*Corrected October 2005

Size: px
Start display at page:

Download "*Corrected October 2005"

Transcription

1 ESR-1056* Reissued December 1, 2004 This report is subject to re-examination in two years. ICC Evaluation Service, Inc. Business/Regional Office # 5360 Workman Mill Road, Whittier, California # (562) Regional Office # 900 Montclair Road, Suite A, Birmingham, Alabama # (205) Regional Office # 4051 West Flossmoor Road, Country Club Hills, Illinois # (708) DIVISION: 03 CONCRETE Section: Concrete Anchoring DIVISION: 04 MASONRY Section: Masonry Anchorage REPORT HOLDER: SIMPSON STRONG-TIE COMPANY, INC DUBLIN BOULEVARD, SUITE 400 DUBLIN, CALIFORNIA (925) EVALUATION SUBJECT: TITEN HD SCREW S 1.0 EVALUATION SCOPE Compliance with the following codes: # 2000 International Building Code (IBC). # 2000 International Residential Code (IRC). # 1997 Uniform Building Code (UBC). Properties evaluated: Structural 2.0 USES The Titen HD screw anchor is for installation in predrilled holes in normal-weight concrete, structural sand-lightweight concrete on metal deck, and fully grouted concrete masonry wall construction. The Titen HD screw anchor is an alternative to cast-in-place anchors described in IBC Section 1912 and UBC Section The anchors are permitted to be used in structures regulated by the IRC, provided an engineered design is submitted in accordance with IRC Section R DESCRIPTION 3.1 Materials: Titen HD Screw Anchor: The Titen HD screw anchor is a carbon steel threaded anchor with a hex-washer head. The screw anchor is manufactured from heat-treated steel complying with SAE J403 Grade 10B21, and has either an electrodeposited coating of zinc in accordance with ASTM B 633, Service Condition SC1, Type III; or a mechanically deposited coating of zinc in accordance with ASTM B 695, Class 65, Type I. Titen HD screw anchors are available with nominally 3 / 8 -, 1 / 2 -, 5 / 8 -, and 3 / 4 -inch (9.5, 12.7, 15.9 and 19.1 mm) shank diameters, and with various lengths for multiple embedments as noted in the tables in this report. Refer to Figure 1 for an illustration of a typical screw anchor Normal-weight Concrete: Concrete shall be stoneaggregate normal-weight concrete having a minimum compressive strength as noted in the tables in this report at the time of anchor installation. concrete thickness is 1 1 / 2 times the anchor embedment at the location of anchor installation Structural Sand-lightweight Concrete-fill Metaldeck Assembly: Metal Deck: The metal deck shall be minimum No. 20 gage [0.035 inch (0.889 mm) base-metal thickness] galvanized steel conforming to ASTM A 653/A 653M, with a minimum yield strength of 38 ksi (261.8 MPa) and a minimum ultimate strength of 45 ksi (310 MPa). Figure 2 illustrates required metal-deck bottom-flute dimensions: a minimum of 4 1 / 2 inches (114 mm) wide, a maximum of 3 inches (76 mm) deep, and with a minimum spacing of 12 inches (305 mm). Metal decks having greater bottom flute widths and relative spacings shall be permitted Concrete Fill: The structural sand-lightweight concrete shall have a minimum 3,000 psi (20.7 MPa) compressive strength at time of anchor installation. Aggregates for structural sand-lightweight concrete shall comply with Section 3.3 of ACI concrete thickness measured from the top flute is 3 1 / 4 inches (83 mm). Refer to Figure Grout-filled Concrete Masonry: When prism tests are required, the compressive strength of masonry, fn m, at 28 days shall be a minimum of 1,500 psi (10.3 MPa). Fully grouted masonry walls shall be constructed from the following materials: Concrete Masonry Units (CMUs): CMUs shall be minimum Grade N, Type II, lightweight, medium-weight, or normal-weight conforming to ASTM C 90 or UBC Standard The minimum allowable nominal size of the CMU shall be 8 inches (203 mm) wide by 8 inches (203 mm) high by 16 inches (406 mm) long (i.e., ) Grout: Grout shall comply with IBC Section , IRC Section R , or UBC Section , as applicable. Alternatively, the grout shall have a minimum compressive strength when tested in accordance with ASTM C a equal to its specified strength, but not less than 2,000 psi (13.8 MPa) Mortar: Mortar shall comply with IBC Section , IRC Section R607, or UBC Section and UBC Standard 21-15, as applicable. The mortar shall have a minimum compressive strength of 1,500 psi (10.3 MPa). 3.2 Design: *Corrected October 2005 are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, Inc., express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2005 Page 1 of 11

2 Page 2 of 11 ESR General: Anchors described in this report are assigned allowable tension and shear loads for designs based on allowable stress design (working stress design). Use of the anchors to resist vibratory and moving loads, such as those produced by reciprocating engines, cranes and vehicles, is beyond the scope of this report Design of Anchors in Normal-weight Concrete: Allowable tension and shear loads for installation in normalweight concrete are noted in Tables 3 through 6. Spacing and edge distance requirements are noted in Tables 1 through 6. Allowable load reduction factors noted in Table 2 are applicable only to the allowable loads shown in Tables 3 and 4. For installations in normal-weight concrete, anchors are recognized to resist dead-, live-, wind-, and earthquake-load applications. Allowable loads may be increased by 33 1 / 3 percent when using the alternate basic load combinations in accordance with Section of the IBC or Section of the UBC, for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section may be multiplied by a factor of Allowable loads for anchors installed in normal-weight concrete subjected to combined shear and tension forces shall be determined by the following equation: P s P t 5/3 V + 5/3 s V t # 1.0 where: P s = Applied service tension load. P t = Allowable service tension load. V s = Applied service shear load. V t = Allowable service shear load Design of Anchors in the Top or Bottom of Structural Sand-lightweight Concrete Filled Metal-deck Assemblies: Allowable tension and shear loads, and spacing and edge distance requirements, for anchors installed in the top or bottom of structural sand-lightweight concrete filled metal-deck assemblies are noted in Table 7. Refer to Figure 2 for required assembly details. Anchors installed in the top of structural sand-lightweight concrete and metal-deck assemblies may resist wind or earthquake loads. Allowable tension and shear loads may be increased by 33 1 / 3 percent when using the alternate basic load combinations in accordance with Section of the IBC or Section of the UBC, for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section may be multiplied by a factor of Anchors installed in the bottom of structural sandlightweight concrete and metal-deck assemblies may resist wind or earthquake loads: Allowable tension loads for bottom deck installations may be increased by 33 1 / 3 percent when using the alternate basic load combinations in accordance with Section of the IBC or Section of the UBC, for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section may be multiplied by a factor of Allowable shear loads for bottom deck installations shall not be increased when using the alternate basic load combinations in accordance with Section of the IBC or Section of the UBC, for wind or earthquake loading conditions. Allowable loads for anchors installed into the top or bottom of structural sand-lightweight concrete filled metal-deck assemblies subjected to combined shear and tension forces shall be determined by the following equation: P s P t V + s V t # 1.0 where: P s = Applied service tension load. P t = Allowable service tension load. V s = Applied service shear load. V t = Allowable service shear load Design of Anchors in Fully Grouted CMU Masonry Walls: Allowable tension and shear loads for anchors installed in the face of fully grouted CMU masonry walls are noted in Table 8A for structures complying with the IBC or IRC, and Table 8B for structures complying with the UBC. The allowable tension and shear loads are for anchors installed in the grouted cells, the center web of CMU units, and horizontal mortared bed joints of fully grouted CMU masonry wall construction. Allowable loads for anchors installed in the vertical head joint or the end flanges of the CMU units are outside the scope of this report. Edge and end distances, and spacing requirements for anchors installed in the face of fully grouted CMU masonry walls, as shown in Figure 3, are noted in Tables 8A and 8B. Allowable load reduction factors for anchors installed at reduced edge and end distances, and reduced spacing, are noted in Tables 9 and 10. Allowable tension and shear loads for 1 / 2 -inch and 5 / 8 -inch (12.7 mm and 15.9 mm) anchors installed in the top of fully grouted concrete masonry walls (CMU grouted cores and CMU webs), are noted in Table 11A for anchors installed in structures complying with the IBC or IRC, and Table 11B for anchors installed in structures complying with the UBC. When using the alternate basic load combinations in IBC Section or UBC Section that include wind or earthquake loads, the allowable shear and tension loads for anchors installed in the face and the top in fully grouted CMU masonry walls may be increased by 33 1 / 3 percent. Alternatively, the load combinations in IBC Section may be multiplied by a factor of Allowable loads for anchors installed in the face of fully grouted CMU masonry walls subjected to combined shear and tension forces shall be determined by the following equation: P s P t V + s V t # 1.0 where: P s = Applied service tension load. P t = Allowable service tension load. V s = Applied service shear load. V t = Allowable service shear load. 4.0 INSTALLATION 4.1 General: Titen HD screw anchors shall be installed by drilling a pilot hole into the substrate using a handheld electro-pneumatic rotary hammer drill with a carbide-tipped drill bit conforming to ANSI B The pilot hole shall have the same diameter as the nominal diameter of the anchor. The hole is drilled to the specified embedment depth plus 1 / 2 inch (12.7 mm). Dust and debris in the hole shall be removed by using

3 Page 3 of 11 ESR-1056 oil-free compressed air. The Titen HD screw anchor shall be installed into the hole to the required embedment using a socket wrench or powered impact wrench Anchors in Fully Grouted CMU Masonry Walls: Anchors installed in the face of fully grouted CMU wall construction shall be limited to the face shell of the CMU unit (center web and grouted cores) and the horizontal mortared bed joints, as indicated by the shaded areas in Figure 3. Anchors installed in a T-joint, the mortared head joint, or the end webs of a CMU unit, as indicated in the non-shaded areas in Figure 3, are outside the scope of this report. For anchors installed in the top of fully grouted concrete masonry walls (CMU grouted cores and CMU webs), anchor location shall comply with the minimum edge and end distances noted in Tables 11A and 11B and shown in Figure 4. Anchors installed in the mortared head joint are outside the scope of this report 4.2 Installation with Inspection (When Required): Continuous special inspection shall be provided when required by the tables in this evaluation report. inspection under the IBC and IRC shall conform to IBC Section 1704; under the UBC, special inspection shall be in accordance with UBC Section For fasteners installed with special inspection, the following items, as applicable, shall be inspected: fastener type and dimensions; concrete type and concrete compressive strength (for anchors installed in concrete); masonry unit type and compliance with ASTM C 90; grout and mortar compressive strengths, and (when required) masonry prism compressive strength; drill bit size and compliance with ANSI B ; and fastener embedment, spacing, and edge (and end) distances. The special inspector shall inspect and verify that anchor installation complies with this evaluation report and Simpson Strong-Tie Company s published installation instructions. 5.0 CONDITIONS OF USE The Titen HD Screw Anchors described in this report comply with, or are suitable alternatives to what is specified in, the codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 Anchors are identified and installed in accordance with this report and the manufacturer s published installation instructions. 5.2 Anchors installed in normal-weight concrete to resist dead, live, wind and earthquake load applications shall be in accordance with Section Anchors installed into the top or bottom of structural sand-lightweight concrete filled metal-deck assemblies to resist dead, live, wind and earthquake load applications shall be in accordance with Section Anchors installed in the face or the top of fully grouted CMU masonry walls to resist dead, live, wind, and earthquake load applications shall be in accordance with Section Since an ICC-ES acceptance criteria for evaluating data to determine the performance of anchors subjected to fatigue or shock loading is unavailable at this time, the use of these anchors under these conditions is beyond the scope of this report. 5.6 Anchors are not permitted for use in conjunction with fire-resistive construction. Exceptions would be: Anchors resist wind or seismic loading only. For other than wind or seismic loading, special consideration is given to fire exposure conditions. 5.7 Since an ICC-ES acceptance criteria for evaluating the performance of screw anchors in cracked concrete is unavailable at this time, the use of anchors is limited to installation in uncracked concrete. Cracking occurs when f t > f r due to service loads or deformations. 5.8 Anchors are installed in substrates in holes predrilled with carbide-tipped masonry drill bits complying with ANSI B , and having the same diameter as the nominal diameter of the anchor. 5.9 Calculations demonstrating that the applied loads are less than the allowable loads described in this report, shall be submitted to the building official. The calculations shall be prepared by a registered design professional where required by the statues of the jurisdiction in which the project is to be constructed inspection, when required, shall be provided in accordance with Section Anchors shall be limited to dry, interior use The Titen HD screw anchors are manufactured by Simpson Strong-Tie Company at a facility in Brampton, Ontario, Canada, under a quality control program with inspections by CEL Consulting (AA-639). 6.0 EVIDENCE SUBMITTED 6.1 Data in accordance with the ICC-ES Acceptance Criteria for Predrilled Fasteners (Screw Anchors) in Concrete and Masonry (AC106), dated November 1, 2003, including the following optional tests: Anchors installed in normal-weight concrete: Effects of edge distance on tension and shear performance (Test Series 4, 5, 6, 7, 13, 14, 15, and 16 of AC106); effects of spacing on tension and shear performance (Test Series 9 and 18 of AC106); oblique load tests (Test Series 19 and 20 of AC106); and seismic performance tests (Section 4.6 of AC106) Anchors installed in the top and bottom of structural sand-lightweight concrete and metal-deck assemblies: Effects of edge distance on tension and shear performance (Test Series 4 and 13 of AC106), and seismic performance tests (Section 4.6 of AC106) Anchors installed in the face of fully grouted CMU masonry wall construction: Effects of edge distance on tension and shear performance (Test Series 4, 5, 13, and 14 of AC106), and seismic performance tests (Section 4.6 of AC106) Anchors installed in the top of fully grouted CMU masonry wall construction with a minimum 1 3 / 4 -inch (44 mm) edge distance: Effects on tension and shear performance (Test Series 4 and 13 of AC106), and seismic performance tests (Section 4.6 of AC106). 6.2 A quality control manual. 7.0 IDENTIFICATION Titen HD screw anchor packaging is marked with the Simpson Strong-Tie Company name; product name (Titen HD); anchor diameter and length; the name or logo of the inspection agency (CEL Consulting); and the evaluation report number (ESR-1056). In addition, the symbol and anchor length (in inches) is stamped on the head of each screw anchor.

4 Page 4 of 11 ESR-1056 FIGURE 1 TYPICAL TITEN HD SCREW TABLE 1 SPACING AND EDGE DISTANCE REQUIREMENTS FOR TITEN HD SCREW S (Anchors in Normal-weight Concrete) 1,2 DEPTH, h v EDGE DISTANCE SPACING Tension Shear Tension or Shear Tension or Shear Critical Edge, C cr Critical Edge, C cr Edge, C min Critical Spacing, S cr Spacing, S min 3 / / / / / / / 4 1 / / / / / 4 5 / / / / / / / 4 3 / / / For SI: 1 inch = 25.4 mm. 5 3 / 4 1 The spacing and edge distance requirements in this table are applicable only to Tables 3 and 4. 2 The critical edge and spacing distances are for full anchor capacity, and the minimum edge and spacing distances are for reduced anchor capacity. See Table 2 for applicable load reduction factors for anchors installed at distances less than the critical edge distance or less than critical spacing. DEPTH, h v TABLE 2 LOAD REDUCTION FACTORS FOR TITEN HD SCREW S (Anchors in Normal-weight Concrete) 1,2,3,4 Tension or Shear Critical Edge, C cr EDGE DISTANCE Tension Shear Tension or Shear Edge, C min Edge, C min Critical Spacing, S cr SPACING Tension Spacing, S min Shear Spacing, S min 3 / / / / / / / / / / / / / / / For SI: 1 inch = 25.4 mm. 1 The load reduction factors in this table are applicable only to the allowable loads shown in Tables 3 and 4. 2 Reduction factors are cumulative. Multiple reduction factors for more than one spacing or edge distance are calculated separately and multiplied. 3 Load reduction factors for anchors loaded in tension or shear with spacing between critical and minimum are obtained by linear interpolation. 4 Load reduction factors for anchors loaded in tension or shear with edge distances between critical and minimum are obtained by linear interpolation.

5 Page 5 of 11 ESR-1056 DRILL BIT 5 TABLE 3 ALLOWABLE TENSION LOADS FOR TITEN HD SCREW S INSTALLED IN NORMAL-WEIGHT CONCRETE 1,2,3,4 (pounds) DEPTH CRITICAL EDGE DISTANCE CRITICAL SPACING INSTALLED WITH SPECIAL INSPECTION 6 Concrete Strength, fn c (psi) INSTALLED WITHOUT SPECIAL INSPECTION 7 Concrete Strength, fn c (psi) 2,000 3,000 4,000 2,000 3,000 4,000 3 / 8 3 / / 4 1,075 1,315 1, / 4 1,770 2,115 2, ,060 1, / 4 1,155 1,400 1, / 2 1 / / ,855 2,270 2, ,135 1, / 4 2,570 3,240 3,910 1,285 1,620 1, / 4 1,155 1,400 1, / 8 5 / / ,185 2,630 3,070 1,095 1,315 1, / 4 3,240 3,955 4,670 1,620 1,980 2, / 4 1,170 1,410 1, / 4 3 / / ,585 3,470 4,355 1,295 1,735 2, / 4 3,440 4,055 4,670 1,720 2,030 2,335 For SI: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 psi = 6.89 kpa. 1 Allowable loads are permitted to be increased by 33 1 / 3 percent when using the alternate basic load combinations in accordance with Section of the IBC or Section of the UBC, for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section may be multiplied by a factor of concrete thickness is 1.5 times the anchor embedment. 3 edge distance and spacing shall comply with Table 1. 4 The tabulated loads are for anchors installed in normal-weight concrete having a minimum compressive strength as shown in the table at the time of anchor installation. 5 Anchor installation shall comply with Section 4.0 of this report. 6 These tension loads are applicable only when the anchors are installed with special inspection as set forth in Section 4.2 of this report. 7 These tension loads are applicable when the anchors are installed without special inspection. TABLE 4 ALLOWABLE SHEAR LOADS FOR TITEN HD SCREW S INSTALLED IN NORMAL-WEIGHT CONCRETE 1,2,3,4 (pounds) DRILL BIT CRITICAL CRITICAL ALLOWABLE SHEAR LOAD 6 (lbs) 5 EDGE SPACING DEPTH DISTANCE Concrete Strength, fn c (psi) 2,000 3,000 4,000 3 / 8 3 / / 4 1,585 1,665 1, / / 4 1,595 1,670 1, / 4 1,605 2,050 2,495 1 / 2 1 / / ,330 2,795 3, / 4 2,830 3,045 3, / 4 1,940 2,220 2,495 5 / 8 5 / / / ,175 3,415 4, / 4 3,125 3,890 4, / 4 1,960 2,415 2,865 3 / 8 3 / / ,805 4,490 6, / 4 4,950 5,560 6,170 For SI: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 psi = 6.89 kpa. 1 Allowable loads are permitted to be increased by 33 1 / 3 percent when using the alternate basic load combinations in accordance with Section of the IBC or Section of the UBC, for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section may be multiplied by a factor of concrete thickness is 1.5 times the anchor embedment. 3 edge distance and spacing shall comply with Table 1. 4 The tabulated loads are for anchors installed in normal-weight concrete having a minimum compressive strength as shown in the table at the time of anchor installation. 5 Anchor installation shall comply with Section 4.0 of this report. 6 Allowable shear loads are for installations with or without special inspection.

6 Page 6 of 11 ESR-1056 TABLE 5 ALLOWABLE SHEAR LOADS (PARALLEL TO THE CONCRETE EDGE) FOR TITEN HD SCREW S INSTALLED IN fn c = 2,500 psi NORMAL-WEIGHT CONCRETE 1,2,3,4 (pounds) DRILL BIT 5 DEPTH EDGE DISTANCE END DISTANCE CRITICAL SPACING ALLOWABLE SHEAR LOAD PARALLEL TO THE CONCRETE EDGE 6 (pounds) 2 3 / 4 1,165 1 / 2 1 / / / , / 2 1,950 5 / 8 5 / / / , / 2 1,765 For SI: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 psi = 6.89 kpa. 1 Allowable loads are permitted to be increased by 33 1 / 3 percent when using the alternate basic load combinations in accordance with Section of the IBC or Section of the UBC, for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section may be multiplied by a factor of concrete thickness is 1.5 times the anchor embedment. 3 screw anchor edge and end distances, and critical spacing limitations, are applicable to the tabulated loads. 4 The tabulated loads are for anchors installed in normal-weight concrete having a minimum 2,500 psi compressive strength, fn c, at the time of anchor installation. 5 The drill bit diameter shall be equal to the nominal diameter of the anchor. Anchor installation shall comply with Section 4.0 of this report. 6 Allowable shear loads are for installations with or without special inspection. TABLE 6 ALLOWABLE TENSION LOADS FOR TITEN HD SCREW S INSTALLED IN THE TOP SURFACE OF NORMAL-WEIGHT CONCRETE FOUNDATION STEM WALLS 1,2,3,4,5 (pounds) DRILL BIT DEPTH, h v CONCRETE FOUNDATION STEM WALL THICKNESS LOCATION 6 Critical Edge Critical End ALLOWABLE TENSION LOADS (pounds) Concrete Compressive Strength, fn c fn c = 2,500 psi with Inspection 7 without Inspection 8 fn c = 4,500 psi with Inspection 7 without Inspection 8 1 / 2 1 / / 4 8 3,855 1,930 5,075 2,540 1 / 1 2 / / / 8 3,570 1,785 4,760 2,380 For SI: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 psi = 6.89 kpa. 1 Allowable loads may be increased by 33 1 / 3 percent when using the alternate basic load combinations in accordance with Section of the IBC or Section of the UBC, for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section may be multiplied by a factor of concrete thickness is 12 inches. 3 screw anchor spacing is 15 inches. 4 The tabulated loads are for anchors installed in normal-weight concrete having a minimum compressive strength as shown in the table at the time of anchor installation. 5 Anchor installation shall comply with Section 4.0 of this report. 6 Critical screw anchor edge and end distances are applicable to the tabulated loads. 7 These tension loads are applicable only when the anchors are installed with special inspection as set forth in Section 4.2 of this report. 8 These tension loads are applicable when the anchors are installed without special inspection.

7 Page 7 of 11 ESR-1056 TABLE 7 ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW S INSTALLED ON TOP OR BOTTOM OF STRUCTURAL SAND-LIGHTWEIGHT CONCRETE (f c = 3,000 psi) AND METAL-DECK ASSEMBLIES 1,2 DRILL BIT LOCATION 6 ALLOWABLE LOADS 4 (lbs) Edge Critical Tension Shear 7 DEPTH Spacing Critical with Inspection 5 without Inspection 6 S INSTALLED IN THE TOP OF STRUCTURAL SAND-LIGHTWEIGHT CONCRETE AND METAL-DECK ASSEMBLIES 3 / 8 3 / / ,060 1 / 2 1 / / ,595 5 / 5 8 / / ,595 S INSTALLED IN BOTTOM FLUTES OF STRUCTURAL SAND-LIGHTWEIGHT CONCRETE AND METAL-DECK ASSEMBLIES 8 3 / 3 8 / / (9) 2 N/A 6 1, ,025 1 / 2 1 / / 2 (9) N/A 8 1, ,710 5 / 5 8 / / (9) 2 N/A 10 2,235 1,115 2,675 For SI: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 psi = 6.89 kpa. 1 The assembly shall consist of a metal deck and structural sand-lightweight concrete fill: The deck shall be steel conforming to ASTM A 653/A 653M, with a minimum yield strength of 38,000 psi and minimum tensile strength of 45,000 psi, and shall have a minimum thickness of No. 20 gage [0.035 inch base-metal thickness (0.89 mm)]. Figure 2 illustrates required metal-deck bottom-flute dimensions: a minimum of 4 1 / 2 inches (114 mm) wide, a maximum of 3 inches (76 mm) deep, and a minimum spacing of 12 inches (305 mm). Metal decks having greater bottom flute widths and relative spacings shall be permitted. The structural sand-lightweight concrete shall have a minimum concrete compressive strength, fn c, at the time of anchor installation of 3,000 psi, and shall have a minimum thickness of 3 1 / 4 inches measured from the top flute. Refer to Figure 2. 2 Anchor installation shall comply with Section 4.0 of this report. 3 Anchor edge distance and spacing shall comply with tabulated loads. N/A = Not applicable. 4 Use of anchors installed in the top or bottom of structural sand-lightweight concrete and metal-deck assemblies shall be permitted to resist wind or earthquake tension and shear loads. Refer to Section for design requirements for anchors installed in the top of the assembly, and for anchors installed in the bottom of the assembly. 5 These tension loads are applicable only when the anchors are installed with special inspection as set forth in Section 4.2 of this report. 6 These reduced tension loads are applicable for anchors installed without special inspection. 7 Allowable shear loads are for installations with or without special inspection. 8 Allowable tension and shear loads are for anchors installed in the bottom flute of the steel deck, at a minimum edge distance of 1 1 / 2 inches from the inclined edge of the bottom flute. Allowable shear loads act parallel or perpendicular to the deck flutes. 9 distance from an anchor to the end of a flute for bottom of deck installations shall comply with the following: 6 inches for 3 / 8 -inch-diameter anchor. 8 inches for 1 / 2 -inch-diameter anchor. 10 inches for 5 / 8 -inch-diameter anchor. FIGURE 2 TITEN HD SCREW INSTALLED IN THE TOP AND BOTTOM OF A STRUCTURAL SAND-LIGHTWEIGHT CONCRETE AND METAL-DECK ASSEMBLY

8 Page 8 of 11 ESR-1056 TABLE 8A IBC AND IRC ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW S INSTALLED IN THE FACE OF FULLY GROUTED CMU MASONRY WALL CONSTRUCTION 1 DIA. 2 DRILL BIT DIA. MIN. EMBED. 3 LOCATION 4 S INSTALLED AT DISTANCES $ CRITICAL EDGE DISTANCE, c crit, AND SPACING, 5,6,7 s crit (lbf) Edge Spacing Tension Shear Critical, c crit, c min Critical, s crit, s min 3 / 8 3 / / / 2 1 / / ,385 5 / 8 5 / / ,060 2,085 3 / 3 4 / / ,600 3,000 For SI: 1 inch = 25.4 mm, 1 psi = 6.89 kpa, 1 lbf = 4.48 N 1 Anchors shall be installed a minimum of 1 1 / 4 inches from vertical head joints and T-joints. Refer to Figure 3 for permitted and prohibited anchor installation locations. 2 The drill bit diameter shall be equal to the nominal diameter of the anchor. Anchor installation shall comply with Section 4.0 of this report. 3 Embedment depth is measured from the outside face of the masonry. 4 Critical and minimum edge distances, c cr and c min, respectively, shall comply with this table. Refer to Figure 3. Critical and minimum spacing, s crit and s min, respectively, shall comply with this table. Critical and minimum edge and spacing distances are valid for anchors resisting tension or shear loads. Refer to Table 9 for allowable tension and shear load reduction factors for anchors installed between critical and minimum edge distances, and to Table 10 for anchors installed between critical and minimum spacing. 5 Tabulated loads are for anchors installed in fully grouted masonry wall construction, consisting of Grade N, Type II, lightweight, medium-weight, or normal-weight, closed-end, concrete masonry units (CMUs) conforming to ASTM C 90. Masonry shall be fully grouted with coarse grout having a minimum compressive strength of 2,000 psi, and complying with IBC Section or IRC Section R as applicable. Mortar shall comply with IBC Section or IRC Section R607, as applicable, and shall have a minimum specified compressive strength of 1,500 psi. The specified compressive strength of masonry, fn m, at 28 days shall be a minimum of 1,500 psi. 6 Tabulated allowable loads are based on a safety factor of 5.0 and are based on special inspection being provided during anchor installation. inspection requirements shall comply with Section 4.2 of this report. 7 Allowable loads may be increased by 33 1 / 3 percent when using the alternate basic load combinations in accordance with Section of the IBC for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section may be multiplied by a factor of FIGURE 3 TITEN HD SCREW INSTALLED IN THE FACE OF GROUT-FILLED CMU (CONCRETE MASONRY UNIT) WALL CONSTRUCTION (Refer to Tables 8, 9, and 10)

9 Page 9 of 11 ESR-1056 DIA. 2 TABLE 8B ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW S INSTALLED IN THE FACE OF FULLY GROUTED CMU MASONRY WALL CONSTRUCTION 1 DRILL BIT DIA. MIN. EMBED. 3 LOCATION 4 ALLOWABLE LOADS BASED ON S INSTALLED AT DISTANCES > CRITICAL EDGE DISTANCE, c crit, AND 5,6,7 SPACING, s crit (lbf) Edge Spacing Tension Shear 9 Critical, c crit, c min Critical, s crit, s min with Inspection 7 without Inspection 8 3 / 8 3 / / ,085 1 / 2 1 / / ,730 5 / 8 5 / / , ,605 3 / 3 4 / / ,000 1,000 3,750 For SI: 1 inch = 25.4 mm, 1 psi = 6.89 kpa, 1 lbf = 4.48 N. 1 Anchors shall be installed a minimum of 1 1 / 4 inches from vertical head joints and T-joints. Refer to Figure 3 for permitted and prohibited anchor installation locations. 2 The drill bit diameter shall be equal to the nominal diameter of the anchor. Anchor installation shall comply with Section 4.0 of this report. 3 Embedment depth is measured from the outside face of the masonry. 4 Critical and minimum edge distances, c cr and c min, respectively, shall comply with this table. Refer to Figure 3. Critical and minimum spacing, s crit and s min, respectively, shall comply with this table. Critical and minimum edge and spacing distances are valid for anchors resisting tension or shear loads. Refer to Table 9 for allowable tension and shear load reduction factors for anchors installed between critical and minimum edge distances, and to Table 10 for anchors installed between critical and minimum spacing. 5 Tabulated loads are for anchors installed in fully grouted masonry wall construction, consisting of Grade N, Type II, lightweight, medium-weight, or normal-weight, closed-end, concrete masonry units (CMUs) conforming to UBC Standard Masonry shall be fully grouted with coarse grout having a minimum compressive strength of 2,000 psi, and complying with UBC Section Mortar shall comply with UBC Section and UBC Standard 21-15, and shall have a minimum specified compressive strength of 1,500 psi. The specified compressive strength of masonry, fn m, at 28 days shall be a minimum of 1,500 psi. 6 Allowable loads may be increased by 33 1 / 3 percent when using the alternate basic load combinations in accordance with Section of the UBC for wind or earthquake loading conditions. 7 These allowable tension loads are based on a factor of safety of 4.0 and special inspection being provided during anchor installation. inspection requirements shall comply with Section 4.2 of this report. 8 These reduced allowable tension loads are applicable for anchors installed without special inspection and are based on a factor of safety of These allowable shear loads are based on a factor of safety of 4.0 and anchor installation with or without special inspection.

10 Page 10 of 11 ESR-1056 TABLE 9 LOAD REDUCTION FACTORS FOR TITEN HD SCREW S INSTALLED BETWEEN CRITICAL AND EDGE DISTANCES (Anchors in the Face of Grout-filled CMU Masonry Walls) 1,2,3 DEPTH, h v LOAD REDUCTION FACTORS FOR S INSTALLED AT: Critical Edge Edge, C min, C crit Tension or Shear Load Tension Load Shear Load Acting: Towards an Edge Away from an Edge Parallel to an Edge 3 / / / / / / / / For SI: 1 inch = 25.4 mm. 1 The load reduction factors in this table are applicable to the allowable loads shown in Tables 8A and 8B. 2 Reduction factors are cumulative. Multiple reduction factors for more than one spacing or edge distance are calculated separately and multiplied. 3 Load reduction factors for anchors loaded in tension or shear with edge distances between critical and minimum are obtained by linear interpolation. TABLE 10 LOAD REDUCTION FACTORS FOR TITEN HD SCREW S INSTALLED BETWEEN CRITICAL AND SPACING (Anchors in the Face of Grout-filled CMU Masonry Walls) 1,2,3 DEPTH, h v LOAD REDUCTION FACTORS FOR S INSTALLED AT: Critical Spacing, S crit Spacing, S min Tension or Shear Load Tension Load Shear Load 3 / / / / / / / / For SI: 1 inch = 25.4 mm. 1 The load reduction factors in this table are applicable to the allowable loads shown in Tables 8A and 8B. 2 Reduction factors are cumulative. Multiple reduction factors for more than one spacing or edge distance are calculated separately and multiplied. 3 Load reduction factors for anchors loaded in tension or shear with spacing between critical and minimum are obtained by linear interpolation. DIA. TABLE 11A IBC AND IRC ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW S INSTALLED IN TOP OF GROUT-FILLED CMU MASONRY WALLS 1 DRILL BIT DIA. MIN. EMBED. LOCATION 2 Edge End Spacing IBC AND IRC ALLOWABLE LOADS 3,4,5 (pounds) Tension Parallel to Edge of Masonry Wall Shear Perpendicular to Edge of Masonry Wall 1 / 2 1 / / / / 5 8 / / / For SI: 1 inch = 25.4 mm, 1 pound = 4.45 N, 1 psi = 6.89 kpa. 1 The allowable tension and shear loads in Table 11A are applicable when anchors are installed in structures regulated by the IRC or IBC. 2 edge and end distances are measured from the anchor centerline to the edge and end of the CMU masonry wall, respectively. Refer to Figure 4. spacing is measured from center-to-center of two anchors. Anchors installed in the mortared head joint are outside the scope of this report. 3 The allowable loads in Table 11A are for anchors resisting dead, live, wind, and earthquake load applications. For short-term loading due to wind and earthquake forces, the allowable loads may be increased as indicated in Section of this report. 4 Loads for Grade N, Type II, lightweight, medium-weight, or normal-weight concrete masonry units (CMUs) conforming to ASTM C 90. Allowable minimum nominal dimensions of the CMU shall be 8 inches wide by 8 inches high by 16 inches long (8" 8" 16"). Masonry wall construction shall be fully grouted with coarse grout having a minimum compressive strength of 2,000 psi, and complying with IBC Section or IRC Section R , as applicable. Mortar shall comply with IBC Section or IRC Section R607.1, as applicable, and have a minimum compressive strength of 1,500 psi. The specified compressive strength of masonry, fn m, at 28 days shall be a minimum of 1,500 psi. 5 Allowable tension and shear loads are based on a safety factor of 5.0, and are based on anchor installations with special inspection. inspection shall be provided during anchor installation in accordance with Section of the IBC or Section R104.4 of the IRC, as applicable. Refer to Section 4.2 of this report for special inspection requirements.

11 Page 11 of 11 ESR-1056 DIA. DRILL BIT DIA. TABLE 11B UBC ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW S INSTALLED IN TOP OF GROUT-FILLED CMU MASONRY WALLS 1 MIN. EMBED. LOCATION 2 Edge End Spacing UBC ALLOWABLE LOADS 3,4 (pounds) Tension Shear 5 Perpendicular to Edge of Masonry with Inspection 6 without Inspection 7 Parallel to Edge of Masonry 1 / 2 1 / / / / 5 8 / / / For SI: 1 inch = 25.4 mm, 1 pound = 4.45 N, 1 psi = 6.89 kpa. 1 The allowable tension and shear loads in Table 11B are applicable for anchors installed in structures regulated by the UBC. 2 edge and end distances are measured from the anchor centerline to the edge and end of the CMU masonry wall, respectively. Refer to Figure 4. spacing is measured from center-to-center of two anchors. Anchors installed in the mortared head joint are outside the scope of this report. 3 The allowable loads in Table 11B are for anchors resisting dead, live, wind, and earthquake load applications. For short-term loading due to wind and earthquake forces, the allowable loads may be increased as indicated in Section of this report. 4 Loads for Grade N, Type II, lightweight, medium-weight, or normal-weight concrete masonry units (CMUs) conforming to UBC Standard Allowable minimum nominal dimensions of the CMU shall be 8 inches wide by 8 inches high by 16 inches long (8" 8" 16"). Masonry wall construction shall be fully grouted with coarse grout having a minimum compressive strength of 2,000 psi, and complying with UBC Section Mortar shall comply with UBC Section and UBC Standard 21-15, and have a minimum compressive strength of 1,500 psi. The specified compressive strength of masonry, fn m, at 28 days shall be a minimum of 1,500 psi. 5 Allowable shear loads are based on a safety factor of 4.0. inspection for anchor installation is not required. 6 Allowable tension loads in the column entitled with Inspection are based on a safety factor of 4.0. inspection shall be provided during anchor installation, and shall comply with the requirements described in Section 4.2 of this report. 7 Allowable tension loads in the column entitled without Inspection are based on a safety factor of 8.0. inspection for anchor installation is not required for anchors assigned these reduced allowable tension loads. FIGURE 4 EDGE AND END DISTANCES FOR THE TITEN HD INSTALLED IN THE TOP OF CMU MASONRY WALL CONSTRUCTION