1 ADDENDUM NUMBER TWO (2) DATE: May 1, 2015 PROJECT: FROM: TO: Tenant Improvements for: RELOCATION OF TIME INC. LIFESTYLE GROUP KPS GROUP, INC First Avenue North Birmingham, Alabama All Bidders GENERAL: This Addendum forms a part of the Contract Documents and modifies the original Construction Documents dated April 22, 2015, and Addendum #1, dated April 28, 2015 as noted below. The following Conditions, Drawings, Specification changes, etc. take precedence over items in the Drawings and Specifications of the Contract Documents. Portions of the Contract Documents not changed by this Addendum remain in effect. Bidders are advised to call attention to all sub-bidders and suppliers for any changes, which may affect their work. Acknowledge receipt of this Addendum in the space provided on the Bid Form. Failure to do so may subject Bidder to disqualification. ADDITIONAL INFORMATION / CLARIFICATIONS: 1. Question: Please confirm the door hardware specification is a Time Inc / Samford building requirement. A Door supplier is stating it is written to close him out from pricing but has provided hardware in the building for Southern Progress before. Answer: This should not be considered a sole source specification. The hardware specification indicated intent; the desired function for each opening and products of good quality as a basis of design. Contractor shall match existing as closely as possible and can provide comparable alternatives of same quality. Refer to General Note at start of Part 3.3 of Specification Section Door hardware. 2. Question: Please provide a rebar design for the housekeeping pad for the outside associated CRAC units to support the designed weight. Answer: Reference Detail 5 on drawing M5.01 showing rebar requirements. If you feel the need, please share this detail with the structural engineer. ACC-1 and ACC-2 weigh approximately 600 pounds each, over four legs. 3. Question: Please provide location and design of the building penetration for the HVAC piping servicing the outside units. Answer: Core drill and seal in accordance with specification section , paragraph 3.6, A, 1 and , paragraph 3.6, B, 5. The actual location shall be determined by the submitted shop drawing. ADDENDUM NUMBER TWO (2) May 1, 2015 Page 1 of 7

2 4. Question: Please provide location and design of the building penetration for the gas piping servicing the Building. Answer: Core drill and seal in accordance with specification section , paragraph 3.7, A,1 and , paragraph 3.7, B, 5. The actual location shall be determined by the submitted shop drawing. 5. Please provide a detail of Nana wall bottom track detail and how it is anchored into floor concrete Answer: See detail information on attached updated sheet A Question: In regards to the overhead steel support for the Nanawall system. Please provide structural members sizes and rod sizes and how it attaches to the roof concrete slab. Answer: See detail information on attached updated sheet A Question: Please provide additional details / section cuts / elevations of all the scope for the the landscape / hardscape shown on A508 Answer: This design has not yet been finalized and will not be part of this bid package. 8. Question: Please provide a elevations, or size of tackable walls panels, in work area 176. Answer: There will be 26 6 lineal feet of the wall panels. The wall panels will be 5-6 high. 9. Question: Please provide spec and detail on the vapor barrier seal spray for ceiling, walls, floors, noted on detail 8/M5.0 Answer: For the Concrete Floors: Apply specified floor sealer as specified in Painting section. For the Gyp. Bd. Walls: Use conventional paint or epoxy as specified in Painting section. For all Penetrations: Seal around all penetrations with sealants specified in Joint Sealants section. 10. Question: There is existing batt insulation around the perimeter and below the sill that actually notes it s flammable to remain or is to be removed? Answer: The existing batt insulation around perimeter and below the sill will remain in place. 11. Question: What are the final hardware selections for the Millwork? Answer: 506 SHOWCASE KITCHEN - Door Hardware to be Emtek 1-1/4, Providence Cabinet Knob, Satin Nickel Finish, Drawer Hardware to be Emtek 4 Alexander Pull, Polished Nickel US26, URBAN VIDEO KITCHEN Door Hardware to be Colonial Bronze Co. 4.5 Pull Style 1302, Polished Nickel w/ matte satin black Drawer Hardware to be Emtek 6 Trinity Pull, Satin Nickel US15, TRADITIONAL VIDEO KITCHEN Door Hardware to be Atlas 5.5 Ergo Pull, Brushed Nickel, A868 Drawer Hardware to be Emtex 3 Cup Pull, Satin Nickel, PHOTOBAY SHOOTING KITCHEN Door Hardware to be Emtek 1.75 Geometric Oval Cabinet Knob, Polished Nickel US26, Drawer Hardware to be Emtex 3 Cup Pull, Satin Nickel, & 519 TASTING TABLES ADDENDUM NUMBER TWO (2) May 1, 2015 Page 2 of 7

3 Door Hardware to be Antique Hardware SH110US5 1.5 Solid Brass Egg Knob, Antique Brass Finish Drawer Hardware to be Colonial Bronze COL-1303-M19X5, Solid Brass Cabinet Pull, Matte Satin Black w/ Antique Satin Brass ATTACHMENTS: A. This Addendum includes the following attached Specification Sections: 1. Section UNDER-SLAB VAPOR BARRIER: New Section, dated May 01, 2015 [three (3) pages] 2. Section CAST-IN-PLACE CONCRETE: New Section, dated May 01, 2015 [fifteen (15) pages] 3. Section DOOR HARDWARE: Revised Section, dated May 01, 2015 [Three (3) pages] 4. Section FOOD SERVICE EQUIPMENT: New Section, [Ten (10) pages] 5. Section FOOD STORAGE EQUIPMENT: New Section, [Six (6) pages] 6. Section POWER VENTILATORS: Revised Section, dated May 01, 2015 [Five (5) pages] B. This Addendum includes the following attached 24 x 36 Drawing Sheets All sheets are Revision 1, Addendum #2 05/01/2015 unless otherwise noted. (forty-two (42) sheets): 1. Sheet G000 COVER AND SHEET INDEX 2. Sheet A112 FLOOR PLAN - 5TH FLOOR EAST 3. Sheet A503 ENLARGED PLANS & ELEVATIONS - PHOTO BAY KITCHEN 4. Sheet A504 ENLARGED PLAN - VIDEO DEPARTMENT 5. Sheet A505 INTERIOR ELEVATIONS - VIDEO DEPARTMENT 6. Sheet A506 ENLARGED PLANS & ELEVATIONS - SHOWCASE TASTING TABLE 7. Sheet A507 INTERIOR ELEVATIONS 8. Sheet A601 FINISHES LEGEND 9. Sheet A604 SCHEDULE - DOORS 10. Sheet A705 SECTIONS 11. Sheet A706 DETAILS 12. Sheet A710 DETAILS - TASTING TABLES 13. Sheet A711 DETAILS - MILLWORK ADDENDUM NUMBER TWO (2) May 1, 2015 Page 3 of 7

4 14. Sheet FP0.1 FP SCHEDULES, LEGENDS, NOTES, DETAILS & FIRST FLOOR DEMO & NEW WORK PLANS 15. Sheet FP2.0 FIRST FLOOR FIRE PROTECTION (New Sheet, Addendum # ) 16. Sheet FP2.1 FIRE PROTECTION NEW WORK FIFTH FLOOR PLAN 17. Sheet P0.1 PLUMBING SCHEDULES, DETAILS & LEGENDS 18. Sheet P0.2 PLUMBING RISERS & GAS PIPING SCHEMATIC 19. Sheet P2.0 GROUND FLOOR PLAN PLUMBING PIPING 20. Sheet P2.1 FIFTH FLOOR PLAN NON-PRESSURE PIPING 21. Sheet P2.2 ROOF PLAN - PLUMBING PIPING 22. Sheet P3.1 FIFTH FLOOR PLAN PRESSURE PIPING 23. Sheet P4.1 LARGE SCALE PLANS - PLUMBING PIPING 24. Sheet M0.1 MECHANICAL LEGENDS AND SCHEDULES 25. Sheet M0.2 MECHANICAL SCHEDULES 26. Sheet M1.0 MECHANICAL FIRST FLOOR DEMOLITION & NEW WORK PLANS 27. Sheet M1.1 MECHANICAL FIFTH FLOOR DEMOLITION PLAN 28. Sheet M2.1 MECHANICAL FIFTH FLOOR NEW WORK PLAN 29. Sheet M2.2 MECHANICAL ROOF NEW WORK PLAN 30. Sheet M4.0 MECHANICAL NEW WORK PARTIAL PLANS 31. Sheet M5.0 MECHANICAL DETAILS 32. Sheet M5.1 MECHANICAL DETAILS 33. Sheet M6.0 MECHANICAL CONTROLS 34. Sheet M6.1 MECHANICAL CONTROLS (New Sheet, Addendum # ) 35. Sheet E104 DETAILS 36. Sheet E105 DETAILS 37. Sheet E201 5th FLOOR PLAN - AREA A- LIGHTING 38. Sheet E202 5th FLOOR PLAN - AREA B- LIGHTING 39. Sheet E203 5th FLOOR PLAN - AREA C - LIGHTING ADDENDUM NUMBER TWO (2) May 1, 2015 Page 4 of 7

5 40. Sheet E301 2ND FLOOR PLAN - POWER & VOICE DATA PLAN 41. Sheet E303 4th FLOOR PLAN - POWER & VOICE DATA PLAN 42. Sheet E304 5th FLOOR PARTIAL PLAN AREA A- POWER & VOICE DATA 43. Sheet E305 5th FLOOR PARTIAL PLAN AREA B- POWER & VOICE DATA 44. Sheet E306 5th FLOOR PARTIAL PLAN AREA C- POWER & VOICE DATA 45. Sheet E400 1st FLOOR PARTIAL PLAN AUXILIARY & ELEC CONN. TO MECHANICAL 46. Sheet E401 2nd FLOOR PARTIAL PLAN AUXILIARY & ELEC CONN. TO MECHANICAL 47. Sheet E402 3rd FLOOR PARTIAL PLAN AUXILIARY & ELEC CONN. TO MECHANICAL 48. Sheet E403 4th FLOOR PARTIAL PLAN AUXILIARY & ELEC CONN. TO MECHANICAL 49. Sheet E404 5th FLOOR PARTIAL PLAN AREA A- AUXILIARY & ELEC CONN. TO MECH. 50. Sheet E405 5th FLOOR PARTIAL PLAN AREA B- AUXILIARY & ELEC CONN. TO MECH. 51. Sheet E406 5th FLOOR PARTIAL PLAN AREA C- AUXILIARY & ELEC CONN. TO MECH. 52. Sheet E407 ROOF PLAN AUXILIARY & ELEC CONN. TO MECH. 53. Sheet K2.1 KITCHED EQUIPMENT SCHEDULE CHANGES TO SPECIFICATIONS: 1. SECTION PLUMBING PIPING a. Refer to Article 2.9 Flexible Connections, Paragraph A, revise as follows: A. Stainless steel corrugated tubing with stainless steel wire braid, ANSI Z b. Refer to Article 2.19 Automatic Gas Valve, Paragraph B, revise as follows: B Furnished by General Contractor. Installed by Plumbing Contractor. c. Refer to Article 2.19 Automatic Gas Valve, add Paragraph C as follows: C. Solenoid Valve: Aluminum body, explosion proof enclosure, conduit hub, Buna-N seats, 80-90V DC power, normally closed with manual reset, suitable for use with natural gas, UL labeled, FM approved; ASCO Series 8044 or approved equal. 2. SECTION PLUMBING FIXTURES a. Refer to Article 2.1 Drains, delete Paragraph A. b. Refer to Article 2.1 Drains, delete Paragraph C. c. Refer to Article 2.6 Plumbing Fixtures and Equipment, revise Paragraph J as follows: J. Provide Symmons CK thermostatic mixing valve or approved equal under all sinks and lavatories. Set hot water temperature at 109 deg F. ADDENDUM NUMBER TWO (2) May 1, 2015 Page 5 of 7

6 d. Refer to Article 2.6 Plumbing Fixtures and Equipment, Paragraph K revise Water Softener as follows: Water Softener: Provide and Install a Culligan Gold Series 9 duplex water softener capable of providing 9 gallons per minute of softened water. System shall be provided complete with two (2) 9 inch diameter softening tank, 16 inch diameter, 250 pound capacity brine tanks, automatic controller. e. Refer to Article 2.7 Water Softener, revise Paragraph A as follows: A. The water softener shall be duplex unit Culligan Gold Series 9 capable of softening to 2 MG/L with a flow rate of 9 gallons per minute with a maximum pressure loss of 14 PSI system. 3. SECTION GENERAL HVAC REQUIREMENTS a. Refer to Article 1.13 Submittals for Project Closeout Paragraph C, revise Item 13 as follows: 13. Submit factory start-up/field reports for: a. Make-up air units. b. Computer room units. 4. SECTION BASIC HVAC MATERIALS AND METHODS a. Delete Article 3.7 Sleeves and Openings in The Roof Slabs in Post Tension Slab Construction. b. Refer to Article 3.14 Concrete Bases Paragraph A, revise as follows: A. Provide concrete foundations with nominal dimensions conforming to the following schedule for floor-mounted equipment: Equipment Air cooled condensing units Foundation 6-inch high pad 5. ITEM NO. 5 SECTION HVAC SYSTEMS INSULATION a. Delete Article 2.11 Fire Protective Duct Wrap Insulation System. b. Delete Article 3.13 Fire Protective Duct Wrap Application. c. Refer to Article 3.14 Schedules - Duct Insulation, add Paragraph H as follows: H. Range Hood Exhaust: 1. Round and Rectangular Range Hood Exhaust Ducts from Hood to roof Penetration: 1 1/2 inch thick 0.75 pound density Duct Wrap. 6. SECTION INDIRECT-FIRED H&V UNITS a. Refer to Article 2.8 Indirect-Fired Gas Furnace Paragraph G, revise as follows: G. Heat Exchanger: Stainless steel. b. Refer to Article 2.9 Controls, delete Paragraphs B, D, E and H. 7. SECTION COMPUTER-ROOM AIR-CONDITIONERS a. Refer to Article 2.1 Floor Mounted Units 6 Tons and Larger, delete as specified and revise to read as follows: ADDENDUM NUMBER TWO (2) May 1, 2015 Page 6 of 7

7 A. CRU/ACC-1 & 2pre purchased by General Contractor. b. Delete Article 2.2 Fan Motors. c. Refer to Article 3.1 Examination, delete Paragraph B. d. Refer to Article 3.2 Installation, delete paragraph D. 8. SECTION METAL DUCTS a. Refer to Article 1.4 Quality Assurance, delete Paragraph B. b. Refer to Article 2.2 Sheet Metal Materials - General, delete Paragraphs C, D and H. c. Delete Article 2.7 Double Wall Duct and Fitting Fabrication. d. Refer to Article 3.2 Duct Applications Paragraph A, delete Range Hood Exhaust Ducts from table. Range Hood Exhaust Ducts Comply with NFPA 96 a.concealed: Carbon-steel sheet minimum 16 gauge. b.exposed: Type 304, stainless steel with finish to match range hood minimum 18 gauge. 2 inches All seams and joints to be liquid tight with continuous external weld. e. Refer to Article 3.3 Duct Installation, delete Paragraph N. f. Refer to Article 3.4 Seam and Joint Sealing Paragraph A, revise Item 1 to read as follows: A. 1. Class A Seal: Seal all joints and seams. g. Refer to Article 3.4 Seam and Joint Sealing, delete Paragraph B. 9. SECTION Power Ventilators a. Replace in its entirety. (attached) 10. SECTION HVAC INSTRUMENTATION AND CONTROLS a. Delete Article 2.4 Operator Interface. THIS ADDENDUM CONSISTS OF SEVEN (7) PAGES, PLUS SIX (6) 8 ½ x 11 SPECIFICATION SECTION ATTACHMENTS, PLUS FIFTY THREE (53) 24 X 36 DRAWING ATTACHMENTS. END OF ADDENDUM NUMBER TWO (2) ADDENDUM NUMBER TWO (2) May 1, 2015 Page 7 of 7