1 BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS INTERIM PRESIDENT E. FELICIA BRANNON JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI MAYOR DEPARTMENT OF BUILDING AND SAFETY 201 NORTH FIGUEROA STREET LOS ANGELES, CA RAYMOND S. CHAN, C.E., S.E. GENERAL MANAGER FRANK BUSH EXECUTIVE OFFICER Hilti, Inc. RESEARCH REPORT: RR S. 122 nd East Ave (CSI # ; ) Tulsa, OK BASED UPON ICC ES EVALUATION SERVICE Attn: Andrew T. Liechti REPORT NO. ESR-2795 (918) REEVALUATION DUE DATE: October 1, 2016 Issued Date: August 1, 2014 Code: 2014 LABC GENERAL APPROVAL Reevaluation - Hilti X-HS Threaded Rod Hanger Assemblies. DETAILS The above assemblies and/or products are approved when in compliance with the description, use, identification and findings of ICC Evaluation Services Report No. ESR-2795, reissued May 2014, of the ICC Evaluation Service, Incorporated. The report in its entirety is attached and made part of this general approval. The parts of Report No.ESR-2795 which are excluded on the attached copy have been removed by the Los Angeles Department of Building and Safety as not being included in this approval. The approval is subject to the following conditions: 1. The fasteners shall not be used to resist seismic loads, except when used with architectural, electrical, or mechanical components as described in Section , and of ASCE 7-10 and as follows: a) Concrete base materials: The X-HS Hanger Assemblies fastened to concrete may be used to support acoustical tile or lay-in panel suspended ceiling systems, distributed systems and distribution systems where the service load on any individual X-HS Hanger Assemblies does not exceed the lesser of 90 lbf or the published allowable load shown in Tables 2, or 3 of the attached ICC-ES ESR-2795, as applicable. RR Page 1 of 3 LADBS G-5 (Rev.02/20/2014) AN EQUAL EMPLOYMENT OPPORTUNITY - AFFIRMATIVE ACTION EMPLOYER

2 Hilti, Inc. Re: Hilti X-HS Threaded Rod Hanger Assemblies. b) Steel base materials: The X-HS Hanger Assemblies fastened to steel may be used to support acoustical tile or lay-in panel suspended ceiling systems, distributed systems and distribution systems where the service load on any individual X-HS Hanger Assemblies does not exceed the lesser of 250 lbf or the published allowable load shown in Table 1 of the attached ICC-ES ESR The allowable design values are listed in the Tables 1, 2, 3 of ESR The load carried by the hanger through the rod shall be less than the values in allowable load tables. 3. Allowable loads shall not be increased for duration of load, except as specifically noted in the tables. 4. Design values and minimum embedment requirements shall be per Tables in ICC-ES Report No. ESR The use of the Hilti X-HS Threaded Rod Hanger Assemblies is limited to dry interior locations. 6. The Hilti X-HS Threaded Rod Hanger Assemblies are not approved for masonry application. 7. Fasteners used in the assemblies shall be those approved under City of Los Angeles Research Report no. RR Fastener installation complies with this report and the Hilti, Inc., published instructions. In the event of conflict between this report and Hilti, Inc., published instructions, this report governs. 9. Calculations demonstrating that the applied loads are less than the allowable load values described in this report shall be submitted to the plan check Engineer at the time of permit application. The calculations shall be prepared by a Civil or Structural Engineer registered in the State of California. EXCEPTION: Anchors used for the installation of mechanical, plumbing and electrical equipment may be designed and detailed on a plan prepared by an engineer licensed by the state of California. DISCUSSION The report is in compliance with the 2014 Los Angeles City Building Code. The approval is based on tests in accordance with ICC ES Acceptance Criteria for Fasteners Power-driven into Concrete, Steel and Masonry Elements (AC 70), dated October RR Page 2 of 3

3 Hilti, Inc. Re: Hilti X-HS Threaded Rod Hanger Assemblies. This general approval will remain effective provided the Evaluation Report is maintained valid and unrevised with the issuing organization. Any revision to the report must be submitted to this Department for review with appropriate fee to continue the approval of the revised report. Addressee to whom this Research Report is issued is responsible for providing copies of it, complete with any attachments indicated, to architects, engineers and builders using items approved herein in design or construction which must be approved by Department of Building and Safety Engineers and Inspectors. This general approval of an equivalent alternate to the Code is only valid where an engineer and/or inspector of this Department has determined that all conditions of this Approval have been met in the project in which it is to be used. ALLEN PEERY, Chief Engineering Research Section 201 N. Figueroa St., Room 880 Los Angeles, CA Phone Fax RJG RR25826/MSWord2010 R07/18/14 5A1/1911/1912/ Attachment: ICC ES Report No. ESR-2795 (5 Pages) RR Page 3 of 3

4 ICC-ES Evaluation Report (800) (562) ESR-2795 Reissued May 2014 This report is subject to renewal June 1, A Subsidiary of the International Code Council DIVISION: CONCRETE Section: Concrete Anchors DIVISION: METAL Section: Metal Fastenings REPORT HOLDER: HILTI, INC SOUTH 122ND EAST AVENUE TULSA, OKLAHOMA (800) HNATechnicalServices@hilti.com EVALUATION SUBJECT: HILTI LOW-VELOCITY POWDER-ACTUATED X-HS THREADED ROD HANGER ASSEMBLIES 1.0 EVALUATION SCOPE Compliance with the following codes: 2012 International Building Code (IBC) 2012 International Residential Code (IRC) 2009, 2006 and 2003 International Building Code (IBC)* 2009, 2006 and 2003 International Residential Code (IRC)* *Codes indicated with an asterisk are addressed in Section 8.0. Property evaluated: Structural 2.0 USES Hilti X-HS low-velocity, powder-actuated, threaded rod hanger assemblies are used as alternatives to the cast-inplace anchors described in IBC Section1908 for placement in concrete, and the welds and bolts used to attach materials to steel, described in IBC Sections and , respectively. The assemblies are used to connect threaded steel rods to the supporting material. The hanger assemblies may be used where an engineered design is submitted in accordance with IRC Section R DESCRIPTION 3.1 X-HS Threaded Rod Hanger Assembly: The Hilti X-HS threaded rod hanger assembly consists of a Hilti X-U low velocity, powder-actuated fastener (recognized in RR with two premounted washers (one of zinc-plated steel, one of plastic), and a premounted cold-formed steel bracket (threaded rod hanger) having a 1 / 4 - or 3 / 8 -inch-diameter (6.4 or 9.5 mm) internally threaded hole to accommodate connection of 1 / 4 - or 3 / 8 -inchdiameter (6.4 or 9.5 mm) UNC threaded steel rods, respectively. The X-HS U19 and X-HS U32 hanger assemblies described in this report, include Hilti X-U19 and X-U32 fasteners, respectively, recognized in RR The X-U19 and X-U32 fasteners have shank lengths of 0.75 inch (19 mm) and 1.26 inches (32 mm), respectively. The threaded rod hangers are manufactured from mild carbon steel with a zinc coating in accordance with Hilti s specifications. See Figure 1 for an illustration of the X-HS threaded rod hanger assembly. 3.2 Substrate Materials: Steel: Structural steel used in supports must comply with the minimum strength requirements of ASTM A36, A572 Grade 50 or A992, and must have a minimum thickness of 3 / 16 -inch (4.76 mm) Normal-weight Concrete: Normal-weight concrete must be stone-aggregate and comply with IBC Chapter 19 or IRC Section R402.2, as applicable. The minimum concrete compressive strength at the time of fastener installation is noted in Table Lightweight Concrete: Lightweight concrete must be sand-lightweight complying with IBC Chapter 19. The minimum concrete compressive strength at the time of fastener installation is noted in Table Steel Deck Panels: Steel deck panels must conform to a code-referenced material standard, with the minimum thickness and minimum yield strength noted in Table 3. See Figures 4 through 6 for panel configuration requirements. 4.0 DESIGN AND INSTALLATION 4.1 Design: Allowable Loads: The allowable tension, shear and 45-degree-angle loads for X-HS threaded rod hanger assemblies installed into steel are provided in Table 1. The allowable tension, shear and 45-degree-angle loads for X-HS threaded rod hanger assemblies installed into normal-weight concrete are provided in Table 2. The allowable tension, shear and 45-degree-angle loads for X-HS threaded rod hanger assemblies installed into sandlightweight concrete and into sand-lightweight concrete filled steel deck panels are provided in Table 3. For other angles of installation, allowable loads for assemblies subjected to combined shear and tension forces must be determined using the following equation: ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2014 Page 1 of

5 ESR-2795 Most Widely Accepted and Trusted Page 2 of 5 where: p (p/p a ) + (v/v a ) # 1 = Actual tension load, lbf (N). P a = Allowable tension load, lbf (N). v = Actual shear load, lbf (N). V a = Allowable shear load, lbf (N). The stress increases and load reductions described in IBC Section are not allowed for wind loads acting alone or when combined with gravity loads. No increase is allowed for vertical loads acting alone. Allowable loads apply to the connection of the X-HS Hanger Assembly to the base material only with threaded rod installed. Design of the connection of the X-HS Hanger Assembly to the suspended material must comply with the applicable requirements of the IBC Seismic Considerations: Use with Structural Components: Resistance to seismic loads is outside the scope of this report. Therefore, the suitability of the Hilti X-HS Hanger Assemblies for use with structural components that are subjected to seismic loads is outside the scope of this report Use with Nonstructural Components: Seismic load resistance is outside the scope of this report, except when used with architectural, mechanical and electrical components described in Section of ASCE 7 and as follows: Concrete Base Materials: The X-HS Hanger Assemblies fastened to concrete may be used to support acoustical tile or lay-in panel suspended ceiling systems, distributed systems and distribution systems where the service load on any individual X- HS Hanger Assembly does not exceed the lesser of 90 lbf (400 N) or the published allowable load shown in Table 2 or 3, as applicable. Steel Base Materials: The X-HS Hanger Assemblies fastened to steel may be used where the service load on any individual X-HS Hanger Assembly does not exceed the lesser of 250 lbf (1112 N) or the published allowable load shown in Table Installation: General: The X-HS threaded rod hanger assemblies must be installed in accordance with this report and the Hilti, Inc., published installation instructions, including those shown in Figure 2. A copy of these instructions must be available on the jobsite at all times during installation. Installation is limited to dry, interior locations. Fastener placement requires the use of a low-velocity powder-actuated tool in accordance with Hilti, Inc. recommendations. Nailhead standoff distance must be as noted in the footnotes to the tables and as shown in Figure 2. Installers must be certified by Hilti and have a current, Hilti-issued, operator s license Fastening to Steel: When installation is in steel, minimum spacing between fasteners must be 1 inch (25.4 mm) and minimum edge distance must be 1 / 2 inch (12.7 mm) Fastening to Concrete: Fasteners must be driven into the normal-weight or sand-lightweight concrete after the concrete attains the specified concrete compressive strength. Unless otherwise noted, minimum spacing between fasteners must be 4 inches (102 mm) and minimum edge distance must be 3 inches (76 mm). Unless otherwise noted in this report, concrete thickness must be a minimum of 3 inches (76 mm) Fastening to Sand-lightweight Concrete Filled Steel Deck Panels: Installation in sand-lightweight concrete filled steel deck panels must comply with Figures 4 through 6. Minimum distances from fastener centerline to rolled deck panel flute edges must be as depicted in Figures 4 through CONDITIONS OF USE The Hilti X-HS threaded rod hanger assemblies described in this report comply with, or are suitable alternatives to what is specified in, those codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 The hanger assemblies are manufactured and identified in accordance with this report. 5.2 Hanger assembly installation complies with this report and the Hilti, Inc., published instructions. In the event of conflict between this report and Hilti, Inc., published instructions, this report governs. 5.3 Calculations demonstrating that the actual loads are less than the allowable loads described in Section must be submitted to the code official for approval. The calculations must be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is constructed. 5.4 Refer to Section for seismic considerations. 5.5 The use of the hanger assemblies is limited to installation in uncracked concrete. Cracking occurs when f t > f r due to service loads or deformations. 5.6 Use of the hanger assemblies is limited to dry, interior locations. 5.7 Installers must be certified by Hilti, Inc., and have a current, Hilti-issued, operator s license. 6.0 EVIDENCE SUBMITTED Data in accordance with the ICC-ES Acceptance Criteria for Fasteners Power-driven into Concrete, Steel and Masonry Elements (AC70), dated February IDENTIFICATION The word Hilti and the designation X-HS are stamped on the hanger. The X-U fastener is imprinted with an H on the head. All hanger assemblies are identified on the packaging, with the Hilti, Inc. name, the hanger type, the fastener type and size, and the evaluation report number (ESR-2795). 8.0 OTHER CODES 8.1 Evaluation Scope: In addition to the 2012 IBC and 2012 IRC addressed in Sections 2.0 through 7.0, the products in this report were evaluated for compliance with the requirements of the following codes: 2009, 2006 and 2003 International Building Code (2009, 2006 and 2003 IBC) 2009, 2006 and 2003 International Residential Code (2009, 2006 and 2003 IRC) 8.2 Uses: The Hilti X-HS low-velocity threaded rod hanger assemblies are used to connect materials as described in Section 2.0. The hanger assemblies are used as alternatives to the cast-in-place anchors described in 2009 and 2006 IBC Sections 1911 and 1912, and 2003 IBC Sections 1912 and 1913 for placement in concrete, and the

6 ESR-2795 Most Widely Accepted and Trusted Page 3 of 5 welds and bolts used to attach materials to steel, as described in 2009, 2006 and 2003 IBC Sections and , respectively. The hanger assemblies may be used where an engineered design is submitted in accordance with 2009, 2006 and 2003 IRC Section R , as applicable. 8.3 Description: See Section Design and Installation: Design: Allowable Loads: See Section Seismic Considerations: See Section Installation: See Section Conditions of Use: See Section Evidence Submitted: See Section Identification: See Section 7.0. TABLE 1 ALLOWABLE LOADS FOR HILTI X-HS THREADED ROD HANGER ASSEMBLIES DRIVEN INTO STEEL (lbf) 1,2,3,4 HANGER ASSEMBLY LOADING CONDITION Tension Shear 45-degree X-HS U For SI: 1 inch = 25.4 mm, 1 lbf = 4.4 N. 1 Nailhead Standoff, h NVS, must be less than or equal to 3 / 8 in. See Figure 2. 2 Allowable loads apply to X-HS threaded rod hanger assemblies with either the 1 / 4 - or 3 / 8 -inch-diameter internally threaded hole. 3 See Figures 3a, 3b and 3c for load directions. 4 Allowable load capacities apply to base steel with minimum yield strength (F y ) of 36 ksi, a minimum tensile strength (F u ) of 58 ksi and a minimum thickness of 3 / 16 -inch. 5 Allowable loads for 45-degree applications are based on testing. For allowable loads at other angles of installation, refer to Section TABLE 2 ALLOWABLE LOADS FOR HILTI X-HS THREADED ROD HANGER ASSEMBLIES INSTALLED IN NORMAL-WEIGHT CONCRETE (lbf) 1,2,3,4,5 CONCRETE COMPRESSIVE STRENGTH HANGER ASSEMBLY 2000 psi 4000 psi Tension Shear 45-degree Tension Shear 45-degree X-HS U For SI: 1 inch = 25.4 mm, 1 lbf = 4.4 N, 1 psi = 6895 Pa. 1 Fasteners must not be driven until the concrete has reached the specified compressive strength. 2 Concrete material thickness at the point of penetration must be a minimum of 3 inches. 3 Nailhead Standoff, h NVS, must be less than or equal to 3 / 8 in. for the X-HS U32 hanger assembly. See Figure 2. 4 Allowable loads apply to X-HS threaded rod hanger assemblies with either the 1 / 4 - or 3 / 8 -inch-diameter internally threaded hole. 5 See Figures 3a, 3b and 3c for load directions. 6 Allowable loads for 45-degree applications are based on testing. For allowable loads at other angles of installation, refer to Section TABLE 3 ALLOWABLE LOADS FOR HILTI X-HS THREADED ROD HANGER ASSEMBLIES INSTALLED INTO MINIMUM f c = 3,000 psi SAND-LIGHTWEIGHT CONCRETE AND COMPOSITE STEEL DECK PANELS (lbf) 1,2,3,4,5,6,7 HANGER ASSEMBLY Installed into Structural Sandlightweight Concrete FASTENER LOCATION Installed through 1 1 / 2 in. Deep Steel Deck Panel Installed through 3 in. Deep Steel Deck Panel Into Into Sand-lightweight Concrete Sand-lightweight Concrete Upper Flute Lower Flute Upper Flute Lower Flute Tension Shear Tension Shear degree degree Tension Shear 45- degree Tension Shear 45- degree Tension Shear 45- degree X-HS U For SI: 1 inch = 25.4 mm, 1 lbf = 4.4 N, 1 psi = 6895 Pa. 1 Fasteners must not be driven until the concrete has reached the specified compressive strength. 2 Concrete material thickness at the point of penetration must be a minimum of 3 inches, except as shown in Figures 4, 5 and 6. 3 Deck panel must have a minimum No. 20 gage ( inch) base-metal thickness and a minimum yield strength of 33,000 psi. 4 Nailhead Standoff, h NVS, must be less than or equal to 3 / 8 in. for the X-HS U32 hanger assembly. See Figure 2. 5 Allowable loads apply to X-HS threaded rod hanger assemblies with either the 1 / 4 - or 3 / 8 -inch-diameter internally threaded hole. 6 See Figures 3a, 3b and 3c for load directions. 7 See Figures 4, 5 and 6 for nominal flute dimensions, fastener locations, and load orientations. 8 Allowable loads for 45-degree applications are based on testing. For allowable loads at other angles of installation, refer to Section

7 ESR-2795 Most Widely Accepted and Trusted Page 4 of 5 FIGURE 1 X-HS THREADED ROD HANGER ASSEMBLY FIGURE 2 X-HS INSTALLATION INSTRUCTIONS FIGURE 3 X-HS LOAD DIRECTIONS

8 ESR-2795 Most Widely Accepted and Trusted Page 5 of 5 FIGURE 4 HILTI X-HS THREADED ROD HANGER ASSEMBLY LOCATION IN 3-INCH-DEEP COMPOSITE FLOOR DECK PANEL, NORMAL DECK PANEL PROFILE ORIENTATION FIGURE 5 HILTI X-HS THREADED ROD HANGER ASSEMBLY LOCATION IN 1 1 / 2 -INCH-DEEP FLOOR DECK PANEL, NORMAL DECK PANEL PROFILE ORIENTATION For SI: 1 inch = 25.4 mm, 1 psi = 6895 Pa. FIGURE 6 HILTI X-HS THREADED ROD HANGER ASSEMBLY LOCATION IN 1 1 / 2 -INCH-DEEP FLOOR DECK PANEL, INVERTED DECK PANEL PROFILE ORIENTATION

9 ICC-ES Evaluation Report (800) (562) ESR-2795 FBC Supplement Reissued May 2014 This report is subject to renewal June 1, A Subsidiary of the International Code Council DIVISION: CONCRETE Section: Concrete Anchors DIVISION: METALS Section: Metal Fastenings REPORT HOLDER: HILTI, INC SOUTH 122ND EAST AVENUE TULSA, OKLAHOMA (800) HNATechnicalServices@hilti.com EVALUATION SUBJECT: HILTI LOW-VELOCITY POWDER-ACTUATED X-HS THREADED ROD HANGER ASSEMBLIES 1.0 EVALUATION SCOPE Compliance with the following codes: 2007 Florida Building Code Building 2007 Florida Building Code Residential Property evaluated: Structural 2.0 PURPOSE OF THIS SUPPLEMENT This supplement is issued to indicate that the Hilti Low-Velocity Powder-Actuated X-HS Theaded Rod Hanger Assemblies, described in Sections 2.0 through 7.0 and in Tables 1 through 3 of the master report ESR-2795, comply with the 2007 Florida Building Code Building and the 2007 Florida Building Code Residential, when designed and installed in accordance with the master evaluation report, and under the following condition: The use of threaded rods for lateral bracing of habitable structures in the High-Velocity Hurricane Zone is prohibited, in accordance with Section of the 2007 Florida Building Code Building and Section R of the 2007 Florida Building Code Residential. For products falling under Florida Rule 9B-72, verification that the report holder s quality assurance program is audited by a quality assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the responsibility of an approved validation entity (or the code official when the report holder does not possess an approval by the Commission). This supplement expires concurrently with the master evaluation report reissued on May ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2014 Page 1 of