VIA 2 LED RECESSED W W W. L U M E N W E R X. C O M

Size: px
Start display at page:

Download "VIA 2 LED RECESSED W W W. L U M E N W E R X. C O M"

Transcription

1 IMPORTANT: a qualified integration consultant is required to ensure proper installation and function of any network DESCRIPTION Via is the elegant and flexible linear PROJECT: LED luminaire system for pendant, surface, and recessed or in-wall TYPE: installation, whether as discrete NOTES: luminaires, continuous runs, or patterns. Via features numerous optical configurations, which are difficult to achieve in luminaires. Via is an ideal vehicle for ChromaWerx color tuning in education, office, and Grid ceiling Drywall ceiling healthcare applications where modular ORDER GUIDE luminaires are used. IC RATED VIAR HLO LED LUMINAIRE ID OPTICS LIGHT SOURCE CHROMAWERX OUTPUT WATTAGE VIAR - via " recessed HLO - High-Efficiency LED - high QUADRO - four-channel RGB with 500K white.5wf -.5 w/ft output (for solid colors only) Lambertian Optic performance LED RS - red solid WF - w/ft output (quadro only) GS - green solid 6WF - 6 w/ft output (quadro only) BS - blue solid 9WF - 9 w/ft output (quadro only) LUMINAIRE LENGTH VOLTAGE DRIVER ELECTRICAL MOUNTING Available sections - 4', 6', 8', 0' & ' 0-0V - to specify see pages 4 to 9 - circuit TG9 - tegular 9/6" #FT - nominal length in feet 77-77V DA - Dali (solid colors only) local on-site TG5 - tegular 5/6" (' increments only) commissioning is required TB9 - t-bar 9/6" Continuous Run - for luminaires over ' (solid colors only) TB5 - t-bar 5/6" Minimum Individual section 4' ST - screw slot t-bar DTR - drywall trim DTL - drywall trimless DMF - drywall mud flange See page for ordering code detailed information FINISH OPTIONS WALL CONTROLS W - matte white FU - fuse To specify see pages 4 to 9 CF# - custom finish ITR - integrated track (consult factory) specify RAL# FWC - flexible whip cable (6' std) CP - Chicago Plenum CROSS SECTION CU - custom OPTICS Y nm /4" 770 nm VIAR - recessed HLO - High-efficiency Lambertian Optic nm X 0.8 File Name: VIA-RGBW-RECESSED-SPEC Page: / 9

2 OPTICS HIGH EFFICIENCY LAMBERTIAN OPTIC (HLO) - matte white side reflectors combined with High-Efficiency Lambertian Optic (HLO) shielding of diffusing 0.075" thick acrylic with up to 88% transmission and good source obscuration. Luminaire brightness is controlled by the flux-to-shielding area ratio. LIGHT SOURCE - LED Custom linear array of mid-flux LEDs, comprised of an alternation of an RGB and a dedicated white LED. The white LED is used for when a static white CCT is required in the space. RGB LEDs are tightly binned for excellent color control between fixtures. The white LEDs have been tested in accordance with IESNA LM and the results have shown L80 lumen maintenance greater than 60,000 hours. Absolute product photometry is measured and presented in accordance with IESNA LM-79, unless otherwise indicated. CHROMAWERX - RGBW ChromaWerx Quadro is a four-channel control that operates an RGBW LED array and addresses the need for more expressive color in architectural applications. The driver supports familiar programming tools for both dynamic multi-hued color and precise white color point control. While a typical user interface will be a controller by others, LumenWerx also offers a simple control station for stand-alone color changing applications. Y nm LUMINAIRE LENGTH Via is made up of standard 4, 6, 8, 0 and foot sections that may be joined together to create longer continuous run lengths. Exact run length must be noted in the product code. The minimum individual section available is 4 foot, and continuous run lengths can be ordered in foot increments. All individual sections are joined together onsite using the joiner kits provided. LumenWerx offers joiner kits that are extremely simple to work with in the field 770 nm and result in a fixture that appears virtually seamless with no light leak at any connection. Joining system nm X 0.8 CIE 9 Chromaticity space t-bar Mud flange The above diagram overlays the full gamut of colors attainable with the RGBW on top of the CIE 9 color space. Any color point inside of the triangle can be obtained by setting the correct output levels for each of the individual red, green, blue, and white channels. ELECTRICAL Factory-set, adjustable output current, multichannel LED driver with universal (0-77VAC) input. Using wall controls (optionally supplied by LumenWerx) or an existing control system, four channels of LEDs (Red/Green/Blue/White) are independently adjustable. Each driver has multiple output channels that can be independently addressed at the factory or on-site using built-in RDM (Remote Device Management) functionality. Dimming range from 00%-0%. At maximum driver load, efficiency<89%, PF>0.9, THD<0%. File Name: VIA-RGBW-RECESSED-SPEC Page: / 9

3 MOUNTING OPTIONS Recess mount into exposed or concealed T-Bar or Tegular grid ceiling TG9 - tegular 9/6" TG5 - tegular 5/6" TB9 - t-bar 9/6" CONSTRUCTION Housing - Extruded Aluminum (0.095" nominal) up to 90% Recycled Content Interior brackets - Die formed cold rolled sheet steel 8 gauge thick Joining system - Die cast Zinc (0.95" nominal) and die Formed galvanized sheet 8 gauge Reflectors - Extruded Aluminum (0.075 nominal) up to 95% reflective matte Mud flange - Extruded Aluminum (0.075" nominal) up to 90% Recycled Content Slip-through bracket - Die Formed galvanized sheet 8 gauge End plate - Die formed cold rolled sheet steel 8 gauge thick TB5 - t-bar 5/6" ST - screw slot t-bar Mounting for drywall ceilings are available with visible trim, mud flange trim or trimless 4 5/8" /4" /4" WEIGHT Via 4ft - 9.0lbs - 4.kg Via 8ft - 8.8lbs - 8.kg Via ft lbs -.7kg CERTIFICATIONS ETL - Rated for Indoor Dry/Damp locations. Conforms to UL Standard 598 and certified to CAN/CSA Standard C. No Chicago plenum - City of Chicago Approved (CCEA) IC rated - suitable for direct contact with insulation. 9/" hole width with flanges DTR - drywall trim /4" hole width 4 7/8" with flanges /4" DMF - drywall mud flange /" hole width DTL - drywall trimless WARRANTY For all ChromaWerx products, LumenWerx provides a three-year limited warranty of electrical and mechanical performance of the luminaires, including the LED boards, drivers, and auxiliary electronics. LumenWerx will repair or replace defective luminaires or components at our discretion, provided they have been installed and operated in accordance with our specifications. Other limitations apply, please refer to the full warranty on our website. Wall controllers are covered by the manufacturer warranty. FINISH Interior - 95%, reflective matte powder coated white paint Exterior - matte white or aluminum powder coating. Custom finishes are also available. File Name: VIA-RGBW-RECESSED-SPEC Page: / 9

4 QUADRO SPECIFICATION A qualified integrator is required to assure proper installation and commissioning of the network. When placing the PO, please provide the contact information of your integrator. YES controller supplied by Lumenwerx Please answer the following questions to help us identify your network requirements. Do you require a wall controller provided by Lumenwerx? NO control system supplied by others. Lumenwerx will supply -enabled fixtures with default addressing. See following pages for technical informations. How many zones do you have? A zone consists of one or more luminaires behaving identically. Zone Zones How to calculate the required number of drivers: per 4' fixture x driver Less than.5w/ft, direct only per 4' fixture x driver Above.5W/ft or for all direct/indirect fixture To Calculate # of drivers Zone to Zones Do you have more than drivers in total? 4 or more Zones NO YES NO YES Order a standard Lumenwerx wall controller type. WALL CONTROLLER WCW - wall controller white WCB - wall controller black Add the control code at the end of your order code. Please provide a fixture layout or RCP (Reflected Ceiling Plan) showing the locations of the fixtures, zones and the wall controller. Refer to your integrator for the installation. Order a standard Lumenwerx wall controller type. WALL CONTROLLER WCW - wall controller white WCB - wall controller black Add the control code at the end of your order code. Please provide a fixture layout or RCP (Reflected Ceiling Plan) showing the locations of the fixtures, zones and the wall controller. Refer to your integrator for the installation. Subject to factory evaluation ans approval. Please contact our controls specialist at controls@lumenwerx.com Additional cost and equipment will be required. Subject to factory evaluation. Please contact our controls specialist at controls@lumenwerx.com Additional cost and equipment will be required. Subject to factory evaluation. Please contact our controls specialist at controls@lumenwerx.com Additional cost and equipment will be required. File Name: VIA-RGBW-RECESSED-SPEC Page: 4 / 9

5 GENERIC NETWORK ARCHITECTURE Lumenwerx supplied controller Controls IN OUT Wire + Shield LOW CAP CABLE Network & control by others First enabled fixture supplied by Lumenwerx 0/77V PROTOCOL CONSIDERATIONS: drivers/fixtures must be daisy chained. Maximum drivers per run. The end of the line must be terminated by a 0 Ω resistor Electrical Controls IN OUT Next enabled fixture supplied by Lumenwerx 0/77V Electrical Wire + Shield LOW CAP CABLE Controls IN OUT Last enabled fixture supplied by Lumenwerx max drivers per run 0/77V Electrical 4 0 OHM END OF LINE RESISTOR File Name: VIA-RGBW-RECESSED-SPEC Page: 5 / 9

6 LUMENWERX SUPPLIED CONTROLLER To the first fixture Wire + Shield Low Cap Cable WALL BOX SUPPLIED BY OTHERS Back Panel Front Panel GND V+ -4 Vdc BLACK RED - WHT- BLUE + SHIELD BARE BLUE SS S G B W Controller image may differ I.E.: Cerco Cable Belden 984 Belden 84 DC out Power Supply 0-40V AC / VDC or 4VDC N L BLUE DC in BROWN Neutral Line Ground Electrical File Name: VIA-RGBW-RECESSED-SPEC Page: 6 / 9

7 J-BOX DAISY CHAIN DETAIL Low capacitance Cable from Previous Fixture Shielding foil touches the bare metal drain wire inside IN Bare metal drain wire (shield) MUST NOT TOUCH J-BOX Ground Controls IN OUT ENABLED FIXTURE OUT Bare metal drain wire (shield) MUST NOT TOUCH J-BOX Low capacitance cable to next fixture CONNECTION RECESSED & SURFACE IN OUT Shield - + Shield - + POWER LINE VOLTAGE green black white N L G ENABLED FIXTURE PWR File Name: VIA-RGBW-RECESSED-SPEC Page: 7 / 9

8 4 LAST FIXTURE DETAIL IN From other fixtures + - S Last OUT + - S 0 OHM END OF LINE RESISTOR CAP OFF SHIELD + = Blue - = White-Blue Shield = Bare metal LAST FIXTURE OF THE NETWORK MAX DRIVERS PER RUN + - SHIELD LED output ENABLED FIXTURE File Name: VIA-RGBW-RECESSED-SPEC Page: 8 / 9

9 WALL CONTROLLER WC () Power: Use this button to turn ON or OFF the RGBW fixture S S S S4 S 6 4 () Color Wheel: The wheel is used to rapidly select a color () Brightness (RGB): Hold down this button to either increase or decrease the brightness of the current RGB selection. White will not be affected by the RGB brightness button. (4) Color Cycle: This button will start an animation, rotating between Reds Greens and Blues, the arrows allows the user to speed up or slow down the animation 5 R G B W (5) Individual Colors: By pressing and holding a color it will be possible to brighten or dim it. Quickly pressing a color will turn it OFF or turn it ON to it s previous dim level. White: In Order to activate or deactivate and dim the White channel, the White button needs to be used. (6) Scenes: By holding down one of the scenes button, the current color selection is saved. It can be later accessed by quickly pressing on one of the Scene buttons. WC () Power: Use this button to turn ON or OFF the RGBW fixture () Color Wheel: The wheel is used to rapidly select a color 5 () Brightness: Hold down this button to either increase or decrease the brightness of the current RGB selection. White will not be affected by the RGB brightness button. (4) Color Cycle: This button will start an animation, rotating between Reds Greens and Blues, the arrows allows the user to speed up or slow down the animation 4 6 (5) Individual Colors: By pressing a color it will be possible to brighten or dim that specific color White: In Order to activate or deactivate and dim the White channel, the White button needs to be used. (6) Zone: By holding down one of the zone button, a zone can be selected and control Default Addresses: Red Green Blue 4 White File Name: VIA-RGBW-RECESSED-SPEC Page: 9 / 9