CP Hearnes Center Upgrade HVAC to Various 2 nd Floor Rooms at 600 E. Stadium Blvd Columbia, MO 65211

Size: px
Start display at page:

Download "CP Hearnes Center Upgrade HVAC to Various 2 nd Floor Rooms at 600 E. Stadium Blvd Columbia, MO 65211"

Transcription

1 ADDENDUM No. 01 Date: December 14, 2017 TO CONTRACT DOCUMENTS ENTITLED: CP Hearnes Center Upgrade HVAC to Various 2 nd Floor Rooms at 600 E. Stadium Blvd Columbia, MO Advertisement Date: November 20, 2017 Prepared for: Consultants: The Curators of the University of Missouri Simon Oswald Associates, Inc dba SOA 2801 Woodard Drive, Suite 103 Columbia, MO (573) Drawings and Specifications for the above referenced project and the work covered thereby are herein modified as follows, and except as set forth herein, otherwise remain unchanged and in full force and effect: GENERAL: N/A PROJECT MANUAL: 1) Section 1.E Special Conditions: a) REVISE Item 2.e. to read as follows: Air Handling Unit 18 (AHU-18) in Mechanical 237: Contractor shall complete the AHU-18 shutdown and new premanufactured cooling coil installation during the following dates: March 23, 2018 April 1, b) REVISE Item 2.e. to add the following paragraph: The Contractor is allowed to hot tap the chilled water supply, chilled water return, hot water supply and hot water return lines for the connections set forth in the drawings. The Contractor shall make the hot taps in conformance with the MU design standards and use products manufactured for the hot tap process such as Weldolet or Threadolet as indicated in specification section Hydronic Piping. If the Contractor chooses to not use the hot tap method, the chilled water and hot water outages shall occur during the following dates: March 23, 2018 April 1, c) REVISE Item 2.f. to read as follows: Training Room: Without exception, the Contractor shall complete the scope of work in Training 282, Office 282A, Hydro 282D and Training 288 during the following dates: March 15, 2018 May 4, d) REVISE Item 9.c.4 to read as follows: Area within drip line of trees and shrubs shall be protected from work area by use of a standard 60" high woven plastic or woven wire fence mounted on standard steel posts set not more than 10 apart. The fence color shall be green. Tree protection shall be removed during work in area of protection only when necessary to perform grading and other work required by Drawings and only as authorized by Owner's Representative.

2 2) Section 1.H Alternates: a) REVISE Paragraph 2 to read as follows: The scope of work includes all labor, materials, tools and equipment required to modify the existing training room including new flooring, new casework, new plumbing fixtures and installation of owner-provided custom hydrotherapy; all as indicated on the Drawings and described in these Specifications. The scope of work includes modifications to Training 282, Office 282A, Office 282B, Hydro 282D, Mech 282D1, Training 288 and Cage 288B as shown on the following drawings sheets: A202.A, A501.A, P101, P102 and P601. Additionally, the Contractor shall reference the specifications Table of Contents for specifications impacted by the Additive Alternate No.2 Scope of Work. b) REVISE Paragraph 4 to read as follows: The scope of work includes all labor, materials, tools and equipment required to modify the existing auxiliary locker room including new flooring, new wall treatments and new plumbing fixtures; all as indicated on the Drawings and described in these Specifications. The scope of work includes modifications to Aux Locker 273, Lock. 273A and Lockers 273E as shown on the following drawings sheets: A203.A, A501.A, P101, P102 and P601. Additionally, the Contractor shall reference the specifications Table of Contents for specifications impacted by the Additive Alternate No.4 Scope of Work. 3) Universal/Hazardous Materials Removal and Disposal: Add section in its entirety. 4) Supplemental Information: Asbestos Survey Reports by University of Missouri Environmental Health and Safety dated April 26, 2017, April 28, 2017 and December 6, Add Supplemental Information in its entirety. 5) Supplemental Information: Lead Paint Survey Report by University of Missouri Environmental Health and Safety dated April 26, Add Supplemental Information in its entirety. 6) Supplemental Information: Hazardous Building Material Survey by University of Missouri Environmental Health and Safety dated December 13, Add Supplemental Information in its entirety. 7) Hydronic Piping: a) REVISE Section 1.01 to add F. Weldolets and Threadolets. b) REVISE Section 1.03 to add S. MSS-SP-97 Standard-Integrally Reinforced Forged Branch Outlet Fittings, 2001 edition. c) REVISE Part 2 to add 2.06 Weldolets and Threadolets: i) A. Provide weldolets and threadolets that comply with MSS-SP-97. ii) B. Tap side of weldolet or threadolet to be no more than 1/3 of the size of the tapped pipe. d) REVISE Section 3.02 to add M. Weldolets or threadolets may be used to make a connection to existing piping without interrupting or emptying of that section of pipe. DRAWINGS: 1) G002: ALTERNATES & USE OF PREMISES: a) REVISE the Staging Plan to reflect the expanded extents of the construction fence and the addition of fencing at the drip line of the existing trees. Refer to the attached sheet G002 which is replaced in its entirety and revisions noted with ADD 01 cloud and tag. 2) A501.A: INTERIOR ELEVATIONS AND FINISHES (ALTERNATES): a) REVISE the Room Finish Schedule Base Bid to reflect AC-1 Ceiling Material in the following rooms: 272, 272B,272C, 272D, 272E, 273B, 273C, 273D, 273F and 278. Refer to the attached sheet A501.A which is replaced in its entirety and revisions noted with ADD 01 cloud and tag. b) REVISE the Room Finish Schedule Alternates to reflect the existing flooring to remain in the following rooms: Wrestling Lockers 285 and Wrestling 285B. Refer to the attached sheet A501.A which is replaced in its entirety and revisions noted with ADD 01 cloud and tag.

3 ATTACHMENTS: 1) Universal/Hazardous Materials Removal and Disposal: Add section in its entirety. Total of Twelve (12) 8 ½ x 11 sheets. 2) Supplemental Information: Asbestos Survey Reports by University of Missouri Environmental Health and Safety: Total of Fourteen (14) 8 ½ x 11 sheets. 3) Supplemental Information: Lead Paint Survey Report by University of Missouri Environmental Health and Safety: Total of Seven (7) 8 ½ x 11 sheets. 4) Supplemental Information: Hazardous Building Material Survey by University of Missouri Environmental Health and Safety: Total of Four (4) 8 ½ x 11 sheets. 5) G002: replaced sheet in its entirety. 6) A501.A: replaced sheet in its entirety. End of Addendum #01

4 SECTION UNIVERSAL/HAZARDOUS MATERIALS REMOVAL AND DISPOSAL PART 1 - GENERAL Provisions of the General Conditions and Special Conditions are part of this Division. 1.1 WORK COVERED BY CONTRACT DOCUMENTS The Contractor shall inform him/herself of the conditions for the project, and is responsible for verifying the quantities and location of all work to be performed as outlined in this section. Failure to do so shall not relieve the Contractor of his obligation to furnish all materials and labor necessary to carry out the provisions of the Contract. The work of the Contract can be summarized as follows: The work consists of the proper removal of the following approximate quantities of hazardous materials from Hearnes Center 2 nd Floor, Alternates #1, 2, 3, 4: Demolition/Construction Waste Hazardous Waste Nine (9) door closers One mercury thermostat Universal Waste Two hundred fifty six (256) four foot fluorescent light bulbs Thirty seven (37) fluorescent light fixture ballasts Thirteen (13) fire alarm strobes Reclaim/Recycle Two (2) refrigeration units with compressors- One refrigerator One ice machine (in training room) Building Materials Painted with Regulated Heavy Metals Three thousand nine hundred (3900) square feet of glazed ceramic block from shower areas and rest rooms in the scope of the project Hearnes Center, Alternate Plans #1, 2, 3, 4, Project CP

5 SECTION UNIVERSAL/HAZARDOUS MATERIALS REMOVAL AND DISPOSAL 1.2 CODES AND REGULATIONS: All applicable codes, regulations, standards, statutes, laws, and rules have the same force and effect (and are made a part of the contract documents by reference) as if copied directly into the contract documents, or as if published copies are bound herewith. Where conflicts arise, the most stringent specification shall apply Federal and State requirements which govern universal and hazardous removal work or hauling and disposal of such waste materials include but are not limited to the following: U.S. Department of Labor, Occupational Health and Safety Administration (OSHA), 29 CFR 1910 and 29 CFR Construction Industry - 29 CFR Respiratory Protection 29 CFR Hazard Communication 29 CFR Accident Prevention Signs 29 CFR U.S. Environmental Protection Agency (EPA) CONTRACTOR'S DUTIES Except as specifically noted, provide and pay for: Labor, materials, and equipment. Tools, construction equipment, and machinery. Other facilities and services necessary for proper execution and completion of work Pay legally required sales, consumer, use, payroll, privilege and other taxes. Retail sales tax shall not be included in the bid amount Secure and pay for, as necessary for proper execution and completion of work, and as applicable at the time of bids: Permits Government Fees Licenses Except where specifically noted, provide and pay for waste disposal permits and costs Give required notices Contractor shall assume full responsibility and liability for compliance with all codes, ordinances, rules, regulations, orders and other legal Hearnes Center, Alternate Plans #1, 2, 3, 4, Project CP

6 SECTION UNIVERSAL/HAZARDOUS MATERIALS REMOVAL AND DISPOSAL requirements of Local, State, and Federal public authorities including Environmental Protection Agency (EPA) regulations, Missouri Department of Natural Resources (MDNR) and Occupational Safety and Health Administration (OSHA) which bear on performance work. Where conflicts occur between these specifications and/or the abovementioned regulations, the more stringent shall govern. The Contractor shall hold the owner and owner s air monitoring firm harmless for failure to comply with any applicable work, hauling, safety, health, or other regulations on the part of the contractor, contractor s employees, or contractor s subcontractors If the Contractor observes that any of the Contract Documents are at variance therewith in any respect, he shall promptly notify MU in writing, and any necessary changes shall be accomplished by appropriate modification. It is not the Contractor's responsibility to make certain that the Contract Documents are in accordance with applicable laws, statutes, building codes and regulations. If the Contractor performs any work knowing it to be contrary to such laws, ordinances, rules and regulations, and without such notice to MU, he shall assume full responsibility therefore and shall bear all cost attributable thereto Enforce strict discipline and good order among employees. Do not employ unfit persons or persons not skilled in assigned task Comply with all applicable federal, state, and local laws regarding job discrimination and payment of prevailing wage rates for the base bid The use of the best available technology, procedures, and methods for preparation, execution, cleanup, disposal, and safety are absolutely required. This compliance is the sole responsibility of the abatement contractor Assume responsibility for the proper and safe execution of the work COORDINATION: The hazard remediation contractor shall be responsible for the coordination of the universal/hazardous materials removal for this project. The hazard remediation contractor shall coordinate with all other on-site contractors and all subcontractors working under separate contracts so as to facilitate the general progress of the work. Each trade shall afford all trades every reasonable opportunity for the installation of their work. 1.2 STOP WORK If the Owner, or his designated representative, presents a written or verbal stop work order, immediately stop all work or that portion of the work designated. A verbal stop work order shall be confirmed by a written stop work order within 24 hours. Do not commence referenced work until authorized in writing by the Owner or his representative. 1.3 CONTRACTOR USE OF PREMISES Hearnes Center, Alternate Plans #1, 2, 3, 4, Project CP

7 SECTION UNIVERSAL/HAZARDOUS MATERIALS REMOVAL AND DISPOSAL GENERAL: During the construction period for each building, the hazard remediation contractor will have full access to Hearnes Center, (all alternate plans) for construction operations. Owner will keep the elevators operational USE OF THE SITE: Confine operations at the site to the areas permitted under the Contract. Portions of the site beyond areas on which work is indicated are not to be disturbed. Conform to site rules and regulations affecting the work while engaged in project construction Keep existing driveways and entrances serving the premises clear and available to the Owner and his employees at all times. Contractor will be allowed to use the parking lot to the north of the building for parking and/or storage of materials Do not unreasonably encumber the site with materials or equipment. Confine stockpiling of materials and location of storage to areas acceptable to Owner. If additional storage is necessary, obtain and pay for such storage off-site Do not load structure with weight that will endanger structure Assume full responsibility for protection and safekeeping of products stored on premises Move any stored products which interfere with operations of Owner or other contractors Contractor personnel shall utilize only those entrances/exits and parking lots designated by the Owner Contractor shall utilize only those areas designated by the Owner for the storage of equipment and the placement of dumpsters/transport containers Take all cautions necessary to ensure there is no universal and hazardous material contamination to those areas not included in work schedule. Should areas outside the work area become contaminated with hazardous materials, the Contractor shall immediately clean them utilizing the wet cleaning and HEPA vacuum methods specified herein. The hazard remediation contractor is responsible for the proper cleanup of all items in the work areas to maintain a clean and safe environment CONTRACTOR'S USE OF THE EXISTING BUILDING: Maintain the existing building in a safe and weather tight condition throughout the construction period. Take all precautions necessary to protect the building and its occupants during the construction period Keep areas such as walkways and stairs free from accumulation of waste material, rubbish or construction debris Smoking or open fires are prohibited within the building or on the premises. Hearnes Center, Alternate Plans #1, 2, 3, 4, Project CP

8 SECTION UNIVERSAL/HAZARDOUS MATERIALS REMOVAL AND DISPOSAL 1.4 OWNER OCCUPANCY PARTIAL OWNER OCCUPANCY: The Owner reserves the right to occupy areas of the building in which universal/hazardous waste removal has been completed, provided that such occupancy does not substantially interfere with completion of the work. The Owner also reserves the right to occupy portions of the building not involved in this Scope of Work. Such partial occupancy shall not constitute acceptance of the work or any part of the work. The Owner shall also maintain the right to access areas where no universal and hazardous waste work is being performed. 2.1 SUBMITTAL REQUIREMENTS The following will be submitted by the contractor prior to commencement of work for approval by Owner s Certified Industrial Hygienist (one copy for the Owner s Representative). The Owner s C.I.H. will return reviewed copies to contractor and Owner s Representative One copy of any Safety Data Sheets (SDS) for products to be used by the contractor in the performance of his work. Contractor will also maintain copies of SDS on site per OSHA Submit the following for all Supervisor(s) and Workers who will be on the project site prior to commencement of work: A list of project personnel and contact phone numbers Current training certificates, if applicable Physician s Statement that each person is physically fit to wear a respirator, if respirator use is required Respirator Fit Test, if respirator use is required Submit a detailed plan of the procedures proposed for use in complying with requirements of this specification. Include in the plan the layout and location of work areas, route of ingress and egress for the work areas, methods used to assure safety of building occupants and visitors, method of removal of material, and disposal container requirements for lead based paint material to be disposed Proposed disposal site for lead-based paint materials, including a disposal plan to detail type of disposal container, method of transportation to disposal site, and waste hauler Any other submittals as required by MU Upon completion of the universal/hazardous material removal, submit to the Owner s Representative, copies of hazardous materials shipping records, disposal receipts, incineration documentation, etc. for all hazardous materials removed from the project site Upon completion of the universal waste/hazardous material removal, the following information shall be submitted by the Owner s C.I.H. to the contractor: Hearnes Center, Alternate Plans #1, 2, 3, 4, Project CP

9 SECTION UNIVERSAL/HAZARDOUS MATERIALS REMOVAL AND DISPOSAL Construction and demolition waste landfill receipts, disposal receipts, truck tickets, incineration/recycling receipts and documentation Written visual certification from the Owner s Certified Industrial Hygienist that universal waste/hazardous material have been removed from the facility. 2.2 TERMINOLOGY (Definitions) APPROVED Construction and Demolition WASTE DISPOSAL SITE: A permitted solid waste landfill that is authorized by the Missouri Department of Natural Resources to receive construction and demolition wastes AUTHORIZED VISITOR: The Building Owner, the Building Owner's representative, MU personnel, or a representative of any regulatory or other agency having jurisdiction over the project BARRIER: Any surface that seals off the work area to non-authorized personnel from entering the work area BUILDING OWNER: A representative of the University of Missouri DISPOSAL CONTAINER: A properly labeled container for universal/hazardous materials. The proposed disposal container for lead-based paint will be provided to the Owner s Representative and part of the hazard remediation contractor s prework HEPA VACUUM EQUIPMENT: High efficiency particulate air filtered vacuuming equipment with a filter system capable of collecting and retaining hazardous particulates. Filters should be of 99.97% efficiency for retaining particulates greater than 0.3 microns ON-SITE REPRESENTATIVE: MU s full-time representative responsible for air monitoring and enforcement of the specifications OWNER S CERTIFIED INDUSTRIAL HYGIENIST (C.I.H.): An Industrial Hygienist, certified in comprehensive practice by the American Board of Industrial Hygiene (ABIH) HAZARDOUS MATERIAL SHIPMENT RECORD/DISPOSAL RECEIPT: The shipping document, required to be originated and signed by the waste generator, used to track and substantiate the disposition of universal/hazardous materials WET CLEANING/WIPING: The process of eliminating contamination from building surfaces and objects by using cloths, mops, or other cleaning tools which have been dampened with water, and by afterwards disposing of these cleaning tools as necessary WORK AREA: A specific isolated area in which universal/hazardous waste materials are required to be handled. The area is designated as a work area from the time that the area is secured and access restrictions are in place. The area remains designated as a work area until the time that it has been cleaned in Hearnes Center, Alternate Plans #1, 2, 3, 4, Project CP

10 SECTION UNIVERSAL/HAZARDOUS MATERIALS REMOVAL AND DISPOSAL accordance with any requirements applicable to the operations conducted. 2.3 EXISTING CONDITIONS Building Owner and Contractor shall agree on building conditions prior to commencement of work. It shall be the Contractor's responsibility to replace or repair to the Owner's satisfaction, prior to close-out of the project, all damaged items caused by the Contractor and not proven otherwise. All items damaged prior to remediation shall be noted during preconstruction walk-through. 3.1 PERSONNEL PROTECTION REQUIREMENTS Prior to commencement of work, the workers shall be instructed and shall be knowledgeable on the hazards of the universal hazardous materials involved and other environmental exposures, use and fitting of respirators, protective clothing, decontamination procedures, and all aspects of remediation work procedures; workers shall have medical examinations The Contractor acknowledges that he alone is responsible for enforcing personnel protection requirements and that these specifications provide only a minimum acceptable standard for each phase of operation If required or requested of the workers, provide workers with personally issued and marked respiratory equipment approved by NIOSH and accepted by OSHA No visitors shall be allowed in work areas, except as authorized Where required or if requested by the workers, provide workers with sufficient sets of disposable protective full-body clothing. Such clothing shall consist of full-body coveralls, footwear, and head gear, one-piece coveralls or equal. Provide eye protection and hard hats as required by applicable safety regulations. Disposable clothing shall not be allowed to accumulate and shall be disposed of as contaminated waste Provide authorized visitors with suitable protective clothing, headgear, footwear, and gloves as described above whenever they are required to enter the work area. 3.2 MATERIALS Deliver all materials in the original packages, containers, or bundles bearing the name of the manufacturer and the brand name Store all materials subject to damage off the ground, away from wet or damp surfaces, and under cover sufficient to prevent damage or contamination Damaged or deteriorating materials shall not be used and shall be removed from the premises PLASTIC SHEETING: A minimum 6-mil (or as specified) TAPE: Capable of sealing joints of adjacent sheets of polyethylene and for Hearnes Center, Alternate Plans #1, 2, 3, 4, Project CP

11 SECTION UNIVERSAL/HAZARDOUS MATERIALS REMOVAL AND DISPOSAL attachment of polyethylene sheets to finished or unfinished surfaces of dissimilar materials and capable of adhering under both dry and wet conditions, including use of amended water, duct tape, poly prep tapes or approved equal ADHESIVES: Capable of sealing joints of adjacent sheets of polyethylene and for attachment of polyethylene sheet to finished or unfinished surfaces of dissimilar materials and capable of adhering under both dry and wet conditions, including use of amended water IMPERMEABLE CONTAINERS: Suitable to receive and retain any hazardous materials until disposal by the owners rep. The containers shall be labeled as required by owner. Containers must be resistant to damage and rupture WARNING LABELS AND SIGNS: As required by owner OTHER MATERIALS: Provide all other materials, such as, but not limited to lumber, plywood, nails, and hardware, which may be required to properly prepare and complete this project. 3.3 TOOLS AND EQUIPMENT Provide suitable tools for universal/hazardous waste removal and disposal Water Sprayer: Airless or a low pressure sprayer for amended water application as applicable Air-Purifying Equipment: High Efficiency Particulate Air Filtration Systems (HEPA) shall comply with ANSI Z No air movement system or air equipment should discharge particulates outside the work area. Thus, the negative air unit shall be equipped with a three filter bank with the last being the HEPA filter capable of removing 99.97% of fibers/particulates >0.3 microns Scaffolding: As required to accomplish the specified work and meet all applicable safety regulations Vacuums: Use HEPA type from a known manufacturer Other tools and equipment as necessary. 3.4 SUPERVISION OF UNIVERSAL/HAZARDOUS Material REMOVAL The contractor shall designate a competent supervisor subject to the approval of the Owner s C.I.H. and the Owner s Representative. The supervisor shall be the Contractor s representative on the project, shall meet the requirements of all applicable regulations, and perform or meet the following minimum requirements: Be knowledgeable in all aspects of removal, cleanup and proper disposal of universal hazardous materials as listed in the Scope of Work Be onsite and supervise all removal, cleanup and disposal activities Maintain a daily log on the project documenting events, violations, Hearnes Center, Alternate Plans #1, 2, 3, 4, Project CP

12 SECTION UNIVERSAL/HAZARDOUS MATERIALS REMOVAL AND DISPOSAL problems, equipment failures, accidents, and inspections Be responsible for implementation of first aid, safety training, respiratory protection, and ensuring all workers are trained in emergency procedures Be responsible for conducting a visual inspection of the work area prior to a visual inspection by the Owner s Certified Industrial Hygienist. Inspection shall be documented. 3.5 WORKER PROTECTION / TRAINING The contractor shall be responsible for providing his employees with proper respiratory protection, respiratory training, a written respirator program, medical examinations, maintaining medical records, protective clothing and equipment to comply with OSHA requirements, if necessary All workers shall be trained in the dangers inherent in handling universal waste, and hazardous materials, in proper work procedures, and personal protective measures. 3.6 OWNER S CERTIFIED INDUSTRIAL HYGIENIST It will be the Owner s responsibility to hire a Certified Industrial Hygienist. The Certified Industrial Hygienist will also be required to perform the following duties as a minimum: Approval of the Contractor s work plan and methods of remediation to meet regulatory requirements and ensure the health and safety of University faculty, staff, and students Verify that the Contractor is satisfactorily performing the work in accordance with OSHA regulations Visual inspection of the work areas Certify in writing that the Contractor s procedures, methods, and practices were, to the best of his/her knowledge and belief, in compliance with current EPA, OSHA, State, and Local applicable regulations, that the work areas meet the requirements for a final visual inspection prior to re-occupancy, and an accounting of any known deviations. 3.7 SEPARATION OF WORK AREAS FROM NONWORK AREAS Visual separation shall be accomplished at all "see-through" locations using opaque polyethylene. This separation shall not be incorporated within the other seals involved on this project. 3.8 EMERGENCY PROTECTION PLAN / FIRE EXITS The contractor shall be responsible for developing a written Emergency Protection Plan and shall maintain this plan onsite. The plan shall include considerations of fire, explosion, toxic atmospheres, electrical hazards, slips, Hearnes Center, Alternate Plans #1, 2, 3, 4, Project CP

13 SECTION UNIVERSAL/HAZARDOUS MATERIALS REMOVAL AND DISPOSAL falls, and heat related injury. All employees shall be instructed and trained in the procedures The Emergency Protection Plan shall also include written notification of police, fire, and medical personnel of the planned remediation activities, work schedule, and layout of the work area, particularly barriers that may affect response capabilities Designate and maintain emergency and fire exits from the work area in accordance with local codes and regulations. All exits shall be clearly marked with fluorescent tape or red paint and shall be clearly visible from any part of the work area. 3.9 LOCAL AREA PROTECTION / SITE SECURITY The contractor shall secure the work areas to make sure of no inadvertent entry. Any breach to the exterior of the building shall be secured by the hazard remediation contractor. The Contractor shall be responsible for maintaining security of the remediation areas throughout the contract period The contractor shall be responsible for all areas of the building used by contractor and/or subcontractors in the performance of the work. Contractor shall exert full control over the actions of all employees and other persons with respect to the use and preservation of the existing building, except such controls as may be specifically reserved to the owner Contractor has the right to exclude from the work area all persons who have no purpose related to the work or its inspection, and shall require all persons in the work area to observe the same regulations required of Contractor s employees The contractor shall have control of site security during remediation operations in order to protect the work environment and equipment. Contractor shall have the owner s assistance in notifying building occupants of impending activity and enforcement of restricted access by owner s employees The contractor shall keep a minimum of two (2) 10lb type ABC fire extinguishers onsite. One shall be maintained outside the work area and one inside each work area. Contractor employees shall be trained in the operation of fire extinguishers The contractor shall maintain the work area free from rubbish, debris, and dirt, and keep a clean, safe working area UNIVERSAL WASTE/HAZARDOUS MATERIALS REMOVAL OPERATIONS Any light fixtures, housings, etc. concealing items considered to be universal waste/hazardous material shall be removed, containerized, labelled, and left on site for disposal by MU EHS. This does not include refrigerant or CHC/HCFC-containing equipment which are being replaced by the contractor. It does not include TCLP ceramic tile, which should be handled by the contractor. Hearnes Center, Alternate Plans #1, 2, 3, 4, Project CP

14 SECTION UNIVERSAL/HAZARDOUS MATERIALS REMOVAL AND DISPOSAL MATERIALS PAINTED WITH RCRA-Metals PAINT It is anticipated that these items will be removed as part of the demolition process and will be segregated from the remainder of the demolition debris. It is anticipated that these items will be hauled away and disposed of in a sanitary landfill approved by the State of Missouri to accept construction and demolition waste. These areas should be sealed off with polyethylene sheeting over the doors, vents, windows, or any other openings into/out of the area FLUORESCENT LIGHT TUBES may contain small amounts of Mercury. This can potentially be harmful to human health and the environment. The bulbs should be placed in fiberboard boxes provided by MU EHS to minimize breakage. MU EHS will manage disposal of this material POLYCHLORINATED BIPHENYL (PCBS) are a known carcinogenic material. Its use was discontinued January 1, Due to the age of the building, it should be assumed that any ballast can contain PCBs unless it is labeled as PCB free by the manufacturer. Due to this, any light ballasts presumed to contain PCBs should be properly disposed of. MU Environmental Health Safety will provide collection container for this purpose. Non-PCB ballasts will also be managed by MU Environmental Health Safety. Collection containers will be provided to the contractor upon their request SMOKE DETECTORS are typically ionization smoke detectors that may contain a small amount of radioactive material. MU Environmental Health and Safety will provide collection containers for this material and will also be responsible for the disposal of this material FIRE ALARMS (STROBE LIGHT) are typically not considered a universal or hazardous waste. However, for the purposes of this project, these items should be collected by the contractor and managed by MU Environmental Health and Safety. Collection containers will be provided to the contractor upon their request EXIT SIGNS AND EMERGENCY LIGHTS typically have backup batteries that may contain small amounts of lead. Some exit signs are powered by a small amount of radioactive material. Powered exit signs and emergency lights should have the battery removed and disposed of by MU Environmental Health and Safety. Non powered exit signs should be assumed to contain radioactive material and should be collected for disposal via MU Environmental Health and Safety. MU Environmental Health and Safety will provide collection containers for these items DRINKING FOUNTAINS: Some drinking fountains have reservoirs that may contain lead and a CFC/HCFC refrigerant that must be recovered. The lead Hearnes Center, Alternate Plans #1, 2, 3, 4, Project CP

15 SECTION UNIVERSAL/HAZARDOUS MATERIALS REMOVAL AND DISPOSAL reservoirs should be removed and recycled. The CFC/HCFC refrigerant must be recovered by a contractor licensed and trained in this type of work. The remainder of the unit should be managed as scrap metal DOOR CLOSURES: Some of the older door closures have oil reservoirs for lubrication. These oils may contain small amounts of PCBs. MU Environmental Health and Safety will provide a collection container for this material, and will be responsible for disposal THERMOSTATS may contain Mercury. This can potentially be harmful to human health and the environment. Mercury containing thermostats shall be disposed of as a hazardous waste. MU EHS will provide a collection container for this material, and will be responsible for disposal WINDOW AIR CONDITIONING UNITS: Where possible, these window units should be removed and stored for use elsewhere. Otherwise these units may contain CFC/HCFC refrigerants that must be recovered. CFC/HCFC refrigerants are suspected to damage the atmosphere. The CFC/HCFC refrigerant must be recovered by a contractor licensed and trained in this type of work. The remainder of the unit should be managed as scrap metal CERAMIC TILE: are made from clay bodies that contain high concentrations of silica. Respirable crystalline silica is a known human carcinogen. When ceramic tiles are cut, abraded, shattered, or crushed, hazardous silica dust can be generated. Ceramic tiles can also have high concentrations of toxic metals, in the clay body and in the glazing, and potentially be classified as Hazardous Waste. The ceramic tiles will need to be collected, containerized by the contractor, and picked up by MU EHS REESTABLISHMENT OF THE WORK AREA Reestablishment of the work area shall only occur after the Contractor has received a final visual inspection from the Owner s C.I.H. documenting that the universal/hazardous waste materials have been removed from the project site. END OF SECTION Hearnes Center, Alternate Plans #1, 2, 3, 4, Project CP

16 Asbestos survey Hearnes Center AHU #18 Base and Alt (1 to 3) Project # CP UNIVERSITY of MISSOURI ENVIRONMENTAL HEALTH AND SAFETY To: Heiddi Davis Planning Design & Construction From: Rudy Zachary EHS EHS inspected building materials within rooms on the 2 nd floor of the Hearnes Center for asbestos. The purpose is to specifically identify any Asbestos Containing Materials (ACM), which may be disturbed by upcoming renovations to existing HVAC ductwork. This inspection was performed to cover the project scope outlined by Planning Design and Construction which address not only the base bid, but also includes some information pertaining to the potential alternate renovations plans within other areas of the 2 nd floor. In accordance with state and federal law, a licensed Missouri Asbestos Building Inspector conducted the building inspection. The licensed inspector for this project was Rudy Zachary (ACM License #14679, expires 1/19/18). The inspection was conducted to satisfy the requirements of 40CFR 61, subpart M, which requires that all buildings be thoroughly inspected for asbestos before the commencement of renovation or demolition activities. As a result of this survey none of the building materials identified for renovation or removal were found to contain asbestos. Project Specifications Current Project specifications indicates the following Base Bid: HVAC Modifications to AH 18; Addition of Fan Coil Units & modification of ductwork current system is ventilation only (project purpose it to add AC to the training/locker room areas) Alternate #1: Wrestling Shower Renovations Alternate #2: Training Room Renovation o Two new floor drains and power will be required for the new hydrotherapy tubs. Alternate #3: Wrestling Locker Room Renovation 8 Research Park Dev Bldg, Columbia, MO Phone: Fax: ehs.missouri.edu Missouri s Flagship University

17 Hearnes Center AHU #18 Project # CP Field Observations Walls Walls within most renovation areas are painted cinderblock, some areas have other finish surfaces either adhered to or screwed onto the existing cinderblock. Samples were collected from; plaster finish coatings, fiberboard wall panels and fibrous membrane beneath plaster finish coats and spray on wall covering within room 286A Plaster finish coat sample room 273 Negative for Asbestos TSI debris on ceiling panel room 273 Negative for Asbestos Spray on wall covering Locker room 286A Negative for Asbestos Fiberboard wall sample room 286B Negative for Asbestos Ceilings The ceilings within renovation area are limited to either a plaster finish coat on light wt. concrete, which is present mainly within locker rooms and rest rooms or non asbestos containing white ceiling tiles suspended in a metal grid from the corrugated steed deck above. Ceilings within shower areas have plaster sections which are coming loose x48 White ceiling tile sample room 272E Negative for Asbestos Plaster finish coat sample from damaged ceiling room 288 Negative for Asbestos Plaster finish coat sample room Negative for Asbestos X24 White ceiling tile sample corridor by locker room Negative for asbestos Plumbing Plumbing lines above the suspended ceiling sections are mainly bare metal, some straight sections have fiberglass insulation present with either PVC or hard mud covered elbows. Drain lines above suspended ceilings are also bare metal. Inspection of hard mud elbows above suspended ceilings did reveal damaged mud above suspended ceiling sections within locker room 273 this insulation tested negative for asbestos. HVAC HVAC duct above suspended ceilings are bare metal with fiberglass flex duct and metal diffusers. Some sections of duct have been painted making it difficult to detect the presence of seam tape or sealants, if these materials are found during modification or renovation it is recommended that they be tested. 8 Research Park Dev Bldg, Columbia, MO Phone: Fax: ehs.missouri.edu Missouri s Flagship University

18 Hearnes Center AHU #18 Project # CP Electrical Electrical conduit above suspended ceiling sections is bare metal, electrical wiring within conduit is energized and was not inspected. Flooring Flooring within renovation areas is fairly consistent with shower and locker room areas containing ceramic tiles and office / training spaces having either carpet installed or floor tiles installed onto a concrete subfloor. The floor tiles within room 282 are damaged with some sections coming loose these tiles are adhered with blonde adhesive and are negative for asbestos. Other areas also contain 12 in floor tile, the tile within most of these areas do not show signs of failing to adhere to the subfloor with the exception to training room #282 (area contains damaged 12 white speckled floor tiles on blonde adhesive). Analysis Results Sample Number Description and Location Analysis results Plaster finish coat sample room 273 Negative for Asbestos TSI Debris on Ceiling Room 273 Negative for Asbestos x48 Ceiling Tile Sample White Room 272E Negative for Asbestos X12 white floor tile on blonde adhesive room 282 Awaiting Analysis Results Plaster finish coat sample ceiling room 288 Negative for Asbestos Plaster finish coat sample room Negative for Asbestos X24" ceiling tile sample corridor by Negative for Asbestos Black cove base sample corridor by Negative for Asbestos Spray on wall cover locker room 286A (demo wall section) Negative for Asbestos Fiberboard wall sample 286B Negative for Asbestos 8 Research Park Dev Bldg, Columbia, MO Phone: Fax: ehs.missouri.edu Missouri s Flagship University

19 Asbestos survey Addendum Hearnes Center AHU #18 Base and Alt (1 to 3) Project # CP To: Heiddi Davis Planning Design & Construction From: Rudy Zachary EHS UNIVERSITY of MISSOURI ENVIRONMENTAL HEALTH AND SAFETY This is an addendum to the report sent on for the Hearnes Center AHU #18 Base and Alternate (1 to 3) for Project # CP The report includes floor tile analysis results for room 282 which was not included in the initial report. This inspection was performed to cover the project scope outlined by Planning Design and Construction which address not only the base bid, but also includes some information pertaining to the potential alternate renovations plans within other areas of the 2 nd floor. In accordance with state and federal law, a licensed Missouri Asbestos Building Inspector conducted the building inspection. The licensed inspector for this project was Rudy Zachary (ACM License #14679, expires 1/19/18). The inspection was conducted to satisfy the requirements of 40CFR 61, subpart M, which requires that all buildings be thoroughly inspected for asbestos before the commencement of renovation or demolition activities. As a result of this survey none of the building materials identified for renovation or removal were found to contain asbestos. Project Specifications Current Project specifications indicates the following Base Bid: HVAC Modifications to AH 18; Addition of Fan Coil Units & modification of ductwork current system is ventilation only (project purpose it to add AC to the training/locker room areas) Alternate #1: Wrestling Shower Renovations Alternate #2: Training Room Renovation o Two new floor drains and power will be required for the new hydrotherapy tubs. 8 Research Park Dev Bldg, Columbia, MO Phone: Fax: ehs.missouri.edu Missouri s Flagship University

20 Alternate #3: Wrestling Locker Room Renovation Hearnes Center AHU #18 Project # CP Field Observations Walls Walls within most renovation areas are painted cinderblock, some areas have other finish surfaces either adhered to or screwed onto the existing cinderblock. Samples were collected from; plaster finish coatings, fiberboard wall panels and fibrous membrane beneath plaster finish coats and spray on wall covering within room 286A Plaster finish coat sample room 273 Negative for Asbestos TSI debris on ceiling panel room 273 Negative for Asbestos Spray on wall covering Locker room 286A Negative for Asbestos Fiberboard wall sample room 286B Negative for Asbestos Ceilings The ceilings within renovation area are limited to either a plaster finish coat on light wt. concrete, which is present mainly within locker rooms and rest rooms or non asbestos containing white ceiling tiles suspended in a metal grid from the corrugated steed deck above. Ceilings within shower areas have plaster sections which are coming loose x48 White ceiling tile sample room 272E Negative for Asbestos Plaster finish coat sample from damaged ceiling room 288 Negative for Asbestos Plaster finish coat sample room Negative for Asbestos X24 White ceiling tile sample corridor by locker room Negative for asbestos Plumbing Plumbing lines above the suspended ceiling sections are mainly bare metal, some straight sections have fiberglass insulation present with either PVC or hard mud covered elbows. Drain lines above suspended ceilings are also bare metal. Inspection of hard mud elbows above suspended ceilings did reveal damaged mud above suspended ceiling sections within locker room 273 this insulation tested negative for asbestos. HVAC HVAC duct above suspended ceilings are bare metal with fiberglass flex duct and metal diffusers. Some sections of duct have been painted making it difficult to detect the presence of seam tape or sealants, if these materials are found during modification or renovation it is recommended that they be tested. 8 Research Park Dev Bldg, Columbia, MO Phone: Fax: ehs.missouri.edu Missouri s Flagship University

21 Hearnes Center AHU #18 Project # CP Electrical Electrical conduit above suspended ceiling sections is bare metal, electrical wiring within conduit is energized and was not inspected. Flooring Flooring within renovation areas is fairly consistent with shower and locker room areas containing ceramic tiles and office / training spaces having either carpet installed or floor tiles installed onto a concrete subfloor. The floor tiles within room 282 are damaged with some sections coming loose these tiles are adhered with blonde adhesive and are negative for asbestos. Other areas also contain 12 in floor tile, the tile within most of these areas do not show signs of failing to adhere to the subfloor with the exception to training room #282 (area contains damaged 12 white speckled floor tiles on blonde adhesive). Project specifications did not indicate any flooring changes within the east locker room area (coach locker room) the black 12 X12 floor tile located within room 272C was not tested. Analysis Results Sample Number Description and Location Analysis results Plaster finish coat sample room 273 Negative for Asbestos TSI Debris on Ceiling Room 273 Negative for Asbestos x48 Ceiling Tile Sample White Room 272E Negative for Asbestos X12 white floor tile on blonde adhesive room 282 Negative for Asbestos Plaster finish coat sample ceiling room 288 Negative for Asbestos Plaster finish coat sample room Negative for Asbestos X24" ceiling tile sample corridor by Negative for Asbestos Black cove base sample corridor by Negative for Asbestos Spray on wall cover locker room 286A (demo wall section) Negative for Asbestos Fiberboard wall sample 286B Negative for Asbestos 8 Research Park Dev Bldg, Columbia, MO Phone: Fax: ehs.missouri.edu Missouri s Flagship University

22 HAZARDOUS BUILDING MATERIAL SURVEY PROJECT CP HEARNES CENTER ROOMS 272,272B, C, D, E, 273, 273B, D 12/06/2017 TO: Heiddi Davis Planning, Design, & Construction FROM: Pete Kohler Environmental Health & Safety MU EHS has completed a survey of specific rooms on 2 nd floor of Hearnes Center, identified as Alternate Area #4 on floor plans for the project. The area is the southeast corner of locker rooms off the corridor which runs along the north side of the indoor track. These rooms are 272, 272B, C, D, and E, 273, 273B, and D. The survey was made to identify asbestos-containing material (ACM) which will be disturbed by the upcoming renovation; to identify lead-based paint in the project area that might represent a potential worker safety hazard and/or might require special handling and waste disposal prior to the demolition or renovation; and to identify hazardous waste that will require special handling in the project scope. A survey of RCRA metals was made on finished surfaces of the locker rooms to determine if building materials may be disposed of as clean fill. ASBESTOS SURVEY The inspection was conducted to satisfy the requirements of 40CFR 61, subpart M, which stipulates that all buildings be thoroughly inspected for asbestos before the commencement of renovation or demolition activities. An initial inspection was conducted by Rudy Zachary (Missouri Asbestos Inspector #14679, expires 01/19/2018), for part of this space and an adjacent area in Hearnes. That report was written in April, This asbestos inspection was conducted by Rudy Zachary and Pete Kohler (Missouri Asbestos Inspector #10883, expires 01/19/2018). The survey was conducted in November, 2017 and the report was completed on December 6, 2017.

23 FIELD OBSERVATIONS Flooring in these rooms is carpet on top of concrete, except in 272D, and in the showers and rest rooms. 272D has carpet laid on 12 black floor tile, laid with blond mastic. The floor tile and mastic were sampled and analyzed. They do not contain asbestos. The showers and rest rooms have ceramic tile floors which is not suspect material. Cove base was suspect, and we collected a sample and had it analyzed. It does not contain asbestos. Cove base mastic is negative for asbestos. There are rooms in the area which have bare concrete flooring, and these were not sampled. The ceilings are plaster, which was sampled in the earlier survey, and found negative for asbestos; or drop ceilings with 2x4 acoustic ceiling tiles. The 2x4 drop ceiling tiles were found not to contain asbestos. Walls in the area are painted cinder block, or plaster. Plaster walls were sampled for the original survey, and no asbestos was found. Cinder block is not suspect material. Above the drop ceilings, the HVAC is bare metal and fiberglass flex-duct. Plumbing lines are generally fiberglass, with elbows often clad in PVC. Above an access panel in Room 273, above a toilet stall, there is debris from a hard mud elbow. This material was sampled for the earlier survey, and analysis was negative for asbestos. No other suspect material was identified. As a result of the original surveys and additional sampling for this survey, no asbestos was identified in the scope of the project.

24 ASBESTOS SAMPLING TABLES HISTORICAL DATA- SURVEY 4/28/17 Sample Number Description and Location Plaster finish coat sample room TSI Debris on Ceiling Room x48 Ceiling Tile Sample White Room 272E X12 white floor tile on blond adhesive room Plaster finish coat sample ceiling room Plaster finish coat sample room X24" ceiling tile sample corridor by Black cove base sample corridor by Spray on wall cover locker room 286A (demo wall section) Fiberboard wall sample 286B Analysis results Negative for Asbestos Negative for Asbestos Negative for Asbestos Negative for Asbestos Negative for Asbestos Negative for Asbestos Negative for Asbestos Negative for Asbestos Negative for Asbestos Negative for Asbestos

25 ADDITIONAL SAMPLING SAMPLE ID LOCATION/DESCRIPTION ANALYSIS Hearnes Center Room 272E, 2x4 drop ceiling tile 35% mineral wool, 26% cellulose, 26% perlite, 13% non-fibrous C, 12 black floor tile 100% matrix material A Blond mastic from tile 100% matrix material above C, black cove base 100% non-fibrous A Mastic from cove base 100% non-fibrous C, 2x4 drop ceiling tile 36% mineral wool, 27% cellulose, 27% perlite, 10% non-fibrous ASBESTOS SUMMARY: No asbestos-containing materials were identified in the scope of the project. LEAD SURVEY The lead survey was conducted on 11/20/17 by Rudy Zachary (Missouri Lead Inspector #3103, expires 12/20/18) and Pete Kohler (Missouri Lead Inspector #00783, expires 5/17/19). The EPA and the U.S. Department of Housing and Urban Development (HUD) consider lead-based paint as containing a lead concentration equal to or greater than 1.0 milligram per square centimeter (mg/cm²) or 0.5% lead by weight, as defined by Title X of the 1992 Housing and Community Development Act. The US Consumer Product Safety Commission considers paint with up to 600 ppm of lead to be Lead Free. Finished surfaces were tested for lead, using a Niton XL2 analyzer. The XL2 was checked before the survey and found to be in calibration. As a result of the survey, no finished surfaces were identified having lead in concentrations which reach the HUD standard.

26 Some of the paint (gold paint on tiger decals fixed to doors) was found to have concentrations approaching the HUD standard. OSHA has found that certain work, including aggressive disturbance of the painted surface, may result in lead levels exceeding the Action Level or the Permissible Exposure Limit (PEL)- even when the concentration is below 1 mg/cm2. Finishes that were checked for RCRA metals were not surveyed for lead, as lead is one of the metals RCRA includes. LEAD SAMPLING TABLE LOCATION/DESCRIPTION LEAD READINGS (mg/cm2) Hearnes Room 273, north walls, white 0.01, 0.01 cinder block North wall, tan cinder block 0.01 East wall, tan cinder block 0.01 South wall, tan cinder block 0.01 West wall, white cinder block 0.01 Ceiling, white plaster 0.01, , black metal door frame 0.01, , tan metal door 0.01, , tan cinder block walls 0.01, 0.01, 0.01, , black metal door frame , black metal door 0.05, , tan metal door 0.05, , rest room area, white plaster ceiling 0.01, 0.01 Old shower area (not used), white plaster 0.01 ceiling 273D, yellow cinder block walls 0.01, 0.01, 0.03, D, black metal door frame 0.01, D, black metal door 0.01, B, yellow cinder block walls 0.04, 0.01, 0.01, 0.01

27 Corridor between 273B and 273D, yellow 0.01, 0.01, 0.01, 0.01 cinder block walls Corridor between 273B and 273D, black 0.01, 0.13 metal door frame Same location, black metal door 0.01, 0.01 Same door, tiger decal on black door 0.94, 0.35, 0.99, 0.90 GOLD PAINT on decal Corridor at SW corner of project, just 0.01, 0.01, 0.01, 0.01 inside exit door, tan cinder block walls LEAD SUMMARY: None of the surfaces tested have lead concentrations which exceed HUD standards for lead-based paint. RCRA METALS TESTING The Niton XL2 Analyzer was used on finished surfaces, to check for RCRA metals, to determine if the construction materials can be used as clean fill. MO DNR publishes Using Painted Block and Brick as Clean Fill. The publication states, heavy metals of concern are the eight metals.commonly referred to as the Resource Conservation and Recovery Act (RCRA) metals. They are: arsenic, cadmium, lead, mercury, selenium, barium, chromium, and silver. listed: Maximum concentrations allowed for clean fill are equal to or below the levels Silver (Ag): 99 parts per million (ppm); Arsenic (As): 87 ppm; Barium (Ba): 15,200 ppm; Cadmium (Cd): 429 ppm; Chromium (Cr): 3,285 ppm; Lead (Pb): 4,999 *ppm Mercury (Hg): 100 ppm; Selenium (Se): 50 ppm.

28 Our survey found the glazed block of the shower and rest room areas is above these limits for several metals. Painted cinder block walls were found not to exceed the levels for clean fill by MO DNR. The glazed ceramic blocks may not be used as clean fill. RCRA SAMPLING TABLE RCRA METAL TEST DATA Results are in parts per million (PPM) Test Location Information Test Number Ag As Ba Cd Cr Hg Pb Se Test Result Interior (I) or Room Wall Component Substrate Color Exterior (E) Number <LOD <LOD <LOD <LOD <LOD ABOVE CLEAN FILL STANDARDS OF K 2176 <LOD MO DNR <LOD <LOD 353 <LOD <LOD <LOD <LOD <LOD <LOD <LOD 361 <LOD <LOD <LOD <LOD <LOD <LOD <LOD 727 <LOD <LOD <LOD <LOD <LOD <LOD <LOD 258 <LOD <LOD <LOD <LOD <LOD ABOVE CLEAN FILL STANDARDS OF K MO DNR <LOD <LOD 518 <LOD <LOD <LOD <LOD <LOD I 272C EAST CINDER BLOCK GLAZED I 272C SOUTH CERAMIC BLOCK I 272B NORTH CINDER BLOCK I 272B NORTH CINDER BLOCK I 272D NORTH CINDER BLOCK I 272D SOUTH CINDER BLOCK GLAZED I 273 WEST CERAMIC BLOCK I CORRI CINDER WEST DOR BLOCK YELLOW CREAM WHITE GOLD TAN TEXTURE BLACK CREAM YELLOW 9

29 In addition to the glazed ceramic block above, the following items must be removed from the area, before demolition: Eighty eight (88) fluorescent bulbs Thirty seven (37) fluorescent light fixture ballasts Nine (9) door closers Ten (10) fire alarm strobes

30 Lead Paint Survey Hearnes Center AHU #18 Base and Alt (1 to 3) Project # CP To: Heiddi Davis Planning Design & Construction From: Rudy Zachary EHS UNIVERSITY of MISSOURI ENVIRONMENTAL HEALTH AND SAFETY A Niton XF2 was used to check painted surfaces for lead within specific rooms on the 2 nd of the Hearnes Center, the areas tested were either a site for future renovation or are within the areas that the augmentation to existing HVAC will take place. The Niton was checked before the survey and found to be in calibration. HUD has established a lead standard of 1.0 mg/cm2 for child occupied facilities. This does not relate directly to this project, but is a useful guideline in evaluating lead in painted and varnished surfaces. OSHA has found that certain work, including aggressive disturbance of the painted surface, may result in lead levels exceeding the Action Level or Permissible Exposure Limit (PEL) even when the concentration of lead is below 1 mg/cm2. Lead Summary: None of the painted surfaces tested within the project area contain lead in concentrations that are in excess of the HUD standard of 1.0 mg/cm2; Location and Description 272C Locker room Readings (mg/cm2) Walls are painted cinderblock, lt. tan paint (damaged) North wall 0.06, 0.13 East wall 0.01 South wall 0.06, 0.06 West wall (exterior of rest room) 0.01 Locker room 273 Painted Plaster Ceiling sections white paint Ceiling section south west corner of rest room 0.05 Ceiling section shower Research Park Dev Bldg, Columbia, MO Phone: Fax: ehs.missouri.edu Missouri s Flagship University

31 UNIVERSITY of MISSOURI ENVIRONMENTAL HEALTH AND SAFETY Training room 282 & 282(A C) Room 282 Walls are cinderblock with white paint North wall 0.04, 0.04 East wall 0.01, 0.01, 0.05 South wall 0.09, 0.01 West wall 0.07, 0.57 Metal window frame office 282A 0.35, 0.30, 0.32 Ceiling sections 0.01, 0.01 Room 282A North wall 0.01 South wall 0.03, 0.05 West wall 0.03 Entrance door 0.01, 0.01 Door frame 0.07, 0.05 Room 282B North wall 0.04 West wall 0.68 South wall 0.04 East wall 0.06 Room 282C North wall 0.06 East wall 0.01 South wall 0.04 West wall Research Park Dev Bldg, Columbia, MO Phone: Fax: ehs.missouri.edu Missouri s Flagship University

32 UNIVERSITY of MISSOURI ENVIRONMENTAL HEALTH AND SAFETY Office 282D Storage 282D1 Room 285 (Paint survey limited to wall sections identified for future door installations) Room A (Paint survey limited to wall sections identified for future door installations) Walls are cinderblock with white paint North wall 0.01 East wall 0.02 South wall 0.02 West wall 0.05 Ceiling sections 0.02 Walls are cinderblock with tan paint North wall 0.04 East wall 0.05 South wall 0.01 West wall 0.02 Ceiling section 0.03 Entrance door and Frame Door 0.20, 0.27 Frame 0.03, 0.31 North wall white paint 0.01, 0.02, 0.03 West wall gold paint 0.01 Walls are cinderblock white paint North wall 0.05, 0.01, 0.34 South wall 0.03, 0.05, 0.08 West wall 0.05 East wall (spay on wall covering brown on lt tan paint) Research Park Dev Bldg, Columbia, MO Phone: Fax: ehs.missouri.edu Missouri s Flagship University

33 UNIVERSITY of MISSOURI ENVIRONMENTAL HEALTH AND SAFETY 286A1 South locker room section North wall 0.09 East wall 0.02 South wall 0.01 West wall 0.06 Center locker room section North wall 0.01 East wall 0.01 South wall 0.02 West wall 0.01 Metal lockers 0.01, 0.05 Painted wood bench black paint 0.28, 0.05 Ceiling painted plaster finish coat 0.04 North rest room section North wall 0.01 West wall 0.01 South wall 0.01 West wall 0.01 Ceiling painted plaster finish coat B Door entrance to office 264 (area to be filled in) Wood door trim black paint 0.22, 0.27 Wood door gold paint 0.05, 0.29 Painted cinderblock section next to entrance door white paint F South wall section painted cinderblock (potential door installation area) 0.01 Walls are painted cinderblock with bathroom sections having ceramic brick installed onto the cinderblock walls. North wall 0.01, 0.01, 0.01 East wall 0.01 South wall 0.08, 0.18 West wall 0.05 Ceiling 0.01 Ceiling sections shower areas 0.01, Research Park Dev Bldg, Columbia, MO Phone: Fax: ehs.missouri.edu Missouri s Flagship University

34

35

36

37 HAZARDOUS BUILDING MATERIAL SURVEY PROJECT CP HEARNES CENTER ALTERNATES 1, 2, 3, AND 4 12/13/2017 TO: Heiddi Davis Planning, Design, and Construction FROM: Pete Kohler Environmental Health and Safety MU EHS has completed additional sampling in specific areas of 2 nd floor in Hearnes Center, as an addendum to a survey and spec sent 12/06/17. This survey was made to determine if building materials in this area may be used as clean fill, if the area is to be demolished. Also, hazardous building material which must be removed before demolition, was identified. We used a Niton XL2 to analyze finished surfaces in locker rooms and shower/rest rooms on the west end of the hallway running along the north edge of the indoor track in Hearnes. The areas we checked are alternates #1, 2, and 3 from the original survey request. As a result of the survey, material was identified which may not be used as clean fill. Glazed, ceramic block exceeds the MO DNR standards for several RCRA metals. The walls in the areas we tested are similar to the walls in Alternate #4: painted cinderblock or glazed ceramic block. The materials we tested are representative of the rooms throughout the hallway. The glazed ceramic blocks may not be used for clean fill.

38 In addition to the material above, the following items must be removed before demolition: One hundred sixty eight (168) fluorescent bulbs Sixty seven (67) ballasts from fluorescent fixtures Three (3) emergency fire strobes Two refrigeration units ( one refrigerator and one ice machine in treatment room) One mercury thermostat

39 RCRA TESTING LOCATIONS CP170201, HEARNES 2ND FLOOR

40 Test Number RCRA METAL TEST DATA Results are in parts per million (PPM) Ag As Ba Cd Cr Hg Pb Se Analysis Results Interior (I) or Exterior (E) <LOD <LOD 5374 <LOD <LOD <LOD 26 <LOD <LOD <LOD 5500 <LOD <LOD <LOD 48 <LOD <LOD <LOD 4287 <LOD <LOD <LOD 27 <LOD <LOD <LOD <LOD <LOD 6176 <LOD <LOD <LOD <Lod <LOD <LOD 2329 <LOD Room Wall Component Substrate Color Number Below LOD on all RCRA metals Interior 282 South Wall CinderblocK White paint Below LOD on all RCRA metals Interior 282 East Wall CinderblocK White paint Below LOD on all RCRA metals Interior 282 North Wall CinderblocK White paint Above RCRA levels for; Ag, As, Ba, Hg & Cd Interior 282 Center of room Wall Glazed Ceramic Block Below LOD on all RCRA metals Interior 282 West Wall CinderblocK White paint Above RCRA levels for; Ag, As, Ba,Cd, Cr Hg & Cd Interior 282D West Wall Glazed Ceramic Block <LOD <LOD <LOD 23 <LOD Below LOD on all RCRA metals Interior 282D East Wall CinderblocK Gold <LOD <LOD 941 <LOD <LOD <LOD <lod <LOD <LOD <LOD 8238 <LOD <LOD <LOD 52 <LOD <LOD <LOD 5102 <LOD <LOD <LOD 61 <LOD Test Location Information Below LOD on all RCRA metals Interior 282 West Ceiling plaster white paint Below LOD on all RCRA metals Interior 288 North Wall CinderblocK White paint Below LOD on all RCRA metals Interior 288 East Wall CinderblocK White paint White white

41 UP DN ST ATE O F M ISSOUR WILLIAM HOWARD OSWALD NUMBER A-5419 REGIST ERED ARCH ITECT I UP 11/20/2017 William H. Oswald - Architect License No. A-5419 NOTE: FLOOR PLAN AREAS SHADED IN GRAY ARE OUT OF SCOPE ADD 01 Architecture Interior Design 5'-0" MIN CLEAR AT SIDEWALK LOT K CONTRACTOR ACCESS INTO BUILDING FENCING AROUND TREE DRIP LINE AS INDICATED IN SPECIAL CONDITIONS Planning Sustainability 2801 Woodard Drive, Suite 103 Columbia, MO MECHANICAL 237 CONTRACTOR PARKING STAGING PLAN 1" = 80'-0" CONSTRUCTION FENCE AROUND STAGING AREA AS INDICATED IN SPECIAL CONDITIONS. LOCATE GATE WITH OWNER'S REP. Missouri Certificate of Authority Number: MEP ENGINEER: WRESTLING LOCKERS 286F TRAINING 288 CONSTRUCTION SCHEDULING NOTES: 3100 BROWN STATION ROAD SUITE C COLUMBIA, MO PHONE: (573) FAX: (573) Midwest Engineering & Design Missouri State Certificate of Authority # WRESTLING SHOWERS 286A1 WRESTLING COACHES 286A WRESTLING LOCKERS USE OF PREMISES - LEVEL 02 G002 1/16" = 1'-0" TRAINING 282 MAINTAIN CLEAR EGRESS PATH AT ALL TIMES DEBRIS REMOVAL PATH AUX LOCKER ROOM 273 MECHANICAL 237 TO CONTRACTOR PROVIDED DUMPSTER - CONFIRM DUMPSTER LOCATION WITH OWNER'S REP. 1. REFER TO SPECIFICATIONS FOR SPECIAL SCHEDULING REQUIREMENTS LIFE SAFETY GENERAL NOTES 1. EGRESS, EXCEPT AS SHOWN ON DRAWINGS, ALL EGRESS CORRIDORS AND STAIRS SHALL BE KEPT CLEAR WITH NO OBSTRUCTIONS. 2. FIRE ALARM AND SMOKE DETECTION SYSTEMS SHALL BE LEFT IN SERVICE WHENEVER FEASIBLE, ALL FUNCTIONALITY SHALL BE RESTORED AT THE END OF EACH SHIFT, EXCEPT DURING ACTUAL FIRE ALARM DEVICE MOVEMENT. ALL FIRE ALARM OUTAGES SHALL BE APPROVED IN ADVANCE BY OWNER'S REPRESENTATIVE. OUTAGES DUE TO FIRE ALARM WORK SHALL BE MINIMIZED. 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE KEPT WITHIN THE CONSTRUCTION AREA. CONSTRUCTION STAFF SHALL BE TRAINED IN PROPER USE OF PORTABLE FIRE FIGHTING EQUIPMENT. 4. STORAGE OF COMBUSTIBLE MATERIALS WITHIN THE PROJECT SHALL BE MINIMIZED AND DEBRIS SHALL BE REMOVED DAILY. 5. USE OF ALL TOBACCO PRODUCTS IS PROHIBITED ON THE OWNER'S PREMISES. STAGING & USE OF PREMISES NOTES 1. PROTECT ALL EXISTING SURFACES AND GOODS FROM DAMAGE. CONTRACTOR WILL BE RESPONSIBLE FOR THE REPAIR & REPLACEMENT OF ANY DAMAGED SURFACES OR GOODS. MU PROJECT #CP UNIVERSITY OF MISSOURI - HEARNES CENTER - UPGRADE HVAC TO VARIOUS 2ND FLOOR ROOMS 600 E STADIUM BLVD, WRESTLING SHOWERS 286A1 ALTERNATE #1 WRESTLING COACHES 286A WRESTLING LOCKERS 285 ALTERNATE #3 WRESTLING LOCKERS 01 ALTERNATES OVERALL FLOOR PLAN - LEVEL 02 G002 1/16" = 1'-0" 286F ALTERNATE #2 TRAINING 282 TRAINING 288 AUX LOCKER ROOM 273 ALTERNATE #4 2. IF ALLOWED BY OWNER, CONSTRUCTION TRAILER STORAGE LOCATION SHALL BE APPROVED BY THE OWNER'S REPRESENTATIVE. 3. DUMPSTER LOCATION & RECYCLING BINS TO BE APPROVED BY THE OWNER'S REPRESENTATIVE. 4. CONTRACTOR TO COORDINATE WITH OWNER'S REPRESENTATIVE BEFORE MOVING ANY EQUIPMENT CURRENTLY IN THE WAY. EQUIPMENT WILL BE MOVED BY OWNER. 5. PROTECTIVE COVER (6 MIL POLY) SHALL BE INSTALLED PRIOR TO THE START OF CONSTRUCTION IN THE SPECIFIC SPACE AND SHALL REMAIN THROUGHOUT THE DURATION OF CONSTRUCTION ACTIVITIES. CONTRACTOR TO REMOVE PROTECTIVE COVERING UPON COMPLETION AND PERFORM GENERAL CLEANUP OF SPACE. 6. CONTRACTOR TO REPAIR AND/OR PATCH EXISTING SURFACES AFFECTED DURING DEMOLITION AND NEW CONSTRUCTION TO MATCH EXISTING ADJACENT SURFACES FOR A FINISHED INSTALLATION. ISSUE FOR BID DOCUMENTS November 20, 2017 REVISION DATE ADD 01 12/14/2017 ALTERNATES & USE OF PREMISES SHEET 2 OF 29 G002 If you must print this drawing, please recycle