7. For items classified in Section K as C1 ( Danger

Size: px
Start display at page:

Download "7. For items classified in Section K as C1 ( Danger"

Transcription

1 NAPIT Electrical Installation Condition Report Guidance for recipients This report is an important and valuable document which should be retained for future reference. 1. The purpose this condition report is to confirm, so far as reasonably practicable, whether or not the electrical installation is in a satisfactory condition for continued service (see Section report should identify any damage, deterioration, defects and/or conditions which may give rise to danger (see Section 2. The person ordering the Report should have received the original Report and the inspector should have retained a duplicate. 3. The original Report should be retained in a safe place and be made available to any person inspecting or undertaking work on the electrical installation in the future. If the property is vacated, this Report will provide the new owner /occupier with details the condition the electrical installation at the time the Report was issued. 4. incorporates residual current devices there should be a notice at or near the devices stating that they should be tested quarterly. For safety reasons it is important that these instructions are followed. 5. identify fully the extent the installation covered by this Report and any limitations on the inspection and testing. The inspector should have agreed these aspects with the person ordering the Report and with other interested parties (licensing authority, insurance company, mortgage provider and the like) before the inspection was carried out.. Some operational limitations such as such as inability to gain access to parts the installation or an item equipment may have been encountered during the inspection. The inspector should have noted these in Section 7. For items classified in Section K as C1 ( Danger Present ), the safety those using the installation is at risk and it is recommended that a skilled person or persons competent in electrical installation work undertakes the necessary remedial work immediately. 8. as C2 ( Potentially Dangerous ), the safety those using the installation may be at risk and it is recommended that a skilled person or persons competent in electrical installation work undertakes the necessary remedial work as a matter urgency. 9. it has been an observation requires further investigation code FI the inspection has revealed an apparent deficiency which may result in a code C1 or C2 could not, due to the extent or limitations this inspection, be fully identified. Such observations should be investigated as soon as possible. A further examination the installation will be necessary, to determine the nature and extent the apparent deficiency (see Section F). 10. For Safety reasons, the electrical installation should be re-inspected at appropriate intervals by a skilled person or persons competent in such work. The recommended date by which the next inspection is due is stated in Section F the Report under Recommendations and on a label at or near to the consumer unit /distribution board.

2 A B C Details the installation Client Address Postcode Electrical Installation Condition Report installation. Mr T Payne Autohaus Van Conversions, Unit 12 Vennlands Business Park, Mart Road Minehead, Somerset TA24 5BJ Installation (If different from client) Address Postcode Reason for producing this report This form to be used only for reporting on the condition an existing installation. Purchasers request Date(s) on which the inspection and testing were carried out Details the installation which is the subject this report Evidence alterations or addition No Not apparent If, estimated years Date last inspection Not Known Electrical Installation Certificate No. or previous Inspection Report No. Extent electrical installation covered by this report: D Extent and limitations inspection and testing Consumer unit, 2 x socket outlet and RCD to Description premises Domestic Commercial Industrial Other (please state) Mobile vehicle Estimated age the wiring system New years Records installation available No Records held by NA MW FZG Mobile van Not known 1 Agreed limitations (See Regulations 34.2) Operational limitations including the reasons Agreed with: Installation is mobile so characteristics subject to change The inspection and testing detailed within this report and accompanying schedule has been carried out in accordance with BS 771: 2008 (IET Wiring Regulations), amended to 2015 (date) It should be noted that cables concealed within the trunkings and conduits, under floors, in ro spaces and generally within the fabric the building or underground have not been inspected unless specifically agreed between the client and inspector prior to the inspection. ESummary the condition the installation General conditions the Installation (in terms safety) New installation F Overall assessment the installation in terms its suitability for continued use SATISFACTORY UNSATISFACTORY* * An UNSATISFACTORY assessment indicates that dangerous (code C1) and/or potentially dangerous (code C2) conditions have been identified Recommendations Where the overall assessment the suitability the installation for continued use above is stated as UNSATISFACTORY, I / We recommend that any observations classified as Danger present ( ) or Potentially dangerous ( ) are acted upon as a matter urgency. Investigation without delay is recommended for observations identified as further investigation required ( ) Observations classified as Improvement recommended ( ) should be given due consideration. Subject to the necessary remedial action being taken, I / we recommend that the installation is further inspected and tested by 20/12/2021 (date) G Declaration I/We, being the person(s) responsible for the inspection and testing the electrical installation (as indicated by my/our signatures below), particulars which are described above, having exercised reasonable skill and care when carrying out the inspection and testing, hereby declare that the information in this report, including the observations and the attached schedules, provides an accurate assessment the condition the electrical installation taking into account the stated extent and limitations in section D this report. Company Limited Inspected and tested by Authorised for issue by Membership No Name: Address Flat 1, Marionsleigh : 37 Blenheim Road Position: Director Director MINEHEAD, Somerset Postcode TA24 5QA Date: H Schedule(s) 1 schedule(s) inspection and 1 schedule(s) test results are attached. The attached schedule(s) are part this document and this report is valid only when they are attached to it. This form is based on the requirements Appendix BS 771 NAPIT Administration Centre, 4th Floor, Mill 3, Pleasley Vale Business Park, Mansfield, Nottinghamshire NG19 8RL Copyright NAPIT January 2015

3 I J Electrical Installation Condition Report installation. Supply characteristics and earthing arrangements Earthing Arrangements TN-S TN-C-S TT Other Please specify: Varies as mobile Number & type live conductors a.c. d.c. No. phases No. wires Nature Supply Parameters (Note: ( 1 ) by enquiry, ( 2 ) by enquiry or by measurement) Nominal voltage, U/U 0 ( 1 ) v Nominal frequency, f( 1 ) Hz Confirmation supply polarity Prospective fault current, I pf ( 2 ) ka External loop impedance, Z e ( 2 ) Supply Protective Device BS Type Nominal Current Rating A Other Sources Supply Particulars installation referred to in this report Means Earthing Distributor s facility Installation earth electrode Details Installation earth electrode (where applicable) Type (e.g. rod(s), tape etc) Location Electrode resistance to earth Main Protective Conductors Material Csa (mm 2 ) ( ) 2 Copper 2.5 (s) Copper 2.5 Other Main Switch / Switch-Fuse/ Circuit Breaker / RCD Location Cupboard BS (EN) 1008 No. Poles 2 Current rating 3 A Fuse/device rating or setting 3 A Voltage rating 230 V If RCD main switch: Rated residual operating current I n = 30 ma Rated time delay ms (at I n ) Measured operating time at I n = 22 ms K Observations Referring to the attached schedule inspection and test results, and subject to the limitations at Section D. No remedial work required The following observations are made Explanation codes C1. Danger present. Risk injury. Immediate remedial action required C2. Potentially dangerous. Immediate remedial action required. C3. Improvement recommended. FI. Further investigation required without delay Item No. Observation Code One the above codes, as appropriate, has been allocated to each the observations made above and/or any attached observation sheets to indicate to the person(s) responsible for the installation the degree urgency for remedial action. Immediate remedial work required for items Urgent remedial work required for items for items Further investigation required without delay This form is based on the requirements Appendix BS 771 NAPIT Administration Centre, 4th Floor, Mill 3, Pleasley Vale Business Park, Mansfield, Nottinghamshire NG19 8RL Copyright NAPIT January 2015

4 A Schedule Inspections Outcomes Acceptable condition: Electrical Installation Condition Report Inspection Schedule installation. Note: This form is suitable for many types smaller installation not exclusively domestic. Unacceptable condition: State C1 or C2 Improvement recommended: C3 Further investigation FI Not verifi ed: NV Limitation: Lim 3 Not applicable: (In the Outcome column use the codes above. Provide additional comment where appropriate. C1/C2/C3 and FI coded items to be recorded in section K the condition report) Item No. Description Outcome Inspector s Name Date 1.0 DISTRIBUTOR S / SUPPLY INTAKE EQUIPMENT 1.1 Condition service cable 1.2 Condition service head 1.3 Condition distributor's earthing arrangement 1.4 Condition meter tails - Distributor / Consumer 1.5 Condition metering equipment 1. Condition isolator (where present) 2.0 Presence adequate arrangements for: 2.1 Other sources such as microgenerators [551.; 551.7] 3.0 EARTHING / BONDING ARRANGEMENTS [411.3; Chap.54] 3.1 Presence and condition distributor's earthing arrangement [ ; ] 3.2 Presence and condition earth electrode connection where applicable [ ] 3.3 Provision earthing / bonding labels at all appropriate locations [ ] 3.4 Confi rmation earthing conductor size [542.3; ] 3.5 Accessibility and condition earthing conductor at MET [ ] 3. Confi rmation main protective bonding conductor sizes [544.1] 3.7 Condition and accessibility main protective bonding conductor connections [ ; ] 3.8 Accessibility and condition all other protective bonding connections [ ] 4.0 CONSUMER UNIT(S) / DISTRIBUTION BOARD(S) 4.1 Adequacy working space / accessibility to consumer unit / distribution board [132.12; 513.1] 4.2 Security fi xing [ ] 4.3 Condition enclosure[s] in terms IP rating etc [41.2] 4.4 Condition enclosure[s] in terms fi re rating etc [ ; 52.5] 4.5 Enclosure not damaged/deteriorated so as to impair safety [[21.2 [iii]] 4. Presence linked main switch [as required by ] 4.7 Operation main switch [functional check] [ ] 4.8 Manual operation circuit-breakers and RCDs to prove disconnection [ ] 4.9 Correct identifi cation circuit details and protective devices [ ; ] 4.10 Presence RCD quarterly test notice at or near consumer unit / distribution board [ ] 4.11 Presence non-standard (mixed) cable colour warning notice at or near consumer unit / distribution board [514.14] 4.12 Presence alternative supply warning notice at or near consumer unit / distribution board [514.15] 4.13 Presence other required labelling [Please specify] [Section 514] 4.14 Examination protective device[s] and base[s]; correct type and rating [no signs unacceptable thermal damage, arcing and overheating] [ ] 4.15 Single-pole switching or protective devices in line conductors only [ ; ] 4.1 Protection against mechanical damage where cables enter consumer unit / distribution board [ ; ] 4.17 Protection against electromagnetic effects where cables enter consumer unit / distribution board / enclosures [ ] 4.18 RCD[s] provided for fault protection - includes RCBO[s] [ ; ; 531.2] Copyright NAPIT June 2015 NAPIT Administration Centre, 4th Floor, Mill 3, Pleasley Vale Business Park, Mansfi eld, Nottinghamshire NG19 8RL EICR/001 (V4)

5 Electrical Installation Condition Report Inspection Schedule installation. Note: This form is suitable for many types smaller installation not exclusively domestic. 4 Schedule Inspections Outcomes Acceptable condition: Unacceptable condition: State C1 or C2 Improvement recommended: C3 Further investigation FI Not verifi ed: NV Limitation: Lim Not applicable: (In the Outcome column use the codes above. Provide additional comment where appropriate. C1/C2/C3 and FI coded items to be recorded in section K the condition report) Item No. Description Outcome 4.19 RCD[s] provided for additional protection includes RCBO[s] [ ;415.1] 4.20 Confi rmation indication that the SPDs functional [ ] 4.21 Confi rmation that ALL conductor connections including busbars, are correctly located in terminals and are tight and 4.22 Adequate arrangements where a generator set operates as a switched alternative to the public supply [551.] 4.23 Adequate arrangements where a generator set operates in parallel with the public supply [551.7] 5.0 FINAL CIRCUITS 5.1 Identifi cation conductors [ ] 5.2 Cables correctly supported throughout their run [ ] 5.3 Condition insulation live parts [41.1] 5.4 Non-sheathed cables protected by enclosure in conduit, ducting or trunking [ ] To include the integrity conduit and trunking systems [metallic and plastic] 5.5 Adequacy cables for current-carrying capacity with regard for the type and nature the installation [Section 523] 5. Co-ordination between conductors and overload protective devices [433.1; ] 5.7 Adequacy protective devices; type and rated current for fault protection [411.3] 5.8 Presence and adequacy circuit protective conductors [ ; 543.1] 5.9 Wiring system[s] appropriate for the type and nature the installation and external infl uences [Section 522] 5.10 Concealed cables installed in prescribed zones [See Section D. extent and limitations] [ ] 5.11 Cables concealed under fl oors, above ceilings or in walls / partitions, adequately protected against damage. [See section D, Extent and limitations] [ ] 5.12 Provision additional protection by RCD not exceeding 30mA: for all socket-outlets rating 20 A or less unless exempt [Regulation ] for supply to mobile equipment not exceeding 32 A rating for use outdoors [ ] for cables concealed in walls / partitions at a depth less than 50mm [ ; ] for cables concealed in walls / partitions containing metal parts regardless depth [ ] 5.13 Provision fi re barriers, sealing arrangements and protection against thermal effects [Section 527] 5.14 Band II Cables segregated / separated from Band I cables [528.1] 5.15 Cables segregated / separated from communications cabling [528.2] 5.1 Cables segregated / separated from non-electrical services [528.3] 5.17 Termination cables at enclosures indicate extent sampling in Section D the report [Section 52] Connections soundly made and under no undue strain [52.] No basic insulation a conductor visible outside enclosure [52.8] Connections live conductors adequately enclosed [52.5] Adequately connected at point entry to enclosure [glands, bushes etc ] [ ] 5.18 Condition accessories including socket-outlets, switches and joint boxes [21.2 [iii]] 5.19 Suitability accessories for external infl uences [512.2] 5.20 Adequacy working space / accessibility to equipment [132.12; 513.1] 5.21 Single-pole switching or protective devices in line conductors only [ ; ] Inspector s Name Date Copyright NAPIT June 2015 NAPIT Administration Centre, 4th Floor, Mill 3, Pleasley Vale Business Park, Mansfi eld, Nottinghamshire NG19 8RL EICR/001 (V4)

6 Electrical Installation Condition Report Inspection Schedule installation. Note: This form is suitable for many types smaller installation not exclusively domestic. 5 Schedule Inspections Outcomes Acceptable condition: t Unacceptable condition: State C1 or C2 Improvement recommended: C3 Further investigation FI Not verifi ed: NV Limitation: Lim Not applicable: (In the Outcome column use the codes above. Provide additional comment where appropriate. C1/C2/C3 and FI coded items to be recorded in section K the condition report) Item No. Description Outcome.0 LOCATION(S) CONTAINING A BATH OR SHOWER.1 Additional protection for all low voltage LV circuits by RCD[s] not exceeding 30 ma [ ].2 Where used as a protective measure, requirements for SELV or PELV met [ ].3 Shaver sockets comply with BS EN formerly BS 3535 [ ].4 Presence supplementary bonding conductors, unless not required by BS 771:2008 [ ].5 Low voltage (e.g. 230 volt) socket-outlets sited at least 3 m from zone 1 [ ]. Suitability equipment for external infl uences for installed location in terms IP rating [ ].7 Suitability accessories and control gear etc for a particular zone [ ].8 Suitability current-using equipment for particular position within the location [701.55] 7.0 OTHER SPECIAL INSTALLATIONS OR LOCATIONS 7.1 List all other special installations or locations present, if any. [Record the results particular inspections applied separately] Schedule Tests Results to be recorded on Schedule Test Results (insert or ) External earth loop Impedance, Ze Insulation Resistance between Live conductors Installation earth electrode Prospective fault current lpf Continuity Earth Conductors Continuity Circuit Protective Conductors Continuity ring fi nal conductors Continuity Protective Bonding Conductors Volt drop verifi ed Inspector s Name Date Insulation Resistance between Live conductors & Earth Polarity (Prior to energisation) Polarity (prior to energisation) Polarity (after energisation) including phase sequence Earth fault loop impedance RCDs / RCBOs including discrimination Functional testing devices. Copyright NAPIT June 2015 NAPIT Administration Centre, 4th Floor, Mill 3, Pleasley Vale Business Park, Mansfi eld, Nottinghamshire NG19 8RL EICR/001 (V4)

7 Electrical Installation Condition Report Test Schedule Requirements for Electrical Installations BS 771:2008 incorporating Amendment No [IET Wiring Regulations 17th Edition] Client Mr T Payne Installation address,, Postcode MW FZG Complete in every case Complete only if the distribution board is not connected directly to the origin the installation Test instrument serial number(s) Location Supply to distribution Characteristics at this distribution board Associated RCD Earth fault distribution board Cupboard board is from (if any): BS (EN) loop imped Distribution board Overcurrent protective device No. Nominal V Z Operating At I Insulation n ms designation DB1 for the distribution circuit: phases 1 Voltage times RCD resistance I n ma Continuity Number ways Type BS(EN) Rating A I associated No pf ka at 5 I n ms RCD(if any) Poles Supply polarity confirmed Phase sequence confirmed RCD Circuit No. Circuit designation CIRCUIT DETAILS Type wiring Ref. method No. points served Circuit conductors csa Live (mm 2 ) CPC (mm 2 ) Maximum disconnection time (BS:771) (S) Overcurrent protective devices BS EN Number Type No. Rating Breaking capacity RCD operating current I n BS771 Max. permitted value Z s Other 80% Circuit impedence Ring final circuits only (measured end to end) Figure 8 check TEST RESULTS All circuits to be completed using R1 R2, or R2, not both Insulation resistance (Record lower reading) Maximum measured Z s (A) (ka) (ma) r 1 r n r 2 ( ) R 1 +R 2 R 2 (M ) (M ) ( ) ( ) ms ms ( ) 1 Sockets 1 A B NA NA NA NA 0.08 > Live / Live Live / Earth Polarity at I n RCD testing at 5 I 9 n Test Button operation Details circuits and/or installed equipment vulnerable to damage when testing Tested by: Name (capital letters) COLIN FLETCHER Position Director Wiring Types 1= PVC/PVC 2= Single Insulated in Conduit or Trunking 3= Mineral Insulated 4= SWA/XPLE 5= FP200 Date Copyright NAPIT January 2015 This form is based on the requirements Appendix BS 771 NAPIT Administration Centre, 4th Floor, Mill 3, Pleasley Vale Business Park, Mansfield, Nottinghamshire NG19 8RL