AS REQUIRED - MC 107, MC ALL BUILDING DEPARTMENT FORMS REQUIRED, INCLUDING THOSE REQUIRED FOR SPECIAL INSPECTIONS, PROGRESS INSPECTIONS, CERTIFICATE OF COMPLIANCE, SERVICE EQUIPMENT PERMIT OR OTHER REASONS WITH REGARD TO THIS PROJECT SHALL BE COMPLETED AND FILED WITH THE NYC BUILDING DEPARTMENT BY THE OWNER. THE OWNER SHALL ENGAGE THE SERVICES OF A NYS LICENSED PROFESSIONAL ENGINEER AND AGENCIES APPROVED FOR SPECIAL INSPECTIONS TO SIGN AND SEAL ALL REQUIRED BUILDING DEPARTMENT FORMS AND DRAWINGS. 1. DEMOLITION OF HVAC ITEMS SHALL BE PERFORMED BY AN HVAC CONTRACTOR. 2. LOCATION OF THE EXISTING PIPING AS SHOWN ON DRAWINGS IS APPROXIMATE. 3. PROVIDE TEMPORARY SUPPORTS WHERE REQUIRED 4. DURING DEMOLITION, PROPERLY CAP AND PROTECT ALL EQUIPMENT, AND PIPING THAT WILL REMAIN IN OPERATION. 5. WHERE EXISTING INSULATION TO REMAIN IS DAMAGED BY THE REQUIREMENTS OF THE WORK, REPLACE ANY DAMAGED INSULATION TO MATCH EXISTING. 6. DEMOLITION WORK SHALL BE PERFORMED BY WORKMEN EXPERIENCED IN THIS TYPE OF WORK AND SHALL BE CARRIED THROUGH TO COMPLETION WITH DUE REGARD TO THE SAFETY OF ALL BUILDING OCCUPANTS AND THE EMPLOYEES OF THE CONTRACTOR, WITH AS LITTLE DISTURBANCE AS POSSIBLE. 7. DEMOLISH ALL EQUIPMENT AS INDICATED, FIXTURES AND/OR MISCELLANEOUS ARTICLES IN THEIR ENTIRETY INCLUDING AUXILIARY EQUIPMENT, PIPING, WIRING, AND CONDUIT. 8. MATERIALS RESULTING FROM THE DEMOLITION OPERATIONS SHALL NOT BE ALLOWED TO ACCUMULATE ON THE FLOORS AND ROOF SURFACES, EXTERIOR GRADE SURFACES OR OTHER PARTS OF THE PREMISES, AND SHALL BE PROMPTLY REMOVED AND DISPOSED OF AWAY FROM THE PREMISES. 9. INCLUDE ALL DEMOLITION OF SYSTEMS AND COMPONENTS WHERE SYSTEMS SHALL BE REPLACED BY NEW WORK. REFER TO THE DRAWINGS AND SPECIFICATIONS FOR THE SCOPE OF NEW AND RECONNECTED WORK. THE INTENT OF THIS REQUIREMENT IS TO HAVE THE CONTRACTOR DISCONNECT, DEMOLISH AND REMOVE ALL EXPOSED AND CONCEALED WORK WHERE BEING REPLACED OR CONNECTED TO THE NEW LAYOUTS. 10. COORDINATE ELECTRICAL POWER DISCONNECTION PRIOR TO DEMOLITION. POWER DISCONNECTION SHALL BE PROVIDED BY A ELECTRICAL CONTRACTOR. 11. PROTECT ALL EXISTING HVAC WORK AND EXISTING WORK OF OTHER TRADES WHICH IS TO REMAIN, FROM DAMAGE DURING DEMOLITION. 12. ALL PIPING TO REMAIN SHALL HAVE ENDS TERMINATED IN A NEAT MANNER READY FOR CONNECTION OF NEW WORK. ALL EXPOSED ENDS OF PIPING SHALL BE CAPPED. SCREWED PIPING SHALL END ON A SCREWED JOINT. FLANGED PIPE SHALL END WITH A FLANGED JOINT. WELDED PIPING SHALL BE MECHANICALLY CUT, CLEANED OF BURRS AND A CAP TACK WELDED TO THE PIPE. 13. REMOVAL OF EQUIPMENT AND PIPING SHALL INCLUDE ALL HANGERS & SUPPORT ASSOCIATED WITH THE EQUIPMENT AND PIPING TO BE REMOVED. 9. CONTRACTOR SHALL OBTAIN AND PROVIDE SERVICE EQUIPMENT PERMITS IN ACCORDANCE WITH SECTION OF THE BUILDING CODE. SERVICE EQUPMENT PERMITS SHALL BE REQUIRED FOR THE USE AND OPERATION OF THE FOLLOWING SERVICE EQUIPMENT. a. COOLING TOWER b. CHILLER

4 FIRE PUMP FLASH TANK HOT WATER STORAGE TANK FIRE PUMP FLASH TANK CHILLER CONTROL PANEL, DISPLAY PANEL & STARTER PANEL. EYEWASH STATION AHU ON DUNNAGE 4'-8" AFF CHWS/R UP 4" CHWR DN CWS/R 8" UP CONDENSER WATER PUMPS AHU ON DUNNAGE 4'-8" AFF CAP 2" 2" CWP-1 CWP-2 4" CHWR DN 2" Ø TO FLOOR DRAIN CONDENSER WATER CHEMICAL TREATMENT 3DT ANALYZER PANEL CONDENSER WATER CHEMICAL TREATMENT DUAL FEEDER CONDENSER WATER CHEMICAL TREATMENT DUAL DISPENSER H/CHWS DN H/CHWS DN STEAM CONDENSATE RETURN TANK AND PUMP SET 4" STEAM CONDENSATE RETURN TANK AND PUMP SET 6" 4" SAND FILTER 2" Ø (35 GPM BACKWASH) TO DRAIN TANK 150 GAL BACKWASH DRAIN TANK STEAM TO WATER HEAT EXCHANGER P-2 P-1 AIR COMPRESSOR CHEMICAL FEEDER STEAM TO WATER HEAT EXCHANGER CHWS/R 6" UP P-1 P-2 AIR COMPRESSOR CHEMICAL FEEDER EXPANSION TANKS HOT/CHILLED WATER PUMPS HOT/CHILLED WATER PUMPS EXPANSION TANKS CAP CHW S/R UP CHW S/R UP ABANDONED CHWR DN CHWR DN 6"Ø LPS 6"Ø LPS AHU ON DUNNAGE 4'-8" AFF AHU ON DUNNAGE 4'-8" AFF 6"Ø LPS DN 6"Ø LPS DN CAP CAP STEAM TO WATER HEAT EXCHANGER STEAM CONTROL VALVE STEAM CONDENSATE RETURN TANK AND PUMP SET STEAM CONDENSATE RETURN TANK AND PUMP SET LPS TO DWH LPS TO DWH

5 TE-2 KE-3 TE-5 TE-6 TE-2 KE-3 TE-5 TE-6 KE-4 KE-4 CHWS/R DN CWS/R 8" DN 3'-6" ABOVE ROOF CH-1 WATER COOLED CHILLER W/ENCLOSURE 28,000 LBS C-2 AIR COOLED WATER CHILLER 8,668 LBS C-1 AIR COOLED WATER CHILLER 8,668 LBS SWITCHES CHWS/R 6" DN TRANSFORMER 1825 lbs. CT-1 COOLING TOWER 10,020 LBS SWITCHES CAP CHW S/R DN

6 PRESSURE GAUGE WITH GAUGE CLOCK rev. no. date revisions AQUASTAT THERMOMETER A FS AIR COOLED WATER CHILLER CH-2 AIR COOLED WATER CHILLER CH-1 FS A DRAIN VALVE ROOF HE-2 CONVERTOR 3" TO AHU COOLING COIL 3" 4" TO EXPANSION TANK FROM FAN COIL UNITS FROM AHU COOLING COIL TO FAN COIL UNITS INERTIA BASE HOUSEKEEPING PAD MECHANICAL PENTHOUSE FLOOR P-2 STAND BY PUMP P-1 HOT/CHILLED WATER PUMP NTS 8"Ø CWR CH-1 EVAPORATOR CT-1 CONDENSER 6"Ø CHWS&R ROOF 8"Ø CWS 2" DRAIN 3" OVERFLOW DUNNAGE ROOF WATER METER 1" MAKE-UP WATER LINE BY PLBG. 8"Ø CWS&R 6"Ø CHWR 6"Ø 6"Ø 6"Ø FLOW SENSOR COOLING/HEATING MODE DIVERTING VALVE 3" 6"Ø 6"Ø TO AHU COOLING COIL CAP TO FAN COIL UNITS D 1 1/4"Ø FLOW SENSOR 3" D HE-2 CONVERTOR 1 1/4"Ø D D RELIEF VALVE HE-1 CONVERTOR 6"Ø 6"Ø 6"Ø 6"Ø 3" 4" HOUSEKEEPING PAD TO EXPANSION TANK FROM FAN COIL UNITS FROM AHU COOLING COIL 8"Ø 8"Ø 8"Ø 8"Ø 2" D 1 1/4"Ø 6"Ø 6"Ø MECHANICAL PENTHOUSE FLOOR 2" FD FD FD FOR PUMPS PIPING HOOK-UP REFER TO DETAILS ON M-401 P-2 HOT/CHILLED WATER PUMP P-1 HOT/CHILLED WATER PUMP FOR PUMPS PIPING HOOK-UP REFER TO DETAILS ON M-401 CWP-1 HOUSEKEEPING PAD CWP-2 PEP WATER FILTRATION SYSTEM, HMF2-18SS FD 150 GAL BACKWASH DRAIN TANK NTS

7

8

9

10 NOTE: COOLING TOWER AND CHILLER AND ASSOCIATED PIPING INCLUDING MAKE-UP WATER SHALL BE DRAINED FOR HEATING SEASON. rev. no. date revisions NOTES: PROVIDE: 1. FAN MOTOR VFD AND CONTROLS. 2. STEEL DUNNAGE AS SHOWN ON STRUCTURAL DRAWING. 3. ISOLATION RAILS STAINLESS STEEL COLD WATER BASIN. 5. WHISPER QUIET FAN. 6. INTERNAL LADDER. 7. CHEMICAL TREATMENT WATER SYSTEM. NOTES: 1. PROVIDE MOTOR STARTERS & DISCONNECT SWITCHES FOR CWP-1,2 AND VFD PER P-1,P PROVIDE PUMP SEQUENCER FOR EACH PAIR OF PUMPS. 3. PROVIDE INERTIA BASE. 4. PROVIDE PIPING HOOK-UP AS PER DETAILS. PROVIDE: 1. REMOTE MOUNTED CONTROL PANEL, DISPLAY PANEL, STARTER PANEL WITH VFDs. 2. STEEL DUNNAGE AS SHOWN ON STRUCTURAL DRAWING. 3. WEATHERPROOF ENCLOSURE BY CHILLER MANUFACTURER. 4. SINGLE POINT POWER CONNECTION. 5. MICROTECH II INTERFACE AND COMMUNICATION WITH EXISTING BAS SYSTEM. 6. EVAPORATOR AND CONDENSER WATER PIPING CONNECTION FOR VICTAULIC COUPLING. 7. EVAPORATOR AND CONDENSER WATER PIPING CONNECTION AT OPPOSITE SIDES WITH NEW HEAD GASKETS. RELOCATE CONTROL SENSORS. 8. CLEANABLE 20-MESH WATER STRAINER IN BOTH VESSELS WATER INLET LINES. 9. FACTORY INSTALLED AND WIRED THERMAL-TYPE FLOW SWITCHES. NOTES: 1. ONE IS STAND -BY. 2. PIPING HOOK-UP AS PER DETAILS AND DIAGRAMS. 3. PROVIDE 2 PASS "K" HEAD. 4. UNIONS FOR PIPING CONNECTION. 5. HANG FROM BUILDING STRUCTURE.

11

12

13 PLUMBING FIXTURE CONNECTION SCHEDULE 1. ALL PLUMBING FIXTURES TO BE REMOVED SHALL BE TURNED OVER TO THE OWNER. THEY SHALL NOT BE REMOVED FROM THE PREMISES OR DISPOSED OF WITHOUT THE OWNER'S APPROVAL. 2. ALL PIPING TO BE REMOVED SHALL BE PROPERLY PLUGGED OR CAPPED SO THAT UPON COMPLETION OF ALL NEW WORK, ALL ABANDONED PIPING SHALL BE CONCEALED IN FINISHED AREAS. 3. NO DEAD ENDS SHALL BE LEFT ON ANY PIPING UPON COMPLETION OF THE PROJECT. 4. EXISTING EXPOSED PIPING NOT TO BE REUSED AND NOT SPECIFICALLY NOTED OR SHOWN ON DRAWINGS TO BE ABANDONED SHALL BE COMPLETELY REMOVED. 5. THE EXISTING SYSTEMS SHALL BE LEFT IN PERFECT WORKING ORDER UPON COMPLETION OF ALL NEW WORK. 6. LOCATIONS AND SIZES OF EXISTING PIPING ARE APPROXIMATE. EXACT SIZES AND LOCATIONS OF ALL EXISTING PIPING SHALL BE VERIFIED AT THE SITE. 7. NO REMOVED EXISTING PIPING, EQUIPMENT, ETC. SHALL BE REUSED. 8. ALL EXISTING EXPOSED, UNNECESSARY PIPING RELATED TO WORK BEING DONE SHALL BE COMPLETELY REMOVED. 9. THIS CONTRACTOR SHALL NOT INTERRUPT ANY OF THE SERVICES OF THE EXISTING FACILITY, NOR INTERFERE WITH THE SERVICES IN ANY WAY WITHOUT PRIOR POSTED NOTICE OF AT LEAST THE EXPRESS PERMISSION OF THE OWNER IN WRITING. 72 HOURS & SUCH INTERRUPTIONS AND INTERFERENCES SHALL BE COORDINATED WITH THE GENERAL MADE AS BRIEF AS POSSIBLE AND ONLY AT THE TIME CONTRACTOR, OWNER & RESIDENTS & STATED BY THE OWNER, THE BUILDING IS TO REMAIN OPERATIONAL THROUGHOUT CONSTRUCTION. 10. UNDER NO CIRCUMSTANCES SHALL THIS CONTRACTOR OR HIS WORKMEN BE PERMITTED TO USE ANY PART OF THE BUILDING AS A SHOP, EXCEPT PARTS DESIGNATED BY THE OWNER FOR SUCH PURPOSES. 11. REROUTE OR REMOVE ALL EXISTING PIPING WHERE NECESSARY TO AVOID NEW EQUIPMENT, STRUCTURAL, MASONRY OR CARPENTRY WORK AS REQUIRED BY THE PROPOSED ALTERATION. 1. ALL MATERIALS AND APPARATUS SHALL BE INSTALLED IN ACCORDANCE WITH ALL THE RULES AND REGULATIONS OF THE NEW YORK CITY BUILDING CODE AND ALL OTHER AUTHORITIES HAVING JURISDICTION. 2. THIS CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER TRADE AND ALL EXISTING CONDITIONS, AND PROVIDE OFFSETS IN PIPING SYSTEMS TO AVOID STRUCTURAL, ARCHITECTURAL, MECHANICAL AND ELECTRICAL INTERFERENCES, WHETHER INDICATED OR NOT. ALL PLUMBING WORK SHALL MEET THE REQUIREMENTS OF THE NEW YORK CITY BUILDING CODE. 1. PROTECTION OF PIPING AS OUTLINED IN PC 305 SHALL BE PROVIDED AS REQUIRED. 2. ALL PIPING AND MATERIALS SHALL BE AS DIRECTED IN PC PIPING JOINTS AND CONNECTIONS SHALL BE AS APPROVED IN PC 605, PC 705, PC 804 AND PC CONSTRUCTION, QUANTITIES, DEVICES, FIXTURES, FAUCETS, VALVES AND FACILITIES FOR THE DISABLED SHALL BE AS OUTLINED IN PC TRAPS AND CLEANOUTS SHALL BE AS PER PC CONSTRUCTION AND SPACING OF HANGERS AND SUPPORTS SHALL BE AS DIRECTED IN PC WATER SUPPLY SYSTEM, VALVES, TESTS SHALL BE AS DIRECTED IN CHAPTER SANITARY DRAINAGE PIPING, SIZING, GRADING AND OFFSETS SHALL BE AS OUTLINED IN CHAPTER VENT SIZING, GRADING, CONNECTIONS, LOCATIONS AND OFFSETS SHALL BE AS DIRECTED IN CHAPTER STORM DRAINAGE PIPING AND SIZING SHALL BE IN ACCORDANCE WITH CHAPTER SPECIAL AND MISCELLANEOUS PIPING SHALL BE AS DIRECTED IN PC INDIRECT WASTE PIPING SHALL BE AS DIRECTED IN CHAPTER ALL PLUMBING FIXTURES SHALL COMPLY WITH LOCAL LAW 29/89 - LOW FLOW FIXTURES. 14. THE OWNER SHALL ENGAGE THE SERVICES OF AN AGENCY APPROVED BY THE NYC DEPARTMENT OF BUILDINGS TO PERFORM ALL REQUIRED SPECIAL INSPECTIONS (BC 1704) AND PROGRESS INSPECTIONS (BC 110.3). SPECIAL INSPECTION (CODE REFERENCES ARE TO THE DECEMBER 31, 2014 CODE): PLUMBING PIPING SCHEDULE PLUMBING PIPE FITTINGS SCHEDULE SYMBOL DESCRIPTION rev. no. date revisions 3. CONNECTION OF NEW WORK TO EXISTING WORK SHALL BE PERFORMED IN A DISTURBED TO NEAT AND APPROVED MANNER, RESTORING EXISTING WORK ORIGINAL CONDITION. 4. EXISTING PIPING DAMAGED AS A RESULT OF PERFORMING THIS WORK OF THIS CONTRACT SHALL BE REPAIRED OR REPLACED AS REQUIRED WITH MATERIAL AND FINISH TO MATCH NEW. 5. EXISTING RISER & STACK LOCATIONS ARE BASED UPON ORIGINAL CONSTRUCTION DOCUMENTS. EXACT RISER & STACK LOCATIONS ARE TO BE VERIFIED IN THE FIELD. 6. WATER SUPPLY CONNECTION TO PLUMBING FIXTURES AND EQUIPMENT SHALL HAVE OVER-RIM WATER SUPPLIES WHEREVER POSSIBLE OR SHALL BE PROVIDED WITH APPROVED VACUUM BREAKERS AND/OR CHECK VALVES OR BACKFLOW PREVENTERS. SPRAYED FIRE-RESISTANT MATERIALS - BC FIRE-RESISTANT PENETRATIONS AND JOINTS BC SEISMIC ISOLATION SYSTEMS - BC ENERGY CODE COMPLIANCE INSPECTIONS - BC FINAL AND BC AND DIRECTIVE 14 OF 1975 THE FOLLOWING ITEMS REQUIRE PROGRESS INSPECTIONS: ENERGY CODE COMPLIANCE - BC FIRE RESISTANT RATED CONSTRUCTION - BC FINAL INSPECTION AND BC ALL INSPECTIONS AND TESTS WILL BE MADE IN COMPLIANCE WITH BC PROTECTION OF POTABLE WATER SYSTEM PER SECTION PC 608 FIXTURE DESIGNATION MODEL NO. MANUFACTURER (OR EQUAL) DESCRIPTION WATER METER ROOF 1" MAKE-UP WATER LINE BY PLBG. RPZ RPZ MECHANICAL PENTHOUSE FL 17TH FL. DOMESTIC WATER RISER DIAGRAM NO SCALE SANITARY RISER DIAGRAM NO SCALE

14 FIRE PUMP FLASH TANK CHILLER CONTROL PANEL, DISPLAY PANEL & STARTER PANEL. EYEWASH STATION 1/2" CONDENSER WATER PUMPS AHU ON DUNNAGE 4'-8" AFF RPZ EX 1" 1/2" RPZ EX 3" FD S RPZ 3/8" P-1 1-1/2" CONDENSER WATER CHEMICAL TREATMENT 3DT ANALYZER PANEL CONDENSER WATER CHEMICAL TREATMENT DUAL DISPENSER EX SAND FILTER 1" 1/2" EX EX CONDENSER WATER CHEMICAL TREATMENT DUAL FEEDER DRAINAGE POINT FOR 1" CW MAKE-UP PIPE FOR COOLING TOWER. SHUT OFF VALVE ON VERTICAL PIPE. PIPING WILL BE DRAINED DURING HEATING SEASON. SEE DWG M200 FOR DETAILS 1" UP TO COOLING TOWER 2-1/2" CHWS/R 6" UP 1/2" CH-1 WATER COOLED CHILLER W/ENCLOSURE 28,000 LBS EX TO EX DOMESTIC WATER HEATER CHWS/R 6" DN TRANSFORMER 1825 lbs. CT-1 COOLING TOWER 10,020 LBS SWITCHES 1" CW TO COOLING TOWER CAP

15

16 FB

17 CHILLER CONTROL PANEL, DISPLAY PANEL & STARTER PANEL PRP, #3 3#12, 3/4"C J DP-RH VFD VFD VFD CONDENSER WATER PUMPS CWP-1 CWP-2 #1 #7 #13 PRP, #5 3#12, 3/4"C CONDENSER WATER CHEMICAL TREATMENT #2 #8 SAND FILTER PRP PRP P-2 P-1 P-1 P-2 HOT/CHILLED WATER PUMPS HOT/CHILLED WATER PUMPS

18 2 SETS OF 4-400KCMIL IN 2-4" CONDUITS DOWN TO DP-RH 3 #3/0 IN 2"C 3 #8 IN 1"C CH-1 WATER COOLED CHILLER W/ENCLOSURE 28,000 LBS C-2 AIR COOLED WATER CHILLER 8,668 LBS SWITCHES 4 SETS OF 600KCMIL IN 4-4"C C-1 AIR COOLED WATER CHILLER 8,668 LBS PRP, #1 3#12, 3/4"C WP, 3P/600/500 FB WP,GFI TRANSFORMER CT-1 COOLING TOWER 10,020 LBS 3P/60/NF

19

20

21 sim. 4 4

22 3 200

23