FIRESTOP SUBMITTAL PACKAGE

Size: px
Start display at page:

Download "FIRESTOP SUBMITTAL PACKAGE"

Transcription

1 FIRESTOP SUBMITTAL PACKAGE PLUMBING Materials FS-ONE Intumesent Caulk Includes: Technical and Installation Data UL Certificate of Compliance LEED information MSDS UL Details Concrete Assemblies C-AJ Max. 30" steel, cast iron, Max 6" copper (optional sleeve) C-AJ Max. 12" steel, max. 6" copper with 2" glass fiber or Max. 2" calcium silicate C-BJ Max. 4" steel, copper pipe or copper tubing with 1" AB/PVC pipe Insulation Gypsum Wall Assemblies W-L Max. 30" steel, cast iron, Max. 6" copper W-L Multiple steel pipe, Max 4", 0 to 1" annular space - one row W-L Max. 3" steel pipe, steel conduit or EMT (membrane penetration) W-L Max. 1" PEX, Max. 1-1/2 PVC pipe, PVC conduit, CPVC in same hole, Max. diameter Hole 4" W-L Max. 2" Blasemaster CPVC, Max. 2" Flowgaurd Gold W-L Max. 4" steel, Max. 2" copper with 3/4" AB/PVC insulation Wood Floor Assemblies F-C Max. 4" steel, cast iron, copper(chase wall required) F-C Max. 6" steel, cast iron, steel conduit, (Chase wall optional) F-C Max 1-1/2" PVC or ABS drain fittings with bathtub waste/overflow Fittings F-C Max. 2" Blasemaster CPVC, Max. 2" Flowgaurd Gold F-C Max. 1", Max 3 each in same hole crosslinked polyethylene (PEX) SDR 9 tube closed/vented piping F-C Max. 2" steel, copper with 1/2" glass fiber or 3/4" AB/PVC insulation (Chase wall required) Hilti, Inc., 5400 South 122 nd East Avenue, Tulsa, OK 74121, (800)

2 Firestop System Firestop System Product Information Chapter Tabs Chapter Tabs Chapter Tabs Chapter Tabs Chapter Tabs FS-ONE High Performance Intumescent Firestop Sealant Product description Intumescent (expands when exposed to fire) firestop sealant that helps protect combustible and non-combustible penetrations for up to 4 hours fire rating Product features Smoke, gas and water resistant after material has cured Contains no halogen, solvents or asbestos High fire rating properties Water based, easy to clean Protects most typical firestop penetration applications Can be painted Single component systems available Meets LEED requirements for indoor environmental quality credit 4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paints and Coatings Areas of application Steel, copper and EMT pipes Insulated steel and copper pipes Cable bundles Closed or vented plastic pipes HVAC penetrations For use with Concrete, masonry, drywall and wood floor assemblies Wall and floor assemblies rated up to 4 hours Examples Sealing around plastic pipe penetrations in fire rated construction Sealing around combustible and non-combustible penetrations in fire rated construction Installation instructions for FS-ONE Notice Before handling, read Material Safety DataSheet and product label for safe usage and health information. Instructions below are general guidelines always refer to the applicable drawing in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information Opening 1. Clean the opening. Surfaces to which FS-ONE will be applied should be cleaned of loose debris, dirt, oil, moisture, frost and wax. Structures supporting penetrating items must be installed in compliance with local building and electrical standards. Application of firestop sealant 2. Install the prescribed backfilling material type and depth to obtain the desired rating (if required). Leave sufficient depth for applying FS-ONE. 3. Application of firestop sealant: Apply FS-ONE to the required depth in order to obtain the desired fire rating. Make sure FS-ONE contacts all surfaces to provide maximum adhesion. For application of FS-ONE use a standard caulking gun, foil pack gun, bulk loader and bulk gun. With FS-ONE buckets, Graco type sealant pumps may be used. (Contact pump manufacturer for proper selection). 4. Smoothing of firestop sealant: To complete the seal, tool immediately to give a smooth appearance. Excess sealant, prior to curing, can be cleaned away from adjacent surfaces and tools with water. 5. Leave completed seal undisturbed for 48 hours. 6. For maintenance reasons, a penetration seal could be permanently marked with an identification plate. In such a case, mark the identification plate and fasten it in a visible position next to the seal. Not for use High movement expansion joints Underwater CABLE PIPE 1. Clean opening. 2. Pack mineral wool. (If required) tlke0 9^)&(/R 84tc )v 6453 sodfm,ev ijdjfiwhriuh. NöoWE Z8Z23awöp3i4eß0288u27 uze 4i5kirdwiloi4jtf-öx-.vbvbvh, ireiv u9+ß12oeoo FS-ONE Technical Data Chemical basis Water-based intumescent acrylic dispersion Color Red Application temperature 40 F to 104 F (5 C to 40 C) Skin forming time Approx min. Curing time Approx. 2 mm / 3 days Movement capability Approx. 5% Expansion rate Up to 3-5 times (unrestricted): original volume Temperature resistance (cured) 40 F to 212 F ( 40 C to 100 C) Surface burning characteristics Flame Spread: 0 (ASTM E 84-96) Smoke Development: 5 Sound transmission classification 56 (Relates to specific construction) (ASTM E 90-99) Approvals California State Fire Marshal Listing No :108 City of New York MEA M Vol. IV Tested in accordance with UL 1479 ASTM E 814 ASTM E 84 At 73 F (23 C) and 50% relative humidity FILL, VOID OR CAVITY MATERIAL FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY 66Y7 3. Apply FS-ONE. 4. Smooth FS-ONE. FM APPROVED On materials where oil, plasticizers or solvents may bleed i.e. impregnated wood, oil based seals, green or partially vulcanized rubber In any penetration other than those specifically described in this manual or the test reports Storage Store only in the original packaging in a location protected from moisture at temperatures between 40 F (5 C) and 86 F (30 C) Observe expiration date on the packaging 5. Leave completed seal undisturbed for 48 hours. Firestop System 6. Fasten identification plate (if required). 1. Clean opening. 2. Pack mineral wool. (If required) 3. Apply FS-ONE. 4. Smooth FS-ONE. 5. Leave completed seal undisturbed for 48 hours. 6. Fasten identification plate (if required). Hilti. Outperform. Outlast. Hilti, Inc. (U.S.) en español Hilti Firestop Systems Guide 2007

3

4

5

6 February 24, 2009 To Whom It May Concern: Re: Hilti FS-ONE Intumescent Firestop LEED Info. The Hilti FS-ONE Intumescent Firestop is manufactured in Kaufering, Germany. The FS-ONE pail is made of polyethylene and can be completely recycled. There is no postconsumer or post-industrial content in FS-ONE and it cannot be recycled. The VOC content for FS-ONE is 75 grams/liter. FS-ONE is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) if you have questions. Sincerely, Jerry Metcalf MPH, CHMM Safety/Environmental Manager Hilti Inc (918) jerry.metcalf@hilti.com Rev. Date: 2/24/09 Hilti, Inc South 122 nd East Avenue Tulsa, OK

7 February 24, 2009 To Whom It May Concern: Re: Hilti Mineral Wool-LEED Info. The Hilti Mineral Wool is manufactured in Waubash Indiana. There is no post-consumer or post-industrial content in Hilti Mineral Wool. There is no detectable VOC content in this product. Hilti Mineral Wool is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) if you have questions. Sincerely, Jerry Metcalf MPH, CHMM Safety/Environmental Manager Hilti Inc jerry.metcalf@hilti.com Rev. Date: 2/24/09 Hilti, Inc South 122 nd East Avenue Tulsa, OK

8 Submittal Sheet Description THERMAFIBER Safing Insulation UL- and OPL-labeled* safing insulation for firestops and fire-containment systems Firestop product for curtain wall fire and smoke containment systems, floor and wall penetrations, head-of-wall, and other construction joint systems. Fire resistant and noncombustible. Economical; installs quickly and easily. Aids sound control in many assemblies. Available in unfaced felt (plain) or with a tough scrim-reinforced foil facing (FSP). Durable; nondeteriorating and noncorrosive. THERMAFIBER Safing Insulation is a mineral-wool-type insulation that resists temperatures up to 2,000 F (1,093 C), thus offering superior fire protection in a wide variety of fire-rated applications. It is a UL- and OPL-labeled product especially intended for tested UL and OPL Designs, as well as many other fire- and smoke-tested assemblies. This product is noncombustible per Standard NFPA 220 when tested in accordance with ASTM E 136, and moisture-resistant, noncorrosive, nondeteriorating, mildew-proof and vermin-proof. It permits dry construction for all-year-round work. Also, THERMAFIBER Safing Insulation is available plain, or with scrim-reinforced foil facing (FSP) that serves as a vapor retarder and/or smoke barrier. THERMAFIBER Safing Insulation is compatible with both THERMAFIBER Curtain Wall CW Insulations and THERMAFIBER FIRESPAN Insulations. Perimeter Fire Containment, Penetrations and Construction Joints THERMAFIBER Safing Insulation is a key element in a wide variety of fire-tested construction assemblies. It is used with THERMAFIBER Curtain Wall and FIRESPAN Insulations in applications to contain both fire and smoke to the area of origin. Especially for mid- and high-rise buildings, where fire and smoke must be prevented from spreading to the next floor. Since the floor assembly is typically fire-rated, one route for the fire spread is through and up the exterior curtain wall system. THERMAFIBER Safing Insulation is also used in conjunction with various sealants and caulks, in wall and floor penetration (poke-through) applications, head-of-wall construction joints, and other construction joints. Installation Perimeter Installation It is important to note that one of the most valuable yet misunderstood applications of THERMAFIBER Safing Insulation is its use in exterior curtain wall assemblies to safe-off the opening between concrete floor slabs and the curtain wall assemblies. Many people still believe the myth that all thermal insulations are the same when used in the curtain wall spandrel panels as long as THERMAFIBER Safing Insulation is used in the assembly. This is simply not true. Actual fire tests have proven that low-melt-point insulations, such as glass fiber types, will disintegrate quickly once exposed to fire, leaving the curtain wall unprotected. Then, as the now-unprotected curtain wall disintegrates or falls away, the safing insulation will no longer be supported, and the fire will spread to the floor(s) above. Effective perimeter fire containment can only be achieved when a fire-compatible product with the ability to resist high temperatures (such as THERMAFIBER Curtain Wall Insulations or THERMAFIBER FIRESPAN Insulations) is used in conjunction with the THERMAFIBER Safing Insulation, acting together as a system. (See TF685, TF686 and TF871 for additional information). In curtain wall fire-containment applications, THERMAFIBER Safing Insulation fills the void between the slab edge and the curtain wall insulation to contain fire. Foil-faced insulation impedes the passage of smoke and noxious gases. Install THERMAFIBER Safing Insulation, of proper width (2" to 8" max. opening), compression fit in safe-off area (foil side up, if required) between THERMAFIBER FIRESPAN or CW Curtain Wall Insulation and floor slabs, on safing "Z" clips spaced as required in the design (24" or 12" o.c. maximum), leaving no voids. Compression fitting the safing insulation is critical to assuring a tight seal. See specific test description for proper installation details. Install proper topping material, such as THERMAFIBER SMOKE SEAL Compound, or other approved smoke sealants as indicated in the specific test description or architectural specification. Penetration Application Construction Joint Application THERMAFIBER Safing Insulation provides a noncombustible, fire-resistant forming/packing material for many types of penetrations in walls and floor/ceilings. In all poke-through penetrations, clean substrate of dirt, dust, grease, oil, efflorescence, loose material or other matter. With a serrated knife, cut THERMAFIBER Safing Insulation slightly wider than the opening. Compress and tightly fit the minimum thickness and density of insulation required (per system specification) completely around penetrant. For floor slab openings, compress or install THERMAFIBER Safing Insulation according to details indicated in the specific test description or architectural specification to seal completely around cables, ducts, piping or other utilities. THERMAFIBER Safing Insulation is also used as a forming material in head-of-wall, floor to floor, floor to wall, and wall to wall construction joints. It is compressed and slid into joint openings to completely fill the gap between the intersection of the walls, floor, etc. * UL is an abbreviation for Underwriters Laboratories Inc.; OPL is an abbreviation for Omega Point Laboratories, Inc.

9 Technical Data Surface Burning Characteristics (According to ASTM E 84) Product Designation Flame Spread Smoke Developed Safing, Regular (Unfaced) 0 0 Safing (Foil-Faced) 25 0 Products have a class A interior finish rating per NFPA 101, life safety code. Product Density Product Actual Density Minimum Application Designation Density Tolerance-pcf (1) Thickness Method Safing " safing clips and/or compression fit Safing /2" safing clips and/or compression fit Safing " safing clips and/or compression fit (1) On packaging weight basis. For the most up-to-date technical data, please refer to our website at Product Data Submittal Approvals: Standards Compliance Composition and Materials Warranty Storage Job Name Contractor Trademarks THERMAFIBER, FIRESPAN and THE NAME IN MINERAL WOOL are trademarks of Thermafiber Inc. SMOKE SEAL is a trademark of United States Gypsum Company. THERMAFIBER Safing Insulation meets the following: ASTM C Federal Specification HH-I-521F Safing insulation as Types I and III, Class A, Category 1. ASTM C Federal Specification HH-I-558B Safing insulation as Types IA, IB and II. ASTM E Rated noncombustible as defined by NFPA Standard 220 when tested according to ASTM E 136. ASTM E 814 or UL Safing insulation used in conjunction with SMOKE SEAL Compound, or other approved material in through - penetration firestop systems. UL Safing insulation used in conjunction with various sealants and caulks in construction joint systems. ASTM C THERMAFIBER Insulations absorb less than 1% moisture by weight and volume. Safing insulation products are approved by: New York City Board of Standards & Appeals SM & MEA M, Vol. II. THERMAFIBER blankets are a mineral fiber material manufactured from blast furnace slag, a by-product of iron ore reduction, and naturally occurring rock. THERMAFIBER blankets contain greater than 80% postindustrial recycle content. This product contains No Asbestos. System performance following substitution of materials or compromise in assembly design cannot be certified and may result in failure of fire performance under certain conditions. Products and systems provided by Thermafiber Inc. are warranted to be free from defects in material workmanship. Contact Thermafiber Inc. for complete warranty details. Store in a cool, dry place. Note Products described here may not be available in all geographic markets. Consult your local sales office or representative for information. Notice THERMAFIBER INC. shall not be liable for incidental and consequential damages, directly or indirectly sustained, nor for any loss caused by application of these goods not in accordance with current printed instructions or for other than the intended use. THERMAFIBER S liability is expressly limited to replacement of defective goods. Any claim shall be deemed waived unless made in writing within thirty (30) days from date it was or reasonably should have been discovered. Date Safety First! Follow good safety and industrial hygiene practices while handling and installing products and systems. Take necessary precautions and wear the appropriate personal protective equipment as needed. Read material safety data sheets and related literature on products before specification and/or installation. Health Aspects Information about health aspects of using THERMAFIBER Curtain Wall Insulation products are thoroughly explained in North American Insulation Manufacturers Association s (NAIMA) Health and Safety facts for rock and slag wool insulation document #63. Contact Thermafiber, Inc. for more details. INC 3711 West Mill Street Wabash, IN TFIBER1 ( ) THERMAFIBER MADE FROM RECYCLED MATERIALS MADE IN USA TF612/Rev 11/06 Copyright 2004, Thermafiber Inc. Printed in U.S.A.

10 Material Safety Data Sheet ESTIMATING TABLES / TECH DATA SYSTEM DETAILS APPLICATIONS / PRODUCTS INTRODUCTION MSDS No.: 270 Revision No.: 003 Revision Date: 06/18/03 Page: 1 of 2 Product name: Mineral wool Description: Synthetic vitreous fiber Supplier: Hilti, Inc. P.O. Box 21148, Tulsa, OK Emergency # (Chem-Trec.): (USA, PR, Virgin Islands, Canada); (other countries) INGREDIENTS AND EXPOSURE LIMITS Ingredients: CAS Number: P EL: TLV: STEL: Slag wool fiber NE 1 fiber / cc NE Phenolic resin NE NE NE Polyvinyl alcohol NE NE NE Abbreviations: PEL = OSHA Permissible Exposure Limit. TLV = ACGIH Threshold Limit Value. STEL = Short Term Exposure Limit. NE = None Established. NA = Not Applicable. PHYSICAL DATA Appearance: 2 x 4 x 4 sheets. Odor: Negligible. Boiling Point: Not applicable. Vapor Pressure: Not applicable. Melting Point: Approx F VOC Content: Not applicable. Evaporation Rate: Not applicable. Solubility in Water: Insoluble. ph: Not applicable. Specific Gravity: Not determined. FIRE AND EXPLOSION HAZARD DATA Flash Point: Extinguishing Media: Special Fire Fighting Procedures: Unusual Fire and Explosion Hazards: Not applicable. Flammable Limits: Not applicable. As appropriate for surrounding fire; material does not burn. Soak cartons to help prevent the spread of fire. Use a self-contained breathing apparatus when fighting fires involving chemicals. None known. REACTIVITY DATA Stability: Stable. Hazardous Polymerization: Will not occur. Incompatibility: Strong acids. Hazardous Decomposition Products: Thermal decomposition products can be formed at temperatures exceeding 2000 F. Thermal decomposition can yield CO and CO 2. Conditions to Avoid: None known. HEALTH HAZARD DATA Known Hazards: Routes of Exposure: Signs and Symptoms of Exposure: Carcinogenicity: Medical Conditions Aggravated by Exposure: Acute: Eye, skin and respiratory irritation. Chronic: Respiratory impairment. Inhalation, Dermal. Eyes: Mechanical irritation. Skin: Itching, irritation. Inhalation: Nose, throat and upper respiratory tract irritation. Slag wool has been classified by the IARC as Group 3 Unclassifiable as to Carcinogenicity in Humans. Eye, skin, and respiratory conditions. 480 Saving Lives through innovation & education Hilti Firestop Guide

11 Material Safety Data Sheet MSDS No.: 270 Revision No.: 003 Revision Date: 06/18/03 Page: 2 of 2 EMERGENCY AND FIRST AID PROCEDURES Eyes: Flush with plenty of water while holding eyelids apart. Avoid rubbing the eyes as mechanical abrasions can occur. Call a physician if symptoms persist. Skin: Wash with soap and water. Launder clothing before reuse. Inhalation: Move to fresh air. Ingestion: No ill effects expected. Other: Referral to a physician is recommended if there is any question about the seriousness of the injury/exposure. CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT Ventilation: General (natural or mechanically induced fresh air movements). Eye Protection: Safety goggles recommended to prevent particulates from irritating the eyes. Skin Protection: Cloth gloves and long sleeves to protect skin from irritating fibers. Respiratory Protection: Use local exhaust and/or a NIOSH-approved dust respirator when air movement is inadequate to control dusts / fibers below recommended exposure levels. PRECAUTIONS FOR SAFE HANDLING AND USE Handling and Storing Precautions: Avoid generating dusts. Local exhaust may be required to control dusts if power tools are used for cutting / trimming. Wear appropriate personal protective equipment. Store away from moisture; keep dry. Spill Procedures: Not applicable. REGULATORY INFORMATION Hazard Communication: HMIS Codes: DOT Shipping Name: IATA / ICAO Shipping Name: TSCA Inventory Status: SARA Title III, Section 313: EPA Waste Code(s): Waste Disposal Methods: This MSDS has been prepared in accordance with the federal OSHA Hazard Communication Standard 29 CFR Health 1, Flammability 0, Reactivity 0, PPE B (Gloves, Goggles) Not regulated. Not regulated. Chemical components listed on TSCA inventory. This product does not contain any toxic chemicals which are subject to reporting under Section 313 of SARA Title III (40 CFR Part 372). Not regulated by EPA as a hazardous waste. Consult with regulatory agencies or your corporate personnel for disposal methods that comply with local, state, and federal safety, health and environmental regulations. CONTACTS Customer Service: Technical Service: Health / Safety: Jerry Metcalf (x6704) Emergency # (Chem-Trec): (USA, PR, Virgin Islands, Canada); (other countries) The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or warranty of any kind expressed or implied is made with respect to the information provided. INTRODUCTION APPLICATIONS / PRODUCTS SYSTEM DETAILS ESTIMATING TABLES / TECH DATA Saving Lives through innovation & education Hilti Firestop Guide

12

13 System No. C-AJ-1226 F Rating 3 Hr T Rating 0 Hr L Rating At Ambient Less Than 1 CFM/Sq Ft L Rating At 400 F 4 CFM/Sq Ft CAJ B A 2 3 4B 1 3 4A A SECTION A-A 1. Floor or Wall Assembly Min 4-1/2 in. thick reinforced lightweight or normal weight ( pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 32 in. 2. Metallic Sleeve (Optional) Nom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve cast or grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3 in. above floor or beyond both surfaces of wall. 2A. Sheet Metal Sleeve (Optional) Max 6 in. diam, min 26 ga galv steel provided with a 26 ga galv steel square flange spot welded to the sleeve at approx mid-height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in. below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor. 2B. Sheet Metal Sleeve (Optional) - Max 12 in. diam, min 24 ga galv steel provided with a 24 ga galv steel square flange spot welded to the sleeve at approx mid-height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in. below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor. 3. Through-Penetrant One metallic pipe, tube or conduit to be installed either concentrically or eccentrically within the firestop system. The annular space between penetrant and periphery of opening shall be min 0 in. (point contact) to max 1-7/8 in. Penetrant may be installed with continuous point contact. Penetrant to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic penetrants may be used: A. Steel Pipe Nom 30 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe Nom 30 in. diam (or smaller) cast or ductile iron pipe. C. Copper Pipe Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tubing Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing. E. Conduit Nom 6 in. diam (or smaller) steel conduit. F. Conduit Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT). 4. Firestop System The firestop system shall consist of the following: A. Packing Material Min 4 in. thickness of min 4 pcf mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or sleeve or from both surfaces of wall or sleeve as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* Sealant Min 1/4 in. thickness of fill material applied within the annulus, flush with top surface of floor or sleeve or with both surfaces of wall or sleeve. At the point or continuous contact locations between penetrant and concrete or sleeve, a min 1/4 in. diam bead of fill material shall be applied at the concrete or sleeve/ pipe penetrant interface on the top surface of floor and on both surfaces of wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC FS-One Sealant *Bearing the UL Classification Mark Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. June 27, 2007 CLASS I F IED C US

14 System No. C-AJ-5091 F Rating 2 Hr T Ratings 0 and 1 Hr (See Items 2 and 4) L Rating At Ambient 4 CFM/Sq Ft L Rating At 400 F Less Than 1 CFM/Sq Ft CAJ 5091 A 5B 2 1 5A A 4 3 SECTION A-A 1. Floor or Wall Assembly Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight ( pcf or kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 19-1/2 in. (495 mm). See Concrete Blocks (CAZT) category in the Fire Resistance directory for names of manufacturers. 2. Metallic Sleeve (Optional) Nom 20 in. (508 mm) diam (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3 in. (76 mm) above floor or beyond both surfaces of wall. If the steel sleeve extends beyond the top surface of the floor or both surfaces of the wall, the T Rating of the firestop system is 0 hr. 2A. Sheet Metal Sleeve (Optional) - Max 6 in. (152 mm) diam, min 26 ga galv steel provided with a 26 ga galv steel square flange spot welded to the sleeve at approximately mid- height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. (51 mm) larger than the sleeve diam. The sleeve is to be cast in place flush with bottom surface of floor and may extend a max of 1 in. (25 mm) above the top surface of the floor. 2B. Sheet Metal Sleeve (Optional) - Max 12 in. (305 mm) diam, min 24 ga galv steel provided with a 24 ga galv steel square flange spot welded to the sleeve at approximately mid- height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. (51 mm) larger than the sleeve diam. The sleeve is to be cast in place flush with bottom surface of floor and may extend a max of 1 in. (25 mm) above the top surface of the floor. 3. Through Penetrants One metallic pipe or tubing to be installed either concentrically or eccentrically within the firestop system. Pipe or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes or tubing may be used: A. Steel Pipe Nom 12 in. (305 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe Nom 12 in. (305 mm) diam (or smaller) cast or ductile iron pipe. C. Copper Pipe Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tubing Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing. Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. May 29, 2008 CLASS I F IED C US Page: 1 of 2

15 System No. C-AJ-5091 F Rating 2 Hr T Ratings 0 and 1 Hr (See Items 2 and 4) L Rating At Ambient 4 CFM/Sq Ft L Rating At 400 F Less Than 1 CFM/Sq Ft CAJ Pipe Covering Min 1/2 in. (13 mm) to max 2 in. (51 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m3) glass fiber units jacketed on the outside with an all-service jacket. Longitudinal joints sealed with metal fasteners or factory-applied, self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. The annular space between the insulated pipe and the edge of the periphery of the opening shall be min 1/2 in. (13 mm) to a max 2-1/4 in. (57 mm). When thickness of pipe covering is less than 2 in. (51 mm), the T Rating for the firestop system is 0 hr. See Pipe Equipment Covering Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 4A. Pipe Covering (Not Shown) As an alternate to Item 4, max 2 in. (51 mm) thick cylindrical calcium silicate (min 14 pcf) units sized to the outside diam of the pipe or tube may be used. Pipe insulation secured with stainless steel bands or min 8 AWG stainless steel wire spaced max 12 in. (305 mm) OC. The annular space shall be min 1/2 in. (13 mm) to max 2-1/4 in. (57 mm). 5. Firestop System The firestop system shall consist of the following: A. Packing Material Min 4 in. (102 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* Sealant Min 1/2 in. (13 mm) thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC FS-One Sealant *Bearing the UL Classification Mark Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. May 29, 2008 CLASS I F IED C US Page: 2 of 2

16 System No. C-BJ-5018 F Rating 3 Hr T Rating 1/2 Hr CBJ B 3 2 4B A A 4A SECTION A-A 1. Floor Assembly Min 8 in. (203 mm) thick reinforced lightweight or normal weight ( pcf or kg/m3) concrete. Floor assembly may also be constructed of any 8 in. (203 mm) thick UL Classified hollow-core Precast Concrete Units*. Max diameter of opening is 7 in. (178 mm). See Precast Concrete Units CFTV) category in the Fire Resistance Directory for names of manufacturers. 2. Through Penetrants One metallic pipe or tube to be installed concentrically or eccentrically within the firestop system. Pipe or tube to be rigidly supported on both sides of floor-ceiling assembly. The following types and sizes of metallic pipes or tubes may be used: A. Steel Pipe Nom 4 in. (102 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Copper Tubing Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tubing. C. Copper Pipe Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe. 3. Tube Insulation - Plastics+ Nom 1 in. (25 mm) thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. The annular space between the insulated pipe or tubing and periphery of the opening shall be min 0 in. (point contact) to max 7/8 in. (22 mm). See Plastics+ (QMFZ2) category in the Plastic Component Directory for names of manufacturers. Any Recognized Component tube insulation material meeting the above specifications and having a UL94 Flammability Classification of 94-5VA may be used. 4. Firestop System The firestop system shall consist of the following: A. Packing Material Min 1 in. (25 mm) thickness of 4 pcf (64 kg/m3) mineral wool insulation tightly packed into the opening as a permanent form. Packing material to be installed flush with the bottom surface of floor assembly and recessed from the top surface of the floor or both sides of the wall assembly to accommodate the required thickness of fill material. B. Fill, Void or Cavity Materials*-Sealant Min 1/4 in. (6 mm) thickness of fill material applied within the annulus, flush with top surface of floor or both sides of the wall. An additional 1/4 in. (6 mm) bead shall be installed at penetrant/concrete interface on top surface of floor or both sides of the wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC FS-ONE Sealant *Bearing the UL Classification Mark +Bearing the UL Recognized Component Mark Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. November 15, 2006 CLASS I F IED C US

17 System No. F-C-1009 F Rating - 1 and 2 Hr (See Item 1) T Rating - 1 Hr and 2 Hr (See Item 1) L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - 4 CFM/sq ft FC Floor-Ceiling Assembly - The 1 or 2 hr fire-rated solid or trussed lumber joist floor-ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor-Ceiling Designs in the UL Fire Resistance Directory. The F Rating of the firestop system is equal to the rating of the floor-ceiling and wall assemblies. The general construction features of the floor-ceiling assembly are summarized below: A. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor-Ceiling Design. Diam of opening to be max 1 in. larger than diam of pipe. As an alternate, the opening may be square-cut with a max dimension 1 in. greater than the diam of the pipe. B. Wood Joists* - Nom 10 in. deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Furring Channels - (Not Shown) -(As required ) Resilient galvanized steel furring installed in accordance with the manner specified in the individual L500 Series Designs in the Fire Resistance Directory. D. Gypsum Board* - Thickness, type, number of layers and fasteners shall be as specified in the individual Floor-Ceiling Design. Diam of opening to be max 1 in. larger than diam of pipe. B. Sole Plate - Nom 2 by 4 in., 2 by 6 in. or parallel 2 by 4 in. lumber plates, tightly butted. Diam of opening is to be max 1 in. larger than diam of pipe. As an alternate, the opening may be square-cut with a max dimension 1 in. greater than the diam of the pipe. Plates may be discontinuous over opening, terminating at two opposing edges of opening. Max length of discontinuity to be 1 in. greater than diam of through penetrant. C. Top Plate - The double top plate shall consist of two nom 2 by 4 in., 2 by 6 in. or two sets of parallel 2 by 4 in. lumber plates, tightly butted. Diam of opening is to be max 1 in. larger than diam of pipe. As an alternate, the opening may be square-cut with a max dimension 1 in. greater than the diam of the pipe. Plates may be discontinuous over opening, terminating at two opposing edges of opening. Max length of discontinuity to be 1 in. greater than diam of through penetrant. Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. December 10, 2004 CLASS I F IED C US Page: 1 of 2

18 System No. F-C-1009 F Rating - 1 and 2 Hr (See Item 1) T Rating - 1 Hr and 2 Hr (See Item 1) L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - 4 CFM/sq ft FC1009 D. Steel Plate - When lumber plates are discontinuous, nom 1-1/2 in. wide No. 20 gauge (or heavier) galv steel plates shall be installed to connect each discontinuous lumber plate and to provide a form for the fill material. Steel plates sized to lap 2 in. onto each discontinuous lumber plate and secured to lumber plates with steel screws or nails. E. Gypsum Board* - Thickness, type, number of layers and fasteners shall be as specified in individual Wall and Partition Design. 2. Chase Wall - The through penetrant (Item 3) shall be routed through a 1 or 2 hr fire-rated single, double or staggered wood stud/gypsum board chase wall having a fire rating consistent with that of the floor-ceiling assembly. Depth of chase wall to be min 1 in. greater than the diameter of the through penetrant. The chase wall shall be constructed of the materials and in the manner specified in the individual U300 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Nom 2 by 4 in., 2 by 6 in. or double nom 2 by 4 in. lumber studs. Nom 2 by 4 in. studs are allowed for through-penetrants (Item 3) not exceeding nom 2 in. diam. 3. Through Penetrants - One metallic pipe, conduit or tubing to be installed within the firestop system. Pipe, conduit or tubing to be rigidly supported on both sides of floor assembly. The annular space within the firestop system shall be min 0 in. (point contact) to max 1 in.. The following types and sizes of metallic pipes or conduits may be used: A. Steel Pipe - Nom 4 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 4 in. diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit. D. Copper Tubing - Nom 4 in. diam (or smaller) Type L (or heavier) copper tubing. E. Copper Pipe - Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe. 4. Fill, Void or Cavity Material* - Sealant - Min 3/4 in. thickness of fill material applied within the annulus, flush with the top surface of the floor or the sole plate. A generous bead of fill material also applied within the annulus of the top plate, flush with bottom surface of lower top plate. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - CP601S, CP606 or FS-One Sealant. (Note: L Ratings apply only when FS-ONE Sealant is used.) *Bearing the UL Classification Mark Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. December 10, 2004 CLASS IF IED C US Page: 2 of 2

19

20

21

22

23

24

25 System No. F-C-2310 F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 1 and 1-1/2 Hr (See Item 1) FC A 4 1A 2B 1B 1D 2C 2D 2A 4 1. Floor-Ceiling Assembly - The 1 or 2 hr fire-rated solid or trussed lumber joist floor-ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor-Ceiling Designs in the UL Fire Resistance Directory. The F Rating of the firestop system is equal to the rating of the floor-ceiling and wall assemblies. The T Rating of the firestop system is 1 hr for 1 hr rated floor-ceiling and wall assemblies and 1-1/2 hr for 2 hr rated floor-ceiling and wall assemblies. The general construction features of the floor-ceiling assembly are summarized below: A. Forming Material - Lumber or plywood subfloor with finish floor or lumber, plywood or Floor Topping Mixture* as specified in the individual Floor-Ceiling Design. Max diam of floor opening is 3 in. B. Wood Joists* - For 1 hr fire-rated floor-ceiling assemblies nom 10 in. deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. For 2 hr fire-rated floor-ceiling assemblies, nom 2 by 10 in. lumber joists spaced 16 in. OC with nom 1 by 3 in. lumber bridging and with ends firestopped. C. Furring Channels - (Not Shown) - (As required) - Resilient galvanized steel furring installed in accordance with the manner specified in the individual L500 Series Designs in the Fire Resistance Directory. D. Gypsum Board* - Thickness, type, number of layers and fasteners shall be as specified in the individual Floor-Ceiling Design. Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. date October 29, 2004 CLASS I F IED C US Page: 1 of 2

26 System No. F-C-2310 F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 1 and 1-1/2 Hr (See Item 1) FC Chase Wall - The 1 or 2 hr fire-rated single wood stud/gypsum wallboard chase wall shall be constructed of the materials and in the manner specified in the individual U300 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Nom 2 by 4 in. lumber studs. B. Sole Plate - Nom 2 by 4 in. lumber plates. C. Top Plate - The double top plate shall consist of two nom 2 by 4 in. lumber plates. Max diam of opening is 3 in. D. Gypsum Board - Thickness, type, number of layers and fasteners shall be as specified in individual Wall and Partition Design. 3. Through-Penetrants - Nom 1 in. diam (or smaller) SDR 9 (or heavier) cross-linked polyethylene (PEX) tubing for use in closed (process or supply) piping systems. A max of three tubes may be installed in the opening. The annular space between the tubing and the periphery of the opening shall be a min of 3/16 in. to a max of 1 in. The space between the tubes shall be a min of 0 in. (point contact) to a max of 1/4 in. Tubing to be rigidly supported on both sides of the floor-ceiling assembly. 4. Fill, Void or Cavity Material* - Sealant - Min 3/4 in. thickness of fill material applied within the annulus, flush with top surface of floor or sole plate and a min 3/4 in. thickness of fill material applied within the annulus, flush with the bottom surface of the lower top plate. Additional fill material forced within the group of tubing to max extent possible on the top surface of floor or sole plate and bottom surface of lower top plate. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - FS-ONE Sealant *Bearing the UL Classification Mark Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. date October 29, 2004 CLASS IF IED C US Page: 2 of 2

27

28

29

30

31 System No. W-L-1408 F Rating - 1 or 2 Hr (See Item 1) T Rating - 0 or 1/4 Hr (See Item 1) WL 1408 A A SECTION A-A 1. Wall Assembly The 1 and 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described in the individual U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs Wall framing shall consist of min 3-5/8 in. (92 mm) wide steel studs spaced max 24 in. (610 mm) OC. B. Gypsum Board* Thickness, type, number of layers and fasteners, as specified in the individual U400 or V400 Series Wall and Partition Design. Max area or opening is 114 in.2 (735 cm2) with max height of 5 in. (127 mm) and max width of 23 in. (584 mm). The hourly F Rating of the firestop system is equal to the hourly rating of the wall. The hourly T Rating of the firestop system is 0 hr and 1/4 hr when installed in 1 hr and 2 hr fire rated wall assemblies, respectively. 2. Through Penetrants Multiple pipes or conduits installed in single layer array within the firestop system. The annular space between the pipes and conduits and the edges of the opening shall be min 0 in. (0 mm, point contact) to max 1 in. (25 mm). The separation between pipes and conduits to be a min 0 in. (0 mm, point contact) to a max 1-1/2 in. (38 mm). Pipes and conduits to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or conduits may be used: A. Steel Pipe Nom 4 in. (102 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Conduit Nom 4 in. (102 mm) diam (or smaller) rigid steel conduit or steel electrical metallic tubing (EMT). 3. Fill Void or Cavity Materials* - Sealant Min 5/8 in. (16 mm) thickness of fill material installed to completely fill annular space between pipes, conduits and gypsum flush with each surface of wall. Min 1/2 in. (13 mm) diam bead of fill material applied to the through penetrant/wall interface at the point contact locations on both sides of the wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC FS-ONE Sealant *Bearing the UL Classification Mark Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. September 05, 2006 CLASS I F IED C US

32

33 System No. W-L-2377 F Ratings - 1 and 2 Hr (See Items 1 and 3) T Ratings - 1 and 2 Hr (See Items 1 and 3) L - Rating at Ambient - Less that 1 CFM/Sq Ft L - Rating at 400 F - 4 CFM/Sq Ft WL A A 2 A 3 SECTION A-A 1B 1. Wall Assembly - The 1 and 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide by 1-3/8 in. deep channels spaced max 24 in. OC. B. Gypsum Board* - The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 3 in. The hourly F and T Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. date June 15, 2004 CLASS I F IED C US Page: 1 of 2

34 System No. W-L-2377 F Ratings - 1 and 2 Hr (See Items 1 and 3) T Ratings - 1 and 2 Hr (See Items 1 and 3) L - Rating at Ambient - Less that 1 CFM/Sq Ft L - Rating at 400 F - 4 CFM/Sq Ft WL Through Penetrant - One nonmetallic pipe, conduit or tubing installed either concentrically or eccentrically within the firestop system. The annular space between pipe and periphery of opening shall be min of 0 in. (point contact) to a max 1-1/4 in. Pipe to be rigidly supported on both sides of wall assembly. The following types and sizes of nonmetallic pipes may be used: A. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 2 in. diam (or smaller) FLOWGUARD GOLD SDR11 CPVC pipe for use in closed (process or supply) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 2 in. diam (or smaller) BLAZEMASTER SDR13.5 CPVC pipe for use in closed (process or supply) piping systems. 3. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. and 1-1/4 in. thickness of fill material applied within annulus, flush with both surfaces of wall for 1 and 2 hr rated assemblies, respectively. At point contact location, a min 1/2 in. diam bead of fill material shall be applied to the wall/penetrant interface on both surfaces of the wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - FS-ONE Sealant *Bearing the UL Classification Mark Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. date June 15, 2004 CLASS IF IED C US Page: 2 of 2

35 System No. W-L-2466 F Ratings - 1 and 2 Hr T Rating - 0 Hr WL A 3 A 2 3 SECTION A-A Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. May 08, 2006 CLASS I F IED C US Page: 1 of 2

36 System No. W-L-2466 F Ratings - 1 and 2 Hr T Rating - 0 Hr WL Wall Assembly The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300, U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide spaced max 24 in. (610 mm) OC. B. Gypsum Board* The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Design in the UL Fire Resistance Directory. Max diam of opening is 4 in. (102 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through-Penetrants One or more nonmetallic pipes, conduits or tubes installed concentrically or eccentrically within opening. Annular space between penetrants and periphery of opening to be min 0 in. (point contact) to max 1 in. (25 mm). Space between penetrants shall be min 0 in. (point contact) to max 1 in. (25 mm). Penetrants to be rigidly supported on both sides of wall. The following types and sizes of penetrants may be used: A. Polyvinyl Chloride (PVC) Pipe Nom 1-1/2 in. (38 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) piping systems. B. Rigid Nonmetallic Conduit++ Nom 1-1/2 in. (38 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA No. 70). C. Chlorinated Polyvinyl Chloride (CPVC) Pipe Nom 1-1/2 in. (38 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems. D. Crosslinked Polyethylene (PEX) Tubing Nom 1 in. (25 mm) diam (or smaller) SDR 9 PEX tubing for use in closed (process or supply) piping systems. 3. Fill, Void or Cavity Material* - Caulk or Sealant Min 5/8 in. (16 mm) thickness of caulk applied within annulus, flush with both surfaces of wall. Min 1/4 in. (6 mm) diam bead of caulk applied to gypsum board/penetrant interface at point contact location on both sides of wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC FS-ONE Sealant *Bearing the UL Classification Mark ++ Bearing the UL Listing Mark Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. May 08, 2006 CLASS I F IED C US Page: 2 of 2