1 Submittal Package HVAC Penetrations Carolinas HealthCare System STI Contacts: Eric Lacroix T: E: Jay Guidotti T: E: Specified Technologies Inc. 210 Evans Way Somerville, NJ USA T:

2 System No. W-J-7005 Ì80WJ0Çf%ÈAAÇ(8+DÎ ANSI/UL1479 (ASTM E814) F ating - 2 Hr T ating - 0 Hr CAN/ULC S115 F ating - 2 Hr FT ating - 0 Hr FH ating - 2 Hr FTH ating - 0 Hr 1. Wall Assembly - Min 6 in. (152 mm) thick reinforced lightweight or normal weight ( pcf or kg/m3 ) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 25-1/2 in. (648 mm). See Concrete Blocks (CAZT) category in the Fire esistance Directory for names of manufacturers. 2. Steel Duct - Max 24 in. (610 mm) diam No. 28 gauge (or heavier) galv steel vent duct or No. 26 gauge (or heavier) spiral wound galv steel duct. One steel duct to be installed either concentrically or eccentrically within the firestop system. An annular space of min 0 in. (0 mm, point contact) to max 1-1/2 in. (38 mm) is required within the firestop system. Steel duct to be rigidly supported on both sides of the wall assembly. 3. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall. At the point contact location between through penetrant and concrete, a min 3/8 in. (10 mm) diam bead of fill material shall be applied at the through penetrant/concrete interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant *Bearing the UL Classification Mark eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: August 24, 2011 W-J-7005 PAGE 1 OF 1

3 System No. W-J-7007 Ì78WJ0Çf'ÈAAÇ(8+cÎ ANSI/UL1479 (ASTM E814) F ating - 2 Hr T ating - 1/2 Hr CAN/ULC S115 F ating - 2 Hr FT ating - 1/2 Hr FH ating - 2 Hr FTH ating - 1/2 Hr 1. Wall Assembly - Min 6 in. (152 mm) thick reinforced lightweight or normal weight ( pcf or kg/m3 ) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max area of opening is 73.7 sq ft (6.85 m2) with max dimension of 104 in. (2.64 m). See Concrete Blocks (CAZT) category in the Fire esistance Directory for names of manufacturers. 2. Steel Duct - Max 100 by 100 in. (2.54 by 2.54 m) No. 26 gauge (or heavier) galv steel duct to be installed either concentrically or eccentrically within the firestop system. The space between the steel duct and periphery or opening shall be min 0 in. ( 0 mm, point contact) to max 2 in. (51 mm). Steel duct to be rigidly supported on both sides of the wall assembly. 3. Firestop System - The firestop system shall consist of the following: A. Packing Material - (Optional, Not Shown) - Polyethylene backer rod, mineral wool batt insulation or fiberglass batt insulation friction fitted into annular space of opening. Packing material to be recessed from both surfaces of wall as required thickness of fill material. B. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall. At the point contact location between the steel duct and the concrete wall, a min 1/4 in. (6 mm) diam bead of fill material shall be applied at the concrete/steel duct interface on both surfaces of wall assembly. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant C. Steel etaining Angles - Min No. 16 gauge galv steel angles sized to lap steel duct a min of 2 in. (51 mm) and to lap wall surfaces a min of 1 in. (25 mm). Angles attached to steel duct on both sides of wall with min No. 10 by 1/2 in. (13 mm) long steel sheet metal screws located a max of 1 in. (25 mm) from each end of the steel duct and spaced a max of 6 in. (152 mm) OC. *Bearing the UL Classification Mark eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: August 24, 2011 W-J-7007 PAGE 1OF 1

4 F ating - 2 Hr T ating - 0 Hr Ì81WJ0Çf-ÈAAÇ!")uÎ 1. Wall Assembly - Min 6 in. (152 mm) thick reinforced lightweight or normal weight ( pcf or kg/m3 ) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max opening shall be 1-1/2 in. (38 mm) larger than the outside dimension of the steel duct. See Concrete Blocks (CAZT) category in the Fire esistance Directory for names of manufacturers. 2. Steel Duct - Max 18 by 36 in. (457 by 914 mm) No. 26 gauge (or heavier) steel flat oval duct to be installed within the opening. The annular space within the firestop system shall be min 0 in. ( 0 mm, point contact) to max 1-1/2 in. (38 mm). Steel duct to be rigidly supported on both sides of the wall assembly. 3. Firestop System - The firestop system shall consist of the following: A. Packing Material - Polyethylene backer rod, mineral wool batt insulation or fiberglass batt insulation friction fit into annular space. Packing material to be recessed from both surfaces of wall to accommodate the required thickness of fill material (Item 3B). B. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of the wall. At the point contact location between the steel duct and the wall, a min 1/4 in. (6 mm) diam bead of sealant shall be applied at the wall/duct interface on both sides of the wall assembly. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant C. etaining Angles - Min 16 gauge galv steel angles sized to lap duct a min of 2 in. (51 mm) and to lap wall surfaces a min of 1 in. (25 mm). Angles attached to top and bottom of steel duct on both sides of wall. Angles attached to duct with min 1/2 in. (13 mm) long No. 10 (or larger) steel sheet metal screws located a max of 1 in. (25 mm) from each end of long side of duct and spaced a max of 4 in. (102 mm) OC. *Bearing the UL Classification Mark eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: January 2, 2009 W-J-7013 PAGE 1 OF 1

5 System No. W-J-7089 Ì68WJ0ÇfyÈAAÇ(8+!Î ANSI/UL1479 (ASTM E814) F ating - 2 Hr T ating - 0 Hr L ating At Ambient - Less Than 1 CFM/sq ft L ating At 400 F - Less Than 1 CFM/sq ft CAN/ULC S115 F ating - 2 Hr FT ating - 0 Hr FH ating - 2 Hr FTH ating - 0 Hr L ating At Ambient - Less Than 1 CFM/sq ft L ating At 400 F - Less Than 1 CFM/sq ft 1. Wall Assembly - Min 6 in. (152 mm) thick reinforced lightweight or normal weight ( pcf or kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max size of opening is 78 sq ft (7.2 m2) with a max width of 106 in. (2.7 m). See Concrete Blocks (CAZT) category in Fire esistance Directory for names of manufacturers 2. Steel Duct - Max 100 by 100 in. (2.5 by 2.5 m) steel duct to be installed within the framed opening. The duct shall be constructed and reinforced in accordance with SMACNA construction standards. Steel duct to be rigidly supported on both sides of wall assembly. 3. Batts and Blankets* - Nom 1-1/2 or 2 in. (38 or 51 mm) thick glass fiber batt or blanket (min 3/4 pcf or 12 kg/m3) jacketed on the outside with a foil-scrim-kraft facing. Longitudinal and transverse joints sealed with aluminum foil tape. During the installation of the fill material, the batt or blanket shall be compressed 50% such that the annular space within the firestop system shall be min 1/2 in. (13 mm) to max 2 in. (51 mm). See Batts and Blankets - (BKNV) category in the Building Materials Directory for names of manufacturers. Any batt or blanket meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index 50 or less may be used. 4. Firestop System - The firestop system shall consist of the following: A. Packing Material - Min 4-3/4 (121 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from both surfaces of wall as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant C. Steel etaining Angles - Min No. 16 gauge (0.059 in. or1.5 mm thick) galv steel angles sized to lap steel duct a min of 1 in. (25 mm) and lap wall surfaces a min of 2 in. (51 mm). Angles attached to steel duct on both sides of wall with min No. 10 steel sheet metal screws spaced a max of 1 in. (25 mm) from each end of steel duct and spaced a max of 6 in. (152 mm) OC. *Bearing the UL Classification Mark eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: August 24, 2011 W-J-7089 PAGE 1 OF 1

6 System No. W-L-7025 Ì81WL0Çf9ÈAAÇ(8+ÂÎ ANSI/UL1479 (ASTM E814) F atings - 1 and 2 Hr (See Item 1) T ating - 1/2 Hr L ating At Ambient - Less Than 1 CFM/sq ft L ating At 400 F - Less Than 1 CFM/sq ft CAN/ULC S115 F atings - 1 and 2 Hr (See Item 1) FT ating - 1/2 Hr FH atings - 1 and 2 Hr (See Item 1) FTH ating - 1/2 Hr L ating At Ambient - Less Than 1 CFM/sq ft L ating At 400 F - Less Than 1 CFM/sq ft A 3B 1A 3C 1A 3B A 2 1B Section A-A 1. Wall Assembly - The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U400 or V400 Series Wall or Partition Design in the UL Fire esistance Directory and shall include the following construction features: A. Studs - Wall framing shall consist of min 3-1/2 in. (89 mm) wide steel channel studs spaced max 24 in. (610 mm) OC. Additional steel studs shall be used to completely frame the opening. B. Gypsum Board* - 5/8 in. (16 mm) thick, 4 ft (1.22 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U400 or V400 Series Design in the UL Fire esistance Directory. Max area of opening is 73.7 sq ft (6.85 m2) with a max dimension of 104 in. (2.64 m). The hourly F ating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Steel Duct - Max 100 in. by 100 in. (2.54 by 2.54 m) No. 26 gauge (or heavier) galv steel duct to be installed either concentrically or eccentrically within the firestop system. The space between the steel duct and periphery of opening shall be min 0 in. ( 0 mm, point contact) to max 2 in. (51 mm). Steel duct to be rigidly supported on both sides of the wall assembly. 3. Firestop System - The firestop system shall consist of the following: A. Packing Material - (Optional, Not Shown) - Polyethylene backer rod, mineral wool batt insulation or fiberglass batt insulation friction fitted into annular space. Packing material to be recessed from both surfaces of wall as required to accommodate the required thickness of fill material. eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: August 24, 2011 W-L-7025 PAGE 1 OF 2

7 B. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall. Min 1/4 in. (6 mm) diam bead of fill material shall be applied at the point contact location between the steel duct and the gypsum board. For 2 hr ated walls when LC150 or LE600 Sealant is used, fill material thickness installed to full depth of gypsum board layers on each side of wall assembly. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant, SpecSeal LCI Sealant, SpecSeal LC150 Sealant or SpecSeal LE 600 Sealant. C. Steel etaining Angles - Min No. 16 gauge (0.059 in. or 15 mm) galv steel angles sized to lap steel duct a min of 2 in. (51 mm) and to lap wall surfaces a min of 1 in. (25 mm). Angles attached to steel duct on both sides of wall with min No. 10 by 1/2 in. (13 mm) long steel sheet metal screws located a max of 1 in. (25 mm) from each end of steel duct and spaced a max of 6 in. (152 mm) OC. *Bearing the UL Classification Mark eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: August 24, 2011 W-L-7025 PAGE 2 OF 2

8 System No. W-L-7026 Ì80WL0Çf:ÈAAÇ(8+&Î ANSI/UL1479 (ASTM E814) F atings - 1 and 2 Hr (See Item 1) T ating - 0 Hr L ating At Ambient - Less Than 1 CFM/sq ft L ating At 400 F - Less Than 1 CFM/sq ft CAN/ULC S115 F atings - 1 and 2 Hr (See Item 1) FT ating - 0 Hr FH atings - 1 and 2 Hr (See Item 1) FTH ating - 0 Hr L ating At Ambient - Less Than 1 CFM/sq ft L ating At 400 F - Less Than 1 CFM/sq ft 3A A 3A 1A A 2 Section A-A 1. Wall Assembly - The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U400 or V400 Series Wall and Partition Designs in the UL Fire esistance Directory and shall include the following construction features: A. Studs - Wall framing shall consist of min 3-1/2 in. (89 mm) wide steel channel studs spaced max 24 in. (610 mm) OC. When diam of opening exceeds width of stud cavity, additional lengths of steel stud installed to frame out opening around steel duct (Item 2). B. Gypsum Board* - 5/8 in. (16 mm) thick, 4 ft (1.22 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U400 or V400 Series Design in the UL Fire esistance Directory. Max diam of opening is 25-1/2 in. (648 mm). The hourly F ating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Steel Duct - Max 24 in. (610 mm) diam No. 28 gauge (or heavier) galv steel vent duct or No. 26 gauge (or heavier) spiral wound galv steel duct. One steel duct to be installed either concentrically or eccentrically within the firestop system. An annular space of min 0 in. (0 mm, point contact) to max 1-1/2 in. (38 mm) is required within the firestop system. Steel duct to be rigidly supported on both sides of the wall assembly. 3. Firestop System - The firestop system shall consist of the following: A. Packing Material - (Optional, Not Shown) - Polyethylene backer rod, mineral wool batt insulation or fiberglass batt insulation friction fit into annular space for 2 hr rated wall assemblies only. Packing material to be recessed from both surfaces of wall to accommodate the required thickness of fill material (Item 3B). B. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall. Min 1/4 in. (6 mm) diam bead of fill material shall be applied at the point contact location between the steel duct and the gypsum board. For 2 hr ated walls when LC150 or LE600 Sealant is used, fill material thickness installed to full depth of gypsum board layers on each side of wall assembly. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant, SpecSeal LC150 Sealant, or SpecSeal LE600 Sealant *Bearing the UL Classification Mark 3A 1B eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: August 24, 2011 W-L-7026 PAGE 1 OF 1

9 F atings - 1 and 2 Hr (See Item 1) T ating - 0 Hr Ì82WL0ÇfAÈAAÇ!")QÎ 1A 3C A 3B 3B 1A 3A 2 A 3C Section A-A 1B 1. Wall Assembly - The 1 or 2 hr fire-rated gypsum wallboard/steel stud wall assembly shall be constructed of the materials and in the manner described in the individual U400 or V400 Series Wall or Partition Designs in the UL Fire esistance Directory and shall include the following construction features: A. Studs - Wall framing shall consist of min 3-1/2 in. (89 mm) wide steel channel studs spaced max 24 in. (610 mm) OC. Additional steel studs shall be used to completely frame the opening. B. Gypsum Board* - 5/8 in. (16 mm) thick, 4 ft (1.22 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U400 or V400 Series Designs in the UL Fire esistance Directory. Max opening size shall be 1-1/2 in. (38 mm) larger than the outside dimensions of the steel duct. The hourly F atings of the firestop system is dependent upon the hourly fire rating of the wall assembly in which it is installed. 2. Steel Duct - Max 18 by 36 in. (457 by 914 mm) No. 26 gauge (or heavier) steel flat oval duct to be installed within the framed opening. The annular space within the firestop system shall be min 0 in. (0 mm, point contact) to max 1-1/2 in. (38 mm). Steel duct to be rigidly supported on both sides of the wall assembly. 3. Firestop System - The firestop system shall consist of the following: A. Packing Material - Polyethylene backer rod, mineral wool batt insulation or fiberglass batt insulation friction fit into annular space. Packing material to be recessed from both surfaces of wall to accommodate the required thickness of fill material (Item 3B). B. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm)_ thickness of fill material applied within annulus, flush with both surfaces of the wall. At the point contact location between the steel duct and the wallboard, a min 1/4 in. (6 mm) diam bead of sealant shall be applied at the wall/duct interface on both surfaces of the wall assembly. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant C. etaining Angles - Min 16 gauge galv steel angles sized to lap onto duct a min of 2 in. (51 mm) and to lap onto wall surfaces a min of 1 in. (25 mm). Angles attached to top and bottom of steel duct on both sides of wall. Angles attached to duct with min 1/2 in. (13 mm) long, No. 10 (or larger) steel sheet metal screws located a max of 1 in. (25 mm) from each end of long side of duct and spaced a max of 4 in. (102 mm) OC. *Bearing the UL Classification Mark eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: January 2, 2009 W-L-7033 PAGE 1 OF 1

10 System No. W-L-7149 Ì74WL0ÇgQÈAAÇ(8+ÉÎ ANSI/UL1479 (ASTM E814) F atings - 1 and 2 Hr (See Item 1) T ating - 0 Hr L ating At Ambient - Less Than 1 CFM/sq ft L ating At 400 F - Less Than 1 CFM/sq ft CAN/ULC S115 F atings - 1 and 2 Hr (See Item 1) FT ating - 0 Hr FH atings - 1 and 2 Hr (See Item 1) FTH ating - 0 Hr L ating At Ambient - Less Than 1 CFM/sq ft L ating At 400 F - Less Than 1 CFM/sq ft 1. Wall Assembly - The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire esistance Directory and shall include the following construction features: A. Studs - Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. Additional framing members shall be used to completely frame around opening. B. Gypsum Board* - Min 5/8 in. (16 mm) thick, 4 ft (1.2 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers and orientation shall be as specified in the individual U300, U400 or V400 Wall and Partition Design. Max size of opening is 210 sq in. (1355 cm2) with a max width of 14-1/2 in. (368 mm) for wood studs. Max size of opening is 78 sq ft. (7.2 m2) with a max width of 106 in. (2.7 m) for steel studs. The hourly F ating of the firestop system is equal to the hourly fire rating of the wall in which it is installed. 2. Steel Duct - Max 100 by 100 in. (2.5 by 2.5 m) steel duct to be installed within the framed opening. The duct shall be constructed and reinforced in accordance with SMACNA construction standards. Steel duct to be rigidly supported on both sides of wall assembly. 3. Batts and Blankets* - Nom 1-1/2 or 2 in. (38 or 51 mm) thick glass fiber batt or blanket (min 3/4 pcf or 12 kg/m3) jacketed on the outside with a foil-scrim-kraft facing. Longitudinal and transverse joints sealed with aluminum foil tape. During the installation of the fill material, the batt or blanket shall be compressed 50% such that the annular space within the firestop system shall be min 1/2 in. (13 mm) to max 2 in. (51 mm). See Batts and Blankets (BKNV) category in the Building Materials Directory for names of manufacturers. Any batt or blanket meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index 50 or less may be used. eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: August 24, 2011 W-L-7149 PAGE 1 OF 2

11 4. Firestop System - The firestop system shall consist of the following: A. Packing Material - Min 3-5/8 (92 mm) or 4-7/8 in. (124 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanent form for 1 or 2 hr fire-rated walls, respectively. Packing material to be recessed from both surfaces of wall as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant C. Steel etaining Angles - Min No. 16 gauge (0.059 in. (1.5 mm)) galv steel angles sized to lap steel duct a min of 1 in. (25 mm) and lap wall surfaces a min of 2 in. (51 mm). Angles attached to steel duct on both sides of wall with min No. 10 steel sheet metal screws spaced a max of 1 in. (25 mm) from each end of steel duct and spaced a max of 6 in. (152 mm) OC. *Bearing the UL Classification Mark eproduced courtesy of Underwriters Laboratories, Inc. Created or evised: August 24, 2011 W-L-7149 PAGE 2OF 2

12 GENEAL CETIFICATE OF CONFOMANCE January 25, 2011 Description: SpecSeal Firestop Products; Pensil Silicone Sealants; EZ-Path Fire ated Pathways; eady Sleeve Firestop Sleeves; STI Firestop Products Included Products: SpecSeal Series SSS Intumescent Sealant SpecSeal Series LCI Intumescent Sealant SpecSeal Series LC Firestop Sealant SpecSeal Series ES Elastomeric Sealant SpecSeal Series SIL300 Silicone Sealant SpecSeal Series SIL300SL Silicone Sealant Pensil PEN300 Silicone Sealant Pensil PEN300SL Silicone Sealant Pensil PEN200 Silicone Foam Type WF300 Firestop Caulk SpecSeal Series AS200 Elastomeric Spray SpecSeal Series FT Fast Tack Firestop Spray SpecSeal Series SSP Putty & Putty Pads SpecSeal Series EP PowerShield Box Insert SpecSeal Series SSM Firestop Mortar SpecSeal Series SSB Firestop Pillows SpecSeal Series CS Composite Sheet SpecSeal Series SSW Wrap Strips SpecSeal Series LCC Firestop Collars SpecSeal Series SSC Firestop Collars SpecSeal Series TC Firestop Collars SpecSeal Series FP Firestop Plugs SpecSeal Series CD Cast-In Firestop Devices FyreFlange Firestop Angle EZ-Path Series 22 EZ-Path Series 33 EZ-Path Series 44 or 44+ eady Sleeve eady Sleeve Split eady Firestop Grommet SpecSeal Series SSAMW Mineral Wool SpecSeal SpeedFlex Fire ated Joint Profile These products are tested to one or more of the following standards: ASTM E814 (ANSI/UL1479) Standard Test Method for Fire Tests of Penetration Firestop Systems ASTM E1966 (ANSI/UL2079) Standard Test Method for Fire-esistive Joint Systems ASTM E119 (ANSI/UL263) Standard Test Methods for Fire Tests of Building Construction and Materials ASTM E2307 Standard Test Method for Determining Fire esistance of Perimeter Fire Barrier Systems Using Intermediate Scale, Multi-Story Test Apparatus ASTM E1399 Standard Test Method for Cyclic Movement and Measuring the Minimum and Maximum Joint Widths of Architectural Joint Systems ASTM E84 (ANSI/UL723) Standard Test Method for Surface Burning Characteristics of Building Materials CAN/ULC S115 Standard Method of Fire Tests of Firestop Systems CAN/ULC S101 Standard Methods of Fire Endurance Tests of Building Construction and Materials IMO esolution A.754(18) Chemical Content Statement: No asbestos, PCB s, lead, or water-soluble intumescent ingredients are used or contained in these products. James P. Stahl Jr., CFPS Vice President of Engineering Paul M. Jankowski Quality Control Manager Certificate of Conformance Technical Service

13 PODUCT DATA SHEET SEIES SSS INTUMESCENT SEALANT APPLICATIONS SpecSeal Series SSS Sealant is used to seal through-penetrations as well as construction gaps and blank openings. SpecSeal Series SSS has been tested for use with metallic penetrants up to 30" (762 mm) trade size. This product is also used with other SpecSeal Products such as SpecSeal Firestop Collars and Wrap Strips. See Table A for a summary application list. PODUCT DESCIPTION SpecSeal Series SSS Sealant is a latex based, high solids firestop compound. This material, when properly installed, will effectively seal penetration openings against the spread of fire, smoke, toxic gasses and water. SpecSeal Series SSS Sealant features STI s patented and proprietary two-stage intumescent technology. When exposed to high temperatures or fire, this material expands aggressively in a highly directionalized fashion to quickly close off voids left by the burning or melting of combustible materials. SpecSeal Series SSS Sealant s unique multi-viscosity formula yields a single grade that has excellent caulking properties as well as high build properties on vertical or overhead surfaces. This single grade may be pumped, caulked (standard cartridge or bulk loaded), knifed or troweled. In addition, SpecSeal Series SSS Sealant does not contain PCB s or asbestos. SpecSeal Series SSS Sealant is storage stable (when stored according to the manufacturer s recommendations) and will not separate nor shrink when dried. SpecSeal Series SSS Sealant will adhere to all common construction and penetrant materials and contains no solvents that might adversely effect plastic pipes or cable jackets. FEATUE BENEFIT PEFOMANCE Water-Based Easy installation, cleanup, and disposal. Two-Stage Intumescence Extremely fast and directionalized expansion. Endothermic Fillers Absorb heat & release water. High Solids Formula No shrinkage! Sandable & Paintable (when dry) Water-esistant Will not re-emulsify when dry! Safe Safe for contact with plastics. ed Color Easy identification and inspection. Multi Viscosity Grade Excellent caulking properties along with high build capabilities. Excellent Smoke Seal SpecSeal Series SSS Sealant is the basis for systems that meet the exacting criteria of ASTM E814 (UL1479) as well as the time-temperature requirements of ASTM E119 (UL263). Systems have been tested for all common forms of construction and most common penetrants with ratings up to 4 hours. STI firestop systems are designed to maximize the fire resistance of the seal by not only sealing off the spread of fire and hot gasses but also by minimizing the amount of heat conducted through the assembly. Thus all systems have been designed to provide T atings capable of matching the rating of the wall or floor assembly (where possible) when tested without penetrants. PHYSICAL POPETIES Properties Color Odor Density FILL, VOID O CAVITY MATEIALS FO USE IN JOINT SYSTEMS AND THOUGH-PENETATION FIESTOP SYSTEMS. SEE UL DIECTOY OF PODUCTS CETIFIED FO CANADA AND UL FIE ESISTANCE DIECTOY. 3L73 Series SSS ed Mild Latex 9.4 lb/gal (1.13 kg/l) Solids Content 80% ± 2% ph 8.3 In Service Temperature Storage Temperature Flame Spread 0* Smoke Developed* 10* -10 F (-23 C) F (85 C) 40 F (4 C) - 95 F (35 C) Properties STC ating (ASTM E90/ASTM C919) 62 VOC Content (EPA Method 24/ASTM D3960) Shelf Life Expansion Begins Expansion ange Volume Expansion Series SSS 0.18 lbs/gal (22.0 g/l) 2 yrs 230 F (110 C) 1st Stage 350 F (177 C) 2nd Stage 230 F to > 1,000 F (110 C to > 538 C) > 500% Free Expansion * Tested to ASTM E84 (UL723) at 14% surface coverage (modified test for sealants and caulks) Technical Service STI Product Data Sheet Series SSS Intumescent Sealant FOD /2010 1

14 Table A: APPLICATIONS TESTED AND CLASSIFIED FO FIE ESISTANCE Metallic Pipes including steel, iron, or copper pipe and tubing through all common constructions. Nonmetallic Pipes, Conduits &Tubing including PVC, CPVC, PVDF, PEX, PEX- AL-PEX, ABS, PB through all common constructions. Cable, Cable Trays & Bus Duct HVAC Ductwork Insulated Pipes Multi-Service Penetrations including AC line sets, electrical, telephone, or TV service entrance and interior penetrations. Complete Wood Floor firestopping package for electrical, plumbing, HVAC, TV and telephone. SPECIFICATIONS The firestopping sealant shall be a one-part, two-stage intumescent latex compound. The sealant when exposed to high heat or flame shall be capable of expanding a minimum of 8 times. ange of continuing expansion shall be from 230 F to >1,000 F (110 C to > 538 C). The sealant shall be thixotropic and shall be capable of caulking or troweling onto vertical surfaces or overhead. The sealant shall be UL Classified and/or FM Systems Approved and tested to the requirements of ASTM E814 (UL1479). Shown below and on the following page are just a few of the most common applications for SpecSeal Series SSS Sealant. Consult the Technical Library at for over 200 available designs utilizing this product. Fig. 1: METALLIC PIPE PENETATIONS - CONCETE/MASONY FLOOS & WALLS UL SYSTEM C-AJ-1079 F ating: 4 Hr T ating: 0 Steel or Iron Pipe: 24", Copper Pipe 6" Annulus: Point Contact to 4" S alant Depth: 1/2" Forming Material: Nom 4 pcf Mineral Wool Thickness: 1-1/2" for 6" Steel or Iron Pipe 3" for 4" Copper or 6" Iron or Steel Pipe Fig. 2: INSULATED METALLIC PIPE PENETATIONS - CONCETE/MASONY FLOOS & WALLS UL SYSTEM C-AJ-1217 F ating: 4 Hr T ating: 0 Steel or Iron Pipe: 30", Copper Pipe 6" Annulus: Point Contact to 2" S alant Depth: 1/2" Forming Material: Nom 4 pcf Mineral Wool Tightly Packed to a 3" Depth. SPECIFIED DIVISIONS DIV Through-Penetration Firestopping DIV Special Construction Fire Suppression & Supervisory Systems DIV Mechanical Insulation Fire Protection DIV Basic Electrical Materials & Methods SEALANT EQUIEMENTS IN CUBIC INCHES PE 1/4 INCH OF INSTALLED DEPTH* Pipe Size Trade Pipe UL SYSTEM C-AJ-5087 F ating: 2 Hr T ating: 1 Steel or Iron Pipe: 24" Insulated with 2" Thick Fiber Glass or Mineral Wool Pipe Insulation Annulus: 1/2" to 1-1/2" Sealant Depth: 1/2" Forming Material: Nom 4 pcf Mineral Wool Tightly Packed to a 4" Depth. Diameter of Opening (in.) Size O.D. 0.5" " " " " " " " " *Different Sealant Depth? /2" Multiply by 2 8" /8" Multiply by " " Multiply by " /4" Multiply by " IMPOTANT NOTE: This table is for estimation purposes only. Consult UL Fire esistance Directory or STI Product & Application Guide for specific installation requirements and limitations Metric Estimation Table available upon request. 2 Technical Service STI Product Data Sheet Series SSS Intumescent Sealant FOD /2010

15 INSTALLATION INSTUCTIONS General: Areas to be protected must be clean and free of oil, loose dirt, rust or scale. Installation temperatures must be between 35 F and 100 F (2 C and 38 C). Allow product to dry a minimum of 24 hours before exposure to moisture. System Selection: Selection of an appropriate firestop system design is critical to the fire protection process. Space limitations preclude highly detailed information pertaining to individual application systems. Please consult the STI Product & Application Guide as well as the UL Fire esistance Directory for additional information. Forming: Some installations may require forming as either an integral part of the system or as an option to facilitate installation. In systems where forming is required, mineral wool batts (min. nom. 4 lb/cu. ft (64 kg/ m 3 ) density) are recommended. Some gypsum wallboard systems utilize fiberglass. Cut forming material over-size to allow for tight packing. Position forming material to allow for the proper depth of fill material. Fill Material: SpecSeal Series SSS Sealant may be installed by caulking using a standard caulking gun or from bulk containers using a bulk loading caulk gun, or by manually troweling using a mason s trowel or putty knife. If the sealant tends to pull back from a surface, clean the surface with a damp rag or sponge and reapply. Work sealant into all areas exercising care to eliminate voids or seams. The surface of the sealant can be smoothed using a putty knife dipped in water. Adding water to the sealant itself is not recommended. Sealant (when dry) may be sanded and painted using most non-solvent based paints. In gypsum wallboard penetrations, crown sealant 1/4" (6 mm) from penetrant to wallboard surface at a point approximately 1/2" (13 mm) or more from opening. Sealant (ehen dry) may be painted using most non-solvent based paints, Smoke Sealing: In some applications including firestop collars, SpecSeal Series SSS Sealant is recommended as a smoke seal. It is suggested in these application that the sealant be applied to both sides of walls. In floor applications, a sealing bead is suggested top and bottom. Fig. 3: ELECTICAL, DATA O COMMUNICATIONS PENETATIONS - ATED GYPSUM WALLBOAD ASSEMBLIES UL SYSTEM W-L-3076 F ating: 1 or 2 Hr T ating: 0 hr Up to 4" Cable Bundle Centered in 4-1/2" Opening Sealant Depth: 5/8" with 1/4" Crown Fig. 4: ELECTICAL PENETATIONS - CONCETE/MASONY FLOOS & WALLS UL SYSTEM C-AJ-3154 F ating: 1, 2, 3 & 4 Hr T ating: 0, 1/2, & 2 3/4 Hr Optional Sleeve-PVC or Steel Electrical, Telephone or Data Cables Annulus: 0" to 2" Sealant Depth: 1/2" Forming Materials: Nom 4 pcf Mineral Wool Sealant Depth: 1/2 for 1, 2, 3 Hr; 1 for 4 Hr Fig. 5: BAE & INSULATED METALLIC PIPE PENETATIONS - ATED GYPSUM WALLBOAD ASSEMBLIES UL SYSTEM W-L-2093 F ating: 1 or 2 Hr T ating: 1, 1-1/2 Hr 2" igid PVC, ENMT, or Optical Fiber aceway. 1-1/4" PVDF Optical Fiber aceway. Sealant Depth: 5/8" with 1/4" Crown UL SYSTEM C-AJ-6008 F ating: 3 Hr T ating: 0 Hr Aluminum or Copper Bus Duct 5,000 Amp Steel Cover Plate Sealant Depth: 1/2" Forming Materials: Nom 4 pcf Mineral Wool Tightly Packed to a depth of 1-1/2" UL SYSTEM W-L-1049 F ating: 2 hr T ating: 0 hr Steel or Iron Pipe: 24", Copper Pipe: 6" Annulus: Point Contact to 2" Sealant Depth: 5/8" with 3/8" Crown UL SYSTEM W-L-5014 F ating: 1 & 2 Hr T ating: 1 & 2 hr Steel or Iron Pipe: 12", Copper Pipe: 4" Insulated with 2" Thick Fiber Glass or Mineral Wool Pipe Insulation Annulus: 0" to 1-1/4" Sealant Depth: 5/8" with 3/8" Crown UL SYSTEM W-L-5051 F ating: 1 & 2 Hr T ating: 3/4, 1, 1-1/2 & 2 Hr Steel or Iron Pipe: 16", Copper Pipe: 6 Foam Glass Pipe Insulation: 1 to 3 Thick 12" Wide 0.010" Thick Metal Jacket Wrapped Around Insulation and Secured with Metal Banding as Shown Annulus: 0 to 1-1/2" Sealant Depth: 5/8" Technical Service STI Product Data Sheet Series SSS Intumescent Sealant FOD /2010 3

16 INSTALLATION INSTUCTIONS LIMITATIONS: SpecSeal Series SSS Sealant is water-based and cures through the evaporation of water. Low temperatures as well as high humidity may retard drying. Non-porous or impermeable backing materials, plates, or coatings may retard the drying process. Do not paint or seal in any way that prevents contact with air until sealant has dried through completely. This product has been designed to be safe with plastics and has been used extensively and successfully with a variety of different types of plastic pipes, tubes, and plastic cable insulations. Variations in these materials however, make it impossible to guarantee compatibility. STI strongly recommends that the user consult with the manufacturer of the pipe, tubing, or cable in question regarding any known sensitivities or potential restrictions before applying this product. MAINTENANCE Inspection: Installations should be inspected periodically for subsequent damage. Any damage should be repaired using SpecSeal products per the original approved design. etrofit: When adding or removing penetrants, care should be taken to minimize damage to the seal. eseal using SpecSeal products per the approved design. NOTE: New penetrants of a different nature than the original design may require a totally new firestop design or extensive modifications to the existing design. eseal all openings as per the requirements of the modified design. TECHNICAL SEVICE Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL Systems, Material Safety Data Sheets and other technical information is available through the Technical Library at PECAUTIONAY INFOMATION Consult Material Safety Data Sheet for additional information on the safe handling and disposal of this material. Wash areas of skin contact with soap and water. Avoid contact with eyes. SEALANT IS CONDUCTIVE UNTIL DY. AVAILABILITY SpecSeal Series SSS Sealant is available from authorized STI distributors. Consult factory or website for the names and locations of the nearest sales representatives or distributors. CATALOG NUMBE DESCIPTION SSS100 SSS129 SSS120 SSS102 SSS oz. Tube (300 ml) 18.2 cu.in. 29 oz. Tube (858 ml) 52 cu. in. 20 oz. Sausage (592 ml) 36 cu. in. 2 Gal. Pail (7.6 liters) 462 cu.in. 5 Gal. Pail (19.0 liters) 1,155 cu.in. CITY OF NEW YOK MEA M IMPOTANT NOTICE: All statements, technical information, and recommendations contained herein are based upon testing believed to be reliable, but the accuracy and completeness thereof is not guaranteed. WAANTY Specified Technologies Inc. manufactures its goods in a manner to be free of defects. Should any defect occur in its goods (within one year), Specified Technologies Inc., upon prompt notification, will at its option, exchange or repair the goods or refund the purchase price. LIMITATIONS AND EXCLUSIONS: THIS WAANTY IS IN LIEU OF ALL OTHE EPESENTATIONS EXPESSED O IMPLIED (INCLUDING THE IMPLIED WAANTIES OF MECHANTABILITY O FITNESS FO USE) AND UNDE NO CICUMSTANCES SHALL SPECIFIED TECHNOLOGIES INC. BE ESPONSIBLE FO ANY INCIDENTAL O CONSEQUENTIAL POPETY DAMAGE O LOSSES. PIO TO USE, THE USE SHALL DETEMINE THE SUITABILITY OF THE PODUCT FO ITS INTENDED USE, AND THE USE ASSUMES ALL ISKS AND LIABILITY FO SUBSEQUENT USE. No statement or recommendation not contained herein shall have any force or effect unless in an agreement signed by officers of seller and manufacturer. MADE IN THE USA COPYIGHT 2010 SPECIFIED TECHNOLOGIES INC. Specified Technologies Inc. 210 Evans Way, Somerville, NJ USA Phone: Fax: Technical Service STI Product Data Sheet Series SSS Intumescent Sealant FOD /2010