1. Refer to SECTION SIGNS and reolace entire document with aftached new soecification. 5. Refer to Electrical Drawing E3.1

Size: px
Start display at page:

Download "1. Refer to SECTION SIGNS and reolace entire document with aftached new soecification. 5. Refer to Electrical Drawing E3.1"

Transcription

1 OTC REALIGNMENT - 8TH FLOOR ADDENDUM THREE June 25, 205 DRAWING CHANGES:. Refer to Mechanical Drawing M3. a. Revised: Fan Powered Terminal Unit Schedule. b. Revised: Variable Air Terminal Unit Schedule. 3. Refer to Electrical Drawing E. a. Reissued sheet in its entirety. 4. Refer to Electrical Drawing E2. a. Reissued sheet in its entirety. 5. Refer to Electrical Drawing E3. a. Reissued sheet in its entirety. 6. Refer to Electrical Drawing E4. a. Reissued sheet in its entirety. 4. Refer to Electrical Drawing E5. a. This sheet was added. 5, Refer to drawing MEP.0 a. Symbols were added to Electrical Legend. PROJECT MANUAL CHANGES:. Refer to SECTION 0400 SIGNS and reolace entire document with aftached new soecification. Please acknowledge receipt of this Addendum as part of your bid. END OF ADDENDUM THREE Page of 903 WEST 30TH r/2 STREET AUST N, TEXA P t W LAUR ESMITHDESIGN COM

2 SIGNS SECTION 0400 PART - GENERAL. RELATED DOCUMENTS A. The Drawings and general provisions of the Contract, including other Division Specification Sections, apply to this Section..2 SUMMARY A. Work under this heading shall include but not be limited to the furnishing and installing all signage as shown and specified herein. B. Related Sections:. Division Section 0352 Sustainable Construction Requirements 2. Division Section 0505 Construction Waste Management 3. Division Section 050 Construction IAQ Management.3 SUBMITTALS A. General: Submit the following in accordance with Conditions of Contract and Division Specification Sections. B. Product data for each type of product specified.. Include sustainability statement for locally manufactured material. 2. Include sustainability statement for recycled content of materials. C. Samples: Submit selection and verification samples for finishes, colors and textures. Submit one sample of each type of panel, trim and fastener. PART 2 - PRODUCTS 2. SIGN TYPES A. Interior signs: Provide ADA compliant sign system with raised letters and Braille.. Material and Copy Process: Raised photopolymer with tactile letters, numbers, icons, arrows and Braille. Letters, numbers and icons to receive tipped color. a. Provide acrylic back panel, inset behind photopolymer sign for floating installation. 2. Edge Finish: Unframed, finished edges. 3. Thickness: /4 photopolymer, 3/8 acrylic. 4. Background and Text Color: To be selected 5. City of Austin logo: Full color 6. Corners: Square 7. Type Style: To be selected a. Suite Number: Bold b. Text: Condensed ONE TEXAS CENTER REALIGNMENT PAGE OF 5 SIGNS SECTION 0400

3 SIGNS SECTION Mounting Method: 3M foam tape and clear silicone a. Adhesive must comply with VOC limits per Section 0352 Sustainable Construction. B. Interior signs: Signs for Paper Insert:. Material: Photopolymer with clear, matte acrylic window. a. Provide photopolymer panel insert w/ vinyl letters and arrows panel to insert inside acrylic window.. /8 Thick. b. Provide acrylic back panel, inset behind photopolymer sign for floating installation. 2. Edge Finish: Unframed, finished edges. 3. Thickness: /4 photopolymer, /4" acrylic window and /4" acrylic back panel. 4. Color: To be selected. 5. Corners: Square 6. Mounting Method: 3M foam tape and clear silicone a. Adhesive must comply with VOC limits per Section 0352 Sustainable Construction. C. Interior signs: Floor-By-Floor Directories. Material: Photopolymer with clear, matte acrylic window. a. Provide photopolymer panel insert w/ vinyl letters and arrows panel to insert inside acrylic window.. /8 Thick. b. Provide acrylic back panel, inset behind photopolymer sign for floating installation. 2. Edge Finish: Unframed, finished edges. 3. Thickness: /4 photopolymer face plate, /4" acrylic window and /4" clear acrylic back plate. 4. Colors: To be selected. 5. Corners: Square 6. Mounting Method: 3M foam tape and clear silicone a. Adhesive must comply with VOC limits per Section 0352 Sustainable Construction. D. Interior signs: Existing Ground Floor Directories:. Update existing directories with new department names and suite numbers as required for way-finding. 2. Description of Existing Directories: X 7.50 overall with digitally printed, changeable tenant listing panels. Text is left clear for illumination. Text Height: Quantity: Two Directories three panels within each directory. ONE TEXAS CENTER REALIGNMENT PAGE 2 OF 5 SIGNS SECTION 0400

4 SIGNS SECTION 0400 E. Interior signs: Translucent Film. Provide horizontal band of translucent film with City of Austin seal cut-out at Suite Entry glazing. 2.2 SIGN FUNCTION A. Elevator Lobby Directional Signs. Provide new signs with: a. Floor number b. City seal c. Department names with directional arrows d. Phrase: For assistance, please call (52) Size: 2 W x 8 H 3. Type: C 4. Quantity: 8 th Floor - 4 B. Suite Entry Signs (Main Entry for each Department or Division). Provide new sign at latch side of entry door. All signs must comply with the requirements of ADA and the Texas Accessibility Standards. Include: a. Suite number b. Office name c. City seal d. Department name 2. Size: 2 W x 2 H 3. Type: A 4. Quantity: 8 th Floor - 4 C. Sign Holder for Paper Insert (by Tenants). Type B. a. Size: for 8 ½ X easily changeable paper insert; allow for standoff mount hardware. b. Quantity: 8 th Floor - 0; quantity includes one for Elevator Lobby, each Suite, Break Room, each conference room door that opens into main corridor and one for the Emergency Evacuation Floor Plan located next to door at each stairwell. 2. Type B.2 a. Size: for X 7 easily changeable paper insert; allow for standoff mount hardware. b. Quantity: 8 th Floor - 8; quantity includes one for Elevator Lobby, each Suite, Break Room, and each conference room door that opens into main corridor. ONE TEXAS CENTER REALIGNMENT PAGE 3 OF 5 SIGNS SECTION 0400

5 SIGNS SECTION Type B.3 a. Size: for 22 X 28 posters. b. Quantity: 8 th Floor Elevator Lobby. D. Room I.D. Signs. Provide new signs at latch side of doors to common spaces off main corridor. All signs must comply with the requirements of ADA and the Texas Accessibility Standards. Include: a. Room name b. Room number c. City seal 2. Size: 8 W X 8 H 3. Type: A 4. Quantity: 8 th Floor - 4; quantity includes conference rooms, break room, and freight elevator. E. Signs Related to Stairs. Elevator Lobby a. Provide new signs in Elevator Lobby. All signs must comply with the requirements of ADA and the Texas Accessibility Standards. b. Phrase: In case of Emergency, DO NOT use Elevators, use EXIT Stairs c. Size: 5 W X 5 H d. Type: A e. Quantity: 2 2. Stair Doors a. Provide new signs at doors to stairs. All signs must comply with the requirements of ADA and the Texas Accessibility Standards. b. Phrase: STAIRS No Re-Entry After Hours c. Size: 5 W X 5 H d. Type: A e. Quantity: 2 per floor F. Toilet Room Signs. Provide new signs at latch side of doors going into rooms off main corridor. All signs must comply with the requirements of ADA and the Texas Accessibility Standards. Include: a. Room name b. Gender symbol c. Accessibility symbol 2. Size: 5 W X 5 H ONE TEXAS CENTER REALIGNMENT PAGE 4 OF 5 SIGNS SECTION 0400

6 SIGNS SECTION Type: A 4. Quantity: 2 per floor G. Interior Signs Translucent film at Glazing. Provide band of translucent film with reverse cut City of Austin seal. 2. Size: 2 H X Full width of glass. 3. Type: D 4. Quantity: 2 per floor one at Suite entry with double doors and one at Suite entry with single door and 4-0 W window. PART 3 - EXECUTION 3. INSTALLATION A. Install in accordance with manufacturer s specifications, square and true. Installation heights and locations shall be as directed by Designer. All adhesives to comply with guidelines stated in Section Upon completion of installation, adjust and clean as required. B. All sign installations shall comply with the Texas Accessibility Standards and other applicable disability standards. END OF SECTION 0400 ONE TEXAS CENTER REALIGNMENT PAGE 5 OF 5 SIGNS SECTION 0400

7

8

9

10

11

12 AIR DEVICE SCHEDULE MARK MIN. CFM RANGE MAX. FACE SIZE (IN.) NECK SIZE (IN.) MAX S.P. (IN.) MAX. NC LEVEL MAKE / MODEL NOTES A 0 B C R X x24 6"Ø x24 8"Ø x PERFORATED DIFUSERS PRICE MODEL PDF PERFORATED DIFUSERS PRICE MODEL PDF PERFORATED RETURN MAXIMUM SQUARE NECK PRICE MODELPDDR PERFORATED RETURN MAXIMUM SQUARE NECK PRICE MODELPDDR, 2, 3, 4, 2, 3, 4, 2, 3, 4, 2, 3, 4 NOTES:. PROVIDE WITH FACTORY-APPLIED, OFF-WHITE ENAMEL FINISH. 2. PROVIDE WITH FLUSH MOUNT FRAME OR T-BAR MOUNT FRAME AS REQUIRED TO MATCH CEILING CONDITION. 3. PROVIDE WITH MITERED CORNERS. 4. PROVIDE SQUARE TO ROUND DUCT TRANSITIONS AS REQUIRED. MARK VAV-8-5 VAV-8-6 VAV-8-7 VAV-8-8 VAV-8- VAV-8-2 VAV-8-3 VARIABLE AIR SCHEDULE TERMINAL TYPE CFM INLET SIZE DESIGN MIN. IN MAKE/MODEL NOTES NOTES:. PROVIDE " FOIL-FACED FIBROUS GLASS DUCT LINER COMPLYING WITH UL8 AND NFPA 90A. MARK FTU-8- FTU-8-2 FTU-8-3 FTU-8-4 FTU-8-9 FTU-8-0 TERMINAL TYPE FAN POWERED FAN POWERED FAN POWERED FAN POWERED FAN POWERED FAN POWERED FAN POWERED SCHEDULE CFM HEATING COIL INLET SIZE FAN (hp) EAT LAT COIL LOAD DESIGN MIN. IN. KW / / / / / / MAKE/MODEL TRANE VPEF OR APPROVED ALTERNATE TRANE VPEF OR APPROVED ALTERNATE TRANE VPEF OR APPROVED ALTERNATE TRANE VPEF OR APPROVED ALTERNATE TRANE VPEF OR APPROVED ALTERNATE TRANE VPEF OR APPROVED ALTERNATE NOTES,2,3,2,3,2,3,2,3,2,3,2,3 NOTES:. PROVIDE UNIT WITH 480 VOLT, THREE PHASE SINGLE POINT POWER CONNECTION WITH FUSED DISCONNECT. 2. PROVIDE SOLID STATE COMULATING HEAT CONTROL FOR ALL HEATING COILS. 3. PROVIDE " FOIL-FACED FIBROUS GLASS DUCT LINER COMPLYING WITH UL8 AND NFPA 90A.

13