1 SECTION PLUMBING S PART 1 - GENERAL 1.1 GENERAL A. General Conditions of the Contract, Special Conditions, Instructions to Bidders, and other General Requirements contained in Division 00 and 01 are a part of these Specifications. B. The cited examples are used only to denote the quality standard of product desired and that they do not restrict bidders to a specific brand, make, manufacturer or specific name; that they are used only to set forth and convey to bidders the general style, type, character and quality of product desired; and that equivalent products will be acceptable. 1.2 SUMMARY A. Section Includes: 1. Water closets 2. Urinals 3. Lavatories 4. Sinks 5. Mop Basins 6. Electric water coolers 7. Showers 8. Hose bibbs 9. Wall hydrants B. Related Sections: 1. Division 07 - Joint Protection: Product requirements for calking between fixtures and building components for placement by this section. 2. Section Domestic Water System and Specialties 3. Section Sanitary Waste and Vent System and Specialties 4. Division 26 - Equipment Wiring Connections PLUMBING S

2 1.3 REFERENCES A. Refer to Section for complete listing of references. 1.4 SUBMITTALS A. Section Plumbing Shop Drawings and Submittals, Substitutions and O&M Manuals: Submittal procedures. B. Product Data: Submit catalog illustrations of fixtures, sizes, rough in dimensions, utility sizes, trim, and finishes. C. Manufacturer's Installation Instructions: Submit installation methods and procedures. D. Manufacturer's Certificate: Certify products meet or exceed specified requirements. 1.5 CLOSEOUT SUBMITTALS A. Division 01 - Execution and Closeout Requirements: Closeout procedures. B. Operation and Maintenance Data: Submit fixture, trim, exploded view and replacement parts lists. 1.6 QUALITY ASSURANCE A. Perform Work in accordance with North Carolina Building Code - Plumbing standard. B. Provide products requiring electrical connections listed and classified by Underwriters Laboratories Inc., as suitable for purpose specified and indicated. 1.7 QUALIFICATIONS A. Manufacturer: Company specializing in manufacturing products specified in this section with minimum three (3) years documented experience. B. Installer: Company specializing in performing Work of this section with minimum three (3) years documented experience. 1.8 PRE-INSTALLATION MEETINGS A. Division 01 - Administrative Requirements: Pre-installation meeting. B. Convene minimum one (1) week prior to commencing work of this section. 1.9 DELIVERY, STORAGE, AND HANDLING A. Division 01 - Product Requirements: Product storage and handling requirements. B. Accept fixtures on site in factory packaging. Inspect for damage. PLUMBING S

3 C. Protect installed fixtures from damage by securing areas and by leaving factory packaging in place to protect fixtures and prevent use WARRANTY A. Division 01 - Execution and Closeout Requirements: Product warranties and product bonds. B. Furnish five year manufacturer warranty for plumbing fixtures EXTRA MATERIALS A. Division 01 - Execution and Closeout Requirements: Spare parts and maintenance products. B. Furnish two sets of faucet washers, flush valve service kits, lavatory supply fittings, shower heads and toilet seats. PART 2 - PRODUCTS 2.1 GENERAL A. All fixtures shall be furnished complete with traps, faucets, wastes, supplies with stops, etc., as required. All exposed metal parts shall be chromium plated. B. All fixtures and equipment of similar types shall be of the same manufacturer unless indicated otherwise on the drawings or specified herein. C. Fixtures shall be mounted at mounting heights as indicated. D. If fixtures and equipment indicated in the Contract Documents are not currently manufactured, the manufacturer's current equivalent to the indicated fixtures and equipment shall be provided at no additional cost, subject to review and acceptance by the Professional. E. All potable water fixtures shall be lead free per ANSI/NSF 372 and NSF 61, Annex G. 2.2 WATER CLOSETS A. P1 Water Closet (Wall Mounted with Sensor-Operated Flush Valve) White vitreous china, wall hung, siphon jet, elongated bowl with l-l/2-inch top spud. Water closet shall be mounted as required using a chair carrier having a flush valve support. Water closet shall be provided with an extra heavy duty, elongated, white plastic seat with an open front and self sustaining stainless steel check hinges and mounting hardware. Flush valve shall be an electronic, electric-powered, sensor-operated, vandal-proof, water-saver type and shall use a maximum of 1.28 gallons per flush. PLUMBING S

4 American Standard Afwall FloWise Kohler "Kingston" K-4325 Sloan ST Toto CT708E (V) Zurn Z FLUSH VALVE (Diaphragm type gpf) Sloan Optima Zurn ZER6000PL-HET-CPM American Standard SEAT Centoco Beneke Church Bemis Olsonite 1500STSCCSS 527 SS 9400SSC 1655SSC 95SSC B. P2 Water Closet (Wall Mounted with Sensor-Operated Flush Valve - Barrier Free) White vitreous china, wall hung, siphon jet, elongated bowl with l-l/2-inch top spud. Water closet shall be mounted as required using a chair carrier having a flush valve support. Water closet shall be provided with an extra heavy duty, elongated, white plastic seat with an open front and self sustaining stainless steel check hinges and mounting hardware. Flush valve shall be an electronic, electric-powered, sensor-operated, vandal-proof, water-saver type and shall use a maximum of 1.28 gallons per flush. The flush valve shall operate with 5-pounds or less operating pressure on the handle and shall have the operating handle located on the approach side of the toilet stall. Mounting height shall be as indicated. American Standard Afwall FloWise Kohler "Kingston" K-4325 Sloan ST Toto CT708E (V) Zurn Z FLUSH VALVE (Diaphragm type gpf) Sloan Optima Zurn ZER6000PL-HET-CPM American Standard PLUMBING S

5 SEAT Centoco Beneke Church Bemis Olsonite 1500STSCCSS 527 SS 9400SSC 1655SSC 95SSC 2.3 WALL HUNG URINALS A. P3 Urinal (Side Shields with Sensor-Operated Flush Valve and Barrier Free) White vitreous china, wall hung, washout type urinal with extended shields, integral trap, floor carrier, 3/4-inch top spud and 2-inch threaded outlet connection. Urinal shall be mounted using a hanger plate carrier. Package flush valve shall be an electronic, electric-powered, sensoroperated, vandal-proof, water-saver type, piston operation and shall use a maximum of (1/8) gallon per flush. American Standard Washbrook FloWise Caroma Cube3 ULTRA Sloan SU-1000 Zurn The Pint Z5798 FLUSH VALVE (Diaphragm type gpf) Sloan Optima Zurn ZER6000PL-HET-CPM American Standard LAVATORIES A. P5 Lavatory (Integral Sink to Counter - Barrier Free) Integral Bowl to Counter Top, See Architectural with overflow and 4-inch faucet centers. Provide lavatory complete with hot / cold center set electronic, metering faucet, 0.5 gpm flow control and vandal resistant aerator, chrome plated semi-cast brass P-Trap, chrome plated PLUMBING S

6 supplies with heavy-duty, ½ IPS x 3/8 O.D. loose key stops, chrome plated brass grid strainer with offset tailpiece and insulation kit for p-trap and supplies. Nominal dimensions shall be 20- inches by 17-inches. See architectural plans, sink bowl is integral to counter top. METERING FAUCET Chicago Speakman T & S Brass AB-1 S-4141-LD-BO B-0831-B F-05 B. P6 Lavatory (Wall Mounted with Backsplash and Anti-Splash Rim - Barrier Free) White, vitreous china lavatory with overflow, 4-inch faucet centers, and drilled for concealed arm carriers. Provide lavatory complete with floor mounted carrier, hot / cold center set electronic, faucet with 4-inch wrist blade handle, 0.5 gpm flow control and vandal resistant aerator, chrome plated semi-cast brass P-Trap, chrome plated supplies with heavy-duty ½ IPS x 3/8 O.D. loose key stops, and chrome plated brass grid strainer with offset tailpiece and insulation kit for p-trap and supplies. Nominal dimensions shall be 20-inches by 18-inches. American Standard Lucerne Eljer Signature Kohler Kingston K-2005 Crane 1412 WRIST BLADE FAUCET Chicago Speakman T & S Brass AB-1 SC-3074-LD-BO B-0890-B F SHOWER TRIM A. P15 Shower (Pressure Balanced Mixing Valve, Fixed Shower Head) Concealed pressure balanced shower mixing valve; cast brass or bronze construction with stainless steel trim; adjustable high temperature limit stop; integral check stops; chrome plated brass wall escutcheon and lever handle; 1.8 gallons per minute fixed type shower head. Provide SD1 drain per specification section PLUMBING S

7 See architectural drawings and specifications. FAUCET Symmons S Leonard 4500 w/ H-04 Powers P413-D-X w/ B. P16 Shower (Pressure Balanced Mixing Valve, Fixed Shower Head, Adjustable Sliding Head and Diverter Valve - Barrier Free) Concealed pressure balanced shower mixing valve; cast brass or bronze construction with stainless steel trim; integral check stops; adjustable high temperature limit stop; chrome plated brass wall escutcheon and lever handle; 1.8 gallons per minute fixed type shower head, chromeplated slider bar assembly, hand held shower, reinforced vinyl flexible hose with in-line vacuum breaker and chrome plated brass diverter valve with lever handle. Provide SD1 drain per specification section See architectural drawings and specifications. FAUCET Symmons S-86-1-X-CHKS T-300B-30-V Leonard 4505 w/h-04 Powers P413-DX-Y-W w/ SINKS A. P40 Mop Receptor (Rectangular) 24-inch x 36-inch x 10-inch high one piece molded stone. Mop receptor shall be furnished complete with 3-inch drain with removable chrome plated strainer, vinyl or stainless steel bumper guard, and faucet with vacuum breaker, support rod, pail hook, adjustable spacing faucet inlets with integral stops and checks; stainless steel wall guards. Fiat MSBID-2436 Florestone Model 90 Mustee Model 65M FAUCET PLUMBING S

8 Chicago Speakman T & S Brass SRCXKCP SC-5812-RCP-CK B-0667-RGH B. P46 Sink (Single Compartment - Barrier Free) Nominal 22-inch x nominal 19-inch x 5-1/2-inch deep, self rimming single compartment sink. Sink shall be fully sound-deadened, eighteen (18) gauge, Type 304 stainless steel. Faucet shall have a swing gooseneck spout outlet with single-lever handle. Provide sink complete with chrome plated semi-cast brass P-trap with cleanout, chrome plated brass waste to wall with chrome plated brass escutcheon, stainless steel crumb cup strainer with chrome plated brass tailpiece; chrome plated supplies with heavy-duty chrome plated ½ IPS x ½ O.D. wheel handle supply stops with escutcheons. The Contractor shall provide a template to allow preparation of casework opening. Elkay Lustertone Just Stylist Advance Tabco LRAD SL-ADA-1921-A-GR SS FAUCET Chicago CP Delta 100-WFELHHDF Symmons S ELECTRIC WATER COOLERS A. P51 Electric Water Cooler (Bi-level Type - Barrier Free w/ (2)Bottle Fill Station) Dual height, wall mounted, with floor carrier, stainless steel enclosure, electric water coolers with two (2) one-piece bubblers, self-closing push-button operators. Coolers shall have a minimum capacity of eight gallons per hour (8 gallons per hour) at ARI standard conditions. Cooler shall be provided complete with heavy-duty ½ IPS x 3/8 O.D. wheel handle supply stop, chrome plated semi-cast brass P-trap with cleanout plug. Waste piping shall be insulated from drain to wall rough-in. Coordinate High / Low arrangement with Architectural requirements. Provide with dual Bottle Fill Stations. Color shall be as selected by the Professional. Elkay Halsey Taylor Oasis LZSTL8WSLP HTHB-HAC8BLWF PG8EBFSL PLUMBING S

9 B. P52 Electric Water Cooler (Bi-level Type - Barrier Free w/bottle Fill Station) Dual height, wall mounted, with floor carrier, stainless steel enclosure, electric water coolers with two (2) one-piece bubblers, self-closing push-button operators. Coolers shall have a minimum capacity of eight gallons per hour (8 gallons per hour) at ARI standard conditions. Cooler shall be provided complete with heavy-duty ½ IPS x 3/8 O.D. wheel handle supply stop, chrome plated semi-cast brass P-trap with cleanout plug. Waste piping shall be insulated from drain to wall rough-in. Coordinate High / Low arrangement with Architectural requirements. Provide with Bottle Fill Station. Color shall be as selected by the Professional. Elkay Halsey Taylor Oasis LZSTL8WSLP HTHB-HAC8BLWF PG8EBFSL C. P53 Electric Water Cooler (Bi-level Type - Barrier Free, Freeze Proof) Dual height, wall mounted, with floor carrier, stainless steel enclosure, electric water coolers with two (2) one-piece bubblers, self-closing push-button operators. Coolers shall have a minimum capacity of eight gallons per hour (8 gallons per hour) at ARI standard conditions. Cooler shall be provided complete with heavy-duty ½ IPS x 3/8 O.D. wheel handle supply stop, chrome plated semi-cast brass P-trap with cleanout plug. Waste piping shall be insulated from drain to wall rough-in. Coordinate High / Low arrangement with Architectural requirements. Color shall be as selected by the Professional. Elkay Halsey Taylor Oasis VRCTLFR8SC/VRCTLFR8SC HVR8BL-ADA PV8ACSL / PRV8ACSL D. P54 Electric Water Cooler (Single-level Type - Barrier Free w/bottle Fill Station) Single height, wall mounted, with floor carrier, stainless steel enclosure, electric water coolers with two (2) one-piece bubblers, self-closing push-button operators. Coolers shall have a minimum capacity of eight gallons per hour (8 gallons per hour) at ARI standard conditions. PLUMBING S

10 Cooler shall be provided complete with heavy-duty ½ IPS x 3/8 O.D. wheel handle supply stop, chrome plated semi-cast brass P-trap with cleanout plug. Waste piping shall be insulated from drain to wall rough-in. Coordinate High / Low arrangement with Architectural requirements. Provide with Bottle Fill Station. Color shall be as selected by the Professional. Elkay Halsey Taylor Oasis LZS8WSLk HTHB-HAC8BLWF PGV8EBF E. E P55 Electric Water Cooler (Bi-level Type - Barrier Free w/bottle Fill Station) Dual height, wall mounted, with floor carrier, stainless steel enclosure, electric water coolers with two (2) one-piece bubblers, self-closing push-button operators. Coolers shall have a minimum capacity of eight gallons per hour (8 gallons per hour) at ARI standard conditions. Cooler shall be provided complete with heavy-duty ½ IPS x 3/8 O.D. wheel handle supply stop, chrome plated semi-cast brass P-trap with cleanout plug. Waste piping shall be insulated from drain to wall rough-in. Coordinate High / Low arrangement with Architectural requirements. Provide with Bottle Fill Station. Color shall be as selected by the Professional. Elkay Halsey Taylor Oasis LZWS-LRPBM28K HTHB-OVLSER M8CRSBF 2.8 HOSE BIBBS AND WALL HYDRANTS A. HB1 Hose Bibb Angle pattern hose bibb; chrome plated brass body, vacuum breaker-backflow preventer with ¾-inch male hose thread nozzle, tee-handle and ¾-inch copper water tube inlet. Acceptable Manufacturers: Chicago Wolverine Brass Woodford 387RCF w/ E27JKCP vacuum breaker w/ key & vacuum breaker Model 24CH B. FPWH1 Wall Hydrant (Non-Freeze in Wall Box) Concealed type, freeze-proof, automatic draining wall hydrant consisting of a stainless steel or PLUMBING S

11 cast bronze wall box and door with chrome finish; vacuum breaker-backflow preventer with ¾- inch male hose thread nozzle; bronze or stainless steel operating stem; ¾-inch copper water tube inlet and wall clamp. A loose tee key shall be furnished with each wall hydrant. Verify wall thickness requirements for each location required. Acceptable Manufacturers: Jay R. Smith 5509QT Josam Wade Zurn Z1300 Woodford B LAVATORY INSULATION KIT A. Manufacturers: 1. Plumberex 2. Skal-Gard 3. Truebro B. Product Description: Where Lavatories are noted to be insulated for ADA compliance, furnish the following: Safety Covers conforming to ANSI A177.1 and consisting of insulation kit of molded closed cell vinyl construction, 3/16 inch thick, white color, for insulating tailpiece, P- trap, valves, and supply piping. Furnish with weep hole and angle valve access covers. PART 3 - EXECUTION 3.1 EXAMINATION A. Division 01 - Administrative Requirements: Coordination and project conditions. B. Verify walls and floor finishes are prepared and ready for installation of fixtures. C. Verify electric power is available and of correct characteristics. D. Confirm millwork is constructed with adequate provision for installation of counter top lavatories and sinks. 3.2 PREPARATION A. Rough-in fixture piping connections in accordance with minimum sizes indicated in fixture rough-in schedule for particular fixtures. 3.3 INSTALLATION PLUMBING S

12 A. Fixtures and equipment shall be installed in a neat and workmanlike manner and in accordance with the manufacturer's recommendations. The quality of installation shall be subject to the approval of the Professional. B. All wall mounted fixture carriers and supports shall be suitable to the type of construction wherein they are located. Urinals shall be supported by chair carriers. Lavatories shall be supported by floor mounted carriers. Install anchor bolts in all available anchor locations. C. All fixtures and equipment must be protected against damage during the progress of construction. Upon completion of construction, all fixtures and equipment must be thoroughly cleaned and left in perfect working order. All piping and accessories having polished, plated or finished surfaces shall be protected to prevent scarring or other damage and protect the finish against damage. D. Provide isolation valves for all fixtures, equipment, and accessories. 1. Exception: Omit stop valves on supplies to emergency equipment, except where permitted by authorities having jurisdiction. When permitted, install valve and locked in OPEN position. E. All fixture supplies and waste lines shall be run to wall unless construction requires they be run to floor. All supplies through walls shall be provided with angle stops. All supplies through floors shall be provided with straight stops. Unions shall be provided adjacent to all equipment or wherever necessary to facilitate the removal of equipment for repair of replacement. Unions for copper tubing up to and including 2-inch diameter shall be brass ground joint with socket ends for solder. Unions for copper tubing 2½-inches in diameter and over shall be standard brass flanges with socket ends for solder. Flanges to be drilled for ASA Standard 125 pounds flanges and so stamped. No lip type unions or long screws will be permitted. The Contractor shall furnish and install all structural steel angles, channels, etc. necessary to properly support all fixtures and equipment to the satisfaction of the Professional. F. Drain piping from all backflow preventers, relief valves and vents, drain down connections, kitchen equipment, etc. shall be extended to within 4-inches of a floor sink or floor drain. G. Mop receptors drains shall be sized for the outlet pipe size shown on drawings and shall be equipped with deep-seal P-traps. The Contractor shall be responsible for proper height setting and leveling of drains. Set mop receptors in leveling bed of cement. H. Water closet floor flanges shall be cast iron, screwed or caulked, not less than ¼-inch thick; not less than 2-inches caulking depth. Bolted with approved gasket between closet bowl and flange. Closet screws shall be of brass. The use of commercial putty or plaster for setting closet bowls is prohibited. I. Apply a bead of sanitary-type, 1-part mildew resistant, silicone sealant around the edge of surface mounted plumbing fixture to mask any irregularities between the fixture and wall finish. Color of sealant shall match the fixture color. 3.4 COLUMN SHOWERS PLUMBING S

13 A. Column showers shall be positioned so that a shower head is not facing the entrance to the shower area. 3.5 MOUNTING HEIGHTS A. Plumbing fixture mounting heights shall be as indicated on the drawings. Mounting heights for barrier free fixtures shall meet the requirements of the ADA Accessibility Guidelines. These guidelines shall apply unless superseded by more stringent State or Local requirements. 3.6 INTERFACE WITH OTHER PRODUCTS A. Review millwork shop-drawings. Confirm location and size of fixtures and openings before rough in and installation. 3.7 ADJUSTING A. Division 01 - Execution and Closeout Requirements: Testing, adjusting, and balancing. B. Adjust stops or valves for intended water flow rate to fixtures without splashing, noise, or overflow. 3.8 CLEANING A. Division 01 - Execution and Closeout Requirements: Final cleaning. B. Clean plumbing fixtures and equipment. 3.9 PROTECTION OF INSTALLED CONSTRUCTION A. Division 01 - Execution and Closeout Requirements: Protecting installed construction. B. Do not permit use of fixtures before final acceptance. END OF SECTION PLUMBING S