ALL DIMENSIONS FROM FINISHED FACE OF PARTITION TO FINISHED FACE OF PARTITION UNLESS OTHERWISE NOTED.

Size: px
Start display at page:

Download "ALL DIMENSIONS FROM FINISHED FACE OF PARTITION TO FINISHED FACE OF PARTITION UNLESS OTHERWISE NOTED."

Transcription

1

2 ALL DIMENSIONS FROM FINISHED FACE OF PARTITION TO FINISHED FACE OF PARTITION UNLESS OTHERWISE NOTED. PARTITION CONSTRUCTION TO BE 3 5/8 METAL STUDS 24 ON CENTER WITH 5/8 TYPE X GYPSUM BOARDS BOTH SIDES. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE REVIEW OF THE SET OF CONSTRUCTION DRAWINGS. SHOULD THERE BE CONFLICTING INFORMATION CONTAINED HEREIN, THE CONTRACTOR IS TO NOTIFY DESIGNER PRIOR TO FABRICATION OR ASSEMBLY. EXTERIOR WALLS ARE TO BE FURRED OUT SEE ELEVATIONS FOR WALL SECTION REFERENCE ALL INTERIOR DIMENSIONS ARE TO (FINISHED FACE OF PARTITION TO FINISHED FACE OF PARTITION) UNLESS OTHERWISE INDICATED CONTRACTOR IS TO PROVIDE AND INSTALL ALL RESTROOM FIXTURES PARTITION TYPES VARY IN THICKNESS. SEE SHEET I-301 FOR PARTITION TYPES CONTRACTOR IS TO PROVIDE AND INSTALL WATER HEATER, REFRIGERATOR, MICROWAVE, DISHWASHER, DISPOSAL, AND ICE-MAKER. GENERAL: INSTALL GYPSUM BOARD TO THE CONCRETE DECK FOR BETTER INSTALLATION. CUT AND FIT GYPSUM BOARD BY SCORING AND BREAKING OR BY SAWING, WORKING FROM FACE SIDE. SMOOTH CUT EDGES AND ENDS OF GYPSUM BOARD ACHIEVE NEAT JOINING. WHERE GYPSUM BOARD MEETS PROJECTING SURFACES, SCRIBE AND CUT, REMOVE CRACKED, BROKEN, OR OTHERWISE DAMAGED BOARDS AND REPLACE WITH NEW MATERIAL. WALLS AND COLUMNS: APPLY GYPSUM BOARD WITH LONG DIMENSION PARALLEL TO METAL STUD FRAMING MEMBERS OR FURRING CHANNELS. EXCEPT FOR COLUMN EDGES LAY OUT GYPSUM BOARD ENDS AND EDGES TO OCCUR OVER STUDS OR CHANNELS HORIZONTALLY AND VERTICALLY. USE GYPSUM BOARD OF MAXIMUM PRACTICAL LENGTH TO MINIMIZE JOINTS. JOINTS NEED TO BE NEATLY FITTED AND STAGGERED ON OPPOSITE SIDES OF STUDS. CUT GYPSUM BOARD TO FIT TIGHT TO PENETRATIONS AND ABUTTING ITEMS. CEILINGS: APPLY GYPSUM BOARD TO THE CEILING WITH LONG DIMENSION AT RIGHT ANGLES TO THE FURRING MEMBERS. GYPSUM BOARD MAY BE APPLIED WITH LONG DIMENSION PARALLEL TO FURRING MEMBERS THAT ARE SPACED 16 ON CENTER WHEN ATTACHMENT MEMBERS ARE PROVIDED AT END JOINTS. WHERE FIRE RATED CONSTRUCTION IS INDICATED, IT SHALL BE IN ACCORD WITH APPROVED MANUFACTURER S FIRE RATED INSTALLATION DIRECTIONS. CONTRACTOR TO VERIFY ALL MEASUREMENTS AND OTHER CONDITIONS OF THE JOB AND SHALL PROVIDE WRITTEN QUANTITY TAKE OFF TO THE OWNER AT THE TIME OF HE SUBMITTAL. COOPERATE WITH OTHER TRADES IN SCHEDULING INSTALLATION AND CUTTING CARPET FOR PENETRATIONS. SUBMITTALS: 1. MANUFACTURER S AFFIDAVIT: CARPETING MATERIALS MANUFACTURERS AFFIDAVIT STATING THAT THE CARPETING INSTALLER IS APPROVED BY MANUFACTURER O INSTALL THE CARPETING MATERIALS. 2. MAINTENANCE DATA: UPON COMPLETION AND PRIOR TO ACCEPTION OF THE WORK FURNISH TWO COPIES OF A LIST OF RECOMMENDED MAINTENANCE MATERIALS AND RECOMMENDED MAINTENANCE METHODS AND PROCEDURES. 3. INSTALLATION INSTRUCTIONS: SUBMIT INSTALLATION DRAWINGS SHOWING DETAILS OF CARPET INSTALLATION, SEAM DIAGRAMS, PATTERN, COLOR, CARPET TO BE USED, STAIN CLEANING SOLVENT AND OTHER PERTINENT DETAILS AS MAY BE REQUIRED. 4. SUBMIT THREE COPIES OF MANUFACTURER S MAINTENANCE MANUAL FOR SPECIFIED CARPET. 5. SUBMIT MANUFACTURER S GUARANTEE FOR CARPET AND PAD. THE CARPET INSTALLATION SHALL BE COVERED BY A WRITTEN GUARANTEE FOR A PERIOD OF TWO YEARS FROM THE DATE OF FINAL COMPLETION OF THE CARPET INSTALLATION. 1. DELAMINATION: WILL NOT OCCUR TO THE BACKING WITHIN THE GUARANTEED PERIOD DUE TO THE MANUFACTURER S PROCESS, FAULTY OR DEFECTIVE ADHESIVES, OR ATTACHMENT METHODS. 2. SEAMS AND PERIMETER ATTACHED EDGES WILL REMAIN STABLE AND IN CORRECT ALIGNMENT WITHOUT ANY NOTICEABLE WRINKLES, UPTURNED EDGES, OR PUCKERING DUE TO THE USE INTENDED FOR THE CARPETING. THE INSTALLER SHALL BE EXPERIENCED IN THE INSTALLATION OF CARPET FLOOR COVERING AND CUSHIONS USING THE METHODS OF INSTALLATION COVERED BY THIS SPECIFICATION. INSTALLER SHALL EMPLOY ONLY EXPERIENCED PERSONNEL, AND SHALL BE FAMILIAR WITH THE MANUFACTURER S RECOMMENDATIONS FOR INSTALLATION OF MATERIALS, AND SHALL BE ACCEPTABLE TO THE OWNER CARPET SHALL BE PROTECTED FROM OTHER WORK AT ALL TIMES. MAINTAIN TEMPERATURE IN SPACE TO RECEIVE CARPET, OF 70 DEGREES F (21 DEGREES C) AND 50 PERCENT RELATIVE HUMIDITY FOR NOT LESS THAN 24 HRS BEFORE AND 48 HRS AFTER INSTALLATION. DO NOT PROCEED WITH THE INSTALLATION OF ANY MATERIALS UNTIL AFTER ALL DEFECTS HAVE BEEN CORRECTED.

3 EXTERIOR WALLS ARE TO BE FURRED OUT SEE ELEVATIONS FOR WALL SECTION REFERENCE ALL INTERIOR DIMENSIONS ARE TO (FINISHED FACE OF PARTITION TO FINISHED FACE OF PARTITION) UNLESS OTHERWISE INDICATED CONTRACTOR IS TO PROVIDE AND INSTALL ALL RESTROOM FIXTURES PARTITION TYPES VARY IN THICKNESS. SEE SHEET I-301 FOR PARTITION TYPES CONTRACTOR IS TO PROVIDE AND INSTALL WATER HEATER, REFRIGERATOR, MICROWAVE, DISHWASHER, DISPOSAL, AND ICE-MAKER.

4 FLOOR FINISHES SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER S SPECIFICATIONS FOR THE PARTICULAR APPLICATION SHOWN ON SCHEDULE. CONTRACTOR IS TO INSPECT FLOOR CONDITIONS PRIOR TO INSTALLATION AND FLASH PATCH AS REQUIRED TO INSURE LEVEL FINISH FLOOR SURFACE (1/4 SLOPE IN 10 ). ALL PAINTED METAL SURFACES SHALL BE SEMI-GLOSS ALKYD ENAMEL UNLESS OTHERWISE NOTED. ALL PAINT SHALL BE APPLIED IN ACCORDANCE WITH MANUFACTURER S SPECIFICATIONS FOR THAT PARTICULAR R SURFACE, 2 COAT MINIMUM. GENERAL CONTRACTOR AND HIS SUBCONTRACTORS ARE TO BE AWARE THAT ANY FIREPROOFING MATERIAL THAT MAY BECOME DISLODGED DURING THE COURSE OF THEIR WORK IS TO BE RESTORED AND ALL EXPOSED STRUCTURE NOT PROPERLY FIRE PROTECTED IS TO BE PROTECTED WITH THE SAME MATERIAL IN USE. INSTALL VINYL (COLOR TO MATCH VINYL BASE) TRANSITION STRIP AT ALL POINTS WHERE CARPET AND VCT FLOORING MEET. INSTALL VINYL COVER BASE IN ROOMS TO RECEIVE VCT AND INSTALL STRAIGHT BASE IN ROOMS TO RECEIVE CARPET. VINYL BASE TO BE 1/8 GAUGE VINYL OR RUBBER. REFER TO FINISH SCHEDULE AND LEGEND FOR SPECIFICATIONS. BEGIN ALL TILE LAYOUT IN THE CENTER OF THE ROOM. USE OUTSIDE PIECES AS FLOAT DIMENSIONS.

5 ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES, THE INSTALLATION OF ELECTRICAL FIXTURES, OUTLETS, ETC. WHERE TELEPHONE AND ELECTRICAL OUTLETS APPEAR BACK TO BACK JUNCTION BOXES SHALL BE STAGGERED TO REDUCE NOISE TRANSMISSION THROUGH PARTITION. SEPARATE CIRCUITS SHALL BE FURNISHED WITH DISCONNECT SWITCHES AS REQUIRED BY CODES. WORK SHALL BE DONE IN ACCORDANCE WITH ALL STATE AND LOCAL ELECTRICAL CODES THAT HAVE AUTHORITY OVER THIS WORK. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE CUTTING AND PATCHING REQUIRED FOR THE INSTALLATION OF THIS WORK. FINAL EXIT SIGN AND EMERGENCY LIGHT LOCATIONS ARE SUBJECT TO THE APPROVAL OF THE LOCAL AUTHORITY. FIRE ALARM PULL, SIGNAL STATIONS, AND LIFE SAFETY SYSTEMS SHALL CONFORM TO ALL APPLICABLE CODES IN ACCORDANCE WITH TENANT LAYOUT. TELEPHONES AND CRT OUTLETS SHALL BE SINGLE OUTLET BOX WITH PULL STRING AND RING FOR WIRING WITH TEFLON COATED WIRE APPROVED FOR RETURN-AIR PLENUM USE. WIRING SHALL BE BY OTHERS UNLESS NOTED. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE TELEPHONE AND DATA LINE COMPANIES AND THE TENANT FOR ALL NECESSARY TELEPHONE AND DATA LINE INSTALLATION WORK. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION AND SCHEDULING OF THESE INSTALLATIONS WITH HIS WORK. ELECTRICAL DRAWING AS PROVIDED ARE FOR THE PLACEMENT AND/OR GENERAL ARRANGEMENT OF FIXTURES, OUTLETS, ETC. ALL REQUIRED ENGINEERING CALCULATIONS SHALL BE BY OTHERS UNLESS NOTED. ALL ELECTRICAL AND TELEPHONE OUTLETS ARE 15 AFF TO BOTTOM OF COVER AND CENTERED ON WALL UNLESS OTHERWISE NOTED. MOUNTING HEIGHT FOR WALL SWITCHES IS TO BE 42 TO CENTER OF COVER AND THERMOSTATS TO BE AT 48 AFF TO CENTER OF COVER. OUTLETS, COVER PLATES, AND SWITCHES ARE TO MATCH EXISTING, UNLESS OTHERWISE SPECIFIED. SWITCHES SHALL MATCH EXISTING. CONTRACTOR IS TO LABEL ALL CIRCUITS AT THE PANEL. RE-USE EXISTING BUILDING STANDARD FLUORESCENT LIGHT FIXTURES AS APPROPRIATE. NEW FIXTURES FOR THOSE IMPLEMENTED INTO LINEAR CEILING ELEMENTS. JUNCTION BOXES FOUND WITHIN THE SUITE S CEILING THAT SERVICE OTHER SUITE S MAY NOT BE USED.

6 ALL MILLWORK AND CASEWORK SHALL COMPLY WITH AWL CUSTOM STANDARD, LATEST EDITION AND AS PER DESIGNER S DETAILS. INSTALL FIRE-RETARDANT TREATED WHERE REQUIRED TO COMPLY WITH BUILDING CODE. ROUGH CARPENTRY AND MISCELLANEOUS BLOCKING SHALL BE FIRE- RETARDANT TREATED MATERIAL IN ACCORDANCE WITH LOCAL MUNICIPAL CODES. PLACEMENT TO BE COORDINATED WITH MILLWORK REQUIREMENTS. COORDINATE INSTALLATION OF IN-WALL STEEL ANCHORAGES AND MISCELLANEOUS BLOCKING WITH OTHER CONTRACTORS FOR PRECISE LOCATION. THE MILLWORK CONTRACTOR SHALL OBTAIN AND VERIFY ALL FIELD MEASUREMENTS AND CONDITIONS AFFECTING HIS WORK AND SHALL BE RESPONSIBLE FOR ALL DETAILS AND DIMENSIONS INSURING PRECISION FITTING AND PROPER ASSEMBLY OF HIS PRODUCTS. WORK SHALL BE ACCURATELY SET PLUMB, LEVEL, AND SQUARE, SCRIBED TIGHTLY AND ACCURATELY TO ADJACENT SURFACES. WORK SHALL BE SECURELY ANCHORED IN THE POSITION INDICATED ON DRAWINGS AND APPROVED SHOP DRAWINGS. REPAIR, REPLACE.AND OTHERWISE CORRECT ALL DAMAGE INCURRED TO PRE- FINISHED WORK DURING HANDLING AND INSTALLATION. ADJUST DRAWERS, DOORS AND ALL HARDWARE FOR PROPER OPERATION AND CLEAN ALL CABINET SURFACES INSIDE AND OUTSIDE. SHOP DRAWINGS OF MILLWORK SHALL BE SUBMITTED TO (YOUR DESIGN FIRM) AND REVIEWED PRIOR TO FABRICATION.

7

8

9 DOOR AND FRAME SCHEDULE DOOR FRAME HARDWARE FIRE RATING TYPE SIZE LOUVER FINISH MARK MATL FINISH MATL SET KEYSIDE WD HGT THK WD HGT SILL LABEL NO RM NO 101 A ¾ MTL PAINTING MTL PAINTING B ¾ MTL PAINTING MTL PAINTING C 1-11 ½ PAINTING PAINTING D /8 PAINTING PAINTING D /8 PAINTING PAINTING E MTL AL/GLASS PAINTING D /8 PAINTING PAINTING C 2-5 ½ PAINTING PAINTING A/C 110A C PAINTING PAINTING B C PAINTING PAINTING C C PAINTING PAINTING D C PAINTING PAINTING F /8 PAINTING PAINTING D /8 PAINTING PAINTING 112 NOTES WINDOW SCHEDULE MARK TYPE SIZE MATERIAL SILL MATERIAL GENERAL NOTES WIDTH HEIGHT 1 A 4-41/2 6-31/2 PAINTING MTL MARBLE 2 A 4-41/2 6-31/2 PAINTING MTL MARBLE 3 A 4-41/2 6-31/2 PAINTING MTL MARBLE ROOM FINISH SCHEDULE ROOM ROOM NAME BASE FLOOR WALLS CELING NOTES N S E W 101 DINING AREA P1 P1 P1 P1 PDT.GYP.BD. WHITE 102 KITCHEN P1 P1 P1 P1 PDT.GYP.BD. WHITE 103 CLOSET P5 P5 P5 P5 PDT.GYP.BD. WHITE 104 BATH #2 P2 P2 P2 P2 PDT.GYP.BD. WHITE 105 BEDROOM P5 P5 P3 P4 PDT.GYP.BD. WHITE 106 LIVING AREA P1 P6 P1 P1 PDT.GYP.BD. WHITE 107 BALCONY P8 P8 P8 P8 PDT.GYP.BD. WHITE 108 MASTER BEDROOM P5 P5 P5 P5 PDT.GYP.BD. WHITE 109 LINEN CLOSET P1 P1 P1 P1 PDT.GYP.BD. WHITE 110 MASTER CLOSET P5 P5 P5 P5 PDT.GYP.BD. WHITE 111 HVAC / WH P1 P1 P1 P1 PDT.GYP.BD. WHITE 112 MASTER BATHROOM P7 P7 P7 P7 PDT.GYP.BD. WHITE DOOR FINISH PNT WINDOW SILL MARBLE

10 THE CEILING IS TO BE INSTALLED USING THE MANUFACTURER S INSTRUCTION SHOULD DIFFUSER OR AIR GRILL LOCATIONS BE IN CONFLICT WITH THE LIGHTING LAYOUT, THE CONTRACTOR IS TO NOTIFY GABRIELA MENDIBLE DESIGN PRIOR TO INSTALLATION FOR INSTRUCTIONS AS TO REVISED LOCATIONS. INSTALL SCONCES AT 6 0 AFF TO CENTER OF FIXTURE INSTALL JUNCTION BOX FOR UNDER-CABINET LIGHT FIXTURES IN THE UPPER CABINET. CONNECTION BETWEEN THE JUNCTION BOX AND LIGHT FIXTURE IS TO BE CONCEALED. ALIGN SOFFITS WITH PARTITIONS CONTRACTOR IS TO CONTACT GABRIELA MENDIBLE DESIGN IF THERE IS ANY CONFLICT WITH ENGINEERING IN THE QUANTITY AND LOCATION OF LIGHTING FIXTURES CONTRACTOR IS TO SUBMIT LIGHTING PACKAGE TO GABRIELA MENDIBLE DESIGN FOR REVIEW PRIOR TO ORDERING.