1 Architectural Inspection Building Assessment Survey Asset: P.S STATEN ISLAND, 450 BUEL AVENUE, New York, Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior :44 AM :55 PM AA : Architectural - Associate :38 AM :17 PM Asset Data Was the building fully accessible for inspection Inspection Access Comment Principal(s) Information Custodian Fireman Principal Name Organization Did you meet with this Principal? Did this Principal provide feedback? Summary of Principal's Feedback Answer Building Square Footage Comments on the Area Comments on the Stories (Floors) plus Basements 3+B Comments on the Number of Classrooms 34 No Shower Room was being used for storage Jane McCord P.S Staten Island Yes Yes The Principal's comments are as follows: 1. New grass paver permeability is not functioning properly. 2. One boiler needs to have a control panel replaced. 3. Old pipe insulation was only partially removed during recent work in Basement and is in disrepair. 4. The Playground is on the property of the Parks Department and there is a clogged drain where students play. 5. Countertops and cabinets in classrooms are in disrepair. 6. Student and staff toilet room tile is in need of replacement. 7. School is awaiting new exterior security cameras and new air conditioning in the Cafeteria. Thomas Maddocks Nicholas Anderson None Comments on the Year Built 1965 Student Population 525 Staff Population 100 Weather Facade Photo Fair Corner of Buel Avenue and Nugent Avenue - West view PB/A&W Page 1 of 43

2 Main Entrance Photo Building Assessment Survey Roof Photo Facade A - Buel Avenue Roof 1 - Northwest view Have any Systems/Major Building Components been upgraded? Yes Systems: Basement Waterproofing including new Windows for emergency egress and full Concrete Slab on Grade reconstruction, Foundation Wall reinforcement, Boiler Room and Electrical Room equipment upgrades, new Playground structures, partial Door replacement Year: 2017 Systems: New Areaway Walls and Gratings at AW1, 2 and 3, New Ash Hoist Doors and Slab Year: 2016 Systems: Exterior Masonry repointing (Buel Avenue), Exterior Door repairs (2004 wing) Year: 2015 Systems: Partial Basement waterproofing Year: 2014 Systems: Partial Exterior Wall repointing Year: 2008 Systems: Windows/Window Guards full replacement, partial Exterior Door replacement Year: 2004 Systems: Full Roofing replacement - Original wing Year: 1998 PB/A&W Page 2 of 43

3 Building Assessment Survey Architectural Inspection Have there been any New Building Additions? Yes Comments on New Building Additions 2004 (+5,000 SF) Tandem Schools? No Leased Space? No Priority Priority Exist Last Year? Priority Category Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No condition recorded Structural Engineer Required Structural Type Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No condition recorded Accessibility Accessibility Status Is the primary or secondary entrance on an accessible route? Is the building a multi-story building? Are all floors of the building accessible through compliant means? Accessible classrooms exists on each floor? Boys and Girls or Unisex accessible toilets exist on at least every other floor? If the following spaces exist, are they ALL accessible? Art Room, Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs Yes Yes Yes Yes Yes Yes Physical Breakdown Structure Exists Complies Required FUNCTIONAL ACCESSIBILITY Exterior Routes Exterior Entrances & Exits Yes Exterior H/C Lifts No No Exterior Ramps and Railings Yes Yes Interior Routes Corridor and Lobby H/C Lifts No No Interior Corridor Doors and Hardware Yes Yes Interior Corridors and Lobbies Yes Interior Elevators Yes Yes Interior Lobby Doors and Hardware Yes Interior Ramps No Rooms & Spaces Art Rooms No Auditorium 1st Floor Yes Cafeteria 1st Floor Yes Classrooms 1st-3rd Floors Yes Computer Rooms No Gymnasium 1st Floor Yes Library Room 204 Yes Main Office Room 114 Yes Multi-purpose Room No Nurse's Room Room 120 Yes Pool No PB/A&W Page 3 of 43

4 Building Assessment Survey Physical Breakdown Structure Exists Complies Required Rooms & Spaces Science Lab No Toilet Rooms (Boys) 1st-3rd Floors Yes Toilet Rooms (Girls) 1st-3rd Floors Yes Toilet Rooms (Staff) 1st Floor Yes Building Template Inspection Architectural AREAWAY Instance on AW1-AW4 Instance 3 - Fair Instance Quantity 4 Instance EACH AREAWAY STAIRS: DETERIORATED MATERIAL SLIDE Quantity 20 REPAIR PB/A&W Page 4 of 43

5 AREAWAY Photo1 Building Assessment Survey AWNINGS AND CANOPIES AW4 4 - Between Fair and Poor CONCRETE: WATER PENETRATION Quantity 30 REPAIR Urgency of Action PRIORITY 5 Photo1 Facade A CONCRETE: MAJOR CRACKS/SPALLING PB/A&W Page 5 of 43

6 AWNINGS AND CANOPIES Building Assessment Survey Quantity 100 REPAIR Urgency of Action PRIORITY 4 Photo1 CHIMNEY Material Type(s) Facade A Masonry 3 - Fair BRICK: OPEN JOINTS Quantity 60 REPOINT PB/A&W Page 6 of 43

7 CHIMNEY Photo1 Building Assessment Survey COPING CORNICE DOORS DOORS AND FRAMES Roof Fair METAL: DETERIORATED DOOR AND FRAME - MAJOR DETERIORATION Quantity 2 EACH Urgency of Action PRIORITY 4 Photo1 DOOR HARDWARE Facade B Exit 7 (frames only) PB/A&W Page 7 of 43

8 Building Assessment Survey Architectural Inspection DOORS LINTELS TRANSOM/SIDE LIGHT WALLS Material Type(s) Masonry Replacement Quantity 30,000 Replacement Uom Instance on All Facades Instance 3 - Fair Instance Quantity 30,000 Instance BRICK: MASONRY SILLS - OPEN JOINTS Elevation Quantity 10 L.F. REPOINT Photo1 Facade C1 PB/A&W Page 8 of 43

9 WALLS Building Assessment Survey GLASS BLOCK: RUSTED SUB-FRAME Elevation Quantity 20 L.F. -IN-KIND Photo1 Facade C1 GLASS BLOCK: OPEN JOINTS PB/A&W Page 9 of 43

10 WALLS Elevation Building Assessment Survey Quantity 30 REPOINT Photo1 Facade C1 GLASS BLOCK: CHIPPED/ BROKEN PIECES Elevation Quantity 10 -IN-KIND PB/A&W Page 10 of 43

11 Building Assessment Survey Architectural Inspection WALLS Urgency of Action PRIORITY 5 Photo1 Facade C1 BRICK: MAJOR / THRU CRACKS Elevation Quantity 15 REMOVE AND REBUILD Urgency of Action PRIORITY 4 Photo1 Facade B PB/A&W Page 11 of 43

12 WALLS Building Assessment Survey BRICK: MINOR CRACKS AND SPALLING Elevation Quantity 100 RESTITCH Photo1 Facade A BRICK: OPEN JOINTS PB/A&W Page 12 of 43

13 WALLS Elevation Building Assessment Survey Quantity 30 REPOINT Urgency of Action PRIORITY 4 Photo1 Facade C missing mortar BRICK: OPEN JOINTS Elevation Quantity 800 REPOINT PB/A&W Page 13 of 43

14 Building Assessment Survey Architectural Inspection WALLS Photo1 Facade A typical weathered joints shown BRICK: DETERIORATED MASONRY SILLS Elevation Quantity 40 L.F. REPAIR Urgency of Action PRIORITY 4 Photo1 Facade B PB/A&W Page 14 of 43

15 WALLS Building Assessment Survey CONCRETE MASONRY UNIT: DETERIORATED CONTROL/EXPANSION JOINTS WITH DAMAGED CAULKING Elevation Quantity 75 L.F. MAINTENANCE Photo1 SOFFITS LOADING DOCK LOUVER PARAPETS Material Type(s) No photo recorded Masonry Replacement Quantity 1,000 Replacement Uom Instance on Facades A, F and partial E Instance C.F. Instance Quantity 1,000 Instance PLAZA DECK ROOF Roofing C.F. PB/A&W Page 15 of 43

16 Building Assessment Survey Architectural Inspection ROOF Roofing Replacement Quantity 37,000 Replacement Uom ROOF HATCH/SMOKE HATCH 5 - Poor WATER INFILTRATION Quantity 1 EACH REPAIR Urgency of Action PRIORITY 5 Photo1 Roof 3 RH DETERIORATED Quantity 1 EACH MAINTENANCE Urgency of Action PRIORITY 4 PB/A&W Page 16 of 43

17 ROOF Roofing ROOF HATCH/SMOKE HATCH Photo1 Building Assessment Survey Roof 3 LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS 5 - Poor CLOGGED Quantity 2 EACH MAINTENANCE Urgency of Action PRIORITY 5 Photo1 ROOF BARRIER Standing water Roof 1 BH1 3 - Fair RAILINGS/PANELS: DETERIORATED, MINOR RUSTING PB/A&W Page 17 of 43

18 ROOF Roofing ROOF BARRIER Building Assessment Survey Quantity 50 MAINTENANCE Photo1 ROOF CAGE ROOF FENCE ROOFING Instance on Built-Up: Built-Up: Roofs 1, 2 and 3 Instance No photo recorded 3 - Fair Instance Quantity 31,000 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 2004 Source of Installation Instance on Single Ply, Fully Adhered Roof: Single Ply, Fully Adhered Roof: Roof 4 Instance No Documented Instance Quantity 6,000 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 2004 Source of Installation 4 - Between Fair and Poor No Documented SINGLE PLY, FULLY ADHERED ROOF: ROOFING: MAJOR ACTIVE ROOF LEAKS IN INSTRUCTIONAL SPACE PB/A&W Page 18 of 43

19 ROOF Roofing ROOFING Building Assessment Survey Quantity 100 Urgency of Action PRIORITY 5 Photo1 ROOFING WITHOUT MAJOR EQUIPMENT REMOVAL ROOFING DRAINS Roof 4 above Room 156 (no damage visible in Room 156 at the time of inspection) 5 - Poor DETERIORATED Quantity 3 EACH Urgency of Action PRIORITY 4 PB/A&W Page 19 of 43

20 ROOF Roofing ROOFING DRAINS Photo1 Building Assessment Survey Specialties BULKHEAD/PENTHOUSE Roof Fair BULKHEAD/PENTHOUSE WALLS/: CRACKS/SPALLING - MINOR Quantity 20 REPAIR Photo1 Roof 1 BH2 BULKHEAD/PENTHOUSE WALLS/: OPEN JOINTS PB/A&W Page 20 of 43

21 ROOF Specialties BULKHEAD/PENTHOUSE Building Assessment Survey Quantity 200 REPOINT Photo1 CUPOLA/ SPIRES/ TOWERS DORMER DUNNAGE STEEL SKYLIGHT/ROOF VENT Material Type(s) BH 1 Glass 4 - Between Fair and Poor DAMAGED FLASHING Quantity 20 L.F. MAINTENANCE PB/A&W Page 21 of 43

22 ROOF Specialties SKYLIGHT/ROOF VENT Photo1 Building Assessment Survey No photo recorded ROOF/GRAVITY TANK STAIRS/RAMPS: BUILDING CHEEK/FLANK WALLS 3 - Fair CAST IN PLACE CONCRETE: CRACKS/SPALLING - MINOR Quantity 10 REPAIR Photo1 Facade C CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR Quantity 15 PB/A&W Page 22 of 43

23 Building Assessment Survey Architectural Inspection STAIRS/RAMPS: BUILDING CHEEK/FLANK WALLS Urgency of Action PRIORITY 4 Photo1 RAILINGS Facade B 3 - Fair RUST - MINOR Quantity 50 L.F. MAINTENANCE Photo1 STAIRS/RAMPS Facade C 3 - Fair CONCRETE: CRACKS/SPALLING - MINOR PB/A&W Page 23 of 43

24 STAIRS/RAMPS: STAIRS/RAMPS Building Assessment Survey Quantity 20 REPAIR Photo1 Facade C STONE: OPEN JOINTS Quantity 40 L.F. REPOINT Urgency of Action PRIORITY 4 PB/A&W Page 24 of 43

25 STAIRS/RAMPS: STAIRS/RAMPS Photo1 Building Assessment Survey Facade A WINDOWS Replacement Quantity 12,000 Replacement Uom GUARDS LINTELS STEEL: MINOR RUSTING Elevation Quantity 30 L.F. MAINTENANCE PB/A&W Page 25 of 43

26 WINDOWS LINTELS Photo1 Building Assessment Survey Facade C1 WINDOWS Material Type(s) Aluminum Instance on Aluminum - Other: Aluminum - Other: All Facades Instance 3 - Fair Instance Quantity 12,000 Instance Installation Year 2004 Source of Installation Documented ALUMINUM - OTHER: DETERIORATED Elevation Quantity 60 WINDOW Urgency of Action PRIORITY 4 PB/A&W Page 26 of 43

27 WINDOWS WINDOWS Photo1 Building Assessment Survey INTERIOR Room 305 shown, Rooms 205, 302 similar POOLS STRUCTURAL COLUMNS/BEAMS/BEARING WALLS FLOOR STRUCTURE FOUNDATION WALLS Material Type(s) ROOF STRUCTURE Location/Instance Quantity 30 Masonry CONCRETE: CRACKED/SPALLED/REINFORCEMENT EXPOSED Gymnasium Roof REPAIR Purpose of Action LEVEL 5 Photo1 VAULTS-BUNKERS Foundation Walls Gymnasium Roof overhang at Facade A PB/A&W Page 27 of 43

28 Building Assessment Survey Architectural Inspection INTERIOR STRUCTURAL VAULTS-BUNKERS Foundation Walls Slab Structure 1 - Good Vault/Ash Hoist Doors and Framing 1 - Good AUDITORIUM Seats Ceiling Seats Door(s) Seats Fixed H/C Lift Seats Fixed Seating Seats Floor Finish Seats Sliding-folding Partition Seats Stage Seats Stage Seats Stage Curtain Rigging Seats Stage Curtains Seats Walls Seats PB/A&W Page 28 of 43

29 Building Assessment Survey Architectural Inspection INTERIOR AUDITORIUM Walls Window Curtains/Shades/Blinds Seats CAFETERIA Ceiling Door(s) Fixed Equipment Floor Finish Sliding-folding Partition Stage Walls WALL PADDING: DETERIORATED Location/Instance Center Quantity 20 Photo1 Center PB/A&W Page 29 of 43

30 Building Assessment Survey Architectural Inspection INTERIOR CAFETERIA Walls GLAZED BLOCK: CRACKS/SPALLING Location/Instance Near windows Quantity 10 Photo1 Near windows Window Curtains/Shades/Blinds CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling ACOUSTIC TILES: DAMAGED/MISSING Location/Instance Room 157 Quantity 10 Photo1 Door(s) Floor Finish Room 157 PB/A&W Page 30 of 43

31 Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Walls PLASTER: CRACKS/SPALLING Location/Instance Rooms 204, 302, 304 Quantity 35 Photo1 Room 302 GLAZED BLOCK: CRACKS/SPALLING Location/Instance Corridor near Rooms 107, 204, 209, 304, 327 and others Quantity 80 Photo1 Corridor near Room 209 Specialties GYMNASIUM Ceiling Location/Instance Quantity 20 PLASTER: CRACKS/SPALLING Storage Room PB/A&W Page 31 of 43

32 Building Assessment Survey Architectural Inspection INTERIOR GYMNASIUM Ceiling Photo1 Storage Room Door(s) 3 - Fair WOOD: DETERIORATED DOOR Location/Instance Entrance Quantity 1 EACH MAINTENANCE Photo1 Fixed Equipment Floor Finish Seating Entrance PB/A&W Page 32 of 43

33 Building Assessment Survey Architectural Inspection INTERIOR GYMNASIUM Sliding-folding Partition Stage Walls Window Curtains/Shades/Blinds INTERIOR DOOR HARDWARE 3 - Fair INTERIOR GUARDS KITCHEN Ceiling PLASTER: CRACKS/SPALLING Location/Instance Storage Room Quantity 15 Photo1 Door(s) Floor Finish Location/Instance Storage Room CERAMIC TILE: BROKEN/MISSING TILES Near sink PB/A&W Page 33 of 43

34 Building Assessment Survey Architectural Inspection INTERIOR KITCHEN Floor Finish Quantity 20 Photo1 Near sink Walls PLASTER: CRACKS/SPALLING Location/Instance Storage Room Quantity 20 Photo1 LIBRARY Instance on Room 204 Built-in Furnishing Instance on Room 204 Ceiling Instance on Room 204 Storage Room PB/A&W Page 34 of 43

35 Building Assessment Survey Architectural Inspection INTERIOR LIBRARY Door(s) Instance on Room 204 Floor Finish Instance on Room 204 VINYL TILES: DETERIORATED SUBSTRATE Location/Instance Center Quantity 20 Photo1 Center Walls Instance on Room 204 LOCKER ROOM MULTI-PURPOSE ROOM SCIENCE DEMO ROOM SCIENCE LAB SCIENCE PREP ROOM SHOWER ROOM STAIRS/RAMPS: INTERIOR Ceiling Do Letter Stair Signs Exist? Door(s) Inaccessible Yes 3 - Fair Location/Instance Stair A/3 Quantity 1 METAL: DETERIORATED DOOR EACH MAINTENANCE PB/A&W Page 35 of 43

36 Building Assessment Survey Architectural Inspection INTERIOR STAIRS/RAMPS: INTERIOR Door(s) Photo1 Stair A/3 Partition Railings Stairs and Landings Walls TOILET ROOMS - STAFF Ceiling Door(s) 5 - Poor WOOD: DAMAGED LOUVER Location/Instance Room 123 Quantity 1 EACH MAINTENANCE Photo1 Room 123 PB/A&W Page 36 of 43

37 Building Assessment Survey Architectural Inspection INTERIOR TOILET ROOMS - STAFF Floor Finish Stalls 5 - Poor RUST - MAJOR Location/Instance Rooms 323, 325, Kitchen Quantity 3 EACH Photo1 Kitchen Walls PLASTER: CRACKS/SPALLING Location/Instance Room 223 Quantity 15 Photo1 TOILET ROOMS - STUDENTS Ceiling Door(s) Room 223 PB/A&W Page 37 of 43

38 Building Assessment Survey Architectural Inspection INTERIOR TOILET ROOMS - STUDENTS Door(s) 5 - Poor WOOD: DETERIORATED DOOR Location/Instance Rooms 217, 317 Quantity 2 EACH MAINTENANCE Photo1 Room 317 Floor Finish CERAMIC TILE: BROKEN/MISSING TILES Location/Instance Rooms 217, 317 Quantity 20 Photo1 Room 317 Stalls Walls Location/Instance Room 221 Quantity 30 CERAMIC TILE: BROKEN/ MISSING PB/A&W Page 38 of 43

39 Building Assessment Survey Architectural Inspection INTERIOR TOILET ROOMS - STUDENTS Walls Photo1 Room 221 LIFE SAFETY F.D. HOLDING AREA STEEL STAIRS SITE CONTAINERIZATION 5 - Poor CONTAINER DAMAGED Location/Instance Along Dongan Hills Avenue Quantity 2 EACH Photo1 Along Dongan Hills Avenue Drainage System for Asphalt Catch Basins/Manhole - Surrounded by asphalt Culverts - Asphalt Covering Drainage System for Concrete PB/A&W Page 39 of 43

40 Building Assessment Survey Architectural Inspection SITE Drainage System for Concrete Catch Basins/Manhole - Surrounded by concrete Culverts - Concrete Covering Drainage System for Soil Catch Basins/Manhole - Surrounded by Soil Culverts - Soil Covering DRINKING FOUNTAINS FENCES CONCRETE CURB: DAMAGED/DETERIORATED Location/Instance Near Exit 10 Quantity 15 Photo1 Near Exit 10 IRRIGATION SYSTEM PAVING Student Non-Use Gravel Exists? No Asphalt Concrete Pavers Student Use Gravel Exists? No Asphalt 4 - Between Fair and Poor CRACKS - MAJOR Location/Instance Near Exits 4, 10 PB/A&W Page 40 of 43

41 Building Assessment Survey Architectural Inspection SITE PAVING Student Use Asphalt Quantity 900 Photo1 Near Exit 4 Concrete Pavers Site Sidewalks & Walkways Asphalt Concrete Pavers DOT Sidewalk Asphalt Concrete 4 - Between Fair and Poor HEAVING Location/Instance Along Buel Avenue Quantity 25 Photo1 Along Buel Avenue PB/A&W Page 41 of 43

42 SITE PAVING DOT Sidewalk Concrete Building Assessment Survey DAMAGED CURBS Location/Instance Along Buel Avenue Quantity 25 L.F. Photo1 Along Buel Avenue DAMAGED/DETERIORATED/MISSING SECTIONS Location/Instance Along Dongan Hills Avenue Quantity 1,325 Photo1 Pavers PLAYGROUNDS Instance on Near Exit 4 Benches Instance on Near Exit 4 Fence Along Buel Avenue PB/A&W Page 42 of 43

43 SITE PLAYGROUNDS Fence Instance on Near Exit 4 Pavement Instance on Near Exit 4 Play Equipment Instance on Near Exit 4 Safety Surfacing Instance on Near Exit 4 Unpaved Area Instance on Near Exit 4 PLAYING SURFACE RETAINING WALLS SEATING Are there any Retaining Walls 6' OR higher facing public street/sidewalk? SITE WALLS (NOT RETAINING WALLS) STAIRS/RAMPS: Railings Site Cheek/flank Walls Stairs/ramps Building Assessment Survey Good 1 - Good No PB/A&W Page 43 of 43