1 Architectural Inspection Building Assessment Survey Asset: I.S QUEENS, ROCKAWAY BLVD, New York, Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior :16 PM :28 AM AA : Architectural - Associate :36 PM :08 PM Asset Data Was the building fully accessible for inspection Inspection Access Comment Principal(s) Information Custodian Fireman Principal Name Organization Did you meet with this Principal? Did this Principal provide feedback? Summary of Principal's Feedback Answer No Exterior Walls - Facades C, D and portion of Facade F, (Schoolyard Construction Fencing-staging area) 2nd Floor Shower Room - Boys, Girls (sealed) Site/Paving/Student Use/Asphalt; Site/ Retaining Walls; Site/Stairs/Ramps:Exterior Security Lighting (Schoolyard Construction) Rushell White I.S Queens No Yes The Principal returned the Principal naire with the following comments: 1. The Auditorium Seating and Flooring is deteriorated and damaged and requires a full replacement. 2. Many Ceilings throughout the School are damaged and require a replacement upgrade. Robert Wick Building Square Footage Comments on the Area Comments on the Stories (Floors) plus Basements Comments on the Number of Classrooms 93 Devon Macdonald None 4+B+PH Comments on the Year Built 1974 Student Population 1681 Staff Population 254 Weather Facade Photo Fair Corner Rockaway Boulevard and 121st Street - Southeast view PB/A&W Page 1 of 63

2 Main Entrance Photo Building Assessment Survey Roof Photo Facade A - Rockaway Boulevard Roof 1 - West view Have any Systems/Major Building Components been upgraded? Yes Systems: Dance Studio upgrade Year: 2016 Systems: Solar Panels installation (Roof 1) Year: 2016 Systems: Two New Science Labs Rooms 207 and 307 Year: 2015 Systems: Roof and Flashing replacements at Roofs 1, 2, 4 and Penthouse Roofs 5 and 6. Partial repointing of Parapets, Chimney, and Bulkheads; Bulkhead Doors replacement; Library upgrade. Year: 2012 Systems: Gymnasium Flooring resurfaced Year: 2010 Systems: Vinyl Flooring replacement including the Cafeteria in the 1974 Building. Year: 2009 Systems: Auditorium Roofing replacement; Auditorium curtains replacement. Year: 2006 Systems: Exterior Doors replacement PB/A&W Page 2 of 63

3 Architectural Inspection Have there been any New Building Additions? Comments on New Building Additions Tandem Schools? Leased Space? Building Assessment Survey Year: 2002 Systems: Windows and Window Guards replacement Year: 2002 Yes SF No No Priority Priority Exist Last Year? Priority Category Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No Broken Glass Broken window pane is a potential safety hazard. EXTERIOR WINDOWS WINDOWS Kitchen window facing the driveway at the east side of the building. Robert Wick Custodian No Potential Falling Debris The underside of the metal stair is severely corroded and posed a potential safety hazard to the passersby. INTERIOR STAIRS/RAMP S: INTERIOR Stairs and Landings Stairs A/2, C/3 Devon MacDonald Fireman Yes Tripping Hazard Severely heaving DOT Sidewalk is a potential tripping hazard. SITE PAVING DOT Sidewalk Concrete Rockaway Boulevard Robert Wick Custodian Structural Engineer Required Structural Type Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No condition recorded Accessibility Accessibility Status Is the primary or secondary entrance on an accessible route? Is the building a multi-story building? Are all floors of the building accessible through compliant means? Accessible classrooms exists on each floor? Boys and Girls or Unisex accessible toilets exist on at least every other floor? If the following spaces exist, are they ALL accessible? Art Room, Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs Yes Yes Yes Yes Yes Yes Physical Breakdown Structure Exists Complies Required FUNCTIONAL ACCESSIBILITY Exterior Routes Exterior Entrances & Exits Yes Exterior H/C Lifts No No Exterior Ramps and Railings Yes Yes Interior Routes PB/A&W Page 3 of 63

4 Building Assessment Survey Physical Breakdown Structure Exists Complies Required Interior Routes Corridor and Lobby H/C Lifts No No Interior Corridor Doors and Hardware Yes Yes Interior Corridors and Lobbies Interior Elevators Yes Yes Interior Lobby Doors and Hardware Interior Ramps Rooms & Spaces Art Rooms Auditorium 1st Floor Yes Cafeteria 1st Floor - Staff, 1st Floor - Students, 1st Floor- Addition Classrooms 1st - 4th Floors Yes Computer Rooms Rooms 282 Yes Gymnasium 2nd Floor Yes Library Room 329 Yes Main Office Multi-purpose Room Room 103, (I.S. 226); Room 361, (I.S. 233-District 75); Room 286, (I.S. 297); Room 423, (Epic School South) Nurse's Room Rooms 117A, 378 Yes Pool Science Lab Rooms 207, 307, 405, 407; Rooms 205, 305 (Alternate Use) Toilet Rooms (Boys) 1st - 4th Floors Yes Toilet Rooms (Girls) 1st - 4th Floors No Insufficient Latch Clearance Toilet Rooms (Staff) Men's - 1st - 4th Floors, Women's - 1st - 4th Floors No No No No Yes Yes Yes Yes Yes Yes Building Template Inspection PB/A&W Page 4 of 63

5 Building Assessment Survey Architectural Inspection Architectural EXTERIOR AREAWAY Instance on AW1-AW4 Instance 3 - Fair Instance Quantity 4 Instance EACH AREAWAY GRATINGS: MINOR RUSTING Roof Plan reference Quantity 20 MAINTENANCE Photo1 Roof Plan reference AW1 AREAWAY WALLS: CRACKS AND SPALLING Quantity 20 REPAIR PB/A&W Page 5 of 63

6 EXTERIOR AREAWAY Photo1 Building Assessment Survey AWNINGS AND CANOPIES Roof Plan reference AW2 3 - Fair CONCRETE: WATER PENETRATION Quantity 20 REPAIR Urgency of Action PRIORITY 5 Photo1 Main Entrance CONCRETE: DETERIORATED PB/A&W Page 6 of 63

7 EXTERIOR AWNINGS AND CANOPIES Roof Plan reference Building Assessment Survey Quantity 30 Urgency of Action PRIORITY 4 Photo1 CHIMNEY Material Type(s) Roof Plan reference Main Entrance Masonry BRICK: MINOR CRACKS AND SPALLING Quantity 10 RESTITCH PB/A&W Page 7 of 63

8 EXTERIOR CHIMNEY Photo1 Building Assessment Survey Roof 2 COPING Roof Plan reference 3 - Fair CAST STONE: OPEN TRANSVERSE JOINTS WITH DAMAGED CAULKING Quantity 15 L.F. MAINTENANCE Photo1 Facade D CAST STONE: CRACKED/BROKEN PIECES PB/A&W Page 8 of 63

9 EXTERIOR COPING Roof Plan reference Building Assessment Survey Quantity 30 L.F. -IN-KIND Urgency of Action PRIORITY 4 Photo1 Roof Plan reference Roof 6 CAST STONE: OPEN BED JOINT Quantity 20 L.F. REPOINT PB/A&W Page 9 of 63

10 EXTERIOR COPING Photo1 Building Assessment Survey CORNICE DOORS DOORS AND FRAMES Roof Plan reference Roof 3 - Fair METAL: DETERIORATED DOOR AND FRAME - MINOR DETERIORATION Quantity 2 EACH MAINTENANCE Photo1 DOOR HARDWARE LINTELS Facade B - Exit 3 - Fair PB/A&W Page 10 of 63

11 EXTERIOR DOORS LINTELS Roof Plan reference Building Assessment Survey STEEL: MINOR RUSTING Quantity 20 L.F. MAINTENANCE Photo1 Facade B exit TRANSOM/SIDE LIGHT EXTERIOR WALLS Material Type(s) Masonry, Concrete Replacement Quantity 50,000 Replacement Uom Instance on All Facades Instance 4 - Between Fair and Poor Instance Quantity 50,000 Instance BRICK: WATER INFILTRATION IN INSTRUCTIONAL SPACE PB/A&W Page 11 of 63

12 EXTERIOR EXTERIOR WALLS Roof Plan reference Building Assessment Survey Elevation Quantity 25 REPAIR Urgency of Action PRIORITY 5 Photo1 Roof Plan reference Room 103b BRICK: MINOR CRACKS AND SPALLING PB/A&W Page 12 of 63

13 EXTERIOR EXTERIOR WALLS Elevation Building Assessment Survey Quantity 10 RESTITCH Photo1 Roof Plan reference Facade A BRICK: CRACKS/DISPLACED/SPALLED BRICK AT BUILDING CORNERS Elevation Quantity 80 PB/A&W Page 13 of 63

14 Building Assessment Survey Architectural Inspection EXTERIOR EXTERIOR WALLS REMOVE AND REBUILD Urgency of Action PRIORITY 4 Photo1 Roof Plan reference Facade B - corner at Facade C BRICK: OPEN JOINTS Elevation Quantity 2,700 REPOINT Photo1 PB/A&W Page 14 of 63

15 EXTERIOR EXTERIOR WALLS Building Assessment Survey Facade B Roof Plan reference CAST IN PLACE / PRE-CAST CONCRETE: MINOR CRACKS, SPALLED, DETERIORATED REBAR Elevation Quantity 10 REPAIR Photo1 Facade A CERAMIC TILE: OPEN JOINTS PB/A&W Page 15 of 63

16 EXTERIOR EXTERIOR WALLS Roof Plan reference Building Assessment Survey Elevation Quantity 10 REPOINT Photo1 EXTERIOR SOFFITS Roof Plan reference Facade F - HC Entrance STUCCO/PLASTER: MINOR CRACKS/SPALLING PB/A&W Page 16 of 63

17 EXTERIOR EXTERIOR SOFFITS Elevation Building Assessment Survey Quantity 10 REPAIR Photo1 Roof Plan reference Facade A CONCRETE: DETERIORATED Elevation Quantity 20 PB/A&W Page 17 of 63

18 Building Assessment Survey Architectural Inspection EXTERIOR EXTERIOR SOFFITS Photo1 LOADING DOCK LOUVER Roof Plan reference Facade B 3 - Fair MISSING SCREEN Elevation Quantity 30 PB/A&W Page 18 of 63

19 EXTERIOR LOUVER Photo1 Building Assessment Survey Facade B PARAPETS Material Type(s) Replacement Quantity 8,000 Replacement Uom Instance on All Facades Instance Masonry, Concrete C.F. Instance Quantity 8,000 Instance PLAZA DECK ROOF Roofing C.F. Replacement Quantity 66,000 Replacement Uom ROOF HATCH/SMOKE HATCH LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS ROOF BARRIER ROOF CAGE ROOF FENCE ROOFING Instance on Built-Up: Roof 3 Instance 3 - Fair Instance Quantity 10,000 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 2006 Source of Installation Instance on Single Ply, Fully Adhered Roof: Roof 4 Instance No Documented PB/A&W Page 19 of Fair

20 EXTERIOR ROOF Roofing ROOFING Instance Quantity 10,000 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 2000 Source of Installation Instance on Modified Bitumen: Roofs 1, 2, 5, 6 Instance No Documented Instance Quantity 46,000 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 2012 Source of Installation Roof Plan reference Building Assessment Survey No Documented MODIFIED BITUMEN: ROOFING: DELAMINATION Quantity 25 Urgency of Action PRIORITY 4 Photo1 ROOFING WITHOUT MAJOR EQUIPMENT REMOVAL Roof 2 MODIFIED BITUMEN: ROOFING: MAJOR ACTIVE ROOF LEAKS IN INSTRUCTIONAL SPACE PB/A&W Page 20 of 63

21 EXTERIOR ROOF Roofing ROOFING Roof Plan reference Building Assessment Survey Quantity 80 ROOFING WITH MAJOR EQUIPMENT REMOVAL Urgency of Action PRIORITY 5 Photo1 ROOFING DRAINS Roof Plan reference Room 443 at Roof 1 shown, also Rooms 341, 442C, 407, BH Stair D, and Gymnasium at Roof 2 similar 5 - Poor DETERIORATED Quantity 2 EACH Urgency of Action PRIORITY 4 PB/A&W Page 21 of 63

22 EXTERIOR ROOF Roofing ROOFING DRAINS Photo1 Building Assessment Survey Specialties BULKHEAD/PENTHOUSE Roof Plan reference Roof Fair BULKHEAD/PENTHOUSE ROOF: MINOR LEAKAGE Quantity 50 MAINTENANCE Urgency of Action PRIORITY 5 Photo1 C/Bulkhead BULKHEAD/PENTHOUSE ROOF: MAJOR LEAKAGE PB/A&W Page 22 of 63

23 EXTERIOR ROOF Specialties BULKHEAD/PENTHOUSE Roof Plan reference Building Assessment Survey Quantity 20 Urgency of Action PRIORITY 5 Photo1 Roof Plan reference C/Bulkhead BULKHEAD/PENTHOUSE WALLS/EXTERIOR: OPEN JOINTS Quantity 175 REPOINT PB/A&W Page 23 of 63

24 EXTERIOR ROOF Specialties BULKHEAD/PENTHOUSE Photo1 Building Assessment Survey CUPOLA/ SPIRES/ TOWERS DORMER DUNNAGE STEEL Roof Plan reference BH1 shown, also at BH2, BH3, BH4 4 - Between Fair and Poor MINOR RUSTING Quantity 120 L.F. MAINTENANCE Photo1 Roof 4 MAJOR RUSTING PB/A&W Page 24 of 63

25 EXTERIOR ROOF Specialties DUNNAGE STEEL Roof Plan reference Building Assessment Survey Quantity 100 L.F. Urgency of Action PRIORITY 4 Photo1 SKYLIGHT/ROOF VENT ROOF/GRAVITY TANK STAIRS/RAMPS: EXTERIOR BUILDING CHEEK/FLANK WALLS Roof Plan reference Roof Between Fair and Poor CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR Quantity 20 PB/A&W Page 25 of 63

26 Building Assessment Survey Architectural Inspection EXTERIOR STAIRS/RAMPS: EXTERIOR BUILDING CHEEK/FLANK WALLS Photo1 RAILINGS STAIRS/RAMPS Roof Plan reference Facade F - HC Ramp 4 - Between Fair and Poor CONCRETE: CRACKS/SPALLING - MAJOR Quantity 50 Urgency of Action PRIORITY 4 Photo1 Facade E - Exit WINDOWS Replacement Quantity 12,000 Replacement Uom PB/A&W Page 26 of 63

27 EXTERIOR WINDOWS EXTERIOR GUARDS Roof Plan reference Building Assessment Survey Fair RUST - MINOR Elevation Quantity 70 MAINTENANCE Photo1 Facade A LINTELS WINDOWS Material Type(s) Instance on Aluminum - Double Hung: 1974 Building - All Facades Instance Aluminum 3 - Fair Instance Quantity 10,000 Instance Installation Year 2000 PB/A&W Page 27 of 63

28 EXTERIOR WINDOWS WINDOWS Source of Installation Roof Plan reference Building Assessment Survey Documented ALUMINUM - DOUBLE HUNG: BROKEN PANE Elevation Quantity 10 MAINTENANCE Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 Facade B - Kitchen INTERIOR POOLS Instance on Aluminum - Double Hung: Partial Facade D, Facades E, F Instance 3 - Fair Instance Quantity 2,000 Instance Installation Year 2000 Source of Installation STRUCTURAL Documented PB/A&W Page 28 of 63

29 INTERIOR STRUCTURAL COLUMNS/BEAMS/BEARING WALLS Location/Instance Quantity Fair STEEL COLUMNS/BEAMS: DETERIORATED MASONRY FIREPROOFING Roof Penthouse Purpose of Action LEVEL 5 Photo1 Building Assessment Survey Roof Penthouse FLOOR STRUCTURE 4 - Between Fair and Poor CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED Location/Instance Room Mechanical Room Quantity 25 REPAIR Purpose of Action LEVEL 5 Photo1 Right side Location/Instance Quantity 100 CONCRETE SLAB ON GRADE: THRU CRACKS Basement Boiler and Electrical Ro REPAIR Purpose of Action LEVEL 5 PB/A&W Page 29 of 63

30 INTERIOR STRUCTURAL FLOOR STRUCTURE Photo1 Building Assessment Survey Boiler Room CONCRETE SLAB ON GRADE: MINOR CRACKS Location/Instance Basement Quantity 40 REPAIR Purpose of Action LEVEL 5 Photo1 Room C7 shown, Also in Boiler room FOUNDATION WALLS Material Type(s) Location/Instance Quantity 40 Concrete 4 - Between Fair and Poor CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONAL SPACE Basement Urgency of Action PRIORITY 5 Purpose of Action LEVEL 5 INSTALL WATERPROOFING PB/A&W Page 30 of 63

31 INTERIOR STRUCTURAL FOUNDATION WALLS Photo1 Building Assessment Survey MDF Room - Water Infiltration Location/Instance Quantity 60 CONCRETE: CRACKED/SPALLED/REINFORCEMENT EXPOSED Basement REPAIR Purpose of Action LEVEL 5 Photo1 ROOF STRUCTURE VAULTS-BUNKERS AUDITORIUM Instance on 1st Floor Seats Ceiling Instance on 1st Floor Seats Door(s) Instance on 1st Floor Seats Fixed H/C Lift Instance on 1st Floor Seats Fixed Seating MDF Room PB/A&W Page 31 of 63

32 Building Assessment Survey Architectural Inspection INTERIOR AUDITORIUM Fixed Seating Instance on 1st Floor Seats 4 - Between Fair and Poor DAMAGED/BROKEN/INOPERABLE Location/Instance Seats A/18, C/10,18, Q/14 Quantity 4 EACH Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 Seat A/18 DAMAGED/BROKEN/INOPERABLE Location/Instance Seats A/12, B/2, C/12, D/2, E/101 and others Quantity 41 EACH Photo1 Seat E/101 Floor Finish Instance on 1st Floor Seats Location/Instance Near Seat F/104 Quantity 10 VINYL TILES: DETERIORATED SUBSTRATE PB/A&W Page 32 of 63

33 Building Assessment Survey Architectural Inspection INTERIOR AUDITORIUM Floor Finish Photo1 Near Seat F/104 VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Location/Instance Left and Right Side Quantity 50 Photo1 Left Side Sliding-folding Partition Instance on 1st Floor Seats 3 - Fair MOVABLE PANELS: DAMAGED Location/Instance Left and Right Side Quantity 80 PB/A&W Page 33 of 63

34 INTERIOR AUDITORIUM Sliding-folding Partition Photo1 Building Assessment Survey Right Side Stage Instance on 1st Floor Seats Stage Instance on 1st Floor Seats RAILINGS/MISSING Location/Instance Right Side Quantity 4 L.F. Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 Right Side Stage Curtain Rigging Instance on 1st Floor Seats Stage Curtains Instance on 1st Floor Seats Location/Instance Quantity Fair WORN/DETERIORATED Back and Right Side PB/A&W Page 34 of 63

35 Building Assessment Survey Architectural Inspection INTERIOR AUDITORIUM Stage Stage Curtains Photo1 Walls Instance on 1st Floor Seats Window Curtains/Shades/Blinds Instance on 1st Floor Seats CAFETERIA Instance on 1st Floor - Addition Instance on 1st Floor - Staff (1200 SF) Instance on 1st Floor - Students Ceiling Instance on 1st Floor - Staff (1200 SF) Instance on 1st Floor - Addition Instance on 1st Floor - Students Door(s) Instance on 1st Floor - Staff (1200 SF) Instance on 1st Floor - Addition Instance on 1st Floor - Students Fixed Equipment Instance on 1st Floor - Addition Back Side PB/A&W Page 35 of 63

36 Building Assessment Survey Architectural Inspection INTERIOR CAFETERIA Fixed Equipment Instance on 1st Floor - Staff (1200 SF) Instance on 1st Floor - Students Floor Finish Instance on 1st Floor - Addition VINYL TILES: DETERIORATED SUBSTRATE Location/Instance Center Quantity 50 Photo1 Center Instance on 1st Floor - Staff (1200 SF) VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Location/Instance Near Servery Quantity 10 Photo1 Near Servery Instance on 1st Floor - Students Location/Instance VINYL TILES: DETERIORATED SUBSTRATE PB/A&W Page 36 of 63 Center

37 Building Assessment Survey Architectural Inspection INTERIOR CAFETERIA Floor Finish Quantity 30 Photo1 Center Sliding-folding Partition Instance on 1st Floor - Students Instance on 1st Floor - Addition Instance on 1st Floor - Staff (1200 SF) Stage Instance on 1st Floor - Addition Instance on 1st Floor - Staff (1200 SF) Instance on 1st Floor - Students Walls Instance on 1st Floor - Addition Instance on 1st Floor - Staff (1200 SF) Instance on 1st Floor - Students Window Curtains/Shades/Blinds Instance on 1st Floor - Staff (1200 SF) Instance on 1st Floor - Addition Instance on 1st Floor - Students CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling ACOUSTIC TILES: DAMAGED/MISSING - ACTIVE LEAK Location/Instance Room 442C Quantity 20 PB/A&W Page 37 of 63

38 Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling Urgency of Action PRIORITY 5 Photo1 Room 442C PLASTER: CRACKS/SPALLING - ACTIVE LEAK Location/Instance Rooms 443, 407 Quantity 60 Urgency of Action PRIORITY 5 Photo1 Room 443 ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING Location/Instance Corridor near Room 423, 339, 203, 140, 121 and others Quantity 350 PB/A&W Page 38 of 63

39 Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling Photo1 Corridor near Room 121 Door(s) 5 - Poor METAL: DETERIORATED DOOR Location/Instance Rooms 342, 312 Quantity 2 EACH MAINTENANCE Photo1 Room 312 WOOD: DETERIORATED DOOR Location/Instance Rooms 442A, 339, 213, 161, 103 and others Quantity 12 EACH MAINTENANCE Photo1 PB/A&W Page 39 of 63

40 Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Door(s) Room 103 Floor Finish TERRAZZO: CRACKS Location/Instance Main Lobby Quantity 10 Photo1 Main Lobby Location/Instance Quantity 350 VINYL TILES: DETERIORATED SUBSTRATE Rooms 419, 312, Corridor near Room 291, 117, Corridor near Stair C/4 and others Photo1 Corridor near Room 117 Location/Instance Quantity 250 VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Rooms 445, 323, 250, Corridor near Room 450, 203 and others PB/A&W Page 40 of 63

41 Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Floor Finish Photo1 Room 347 Walls GLAZED BLOCK: CRACKS/SPALLING Location/Instance Corridor near Room 407, 339, 249, 203, 101 and others Quantity 50 Photo1 Corridor near Room 101 PLASTER: CRACKS/SPALLING - ACTIVE LEAK Location/Instance Rooms 103B, 443, 341 Quantity 60 Urgency of Action PRIORITY 5 PB/A&W Page 41 of 63

42 Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Walls Photo1 Room 443 Specialties Classroom Locker(s) DAMAGED UNITS Location/Instance Lockers 2171, 2241, 2265, 3206, 4339 and others Quantity 9 EACH Photo1 Locker 4339 Fixed Seating GYMNASIUM Instance on 2nd Floor Ceiling Instance on 2nd Floor TECTUM: DAMAGED/MISSING - ACTIVE LEAK Location/Instance Center Quantity 50 Urgency of Action PRIORITY 5 PB/A&W Page 42 of 63

43 INTERIOR GYMNASIUM Ceiling Photo1 Building Assessment Survey Center Door(s) Instance on 2nd Floor Fixed Equipment Instance on 2nd Floor Floor Finish Instance on 2nd Floor WOOD: DAMAGED/DETERIORATED Location/Instance Near Drinking Fountain Quantity 50 Photo1 Seating Instance on 2nd Floor Sliding-folding Partition Instance on 2nd Floor Stage Near Drinking Fountain PB/A&W Page 43 of 63

44 Building Assessment Survey Architectural Inspection INTERIOR GYMNASIUM Stage Instance on 2nd Floor Walls Instance on 2nd Floor MASONRY: CRACKS/SPALLING Location/Instance Near Entrance, rear wall Quantity 80 Photo1 Rear wall Window Curtains/Shades/Blinds Instance on 2nd Floor INTERIOR DOOR HARDWARE 3 - Fair INTERIOR GUARDS KITCHEN Instance on 1st Floor - Original Building (2500 SF) Instance on 1st Floor - Addition Ceiling Instance on 1st Floor - Original Building (2500 SF) METAL PAN: DAMAGED/MISSING Location/Instance Center Quantity 10 PB/A&W Page 44 of 63

45 INTERIOR KITCHEN Ceiling Photo1 Building Assessment Survey Center Door(s) Instance on 1st Floor - Original Building (2500 SF) 3 - Fair WOOD: DETERIORATED DOOR Location/Instance Exit to Staff Cafeteria Quantity 1 EACH MAINTENANCE Photo1 Exit to Staff Cafeteria Floor Finish Instance on 1st Floor - Original Building (2500 SF) 3 - Fair QUARRY TILE: BROKEN/MISSING TILES Location/Instance Left Side Quantity 15 PB/A&W Page 45 of 63

46 INTERIOR KITCHEN Floor Finish Photo1 Building Assessment Survey Left Side CONCRETE: CRACKS Location/Instance Office Quantity 75 Photo1 Office Walls Instance on 1st Floor - Original Building (2500 SF) CERAMIC TILE: BROKEN/ MISSING Location/Instance Exit vestibule Quantity 10 PB/A&W Page 46 of 63

47 INTERIOR KITCHEN Walls Photo1 Building Assessment Survey Exit vestibule LIBRARY Instance on Room 329 Built-in Furnishing Instance on Room 329 Ceiling Instance on Room 329 Door(s) Instance on Room Between Fair and Poor WOOD: DETERIORATED DOOR Location/Instance Entrance Quantity 2 EACH MAINTENANCE Photo1 Floor Finish Instance on Room 329 Walls Room 329 PB/A&W Page 47 of 63

48 INTERIOR LIBRARY Walls Instance on Room 329 LOCKER ROOM Ceiling Instance on 2nd Floor - Boys Alternative use Instance on 2nd Floor - Girls Alternative use Instance on 2nd Floor - Boys Instance on 2nd Floor - Girls Door(s) Instance on 2nd Floor - Girls Instance on 2nd Floor - Boys Floor Finish Instance on 2nd Floor - Boys Instance on 2nd Floor - Girls Locker Room Lockers Instance on 2nd Floor - Boys Instance on 2nd Floor - Girls Walls Instance on 2nd Floor - Girls Instance on 2nd Floor - Boys MULTI-PURPOSE ROOM SCIENCE DEMO ROOM SCIENCE LAB Instance on Rooms 205, 305 Alternative use Building Assessment Survey No No 1 - Good PB/A&W Page 48 of 63 Yes

49 Building Assessment Survey Architectural Inspection INTERIOR SCIENCE LAB Instance on Rooms 207, 307 Alternative use No Instance on Rooms 405, 407 Alternative use No Fixed Equipment Instance on Rooms 205, Fair CABINETRY: MISSING/DAMAGED Location/Instance Rooms 205, 305 Quantity 36 L.F. Photo1 No photo recorded Instance on Rooms 405, Between Fair and Poor CABINETRY: MISSING/DAMAGED Location/Instance Rooms 405, 407 Quantity 20 L.F. Photo1 Room 405 SCIENCE PREP ROOM Instance on Room 341 Alternative use Yes Instance on Rooms 211, 311 Alternative use No Fixed Equipment Instance on Room Fair CABINETRY: MISSING/DAMAGED Location/Instance Room 341 Quantity 24 PB/A&W Page 49 of 63

50 Building Assessment Survey Architectural Inspection INTERIOR SCIENCE PREP ROOM Fixed Equipment L.F. Photo1 No photo recorded SHOWER ROOM Instance on 2nd Floor - Boys Inaccessible Instance on 2nd Floor - Girls Inaccessible STAIRS/RAMPS: INTERIOR Do Letter Stair Signs Exist? Partially Ceiling Door(s) METAL: DETERIORATED DOOR AND FRAME Location/Instance Stair C/1 Quantity 2 EACH MAINTENANCE Photo1 Stair C/1 Partition Railings 3 - Fair METAL: MISSING Location/Instance Auditorium Right Exit Quantity 8 L.F. Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 PB/A&W Page 50 of 63

51 INTERIOR STAIRS/RAMPS: INTERIOR Railings Photo1 Building Assessment Survey Auditorium Right Exit Stairs and Landings METAL: RUST - MAJOR Location/Instance Stairs A/2, C/3 Quantity 15 Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 Stair C/3 VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Location/Instance Stair A/1, B/1,2, C3,4 Quantity 70 Photo1 PB/A&W Page 51 of 63

52 INTERIOR STAIRS/RAMPS: INTERIOR Stairs and Landings Building Assessment Survey Stair C/4 STONE: BROKEN/MISSING Location/Instance Stair A/3, C/2, D/2,3 Quantity 45 Photo1 Stair C/2 VINYL TILES: DETERIORATED SUBSTRATE Location/Instance Stair B/3,4, C/4, D/2,4 Quantity 50 Photo1 Stair D/4 Walls TOILET ROOMS - STAFF Ceiling Door(s) PB/A&W Page 52 of Poor

53 Building Assessment Survey Architectural Inspection INTERIOR TOILET ROOMS - STAFF Door(s) WOOD: DAMAGED LOUVER Location/Instance Kitchen Quantity 1 EACH MAINTENANCE Photo1 Kitchen WOOD: DETERIORATED DOOR Location/Instance Rooms 448, 348, 344, 2nd Floor Men Quantity 4 EACH MAINTENANCE Photo1 Room 448 Floor Finish Stalls 5 - Poor RUST - MAJOR Location/Instance Kitchen, Room 448 Quantity 2 EACH PB/A&W Page 53 of 63

54 Building Assessment Survey Architectural Inspection INTERIOR TOILET ROOMS - STAFF Stalls Photo1 Kitchen Walls PLASTER: CRACKS/SPALLING Location/Instance Kitchen Quantity 10 Photo1 Kitchen CERAMIC TILE: BROKEN/ MISSING Location/Instance Rooms 348, 344 Quantity 10 PB/A&W Page 54 of 63

55 INTERIOR TOILET ROOMS - STAFF Walls Photo1 Building Assessment Survey Room 344 TOILET ROOMS - STUDENTS Ceiling Door(s) 5 - Poor WOOD: MISSING DOOR Location/Instance Boys and Girls Locker Room Quantity 2 EACH MAINTENANCE Photo1 Girls Locker Room WOOD: DETERIORATED DOOR Location/Instance Rooms 317, 306, 244, 217, 215 and others Quantity 7 EACH MAINTENANCE PB/A&W Page 55 of 63

56 INTERIOR TOILET ROOMS - STUDENTS Door(s) Photo1 Building Assessment Survey Room 317 Floor Finish Stalls RUST - MAJOR Location/Instance Toilet inside the Girls Locker Room Quantity 2 EACH Photo1 Toilet inside the Girls Locker Room Walls CERAMIC TILE: BROKEN/ MISSING Location/Instance Room 215 Quantity 10 PB/A&W Page 56 of 63

57 INTERIOR TOILET ROOMS - STUDENTS Walls Photo1 Building Assessment Survey Room 215 LIFE SAFETY F.D. HOLDING AREA STEEL STAIRS SITE CONTAINERIZATION 5 - Poor CONTAINER DAMAGED Location/Instance Rockaway Boulevard Quantity 1 EACH Photo1 No photo recorded FENCING MISSING Location/Instance Rockaway Boulevard Quantity 900 INSTALL NEW Photo1 Rockaway Boulevard PB/A&W Page 57 of 63

58 Building Assessment Survey Architectural Inspection SITE Drainage System for Asphalt Catch Basins/Manhole - Surrounded by asphalt Culverts - Asphalt Covering Drainage System for Concrete Catch Basins/Manhole - Surrounded by concrete Culverts - Concrete Covering Drainage System for Soil Catch Basins/Manhole - Surrounded by Soil Culverts - Soil Covering DRINKING FOUNTAINS FENCES 3 - Fair CONCRETE CURB: DAMAGED/DETERIORATED Location/Instance Rockaway Boulevard, 121st Street Quantity 30 Photo1 Rockaway Boulevard WROUGHT IRON: DAMAGED/DETERIORATED Location/Instance Rockaway Boulevard, 121st Street Quantity 200 PB/A&W Page 58 of 63

59 SITE FENCES Photo1 Building Assessment Survey Rockaway Boulevard IRRIGATION SYSTEM PAVING Student Non-Use Gravel Exists? No Asphalt 4 - Between Fair and Poor CRACKS - MAJOR Location/Instance Parking Lot Quantity 600 Photo1 Parking Lot Concrete 3 - Fair HEAVING Location/Instance Rockaway Boulevard Quantity 25 PB/A&W Page 59 of 63

60 SITE PAVING Student Non-Use Concrete Photo1 Building Assessment Survey Rockaway Boulevard CRACKS - MAJOR Location/Instance Rockaway Boulevard Quantity 50 Photo1 Rockaway Boulevard Pavers Student Use Gravel Exists? Asphalt Concrete Pavers Site Sidewalks & Walkways Asphalt Concrete Location/Instance Quantity 100 No Under Construction 1 - Good 3 - Fair CRACKS - MAJOR Rockaway Boulevard PB/A&W Page 60 of 63

61 Building Assessment Survey Architectural Inspection SITE PAVING Site Sidewalks & Walkways Concrete Photo1 Rockaway Boulevard Pavers DOT Sidewalk Asphalt Concrete 4 - Between Fair and Poor DAMAGED CURBS Location/Instance Rockaway Boulevard, 121st Street Quantity 80 L.F. Photo1 Rockaway Boulevard DAMAGED CURBS Location/Instance Rockaway Boulevard Quantity 10 L.F. Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 PB/A&W Page 61 of 63

62 SITE PAVING DOT Sidewalk Concrete Photo1 Building Assessment Survey Rockaway Boulevard HEAVING Location/Instance 121st Street Quantity 150 Photo1 121st Street DAMAGED/DETERIORATED/MISSING SECTIONS Location/Instance Rockaway Boulevard, 121st Street Quantity 450 Photo1 121st Street PB/A&W Page 62 of 63

63 SITE PAVING DOT Sidewalk Concrete Building Assessment Survey Pavers PLAYGROUNDS PLAYING SURFACE RETAINING WALLS Inaccessible SEATING Benches Concrete Metal/Wood/Plastic Under Construction Bleachers SITE WALLS (NOT RETAINING WALLS) Under Construction STAIRS/RAMPS: EXTERIOR Railings Site Cheek/flank Walls Stairs/ramps 3 - Fair CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR Location/Instance 121 Street Quantity 70 Photo1 121 Street PB/A&W Page 63 of 63