FIREFLY FR FRL-/60/60 MULTI-SERVICE BLOCK. TBA Firefly Head Office P.O. BOX 52 Laidley QLD, 4341 Australia

Size: px
Start display at page:

Download "FIREFLY FR FRL-/60/60 MULTI-SERVICE BLOCK. TBA Firefly Head Office P.O. BOX 52 Laidley QLD, 4341 Australia"

Transcription

1 TBA Protective Technologies Australia Head Office Unit 12, 8 Leighton Place Hornsby, NSW, 2077 TBA Firefly Head Office P.O. BOX 52 Laidley QLD, 4341 Australia TBA Textiles Pty Ltd ABN: Contact Us Phone: (07) Mobile: trevor@tbafirefly.com.au FRL-/60/60 FIREFLY FR MULTI-SERVICE BLOCK

2 SERVICES WHICH MAY PASS THROUGH ELECTRICAL TPS CABLE BUNDLE OF 2 TO 6 WITH 25mm FILLET OF INTUMASTIC HP EACH SIDE TPS CABLE SINGLE CAT 6 CABLE UPTO A BUNDLE OF 6 SMALL CABLE TRAY RG6 CABLE UPTO A BUNDLE OF 6 ROUND ORANGE MAINS CABLE UPTO 16mm 26mm OD PVC CONDUIT WITH UPTO 6 TPS CABLES INSIDE WITH 25mm FILLET OF INTUMASTIC HP EACH SIDE CAT 5 CABLE UPTO A BUNDLE OF 6

3 MECHANICAL / HYDRAULIC 19mm COPPER PIPE LAGGED IN ARMAFLEX PVC FLEXI DRAIN PIPE UPTO 25mm OD PEX PIPE UPTO 32mm OD 19mm DOUBLE ARMAFLEX LAGGED COPPER PIPES WITH FULL DEPTH INTUMASTIC HP BETWEEN PIPES PVC PIPE UPTO 50mm OD HDPE PIPE UPTO 40mm OD WITH 10mm FILLET OF INTUMASTIC HP ON EACH SIDE PEX-AL PIPE 32mm OD, WITH 25mm FILLET OF INTUMASTIC HP EACH SIDE PEX-AL PIPE UPTO 16mm OD PAIR COIL AIR-CON WITH FULL DEPTH INTUMASTIC HP BETWEEN PIPES PVC SPIGOT

4 WET FIRE / SECURITY STEEL SPRINKLER PIPE UPTO 50mm OD WITH 100mm WIDE FIREFLY PENOWRAP EACH SIDE 4 CORE SECURITY CABLE UPTO A BUNDLE OF 6 FR PLASTERBOARD FIRE ALARM CABLE UPTO A BUNDLE OF 2 TO 6 WITH 25mm FILLET OF INTUMASTIC HP EACH SIDE CPVC SPRINKLER PIPE UPTO 48mm OD 5mm & 10mm FIBRE OPTIC CABLES UPTO A BUNDLE OF 2O PATCH/HOLE REPAIR UPTO 30mm x 25mm FIRE ALARM CABLE SINGLE

5 INSTALLATION OF THE FR BLOCK STEP 1. THE FIREFLY FR MULTI-SERVICE BLOCKS CAN BE INSTALLED PRIOR TO ALL OF THE SERVICES RUN 2 X 6mm BEADS OF INTUMASTIC HP AROUND THE INSIDE OF THE APERTURE THEN STEP 2. SQUEEZE INTO PLACE OR RETRO FITTED AROUND EXISTING SERVICES AND GLUED BACK TOGETHER USING INTUMASTIC HP

6 INSTALLING SERVICES SMALL SERVICES STEP STEP 2. THEN SIMPLY INSERT YOUR SERVICE LARGE SERVICES STEP PUT YOUR FINGERS IN THE HOLE, PRISE OPEN THE GRAPHITE LAYERS FOR SMALL SINGLE CABLES USE A POINTY SCREWDRIVER TO CORE A HOLE IN THE SPONGE. FOR LARGER SINGLE CABLES OR SMALL PIPES UP TO 16mm OD, USE A STEAK KNIFE TO CUT A CROSS FOR LARGER PIPES AND CABLE BUNDLES CUT A RECTANGLE OUT OF THE SPONGE USING A STEAK KNIFE. DO NOT CUT THE GRAPHITE LAYERS STEP STEP 3. THEN SLIDE THE SERVICE INTO THE HOLE

7 SUBSTRATES Substrate ID Support Construction Name Width Detail Installation Details S1 Speedpanel 51mm The Speedpanel aperture track is fixed around the aperture and all gaps between track and Speedpanel filled with sealant. Speedpanel aperture track shall have a 100mm wide strip of 13mm standard or fire grade plasterboard fixed on either side of the wall. It shall be fixed with two rows of screws at 100mm centres. S2 S3 S4a Fire Grade Plasterboard lined wall INEX Wallboard TBA Intubatt Penetration Seal 90mm 162mm 50mm The hole in the wall is framed out with a steel track (steel framed walls) or timber nogging (timber walls) Intumastic Sealant is added to fill any gaps between FR Block and the linings. For single stud walls with cavity greater than 76mm the aperture shall be lined with at least one layer of the fire grade lining the wall requires. For double stud walls, the aperture in each wall (maximum 64mm cavity between them) shall be lined with at least one layer of the fire grade lining the wall requires. A neat hole, or add Intumastic Sealant to fill gaps. S4b TBA Firefly Intubatt 2 Layers of 50mm 100mm A neat hole, or add Intumastic Sealant to fill gaps up to 10mm.

8 Substrate ID S6 S7 Support Construction Name Solid and hollow masonry with voids <30% of cross section Hollow masonry with voids >30% of cross section Width Detail Installation Details 90mm 90mm Fit to a neat hole, or add Intumastic Sealant to fill gaps up to 10mm, mortar for large gaps. Install steel sheet over voids above and below FR Block. Fit to a neat hole, or add Intumastic Sealant to fill gaps up to 10mm, mortar for large gaps. S8 Brickworks Prontopanel 60mm Neat hole, or add Intumastic Sealant to fill gaps. S9 Hebel Powerpanel 75mm MAXIMUM APERTURE SIZE FOR THE MSB IS 100mm HIGH x UPTO 1000mm WIDE OR 200mm HIGH UPTO 500mm WIDE HORIZONTAL VERTICAL AND DIAGONAL SPACING BETWEEN THE SERVICES MUST BE A MINIMUM OF 40mm SERVICE EXCLUSION ZONE OUTSIDE OF THE DOTTED LINE