FIRESTOPPING RectorSeal

Size: px
Start display at page:

Download "FIRESTOPPING RectorSeal"

Transcription

1 . Product Name FlameSafeª Firestop Sealants FlameSafeª Firestop Mortar FlameSafeª Firestop Coatings FlameSafeª Firestop Bags/KBSª Sealbags FlameSafeª Firestop Putties FlameSafeª Firestop Devices/Sleeves/Wrap Strips 2. Manufacturer 20 Spenwick Dr Houston, tx (800) Fax: (800) Product Description BASIC USE, COMPOSITION & MATERIALS FS 900+ This elastomeric, endothermic sealant is designed for use in applications that do not require an intumescent sealant. A cost-effective, water-based sealant, the FS 900+ hardens and cures to form a flexible shield against the spread of fire and smoke. It can be used for various construction/architectural joint configurations - floor to floor, floor to wall, head of wall and wall to wall concrete applications. FS 900+ Sealant has been tested and approved by Underwriters Laboratories for rated systems up to 4 hours, in accordance with UL 79. It is available in both caulkable and self-leveling consistencies. FS 900+ will replace the current FS 900 series sealants. FlameSafe FS 900 This high performance, elastomeric and intumescent sealant is a high-solids, water-based compound engineered to provide exceptional adhesive and elastomeric properties for the demanding firestop requirements of pipe, cable, sprinkler penetrations and construction joints in environments subjected to frequent expansion and contraction. FS 900 is highly intumescent. It expands up to 7 times (700%) its original volume to fill the void created by the melting and burning of polyvinyl chloride (PVC), chlorinated polyvinyl chloride (CPVC), cc-pvc, insulated pipe and plastic coated cables. FS 900 does not contain solvents. As a result, it is not toxic and cannot damage plastic pipes or cable jackets. FlameSafe FS 900 is used to seal openings in fire-rated structures where burning plastic pipe, insulated pipe or coated cables may compromise the rated system. It also can be used in bus and heating, ventilation and air conditioning (HVAC) ducts and through-penetrations with metallic pipes and mixed penetrants. It is used in conjunction with mineral wool boards in safing applications to prevent smoke, fire and toxic gasses from spreading through perimeter joints and floor slabs, openings between fluted roof and floor decks, tops of fire rated walls, wood joist and chase wall floor/ceiling assemblies and other construction/seismic joints. FS 900 is particularly suited for use in applications where system vibration and building movement are concerns. FlameSafe FS 3000 This water-based, elastomeric coating is designed for spray applications onto construction joints and curtain wall assemblies. FS 3000 cures to a flexible membrane seal that is suitable for exterior and interior environments. The coating has been tested to dynamic conditions in accordance with ASTM E399 relating to seismic, wind sway and thermal expansion and contraction environments. The ease of application provides an efficient way to firestop. FlameSafe FS 3000 has been tested and approved for use in curtain wall construction and head of wall applications. For curtain wall applications, a minimum 4" (02 mm) depth of mineral wool (4 pcf (4 kg/m 3 ) density) is compressed a minimum 50% into the joint cavity. The coating is spray applied at a minimum /8" (3.2 mm) thickness (wet) over the surface of the mineral wool and overlapping a minimum of /2" (2.7 mm) onto the floor and wall surface. FlameSafe Bags This unique firestop product allows easy access to cables, cable trays and metallic pipes for through-penetrations in fire-rated floors and walls. FlameSafe Bags are patented bags consisting of tightly woven, durable, coated cloth, filled with a combination of mineral fibers, incombustible components, intumescent agents and special fire retardant additives. They are resistive to the environment and retain their properties and effectiveness when subjected to weather, temperature and atmospheric conditions. Unlike plastic covered pillows, FlameSafe Bags are coated and sealed, effectively encasing the fill material to provide a dust-free environment. This feature makes them particularly suitable for cleanrooms, hospitals, schools and applications with sensitive data and communications equipment. FlameSafe Bags allow for unlimited reentry and are warranted for the life of the building. Easy to install, these durable firestop bags function through a unique 3 phase reaction to intumesce and seal out fire, smoke and toxic gasses. FlameSafe Pillow (FSPIL) FSPIL features a 4 pcf (4 kg/m 3 ) density mineral wool compressed between 2 intumescent sheets (intergulated carbon) which are encased in a durable polyethylene liner. This pillow has been tested by Underwriters Laboratories and approved for and 2 hour gypsum wallboard and 2 hour concrete block wall assemblies. It can also be used for a maximum 4" (02 mm) EMT conduit sleeve with data communications cables or up to 24" 5" (0 27 mm) center spine aluminum cable tray containing coaxial power cables, fiber optic cables and telecommunication cables. Available in both ", 2" and 4" (25.4, 5 and 02 mm) thickness, and installed a minimum " (52 mm) into the opening, the FSPIL is a cost-effective, clean solution for firestopping small power cables and data/ telecommunications cables which require retrofit. FlameSafe FSP 000 Putty This easy-to-install, nonhardening cost-effective firestop is approved for power and data communication cables. It is intumescent, expanding approximately 0% (2 times) to arrest the spread of smoke, fire and toxic gasses in fire-rated walls, ceilings and floors. FSP 000 Putty offers excellent dielectric properties and allows for easy re-entry, making it especially well-suited for applications in which penetrants change frequently. Best known for its ease of application and retrofit, FSP 000 does not require tools. Simply hand pack the putty into the opening. In retrofit applications, remove the putty, make the necessary cable changes and repack the opening with the same putty. FlameSafe Mortar Seal FlameSafe Mortar Seal is the most cost-effective endothermic firestop material available for projects with many large openings. It is a lightweight, low density product that is mixed with varying amounts of water to produce the proper consistency for pouring, pumping

2 or troweling into the cavity. Common plaster machines may be used to mix and pump into large openings. Mortar Seal is a paintable, portland cement based product that does not shrink and, when cured, ensures a smoketight seal. It has a 0 flamespread rating and does not contain solvents, asbestos or silicones. It produces virtually no toxic fumes or smoke when burned. FlameSafe Intumescent Sleeve (FSIS) FSIS is a firestop seal for PVC, cc-pvc, CPVC, fiber reinforced plastic (FRPP), polypropylene (PP) and acrylonitrile-butadiene-styrene (ABS) pipe and rigid nonmetallic conduit installations. Easily installed without modification, steel bolts or fasteners, the FSIS is an ideal approach for firestopping combustible pipes penetrating the uneven contours of concrete fluted deck assemblies and also eliminates the need for collars or wrap strips. The FlameSafe Intumescent Sleeve easily wraps around pipes and is manufactured from a durable 28 gauge galvanized steel outer shell that is lined with FlameSafe FSP 00, a highly intumescent, malleable material. It is fastened with either fiberglass tape, pop rivets or hose clamps around the pipe. When used in conjunction with the FS 900+ or FS 900 caulk, it produces an immediate smoke seal. The FlameSafe Intumescent Sleeve will firestop both sides when installed from either side in concrete walls or floors, as well as pipes going through walls and floors at any angle or slope. Easily installed and cost-effective, the sleeve also can be used in applications that require retrofit. The FlameSafe Intumescent Sleeve intumesces in 2 stages, starting at 250 degrees F (2 degrees C) and continuing through the duration of the burning process. It resists water, UV, frost, fuel, oil, diluted acids and bases as well as most organic solvents. FSIS is available in sizes that can cover 0.75" - 8" ( mm), the FlameSafe Intumescent Sleeve can be easily modified to accommodate unique or nonstandard pipe sizes. The sleeve is sold in single units for easy ordering, storage and handling. FlameSafe Intumescent Wrap Strip (FSWS) FSWS is a highly flexible, resilient strip designed to firestop combustible penetrants in firerated walls and floors. Highly intumescent, expanding up to 40 times its original volume (free expansion), the FSWS rapidly forms a dense char to prevent the spread of fire, smoke and toxic gasses when exposed to temperatures in excess of 250 degrees F (2 degrees C). The FSWS continues to expand up to 000 degrees F (538 degrees C). Available in 2' (3.7 m) rolls, the FlameSafe Wrap Strip is easy to cut and fabricate. The FlameSafe Intumescent Wrap Strip (FSWS) is used to firestop combustible penetrants such as PVC, cc-pvc, CPVC, FRPP and ABS pipe as well as insulated pipe. It has been tested and approved for use in concrete floors or walls as well as wood joist and wood chase wall floor/ceiling assemblies. Some applications, where annular space is restricted, may require the use of the FlameSafe Restraining Collar with the wrap strip. FlameSafe Cable Protection. Electrical cables can be a major source of fuel for potential fires in the industrial and utility environment. Plastics make excellent jacketing materials for electrical cables because of their flexibility, chemical resistance, insulation resistance and dielectric properties. While plastics can be formulated to be fire resistant, they cannot be totally fireproof. Cables in trays or mounted on cable racks are configured perfectly for the propagation of fire. These cables provide a source of fuel and the perfect spacing for the necessary flow of oxygen. Tests show that even cables qualified or rated for fire resistance will propagate fire with sufficient airflow. The addition of industrial or utility contaminants such as paper pulp dust or coal dust adds to the dangers by providing fuel that is readily ignitable by welding sparks or even spontaneous combustion. FlameSafe Cable Protection Products and Systems are designed to limit the propagation of fire on electrical conductors such as cables in trays, loose cable bundles and other cable installations. For over 25 years, major utilities and corporations have made FlameSafe Cable Protection Products the industry standard. FlameSafe Cable Protection Products have evolved and changed to meet the needs of the industry that they serve. Today, FlameSafe stands alone as having the most complete systems for protecting cable installations. FlameSafe Firestop Products and Systems protect cable installations where they pass through fire-rated walls and floors. Refer to the FlameSafe products & systems brochure for additional information on FS 900 Intumescent Sealant, FSP 000 Putty, FSP 077 Putty Pads, Mortar, FlameSafe Bags and KBS Sealbags. SIZES Product package size varies with type of product. See manufacturer s catalog or product data sheets. LIMITATIONS Installations are design dependent and must comply with fire tested assembly details published by the agency which conducted the fire test. Failure to comply with tested system details can result in failure under extreme conditions of fire exposure. 4. Technical Data APPLICABLE STANDARDS American Society for Testing & Materials (ASTM) ASTM C79 Standard Test Method for Adhesion and Cohesion of Elastomeric Joint Sealants Under Cyclic Movement (Hockman Cycle) ASTM E84 (UL 723) Standard Test Method for Surface Burning Characteristics of Building Materials ASTM E9 (UL 23) Standard Test Methods for Fire Tests of Building Construction and Materials ASTM E84 (UL 479/CAN4-S5M) Standard Test Method for Fire Tests of Through-Penetration Fire Stops ASTM E399 (UL 79) Standard Test Method for Cyclic Movement and Measuring the Minimum and Maximum Joint Widths of Architectural Joint Systems Institute of Electrical and Electronics Engineers (IEEE) IEEE 383 Vertical Cable Tray Flame Test Method for Electrical Applications IEEE 34 Standard Cable Penetration Firestop Qualification Test Factory Mutual (FM) - Approval Guide Underwriters Laboratories, Inc. (UL) Refer to Listing Card Number 3(N) Refer to the UL Fire Resistance Directory for specific numbered systems Underwriters Laboratories of Canada, Ltd. (ULC) - Refer to Certification Listing Warnock Hersey (Intertek) - Refer to Certification Listing OMEGA Point Laboratories

3 TABLE PRODUCT DATA Catalog No. FS 900+ Latex Sealant Description FS 900 Intumescent/Elastomeric Sealant FS 3000 Elastomeric Coating FlameSafe Bags FSB 50 FSB 75 FSB 50 FlameSafe Pillows FSPIL FSPIL2 FSPIL4 Fire-Rated Mortar FSM 22B FSM 22P Miscellaneous Accessories CG CG 2 MW MW 24 MW 35/ 5 Sleeves/ Wrap Strips/Devices FSIS 50 FSIS 0 FSIS 300 FSIS 400 FSWS 00 FSWS 50 Units Standard package Weight, lb Caulk 0.3 oz (0.32 L) tube 2 (5.0) Caulk qt (0.95 L) tube 8 (8.2) Self- leveling gal (3.8 L) pail 4 44 (.0) Self- leveling 5 gal (9 L) pail 57 (25.9) Caulkable/ trowelable gal (3.8 L) pail 4 44 (.0) Caulkable/ trowelable 5 gal (9 L) pail 57 (25.9) Caulk 0.3 oz (0.32 L) tube 2 (5.0) Caulk qt (0.95 L) tube 8 (8.2) Trowelable gal (3.8 L) pail 4 48 (2.8) Trowelable 5 gal (9 L) pail 53 (24.) Safing sealant 5 gauge (3.8 L) pail 48 (2.8) /2" 7" 3 /2" ( mm) 3/4" 7" 3 /2" ( mm) / 2" 7" 3 /2" ( mm) " 9" " ( mm) " 9" 2" ( mm) " 9" 4" ( mm) 22 lb (0 kg) dry mix bag 22 lb (0 kg) dry mix pail Caulk gun, 0.3 oz (0.32 L) tube Caulk gun, qt (0.95 L) Mineral wool, lb (0.5 kg) bag Mineral wool batts, 2' 4' 2' ( mm) Insertion plates, pair each mm or m Sleeve, / 2" (38 mm).9" (48 mm) OD Sleeve, 2" (5 mm) 2 / 2" (4 mm) OD Sleeve, 3" (7 mm) 3 / 2" (89 mm) OD Sleeve, 4" (02 mm) 4 / 2" (4 mm) OD Wrap strip 2' " / 4" (3.7 m 25.4 mm.4 mm) Wrap strip, 2' / 2" / 4" (3.7 m 38 mm.4 mm) (5.5) 35 (5.9) 3 (.3) 5 (2.3) 7 (3.2) 5 (2.3) 23 (0.4) 2 (.8) 2 (0.9) 3 (.4) (2.7) 4 (.4) - 8 (3.) 0 (4.5) 3 (5.9) 8 (8.2) 2 (0.9) 3 (.4) (kg) APPROVALS California State Fire Marshal (CSFM) : : : : :04 City of New York, New York, Department of Buildings MEA M Vol. IV MEA M, Vol. V MEA 79-9-M MEA 4-00-M MEA M MEA M International Conference of Building Officials (ICBO) PHYSICAL/CHEMICAL PROPERTIES See Tables and 2. Test reports and additional product information are available to design professionals upon request. FIRE PERFORMANCE AND RATINGS See Tables and 2. Assembly fire ratings vary depending on the specific product and tested assembly. Consult manufacturer s product data sheets or the fire resistance design manual published by the testing agency. 5. Installation PREPARATORY WORK Handle and store product according to Grace recommendations. All contact surfaces must be free of loose dirt, scale, oil or other foreign materials. METHODS Installation procedures and materials used vary according to the product, the size of the opening being protected and the type of penetrant. Sealant material may be installed using a standard or powered caulk gun or troweled into place using a mason s trowel or putty knife. Some materials are installed with spray equipment. In many cases, there are temperature range recommendations. Complete installation recommendations are available from the manufacturer. See product data sheets or consult with technical support staff. of The Construction Specifications Institute and is used with their permission. The manufacturer is responsible for technical a ccuracy. 02 Architects First Source. All Rights Reserved.

4 TABLE 2 TECHNICAL DATA Description Blank Openings Wall/ Floor Type F Rating Product System # 5" (38 mm) diameter opening 432 sq. in. opening FS 900 FSM22 CAJ002 CAJ sq. in. opening 2 & 4 hr. FSB/ KBS CBJ / 8" /2" ( mm) opening Metallic Penetrants (4) 4" (02 mm) steel or copper pipes, or EMTs & FSB/ KBS FS 900/FSM22 WL0002 CAJ088/CAJ22 4" (02 mm) steel or copper pipe or EMT FSM22/ FS 900 CAJ09/ WJ09 24" (0 mm) steel, " (52 mm) copper or 4" (02 mm) EMT 2 & FS 900 or 900+ CAJ235/WJ03 () " (25.4 mm) flexible steel conduits FSP 000 CAJ242 24" (0 mm) steel or iron or 4" (02 mm) EMT FS 900+ CAJ379 24" (0 mm) steel, " (52 mm) conduit or 4" (02 mm) EMT 2 & FS 900/FS 900 CBJ035/WJ05 (4) " (25.4 mm) flexible aluminum conduits Concrete Wall/ & FS 900 WJ087/WL4 Multi pene, 3" (7 mm) steel, iron or EMT Concrete Wall/ & FS 900/ FS 900+ WJ0/ WJ090/ WL7 4" (02 mm) steel pipe or EMT or 3" (7 mm) copper pipe Wood Joist Floor/Ceiling & FS 900 FC02/FC0 (3) " (25.4 mm) flexible steel conduits & FS 900 FC037/ FC045 4" (02 mm) steel pipe or EMT, or 3" (7 mm) copper pipe Wood Chase Wall & FS 900 FC023/FC022 / 2" (3 mm) flexible steel or aluminum conduit & FS 900 WL04 24" (0 mm) steel pipe, " (52 mm) copper pipe or & FS 900/FS 900 WL089/WL52 4" (02 mm) EMT Multi pene, 2" (5 mm) steel, iron or EMT FS 900 WL53 4" (02 mm) steel, iron, or copper pipe or EMT Nonmetallic Penetrants 4" (02 mm) RNC, PVC, cc-pvc or CPVC pipe 4" (02 mm) RNC, PVC, cc-pvc, FRPP or CPVC pipe & FS 900 FSIS/FS 900 FSIS/FS 900 WL9 CAJ27 CAJ272 2" (5 mm) RNC, PVC, cc-pvc, FRPP or CPVC pipe FSIS/FS 900 CAJ273 4" (02 mm) ABS pipe FSIS/ FS 900 CAJ274 2" (5 mm) FRPP or PP pipe 2 & FSIS/ FS 900 CAJ275 Up to 2, " (25.4 mm) crossed linked polyethylene (PEX) FS 900 CAJ294 3" (7 mm) RNC, PVC, CPVC or ABS pipe FSWS50* CAJ2 2" (5 mm) RNC, PVC or CPVC pipe FSWS50/ FS 900 CAJ22/ CBJ05/ WJ5 8" (3 mm) PVC pipe FSIS/ FS 900 CAJ220 2" (5 mm) ABS pipe FSWS50* CAJ22 5" (27 mm) RNC, PVC or CPVC pipe FSWS50* CAJ222 3" (7 mm) RNC, CPVC, PVC or cc- PVC pipe Concrete Wall/ & FSWS50* WJ48/WL28 4" (02 mm) RNC, PVC, cc- PVC, CPVC, ABS or cc- ABS pipe Concrete Wall/ & FSWS00* WJ52/WL27 4" (02 mm) RNC, PVC, cc- PVC or CPVC pipe Concrete Wall/ & FSWS00* WJ58/WL289 4" (02 mm) RNC, PVC or CPVC pipe & FSD/ FS 900 FC43/ FC4 2" (5 mm) RNC, PVC or CPVC pipe FSWS00/ FS 900 FC42/ FC84 4" (02 mm) RNC, PVC, cc- PVC, CPVC, ABS or cc- ABS pipe Wood Chase Wall hr. FS 900 FC82 3" (7 mm) RNC, PVC, or CPVC pipe & FSWS00* FC83 4" (02 mm) ABS, FRPP, PVC, cc- PVC or CPVC pipe Wood Chase Wall hr. FSWS00* FC8 4" (02 mm) PVC or ABS waste pipe & closet flange Wood Joist Floor/Ceiling hr. FS 900 FC87 /2" (38 mm) ABS, PVC bathtub waste & overflow Wood Joist Floor/Ceiling hr. FSWS00/FS 900 FC88/FC89 4" (02 mm) ABS pipe & p- trap drain pipe Wood Chase Wall hr. FSWS00* FC90 4" (02 mm) PVC, cc- PVC, or CPVC pipe & p- trap drain pipe Wood Chase Wall hr. FS 900 FC9 2" (5 mm) RNC, PVC, cc- PVC or CPVC pipe Wood Chase Wall hr. FS 900 FC203 3" (7 mm) PVC, cc- PVC, CPVC, cc- CPVC, ABS or cc- ABS pipe Wood Chase Wall hr. FSWS00* FC222 4 (02 mm) PVC, cc- PVC, CPVC, cc- CPVC, ABS or cc- ABS pipe Wood Chase Wall hr. FS 900 FC24 4" (02 mm) RNC, PVC, cc- PVC, CPVC, ABS, cc- ABS, FRPP or glass & FSIS/FS 900 WL2 2" (5 mm) RNC, PVC, cc- PVC, CPVC or ENT pipe & FS 900 WL270 8" (3 mm) RNC, PVC or CPVC pipe Cables & FSIS/ FS 900+ WL285 Multiconductor and telecom cables Multiconductor and telecom cables Concrete Wall FSP000/ FS 900/ FS 900 FS 900/ FS Bags/ FS 900 CAJ30 / CAJ3035/ CAJ33 WJ309/ WJ3038/ WJ3039 Multiconductor power cables Concrete Wall/ & FS 900 WJ3042/ WL3 Telecom, Romex, coaxial and aluminum SER cables Wood Joist Floor/Ceiling & FS 900 FC308/FC309 & FC30/FC302 Romex and telecom cables & FS Bags WL300

5 Coaxial, fiber optic and telecom cables Romex cable Telecom cables Multiconductor and telecom cables Insulated Pipes & & & & FS Bags FS 900 FS 900 FS Bags/ FS 900 WL3007 WL300 WL3072 WL38/ WL39 0" (254 mm) metallic pipe w/ " (25.4 mm) AB/ PVC foam insul. 2" (305 mm) metallic pipe w/ " (25.4 mm) fiberglass insul. -/ FS 900 FS 900 CAJ5073 CAJ5 " (52 mm) metallic pipe w/ " (25.4 mm) AB/ PVC foam insul. FSWS50 & FS 900 CAJ57 8" (3 mm) metallic pipe w/ 2" (5 mm) fiberglass insul. FSWS50 & FS 900 CAJ58 0" (254 mm) metallic pipe w/ " (25.4 mm) foamglas insul. FS 900+ CAJ575 8" (3 mm) metallic pipe w/ 2" (5 mm) fiberglass insul. FS 900 CBJ5008 8" (3 mm) steel pipe w/ / 2" (38 mm) Concrete Wall/ & FS 900 WJ5035/ WL508 calcium silicate insul. 0" (254 mm) metallic pipe w/ 3" (7 mm) foamglas insul. Concrete Wall/ & FS 900 WJ503/ WL5087 2" (305 mm) metallic pipe w/ 3" (7 mm) fiberglass insul. Concrete Wall/ & FSWS00 & FS 900 WJ5043/ WL50974" (02 mm) metallic pipe w/ 2" (5 mm) fiberglass insul. Concrete Wall/ & FS 900 WJ5044/ WL5098 4" (02 mm) metallic pipe w/ 3/ 4" (9. mm) Concrete Wall/ & FS 900 WJ5045/ WL5099 AB/ PVC foam insul. /2" (38 mm) metallic pipe w/ " (25.4 mm ) fiberglass insul. Wood Joist Floor/Ceiling FS 900 FC500 / 2" (38 mm) metallic pipe w/ " (25.4 mm) fiberglass or 3/4 (9. mm) AB/ PVC foam insul. 2" (5 mm) metallic pipe w/ / 2" (3 mm) AB/ PVC foam insul. Wood Joist Floor/Ceiling hr. & FS 900 FSWS00 & FS 900 FC50 FC5030/ FC5025 / 2" (38 mm) metallic pipe w/ " (25.4 mm) fiberglass insul. Wood Chase Wall FS 900 FC502 /2" (38 mm) metallic pipe w/ " (25.4 mm) fiberglass Wood Chase Wall hr. FS 900 FC503 or 3/ 4" (9. mm) AB/ PVC foam insul. Electrical Penetrants 27" " (8 52 mm) Busway 4" 4" (02 02 mm) metallic or nonmetallic outlet box & FS 900/ FSM22/ FS 900 FSP 077 CAJ0/ CAJ02/ CAJ03 R3 HVAC Ducts 24" 2" (0 305 mm) steel duct 0" (254 mm) round steel duct 2" 2" (5 5 mm) steel duct " 40" (508 0 mm) steel duct 4" (02 mm) round steel duct 4" (02 mm) round steel duct 0" " ( mm) steel duct Mixed Penetrants Concrete Wall/ Concrete Wall/ Concrete Wall/ & & & & hr. FS 900 FS 900 FS 900 FS 900 FS 900 FS 900 FS 900 CAJ7008 CAJ7038 WJ7002/ WL700 WJ7008/ WL7027 WJ7023/ WL704 FC7005/ FC7004 FC7008 4" (02 mm) metallic pipes w/ 24" 3 / 2" (0 89 mm) cable tray FSM22 CAJ802 4" (02 mm) metallic and insul. pipe w/ mixed electrical cables FS 900 CAJ8042 2" (5 mm) metallic and insul. pipe w/ mixed electrical cables Wood Joist Floor/Ceiling & FS 900 FC8003/ FC8002 /2" (38. mm) multiple pipes w/ electrical cables Wood Joist Floor/Ceiling hr. FSWS00* FC809 4" (02 mm) metallic and insul. pipe w/ mixed electrical cables & FS 900 WL8007 Joints 8" (3 mm), Concrete floor to steel studded wall w/gypsum 8" (3 mm), Concrete floor to concrete tilt-up panels Curtain Wall Curtain Wall FS 3000 FS 3000 CEJ50P CEJ5P 8" (3 mm), Concrete floor to steel studded wall Curtain Wall FS 3000 CEJ52P w/concrete panels 8" (3 mm), Concrete floor to aluminum framed wall Curtain Wall FS 3000 CEJ53P w/concrete panels 8" (3 mm), Concrete floor to aluminum framed wall Curtain Wall FS 3000 CEJ54P w/glass panels 4" (02 mm), Concrete floor to steel stud wall w/gypsum & EIFS Curtain Wall hr. FS 3000 CEJ93P 2" (5 mm), Concrete floor to concrete floor FS 900 FFD003 2" (5 mm), Concrete floor to concrete floor 4 hr. FS 3000/ FS 900+ FFD0022/ FFD0023 " (25.4 mm), Concrete floor to concrete floor FS 900+ FFD / 2" (89 mm), Concrete floor to concrete floor FS 3000/ FS 900+ FFD024/ FFD027 2" (5 mm), Concrete floor to concrete or block wall Floor/Wall FS 900 FWD000 2" (5 mm), Concrete floor to concrete or block wall Floor/Wall 4 hr. FS 3000/FS 900+ FWD007/FWD008 " (25.4 mm), Concrete floor to concrete or block wall Floor/Wall FS 900+ FWD009 of The Construction Specifications Institute and is used with their permission. The manufacturer is responsible for technical a ccuracy. 02 Architects First Source. All Rights Reserved.

6 3 /2" (89 mm), Concrete floor to concrete or block wall Floor/Wall FS 3000/FS 900+ FWD0/FWD024 2" (5 mm), Concrete or block wall to concrete floor Head-of-Wall FS 900/FS 3000 HWD000/HWD009 " (25.4 mm), Gypsum wall to fluted deck (w/fireproofing) Head-of-Wall & FS 3000 CEJ47H/CEJ4H " (25.4 mm), Gypsum wall to fluted deck (w/fireproofing) Head-of-Wall & FS 3000 CEJ49H/CEJ48H 2" (5 mm), Gypsum wall to fluted deck Head-of-Wall FS 3000/ FS 900+ HWD007/ HWD04 2" (5 mm), Gypsum wall to concrete floor Head-of-Wall FS 3000 HWD008 2" (5 mm), Concrete or block wall to fluted deck Head-of-Wall FS 3000 HWD00 " (25.4 mm), Gypsum wall to fluted deck cookie cutter design Head-of-Wall & FS 900/FS 900+ HWD024/HWD044 3 /2" (89 mm), Concrete or block wall to concrete floor Head-of-Wall FS 3000/FS 900+ HWD02/HWD024 " (25.4 mm), Gypsum wall to concrete floor Head-of-Wall & FS 900/ FS 900+ HWD038/ HWD047 " (25.4 mm), Gypsum wall to fluted deck (parallel) Head-of-Wall & FS 900+ HWD048 " (25.4 mm), Concrete or block wall to fluted deck Head-of-Wall FS 900+ HWD049 " (25.4 mm), Concrete or block wall to fluted deck (parallel) Head-of-Wall FS 900+ HWD050 " (25.4 mm), Concrete or block wall to concrete floor Head-of-Wall FS 900+ HWD05/HWD089 2" (5 mm), Concrete or block wall to concrete or block wall Wall/Wall FS900 WWD00 " (25.4), Concrete or block wall to concrete or block wall Wall/Wall FS 900+ WWD /2" (89 mm), Concrete or block wall to concrete or block wall Wall/Wall FS 3000/FS 900+ WWD028/WWD029 BUILDING CODES Current data on building code requirements and product compliance may be obtained from the manufacturer s technical support specialists. Installation must comply with the requirements of applicable local, state and national code jurisdictions.. Availability & Cost AVAILABILITY FlameSafe products are available through authorized distributors. Contact manufacturer for more information. COST Budget installed cost information may be obtained from a local distributor or through the manufacturer. 9. Technical Services The manufacturer provides toll-free technical support for all its products. Call Customer Service at (800) for assistance in product selection and for detailed specifications and approvals. The manufacturer provides engineering analyses for unique firestopping applications, including system design drawings suitable for submittals. Material Safety Data Sheets (MSDS) are also available. 0. Filing Systems First Source for Products MANU-SPEC«Sweet s Catalog Files Additional product information is available from the manufacturer upon request. 7. Warranty All statements, technical information and recommendations contained in the product documentation are based on tests believed to be reliable. However, since the conditions of use and applications are beyond the manufacturer s control, the manufacturer shall not be liable for any damage direct or consequential, resulting from the use of these materials or designs. The manufacturer s only warranty shall be to replace any of its products found to be defective. 8. Maintenance FlameSafe applications are maintenancefree; however, installations should be periodically inspected for accidental damage and repaired using the material required by the original approved design. hopes the information here will be helpful. It is based upon data and knowledge considered to be true and accurate and is offered for the users consideration, investigation and verification, but we do not warrant the results to be obtained. Please read all statements, recommendations and suggestions in conjunction with our conditions of sale, which apply to all goods supped for any use which would infringe any patent or copyright. 20 Spenwick Dr, Houston, TX FlameSafe and KBS are registered trademarks of FS-050A Printed in the U.S.A. 9/09 AFS/GPS/3M