1 Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut INSULPANE OF CT INC. Hamden, Connecticut PRODUCT TYPE: Curtain Wall System SERIES/MODEL: 250 Test Date: 04/05/11

2 Page 1 of Report Issued To: Leed Himmel Industries, Inc. 76 Leeder Hill Drive Hamden, Connecticut Insulpane of CT Inc. 30 Edmond Street Hamden, Connecticut Test Laboratory: Architectural Testing, Inc. 130 Derry Court York, Pennsylvania Project Summary: 3.1 Product Type: Curtain Wall System 3.2 Series/Model: Compliance Statement: Results obtained are tested values and were secured by using the designated test method(s). The samples tested met the performance requirements set forth in the referenced test procedures for a ±2394 Pa (±50.0 psf) Design Pressure with missile impacts corresponding to Missile Level D and Wind Zone Test Date: 04/05/ Test Location: Architectural Testing, Inc. test facility in York, Pennsylvania. 3.6 Test Sample Source: The test specimen was provided by the client. Representative samples of the test specimen(s) will be retained by Architectural Testing for a minimum of four years from the test completion date. 3.7 Drawing Reference: The test specimen drawings have been reviewed by Architectural Testing and are representative of the test specimen(s) reported herein. Test specimen construction was verified by Architectural Testing per the drawings located in Appendix C. Any deviations are documented herein or on the drawings. 3.8 List of Official Observers: Name Company Adam Stern John Harris Scott A. Garner Michael D. Stremmel, P.E. Eric M. Brennan Leed Himmel Industries, Inc. Leed Himmel Industries, Inc. Architectural Testing, Inc. Architectural Testing, Inc. Architectural Testing, Inc.

3 Page 2 of Test Specification(s): ASTM E , Standard Test Method for Performance of Exterior Windows, Curtain Walls, Doors and Storm Shutters Impacted by Missile(s) and Exposed to Cyclic Pressure Differentials. ASTM E , Standard Specification for Performance of Exterior Windows, Glazed Curtain Walls, Doors and Storm Shutters Impacted by Wind Borne Debris in Hurricanes. 5.0 Test Specimen Description: 5.1 Product Sizes: Overall Area: Width Height 7.4 m² (80.0 ft 2 ) millimeters inches millimeters Inches Overall size Frame Construction: Frame Member Material Description All frame members Aluminum Extruded Vertical/horizontal intersections Pressure plates Joinery Type Square cut and butted N/A Detail All horizontal members were secured to the vertical members with an extruded aluminum shear block/anchor clip. The shear block was secured to the vertical member with three #14 x 1 1/2" long self tapping hex head screws. The horizontal members were secured to the shear block with two #8 x 1" long flat head screws. The shear blocks on either side of the center vertical member at the center horizontals were secured to each other with two 3/8 x 4" long bolts through the center vertical member. All pressure plates were secured to the main frame members with 1/4" x 1" long hex head screws spaced 16" on center. All pressure plates utilized a snap fit aluminum cover.

4 Page 3 of Test Specimen Description: (Continued) 5.3 Weatherstripping: Description Quantity Location Kerf mounted custom shaped, Glazing legs of the exterior pressure 1 Row hollow vinyl bulb gasket plate. Frame exterior, under the pressure Kerf mounted rubber gasket 1 Row plate. 5.4 Glazing: Glass Type 1" IG Spacer Type Aluminum box Interior Lite 1/8" tempered 0.090" PVB interlayer 1/8" tempered Exterior Lite 1/8" tempered 0.090" PVB interlayer 1/8" tempered Glazing Method The glass was exterior glazed against an EPDM gasket and a bed of silicone and secured with an exterior mounted aluminum pressure plate with a gasket against the glass. Daylight Opening Location Quantity Glass Bite millimeters inches Fixed daylight opening x /4 x 56 1/2" 5.5 Drainage: No drainage was utilized. 5.6 Hardware: No hardware was utilized. 5.7 Reinforcement: No reinforcement was utilized. 6.0 Installation: The specimen was installed into a Spruce Pine Fir wood buck. The rough opening allowed for a 1/4" shim space. The exterior perimeter of the window was sealed with sealant. Location Anchor Description Anchor Location Vertical member ends 1/2" x 3" long lag bolts Two anchors were utilized through each shear block/anchor clip into the wood buck at the end of each vertical member (Reference Testing Mock up Drawing, Sheet 1).

5 Page 4 of Test Results: The results are tabulated as follows: ASTM E 1886, Large Missile Impacts Conditioning Temperature: 21 C (70 F) Missile Weight: 4169 g (9.19 lbs) Missile Length: 2.4 m (7' 11 3/4") Muzzle Distance from Test Specimen: 5.2 m (17'0") Test Unit #1: Orientation within ±5 of horizontal Impact #1: Missile Velocity: 15.4 m/s (50.5 fps) Impact Area: Center of glass of upper left lite Observations: Missile hit target area and fractured the laminate glass Results: Pass Impact #2: Missile Velocity: 15.7 m/s (51.5 fps) Impact Area: Upper right corner of glass of lower left lite Observations: Missile hit target area and fractured the laminate glass Results: Pass Impact #3: Missile Velocity: 15.4 m/s (50.4 fps) Impact Area: Lower left corner of upper right lite Observations: Missile hit target area and fractured the laminate glass Results: Pass Note: See Architectural Testing Sketch #1 for impact locations.

6 Page 5 of Test Results: (Continued) ASTM E 1886, Air Pressure Cycling Test Unit #1 Design Pressure: ±2394 Pa (±50.0 psf) Pressure Range Pa (psf) 480 to 1200 (10.03 to 25.07) 0 to 1440 (0 to 30.08) 1200 to 1920 (25.07 to 40.10) 720 to 2400 (15.04 to 50.13) Pressure Range Pa (psf) 720 to 2400 (15.04 to 50.13) 1200 to 1920 (25.07 to 40.10) 0 to 1440 (0 to 30.08) 480 to 1200 (10.03 to 25.07) POSITIVE PRESSURE Number Average Maximum Deflection at Indicator mm (inches) of Cycle Time Cycles (seconds) #1 #2 #3 #4 #5 # (0.06) (0.22) (0.07) (0.05) (0.13) (0.22) (0.06) (0.23) (0.07) (0.05) (0.13) (0.23) (0.11) (0.35) (0.10) (0.06) (0.20) (0.35) (0.13) (0.42) (0.13) (0.07) (0.24) (0.42) Permanent Set mm (inches) 2.5 (0.10) 2.8 (0.11) 1.3 (0.05) 0.8 (0.03) 1.8 (0.07) 2.8 (0.11) NEGATIVE PRESSURE Number Average Maximum Deflection at Indicator mm (inches) of Cycle Time Cycles (seconds) #1 #2 #3 #4 #5 # (0.20) (0.47) (0.20) (0.07) (0.12) (0.47) (0.05) (0.27) (0.09) (0.06) (0.11) (0.27) (0.02) (0.17) (0.05) (0.02) (0.10) (0.17) (0.02) (0.16) (0.06) (0.03) (0.09) (0.16) Permanent Set mm (inches) <0.3 (<0.01) <0.3 (<0.01) 0.5 (0.02) 0.5 (0.02) 0.3 (0.01) <0.3 (<0.01) Observations: No additional damage or deglazing was observed. Result: Pass Note: See Architectural Testing Sketch #2 for indicator locations.

7 Page 6 of 7 General Note: Upon completion of testing, the specimens met the requirements of Section 7 of ASTM E Test Equipment: Cannon: Constructed from steel piping utilizing compressed air to propel the missile Missile: 2x4 Southern Pine Timing Device: Electronic Beam Type Cycling Mechanism: Computer controlled centrifugal blower with electronic pressure measuring device Deflection Measuring Device: Linear transducers Tape and film were not used to seal against air leakage during structural testing.

8 Page 7 of 7 The service life of this report will expire on the stated Test Record Retention End Date, at which time such materials as drawings, data sheets, samples of test specimens, copies of this report, and any other pertinent project documentation, shall be discarded without notice. If test specimen contains glazing, no conclusions of any kind regarding the adequacy or inadequacy of the glass in any glazed test specimen(s) can be made. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, Inc. Eric M. Brennan Technician Michael D. Stremmel, P.E. Senior Project Engineer EMB:dem Attachments (pages): This report is complete only when all attachments listed are included. Appendix A: Sketches (2) Appendix B: Photograph (1) Appendix C: Drawings (3) This report produced from controlled document template ATI 00498, issued 02/28/11.