1 THERMAL INSULATION Axis Architecture + Interiors SECTION SECTION THERMAL INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Foam-plastic board insulation. 2. Glass-fiber blanket insulation. 3. Vapor retarders. B. Related Sections: 1. Division 07 Section "Water-Drainage Exterior Insulation and Finish System (EIFS)" for insulation specified as part of these systems. 2. Division 07 Section(s) " and "Thermoplastic Polyolefin (TPO) Roofing" for insulation specified as part of roofing construction. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product indicated. 1.4 INFORMATIONAL SUBMITTALS A. Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, for each product. B. Research/Evaluation Reports: For foam-plastic insulation, from ICC-ES. 1.5 QUALITY ASSURANCE A. Surface-Burning Characteristics: As determined by testing identical products according to ASTM E 84 by a qualified testing agency. Identify products with appropriate markings of applicable testing agency. 1.6 DELIVERY, STORAGE, AND HANDLING A. Protect insulation materials from physical damage and from deterioration due to moisture, soiling, and other sources. Store inside and in a dry location. Comply with manufacturer's written instructions for handling, storing, and protecting during installation. B. Protect foam-plastic board insulation as follows: 1. Do not expose to sunlight except to necessary extent for period of installation and concealment. 2. Protect against ignition at all times. Do not deliver foam-plastic board materials to Project site before installation time. 3. Quickly complete installation and concealment of foam-plastic board insulation in each area of construction. THERMAL INSULATION

2 THERMAL INSULATION Axis Architecture + Interiors SECTION PART 2 - PRODUCTS 2.1 FOAM-PLASTIC BOARD INSULATION A. Extruded-Polystyrene Board Insulation: ASTM C 578, of type and minimum compressive strength indicated below, with maximum flame-spread and smoke-developed indexes of 75 and 450, respectively, per ASTM E Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. DiversiFoam Products. b. Dow Chemical Company (The). c. Owens Corning. d. Pactiv Building Products. 2. Type IV, 25 psi. 3. Type VI, 40 psi. 4. Provide channeled design at locations where board insulation is installed directly to foundation walls and directly behind siding. B. Adhesive for Bonding Insulation: Product with demonstrated capability to bond insulation securely to substrates without damaging insulation and substrates. 2.2 GLASS-FIBER BLANKET INSULATION A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. CertainTeed Corporation. 2. Guardian Building Products, Inc. 3. Johns Manville. 4. Knauf Insulation. 5. Owens Corning. B. Unfaced, Glass-Fiber Blanket Insulation: ASTM C 665, Type I; with maximum flame-spread and smoke-developed indexes of 25 and 50, respectively, per ASTM E 84; passing ASTM E 136 for combustion characteristics. C. Polypropylene-Scrim-Kraft-Faced, Glass-Fiber Blanket Insulation: ASTM C 665, Type II (nonreflective faced), Class A (faced surface with a flame-spread index of 25 or less); Category 1 (membrane is a vapor barrier). D. Kraft-Faced, Glass-Fiber Blanket Insulation: ASTM C 665, Type II (non-reflective faced), Class C (faced surface not rated for flame propagation); Category 1 (membrane is a vapor barrier). E. Eave Ventilation Troughs: Preformed, rigid fiberboard or plastic sheets designed and sized to fit between roof framing members and to provide cross ventilation between insulated attic spaces and vented eaves. F. Sustainability Requirements: Provide glass-fiber blanket insulation as follows: 1. Free of Formaldehyde: Insulation manufactured with 100 percent acrylic binders and no formaldehyde. 2. Low Emitting: Insulation tested according to ASTM D 5116 and shown to emit less than 0.05-ppm formaldehyde. THERMAL INSULATION

3 THERMAL INSULATION Axis Architecture + Interiors SECTION VAPOR RETARDERS A. Polyethylene Vapor Retarders: ASTM D 4397, 6 mils thick, with maximum permeance rating of 0.13 perm. B. Reinforced-Polyethylene Vapor Retarders: Two outer layers of polyethylene film laminated to an inner reinforcing layer consisting of either nylon cord or polyester scrim and weighing not less than (25 lb/1000 sq. ft.), with maximum permeance rating of ( perm). C. Vapor-Retarder Tape: Pressure-sensitive tape of type recommended by vapor-retarder manufacturer for sealing joints and penetrations in vapor retarder. D. Vapor-Retarder Fasteners: Pancake-head, self-tapping steel drill screws; with fender washers. E. Single-Component Nonsag Urethane Sealant: ASTM C 920, Type I, Grade NS, Class 25, Use NT related to exposure, and Use O related to vapor-barrier-related substrates. F. Adhesive for Vapor Retarders: Product recommended by vapor-retarder manufacturer and has demonstrated capability to bond vapor retarders securely to substrates indicated. PART 3 - EXECUTION 3.1 PREPARATION A. Clean substrates of substances that are harmful to insulation or vapor retarders, including removing projections capable of puncturing vapor retarders, or that interfere with insulation attachment. 3.2 INSTALLATION, GENERAL A. Comply with insulation manufacturer's written instructions applicable to products and applications indicated. B. Install insulation that is undamaged, dry, and unsoiled and that has not been left exposed to ice, rain, or snow at any time. C. Extend insulation to envelop entire area to be insulated. Cut and fit tightly around obstructions and fill voids with insulation. Remove projections that interfere with placement. D. Provide sizes to fit applications indicated and selected from manufacturer's standard thicknesses, widths, and lengths. Apply single layer of insulation units to produce thickness indicated unless multiple layers are otherwise shown or required to make up total thickness. 3.3 INSTALLATION OF BELOW-GRADE INSULATION A. On vertical surfaces, set insulation units using manufacturer's recommended adhesive loosely laid according to manufacturer's written instructions. 1. If not otherwise indicated, extend insulation a minimum of 36 inches below exterior grade line. B. On horizontal surfaces, loosely lay insulation units according to manufacturer's written instructions. Stagger end joints and tightly abut insulation units. 1. If not otherwise indicated, extend insulation a minimum of 36 inches in from exterior walls. 3.4 INSTALLATION OF CAVITY-WALL INSULATION A. Foam-Plastic Board Insulation: Install pads of adhesive spaced approximately 24 inches o.c. both ways on inside face, and as recommended by manufacturer. Fit courses of insulation THERMAL INSULATION

4 THERMAL INSULATION Axis Architecture + Interiors SECTION between wall ties and other obstructions, with edges butted tightly in both directions. Press units firmly against inside substrates. 1. Supplement adhesive attachment of insulation by securing boards with two-piece wall ties designed for this purpose and specified in Division 04 Section "Unit Masonry." 3.5 INSTALLATION OF INSULATION FOR FRAMED CONSTRUCTION A. Apply insulation units to substrates by method indicated, complying with manufacturer's written instructions. If no specific method is indicated, bond units to substrate with adhesive or use mechanical anchorage to provide permanent placement and support of units. B. Glass-Fiber Blanket Insulation: Install in cavities formed by framing members according to the following requirements: 1. Use insulation widths and lengths that fill the cavities formed by framing members. If more than one length is required to fill the cavities, provide lengths that will produce a snug fit between ends. 2. Place insulation in cavities formed by framing members to produce a friction fit between edges of insulation and adjoining framing members. 3. Maintain 3-inch clearance of insulation around recessed lighting fixtures not rated for or protected from contact with insulation. 4. For wood-framed construction, install blankets according to ASTM C 1320 and as follows: a. With faced blankets having stapling flanges, secure insulation by inset, stapling flanges to sides of framing members. b. With faced blankets having stapling flanges, lap blanket flange over flange of adjacent blanket to maintain continuity of vapor retarder once finish material is installed over it. 5. Vapor-Retarder-Faced Blankets: Tape joints and ruptures in vapor-retarder facings, and seal each continuous area of insulation to ensure airtight installation. a. Exterior Walls: Set units with facing placed toward interior of construction. C. Miscellaneous Voids: Install insulation in miscellaneous voids and cavity spaces where required to prevent gaps in insulation using the following materials: 1. Loose-Fill Insulation: Compact to approximately 40 percent of normal maximum volume equaling a density of approximately 2.5 lb/cu. ft.. 2. Spray Polyurethane Insulation: Apply according to manufacturer's written instructions. 3.6 INSTALLATION OF INSULATION IN CEILINGS FOR SOUND ATTENUATION A. Where glass-fiber blankets are indicated for sound attenuation above ceilings, install blanket insulation over entire ceiling area in thicknesses indicated. Extend insulation 48 inches up either side of partitions. 3.7 INSTALLATION OF VAPOR RETARDERS A. Place vapor retarders on inside of construction indicated on Drawings. Extend vapor retarders to extremities of areas to protect from vapor transmission. Secure vapor retarders in place with adhesives or other anchorage system as indicated. Extend vapor retarders to cover miscellaneous voids in insulated substrates, including those filled with loose-fiber insulation. B. Seal vertical joints in vapor retarders over framing by lapping no fewer than two studs and sealing joint with vapor-retarder taepe. 1. Fasten vapor retarders to wood framing at top, end, and bottom edges; at perimeter of wall openings; and at lap joints. Space fasteners 16 inches o.c. THERMAL INSULATION

5 THERMAL INSULATION Axis Architecture + Interiors SECTION Before installing vapor retarders, apply urethane sealant to flanges of metal framing including runner tracks, metal studs, and framing around door and window openings. Seal overlapping joints in vapor retarders with vapor-retarder tape according to vaporretarder manufacturer's written instructions. Seal butt joints with vapor-retarder tape. Locate all joints over framing members or other solid substrates. 3. Firmly attach vapor retarders to metal framing and solid substrates with vapor-retarder fasteners as recommended by vapor-retarder manufacturer. C. Seal joints caused by pipes, conduits, electrical boxes, and similar items penetrating vapor retarders with vapor-retarder tape to create an airtight seal between penetrating objects and vapor retarders. D. Repair tears or punctures in vapor retarders immediately before concealment by other work. Cover with vapor-retarder tape or another layer of vapor retarders. 3.8 PROTECTION A. Protect installed insulation and vapor retarders from damage due to harmful weather exposures, physical abuse, and other causes. Provide temporary coverings or enclosures where insulation is subject to abuse and cannot be concealed and protected by permanent construction immediately after installation. END OF SECTION THERMAL INSULATION

6 SIMULATED STONE COUNTERTOPS Axis Architecture + Interiors SECTION SECTION SIMULATED STONE COUNTERTOPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Solid-surface-material countertops and backsplashes. B. Related Sections: 1.3 ACTION SUBMITTALS A. Product Data: For countertop materials and sinks. B. Shop Drawings: For countertops. Show materials, finishes, edge and backsplash profiles, methods of joining, and cutouts for plumbing fixtures. C. Samples for Initial Selection: For each type of material exposed to view. 1.4 PROJECT CONDITIONS A. Field Measurements: Verify dimensions of countertops by field measurements after base cabinets are installed but before countertop fabrication is complete. 1.5 COORDINATION A. Coordinate locations of utilities that will penetrate countertops or backsplashes. PART 2 - PRODUCTS 2.1 SOLID-SURFACE-MATERIAL COUNTERTOPS A. Configuration: Provide countertops with the following front and backsplash style: 1. Front: 1/8-inchroundover. 2. Backsplash: Straight, slightly eased at corner. 3. Endsplash: Matching backsplash. B. Countertops: 3/4-inch-thick, solid surface material with front edge built up with same material. C. Backsplashes: 3/4-inch-thick, solid surface material. D. Fabrication: Fabricate tops in one piece with shop-applied edges and backsplashes unless otherwise indicated. Comply with solid-surface-material manufacturer's written instructions for adhesives, sealers, fabrication, and finishing. 1. Fabricate with loose backsplashes for field assembly. E. Countertop Materials 1. Particleboard: ANSI A208.1, Grade M-2-Exterior Glue. 2. Plywood: Exterior softwood plywood complying with DOC PS 1, Grade C-C Plugged, touch sanded. 3. Adhesives: Adhesives shall not contain urea formaldehyde. 4. Solid Surface Material: Homogeneous solid sheets of filled plastic resin complying with ANSI SS1. SIMULATED STONE COUNTERTOPS

7 SIMULATED STONE COUNTERTOPS Axis Architecture + Interiors SECTION Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1) Avonite Surfaces. 2) E. I. du Pont de Nemours and Company. 3) Formica Corporation. 4) LG Chemical, Ltd. 5) Wilsonart International. 6. Type: Provide Standard Type unless Special Purpose Type is indicated. 7. Colors and Patterns: As selected by Architect from manufacturer's full range. PART 3 - EXECUTION 3.1 INSTALLATION A. Install countertops level to a tolerance of 1/8 inch in 8 feet. B. Fasten countertops by screwing through corner blocks of base units into underside of countertop. Pre-drill holes for screws as recommended by manufacturer. Align adjacent surfaces and, using adhesive in color to match countertop, form seams to comply with manufacturer's written instructions. Carefully dress joints smooth, remove surface scratches, and clean entire surface. 1. Install backsplashes and endsplashes to comply with manufacturer's written instructions for adhesives, sealers, fabrication, and finishing. 2. Seal edges of cutouts in particleboard subtops by saturating with varnish. END OF SECTION SIMULATED STONE COUNTERTOPS

8 INTERIOR PAINTING Axis Architecture + Interiors SECTION SECTION INTERIOR PAINTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section includes surface preparation and the application of paint systems on interior substrates. 1. Concrete. 2. Concrete masonry units (CMU). 3. Steel. 4. Gypsum board. B. Related Requirements: 1. Division 06 Sections for shop priming carpentry with primers specified in this Section. 1.3 DEFINITIONS A. Gloss Level 1: Not more than 5 units at 60 degrees and 10 units at 85 degrees, according to ASTM D 523. B. Gloss Level 2: Not more than 10 units at 60 degrees and 10 to 35 units at 85 degrees, according to ASTM D 523. C. Gloss Level 3: 10 to 25 units at 60 degrees and 10 to 35 units at 85 degrees, according to ASTM D 523. D. Gloss Level 4: 20 to 35 units at 60 degrees and not less than 35 units at 85 degrees, according to ASTM D 523. E. Gloss Level 5: 35 to 70 units at 60 degrees, according to ASTM D 523. F. Gloss Level 6: 70 to 85 units at 60 degrees, according to ASTM D 523. G. Gloss Level 7: More than 85 units at 60 degrees, according to ASTM D ACTION SUBMITTALS A. Product Data: For each type of product. Include preparation requirements and application instructions. B. Samples for Initial Selection: For each type of topcoat product. C. Samples for Verification: For each type of paint system and in each color and gloss of topcoat. 1. Submit Samples on rigid backing, 200 mm (8 inches) square. 2. Step coats on Samples to show each coat required for system. 3. Label each coat of each Sample. 4. Label each Sample for location and application area. D. Product List: For each product indicated, include the following: 1. Cross-reference to paint system and locations of application areas. Use same designations indicated on Drawings and in schedules. 2. Printout of current "MPI Approved Products List" for each product category specified in Part 2, with the proposed product highlighted. INTERIOR PAINTING Page 1 of 6

9 INTERIOR PAINTING Axis Architecture + Interiors SECTION MAINTENANCE MATERIAL SUBMITTALS A. Furnish extra materials, from the same product run, that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Paint: 5 percent, but not less than 1 gal. of each material and color applied. 1.6 DELIVERY, STORAGE, AND HANDLING A. Store materials not in use in tightly covered containers in well-ventilated areas with ambient temperatures continuously maintained at not less than 7 deg C (45 deg F). 1. Maintain containers in clean condition, free of foreign materials and residue. 2. Remove rags and waste from storage areas daily. 1.7 FIELD CONDITIONS A. Apply paints only when temperature of surfaces to be painted and ambient air temperatures are between 50 and 95 deg F. B. Do not apply paints when relative humidity exceeds 85 percent; at temperatures less than 5 deg F above the dew point; or to damp or wet surfaces. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. provide products by one of the following: 1. Behr Process Corporation. 2. Benjamin Moore & Co. 3. Coronado Paint. 4. ICI Paints. 5. M.A.B. Paints. 6. PPG Architectural Finishes, Inc. 7. Pratt & Lambert. 8. Sherwin-Williams Company (The). 2.2 PAINT, GENERAL A. MPI Standards: Provide products that comply with MPI standards indicated and that are listed in its "MPI Approved Products List." B. Material Compatibility: 1. Provide materials for use within each paint system that are compatible with one another and substrates indicated, under conditions of service and application as demonstrated by manufacturer, based on testing and field experience. 2. For each coat in a paint system, provide products recommended in writing by manufacturers of topcoat for use in paint system and on substrate indicated. C. Colors: As indicated in a color schedule. D. VOC Content: Products shall comply with VOC limits of authorities having jurisdiction and, for interior paints and coatings applied at Project site, the following VOC limits, exclusive of colorants added to a tint base, when calculated according to 40 CFR 59, Subpart D (EPA Method 24). 1. Flat Paints and Coatings: 50 g/l. 2. Nonflat Paints and Coatings: 150 g/l. 3. Primers, Sealers, and Undercoaters: 200 g/l. 4. Anticorrosive and Antirust Paints Applied to Ferrous Metals: 250 g/l. INTERIOR PAINTING Page 2 of 6

10 INTERIOR PAINTING Axis Architecture + Interiors SECTION Zinc-Rich Industrial Maintenance Primers: 340 g/l. 6. Pretreatment Wash Primers: 420 g/l. E. Low-Emitting Materials: Interior paints and coatings shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers." 2.3 BLOCK FILLERS A. Block Filler, Latex, Interior/Exterior: MPI #4. 1. Sherwin Williams; Loxon Block Filler. 2.4 PRIMERS/SEALERS A. Primer Sealer, Interior, Institutional Low Odor/VOC: MPI # Sherwin Williams; ProMar 200 Zero, Interior Latex Primer. B. Primer, Latex, for Interior Wood: MPI # Sherwin Williams; Multi-purpose Latex Primer/Sealer. 2.5 METAL PRIMERS A. Primer, Rust-Inhibitive, Water Based: MPI # WATER-BASED PAINTS A. Latex, Interior, Institutional Low Odor/VOC, (Gloss Level 3): MPI # Sherwin Williams; ProMar 200 Zero VOC, Interior Latex Eg-Shel. B. Latex, Interior, Institutional Low Odor/VOC, Semi-Gloss (Gloss Level 5): MPI # Sherwin Williams, Pro Industrial, Zero VOC Acrylic Semi-Gloss. 2.7 SOLVENT-BASED PAINTS A. Alkyd, Interior, Semi-Gloss (Gloss Level 5): MPI # Sherwin Williams All Surface Enamel. 2.8 DRY FOG/FALL COATINGS A. Dry Fall, Latex, Flat: MPI # Sherwin Williams, Low VOC Waterborne Acrylic Dryfall. 2.9 CEILING PAINTS A. Latex, Interior, Flat: 1. Sherwin Williams, Visible Solutions Ceiling Paint. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates and conditions, with Applicator present, for compliance with requirements for maximum moisture content and other conditions affecting performance of the Work. B. Maximum Moisture Content of Substrates: When measured with an electronic moisture meter as follows: 1. Concrete: 12 percent. 2. Masonry (Clay and CMU): 12 percent. 3. Gypsum Board: 12 percent. INTERIOR PAINTING Page 3 of 6

11 INTERIOR PAINTING Axis Architecture + Interiors SECTION C. Gypsum Board Substrates: Verify that finishing compound is sanded smooth. D. Verify suitability of substrates, including surface conditions and compatibility with existing finishes and primers. E. Proceed with coating application only after unsatisfactory conditions have been corrected. 1. Application of coating indicates acceptance of surfaces and conditions. 3.2 PREPARATION A. Comply with manufacturer's written instructions and recommendations in "MPI Manual" applicable to substrates indicated. B. Remove hardware, covers, plates, and similar items already in place that are removable and are not to be painted. If removal is impractical or impossible because of size or weight of item, provide surface-applied protection before surface preparation and painting. 1. After completing painting operations, use workers skilled in the trades involved to reinstall items that were removed. Remove surface-applied protection if any. C. Clean substrates of substances that could impair bond of paints, including dust, dirt, oil, grease, and incompatible paints and encapsulants. 1. Remove incompatible primers and reprime substrate with compatible primers or apply tie coat as required to produce paint systems indicated. D. Concrete Substrates: Remove release agents, curing compounds, efflorescence, and chalk. Do not paint surfaces if moisture content or alkalinity of surfaces to be painted exceeds that permitted in manufacturer's written instructions. E. Masonry Substrates: Remove efflorescence and chalk. Do not paint surfaces if moisture content or alkalinity of surfaces or mortar joints exceed that permitted in manufacturer's written instructions. F. Steel Substrates: Remove rust, loose mill scale, and shop primer, if any. Clean using methods recommended in writing by paint manufacturer but not less than the following: 1. SSPC-SP 3, "Power Tool Cleaning." G. Shop-Primed Steel Substrates: Clean field welds, bolted connections, and abraded areas of shop paint, and paint exposed areas with the same material as used for shop priming to comply with SSPC-PA 1 for touching up shop-primed surfaces. 3.3 APPLICATION A. Apply paints according to manufacturer's written instructions and to recommendations in "MPI Manual." 1. Use applicators and techniques suited for paint and substrate indicated. 2. Paint surfaces behind movable equipment and furniture same as similar exposed surfaces. Before final installation, paint surfaces behind permanently fixed equipment or furniture with prime coat only. 3. Paint front and backsides of access panels, removable or hinged covers, and similar hinged items to match exposed surfaces. 4. Do not paint over labels of independent testing agencies or equipment name, identification, performance rating, or nomenclature plates. 5. Primers specified in painting schedules may be omitted on items that are factory primed or factory finished if acceptable to topcoat manufacturers. B. Tint each undercoat a lighter shade to facilitate identification of each coat if multiple coats of same material are to be applied. Tint undercoats to match color of topcoat, but provide sufficient difference in shade of undercoats to distinguish each separate coat. C. If undercoats or other conditions show through topcoat, apply additional coats until cured film has a uniform paint finish, color, and appearance. INTERIOR PAINTING Page 4 of 6

12 INTERIOR PAINTING Axis Architecture + Interiors SECTION D. Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks, roller tracking, runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color breaks. E. Painting Fire Suppression, Plumbing, HVAC, Electrical, Communication, and Electronic Safety and Security Work: 1. Paint the following work where exposed in occupied spaces: a. Equipment, including panelboards. b. Uninsulated metal piping. c. Uninsulated plastic piping. d. Pipe hangers and supports. e. Metal conduit. f. Plastic conduit. g. Duct, equipment, and pipe insulation having cotton or canvas insulation covering or other paintable jacket material. h. Other items as directed by Architect. 2. Paint portions of internal surfaces of metal ducts, without liner, behind air inlets and outlets that are visible from occupied spaces. 3.4 CLEANING AND PROTECTION A. At end of each workday, remove rubbish, empty cans, rags, and other discarded materials from Project site. B. After completing paint application, clean spattered surfaces. Remove spattered paints by washing, scraping, or other methods. Do not scratch or damage adjacent finished surfaces. C. Protect work of other trades against damage from paint application. Correct damage to work of other trades by cleaning, repairing, replacing, and refinishing, as approved by Architect, and leave in an undamaged condition. D. At completion of construction activities of other trades, touch up and restore damaged or defaced painted surfaces. 3.5 INTERIOR PAINTING SCHEDULE A. CMU Substrates: 1. Institutional Low-Odor/VOC Latex System: a. Block Filler: Block filler, latex, interior/exterior, MPI #4. b. Intermediate Coat: Latex, interior, institutional low odor/voc, matching topcoat. c. Topcoat: Latex, interior, institutional low odor/voc, (Gloss Level 3), MPI #145. B. Steel Substrates: 1. Water-Based Dry-Fall System: a. Prime Coat: Shop primer specified in Division 05 Section where substrate is specified. b. Topcoat: Dry fall, latex, flat, MPI #118. c. Location: Metal Deck. 2. Alkyd System: a. Prime Coat: Shop primer specified in Division 05 Section where substrate is specified. b. Intermediate Coat: Alkyd, interior, matching topcoat. c. Topcoat: Alkyd, interior, semi-gloss (Gloss Level 5), MPI #47. d. Location: Steel beams and joists. C. Wood Substrates: Including wood trim. 1. Institutional Low-Odor/VOC Latex System: INTERIOR PAINTING Page 5 of 6

13 INTERIOR PAINTING Axis Architecture + Interiors SECTION a. Prime Coat: Primer, latex, for interior wood, MPI #39. b. Intermediate Coat: Latex, interior, institutional low odor/voc, matching topcoat. c. Topcoat: Latex, interior, institutional low odor/voc, semi-gloss (Gloss Level 5), MPI #147. D. Gypsum Board Substrates: 1. Institutional Low-Odor/VOC Latex System: a. Prime Coat: Primer sealer, interior, institutional low odor/voc, MPI #149. b. Intermediate Coat: Latex, interior, institutional low odor/voc, matching topcoat. c. Topcoat: Latex, interior, institutional low odor/voc, (Gloss Level 3 - Eggshell), MPI # EPOXY COATINGS (for concrete floors) A. Epoxy, Gloss: High solids, clear two-component epoxy floor coating. 1. Manufacturer: Sherwin-Williams Company. 2. Base Coat: a. Product: Armorseal 1000 HS. b. Thickness: 5.0 wet mils. c. Color: Clear. 3. Top Coat: a. Product: Armorseal 1000 HS. b. Thickness: 5.0 wet mils. c. Color: Clear. d. Sheen: Glossy. 4. Slip Resistance: a. Coating must meet ADA slip resistance guidelines and have a Static Coefficient of Friction (dry) of 0.6. b. Provide SharkGrip Additive as necessary to meet requirements. END OF SECTION INTERIOR PAINTING Page 6 of 6

14 EXTERIOR PAINTING Axis Architecture + Interiors SECTION SECTION EXTERIOR PAINTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section includes surface preparation and the application of paint systems on the following exterior substrates: 1. Concrete. 2. Concrete masonry units (CMU). 3. Steel. 4. Galvanized metal. 5. Fiber cement boards and trim. B. Related Requirements: 1. Division 05 Sections for shop priming of metal substrates with primers specified in this Section. 2. Division 09 painting Sections for special-use coatings. 3. Division 09 Section "Interior Painting" for surface preparation and the application of paint systems on interior substrates. 1.3 DEFINITIONS A. Gloss Level 1: Not more than 5 units at 60 degrees and 10 units at 85 degrees, according to ASTM D 523. B. Gloss Level 3: 10 to 25 units at 60 degrees and 10 to 35 units at 85 degrees, according to ASTM D 523. C. Gloss Level 4: 20 to 35 units at 60 degrees and not less than 35 units at 85 degrees, according to ASTM D 523. D. Gloss Level 5: 35 to 70 units at 60 degrees, according to ASTM D 523. E. Gloss Level 6: 70 to 85 units at 60 degrees, according to ASTM D 523. F. Gloss Level 7: More than 85 units at 60 degrees, according to ASTM D ACTION SUBMITTALS A. Product Data: For each type of product. Include preparation requirements and application instructions. B. Samples for Initial Selection: For each type of topcoat product. C. Samples for Verification: For each type of paint system and each color and gloss of topcoat. 1. Submit Samples on rigid backing, 200 mm (8 inches) square. EXTERIOR PAINTING Page 1 of

15 EXTERIOR PAINTING Axis Architecture + Interiors SECTION Step coats on Samples to show each coat required for system. 3. Label each coat of each Sample. 4. Label each Sample for location and application area. D. Product List: For each product indicated, include the following: 1. Cross-reference to paint system and locations of application areas. Use same designations indicated on Drawings and in schedules. 2. Printout of current "MPI Approved Products List" for each product category specified, with the proposed product highlighted. 3. VOC content. 1.5 MAINTENANCE MATERIAL SUBMITTALS A. Furnish extra materials, from the same product run, that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Paint: 5 percent, but not less than 1 gal of each material and color applied. 1.6 DELIVERY, STORAGE, AND HANDLING A. Store materials not in use in tightly covered containers in well-ventilated areas with ambient temperatures continuously maintained at not less than 7 deg C (45 deg F). 1. Maintain containers in clean condition, free of foreign materials and residue. 2. Remove rags and waste from storage areas daily. 1.7 FIELD CONDITIONS A. Apply paints only when temperature of surfaces to be painted and ambient air temperatures are between 10 and 35 deg C (50 and 95 deg F). B. Do not apply paints in snow, rain, fog, or mist; when relative humidity exceeds 85 percent; at temperatures less than 3 deg C (5 deg F) above the dew point; or to damp or wet surfaces. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include the following: 1. Behr Process Corporation. 2. Benjamin Moore & Co. 3. ICI Paints. 4. M.A.B. Paints. 5. PPG Architectural Finishes, Inc. EXTERIOR PAINTING Page 2 of

16 EXTERIOR PAINTING Axis Architecture + Interiors SECTION Pratt & Lambert. 7. Sherwin-Williams Company (The). B. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to products listed in other Part 2 articles for the paint category indicated. 2.2 PAINT, GENERAL A. MPI Standards: Provide products that comply with MPI standards indicated and that are listed in its "MPI Approved Products List." B. Material Compatibility: 1. Provide materials for use within each paint system that are compatible with one another and substrates indicated, under conditions of service and application as demonstrated by manufacturer, based on testing and field experience. 2. For each coat in a paint system, provide products recommended in writing by manufacturers of topcoat for use in paint system and on substrate indicated. C. VOC Content: Provide materials that comply with VOC limits of authorities having jurisdiction. D. Colors: As selected by Architect from manufacturer's full range. 2.3 BLOCK FILLERS A. Block Filler, Latex, Interior/Exterior: MPI # PRIMERS/SEALERS A. Primer, Alkali Resistant, Water Based: MPI #3. 1. Sherwin Williams; Loxon, Loxon Concrete & Masonry Primer. B. Primer, Alkyd, Anti-Corrosive for Metal: MPI # Sherwin Williams; Protective & Marine, ken Bond HS. C. Primer, Latex for Cement Board: MPI #6. 1. Sherwin Williams; Multi-Purpose Latex Primer. 2.5 WATER-BASED PAINTS A. Latex, Exterior Semi-Gloss (Gloss Level 3): MPI # Sherwin Williams; Weatherclad, 100% Acrylic latex Satin. B. Light Industrial Coating, Exterior, Water Based, Semi-Gloss (Gloss Level 5): MPI # Sherwin Williams; Pro Industrial, Zero VOC Acrylic Semi-Gloss. C. Latex, Exterior, High Build: MPI # Sherwin Williams; Loxon XP. 2.6 SOURCE QUALITY CONTROL A. Testing of Paint Materials: Owner reserves the right to invoke the following procedure: EXTERIOR PAINTING Page 3 of

17 EXTERIOR PAINTING Axis Architecture + Interiors SECTION Owner will engage the services of a qualified testing agency to sample paint materials. Contractor will be notified in advance and may be present when samples are taken. If paint materials have already been delivered to Project site, samples may be taken at Project site. Samples will be identified, sealed, and certified by testing agency. 2. Testing agency will perform tests for compliance with product requirements. 3. Owner may direct Contractor to stop applying paints if test results show materials being used do not comply with product requirements. Contractor shall remove noncomplying paint materials from Project site, pay for testing, and repaint surfaces painted with rejected materials. Contractor will be required to remove rejected materials from previously painted surfaces if, on repainting with complying materials, the two paints are incompatible. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates and conditions, with Applicator present, for compliance with requirements for maximum moisture content and other conditions affecting performance of the Work. B. Maximum Moisture Content of Substrates: When measured with an electronic moisture meter as follows: 1. Concrete: 12 percent. C. Verify suitability of substrates, including surface conditions and compatibility with existing finishes and primers. D. Proceed with coating application only after unsatisfactory conditions have been corrected. 1. Application of coating indicates acceptance of surfaces and conditions. 3.2 PREPARATION A. Comply with manufacturer's written instructions and recommendations in "MPI Manual" applicable to substrates and paint systems indicated. B. Remove hardware, covers, plates, and similar items already in place that are removable and are not to be painted. If removal is impractical or impossible because of size or weight of item, provide surface-applied protection before surface preparation and painting. 1. After completing painting operations, use workers skilled in the trades involved to reinstall items that were removed. Remove surface-applied protection. C. Clean substrates of substances that could impair bond of paints, including dust, dirt, oil, grease, and incompatible paints and encapsulants. 1. Remove incompatible primers and reprime substrate with compatible primers or apply tie coat as required to produce paint systems indicated. D. Concrete Substrates: Remove release agents, curing compounds, efflorescence, and chalk. Do not paint surfaces if moisture content or alkalinity of surfaces to be painted exceeds that permitted in manufacturer's written instructions. EXTERIOR PAINTING Page 4 of

18 EXTERIOR PAINTING Axis Architecture + Interiors SECTION E. Masonry Substrates: Remove efflorescence and chalk. Do not paint surfaces if moisture content or alkalinity of surfaces or mortar joints exceeds that permitted in manufacturer's written instructions. F. Steel Substrates: Remove rust, loose mill scale, and shop primer if any. Clean using methods recommended in writing by paint manufacturer but not less than the following: 1. SSPC-SP 3, "Power Tool Cleaning." G. Shop-Primed Steel Substrates: Clean field welds, bolted connections, and abraded areas of shop paint, and paint exposed areas with the same material as used for shop priming to comply with SSPC-PA 1 for touching up shop-primed surfaces. 3.3 APPLICATION A. Apply paints according to manufacturer's written instructions and recommendations in "MPI Manual." 1. Use applicators and techniques suited for paint and substrate indicated. 2. Paint surfaces behind movable items same as similar exposed surfaces. Before final installation, paint surfaces behind permanently fixed items with prime coat only. 3. Paint both sides and edges of exterior doors and entire exposed surface of exterior door frames. 4. Paint entire exposed surface of window frames and sashes. 5. Do not paint over labels of independent testing agencies or equipment name, identification, performance rating, or nomenclature plates. 6. Primers specified in painting schedules may be omitted on items that are factory primed or factory finished if acceptable to topcoat manufacturers. B. Tint undercoats same color as topcoat, but tint each undercoat a lighter shade to facilitate identification of each coat if multiple coats of same material are to be applied. Provide sufficient difference in shade of undercoats to distinguish each separate coat. C. If undercoats or other conditions show through topcoat, apply additional coats until cured film has a uniform paint finish, color, and appearance. D. Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks, roller tracking, runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color breaks. 3.4 CLEANING AND PROTECTION A. At end of each workday, remove rubbish, empty cans, rags, and other discarded materials from Project site. B. After completing paint application, clean spattered surfaces. Remove spattered paints by washing, scraping, or other methods. Do not scratch or damage adjacent finished surfaces. C. Protect work of other trades against damage from paint application. Correct damage to work of other trades by cleaning, repairing, replacing, and refinishing, as approved by Architect, and leave in an undamaged condition. D. At completion of construction activities of other trades, touch up and restore damaged or defaced painted surfaces. EXTERIOR PAINTING Page 5 of

19 EXTERIOR PAINTING Axis Architecture + Interiors SECTION EXTERIOR PAINTING SCHEDULE A. Concrete Substrates, Nontraffic Surfaces: 1. Latex System: a. Prime Coat: Primer, alkali resistant, water based, MPI #3. b. Intermediate Coat: Latex, exterior, matching topcoat. c. Topcoat: Latex, exterior, low sheen (Gloss Level 3-4), MPI #15. B. Clay-Masonry Substrates: 1. High-Build Latex System: Dry film thickness not less than 0.25 mm (10 mils). a. Prime Coat: As recommended in writing by topcoat manufacturer. b. Intermediate Coat: As recommended in writing by topcoat manufacturer. c. Topcoat: Latex, exterior, high build, MPI #40. C. CMU Substrates: 1. High-Build Latex System: Dry film thickness not less than 0.25 mm (10 mils). a. Prime Coat: As recommended in writing by topcoat manufacturer. b. Intermediate Coat: As recommended in writing by topcoat manufacturer. c. Topcoat: Latex, exterior, high build, MPI #40. D. Steel Substrates: 1. Water-Based Light Industrial Coating System: a. Prime Coat: Primer, alkyd, anti-corrosive for metal, MPI #79. b. Intermediate Coat: Light industrial coating, exterior, water based, matching topcoat. c. Topcoat: Light industrial coating, exterior, water based, semi-gloss (Gloss Level 5), MPI #163. E. Fiber Cement Substrates: Including siding panels and trim. 1. Latex System: END OF SECTION a. Prime Coat: Primer, latex for exterior wood, MPI #6. b. Intermediate Coat: Latex, exterior, matching topcoat. c. Topcoat: Latex, exterior, low sheen (Gloss Level 3-4), MPI #15. EXTERIOR PAINTING Page 6 of

20 GYPSUM BOARD Axis Architecture + Interiors SECTION SECTION GYPSUM BOARD PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Tile backing panels. B. Related Requirements: 1. Division 07 Section "Polymer based exterior finish system" applied over tile backing panels. 2. Division 09 Section "Non-Structural Metal Framing" for non-structural framing and suspension systems that support tile backing panels. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product. B. Samples: For the following products: 1. Trim Accessories: Full-size Sample in 12-inch- long length for each trim accessory indicated. 1.4 DELIVERY, STORAGE AND HANDLING A. Store materials inside under cover and keep them dry and protected against weather, condensation, direct sunlight, construction traffic, and other potential causes of damage. Stack panels flat and supported on risers on a flat platform to prevent sagging. 1.5 FIELD CONDITIONS A. Environmental Limitations: Comply with ASTM C 840 requirements or gypsum board manufacturer's written recommendations, whichever are more stringent. B. Do not install paper-faced gypsum panels until installation areas are enclosed and conditioned. C. Do not install panels that are wet, those that are moisture damaged, and those that are mold damaged. 1. Indications that panels are wet or moisture damaged include, but are not limited to, discoloration, sagging, or irregular shape. 2. Indications that panels are mold damaged include, but are not limited to, fuzzy or splotchy surface contamination and discoloration. PART 2 - PRODUCTS 2.1 PERFORMANCE REQUIREMENTS A. Fire-Resistance-Rated Assemblies: For fire-resistance-rated assemblies, provide materials and construction identical to those tested in assembly indicated according to ASTM E 119 by an independent testing agency. GYPSUM BOARD Page 1 of 5

21 GYPSUM BOARD Axis Architecture + Interiors SECTION TILE BACKING PANELS A. Glass-Mat, Water-Resistant Backing Board: ASTM C 1178/C 1178M, with manufacturer's standard edges. 1. Products: Subject to compliance with requirements, provide one of the following : a. CertainTeed Corp.; GlasRoc Tile Backer. b. Georgia-Pacific Gypsum LLC; DensShield Tile Backer. 2. Core: 5/8 inch, Type X. 3. Mold Resistance: ASTM D 3273, score of TRIM ACCESSORIES A. Interior Trim: ASTM C Material: Galvanized or aluminum-coated steel sheet, rolled zinc, or paper-faced galvanized steel sheet. Plastic may be used at U-bead only. 2. Shapes: a. Cornerbead. b. Bullnose bead. c. LC-Bead: J-shaped; exposed long flange receives joint compound. d. L-Bead: L-shaped; exposed long flange receives joint compound. e. U-Bead: J-shaped; exposed short flange does not receive joint compound. f. Expansion (control) joint. B. DRYWALL REVEAL MOLDING: 1. Acceptable product: Fry Reglet Number DRM Characteristics: a. Description: Molding shall create a vertical or horizontal recessed reveal. b. Material: Extruded aluminum. c. Dimensions: 5/8 D x 1/2 W. C. DRYWALL F REVEAL MOLDING: 1. Acceptable product: Fry Reglet Number DRMF Characteristics: a. Description: Trim reveal molding forming wall trim reveal where drywall terminates against sill, jamb, ceiling or other finish material in same plane. b. Material: Extruded aluminum. c. Dimensions: 5/8 D x 1/2 W 2.4 JOINT TREATMENT MATERIALS A. General: Comply with ASTM C 475/C 475M. B. Joint Tape: 1. Glass-Mat Gypsum Sheathing Board: 10-by-10 glass mesh. 2. Tile Backing Panels: As recommended by panel manufacturer. C. Joint Compound for Interior Gypsum Board: For each coat use formulation that is compatible with other compounds applied on previous or for successive coats. 1. Prefilling: At open joints, rounded or beveled panel edges, and damaged surface areas, use setting-type taping compound. 2. Embedding and First Coat: For embedding tape and first coat on joints, fasteners, and trim flanges, use setting-type taping compound. GYPSUM BOARD Page 2 of 5

22 GYPSUM BOARD Axis Architecture + Interiors SECTION a. Use setting-type compound for installing paper-faced metal trim accessories. 3. Fill Coat: For second coat, use setting-type, sandable topping compound. 4. Finish Coat: For third coat, use setting-type, sandable topping compound. 5. Skim Coat: For final coat of Level 5 finish, use setting-type, sandable topping compound or high-build interior coating product designed for application by airless sprayer and to be used instead of skim coat to produce Level 5 finish. D. Joint Compound for Tile Backing Panels: 1. Glass-Mat, Water-Resistant Backing Panel: As recommended by backing panel manufacturer. 2.5 AUXILIARY MATERIALS A. General: Provide auxiliary materials that comply with referenced installation standards and manufacturer's written recommendations. B. Steel Drill Screws: ASTM C 1002, unless otherwise indicated. 1. Use screws complying with ASTM C 954 for fastening panels to steel members from to inch thick. 2. For fastening cementitious backer units, use screws of type and size recommended by panel manufacturer. C. Sound Attenuation Blankets: ASTM C 665, Type I (blankets without membrane facing) produced by combining thermosetting resins with mineral fibers manufactured from glass, slag wool, or rock wool. 1. Fire-Resistance-Rated Assemblies: Comply with mineral-fiber requirements of assembly. D. Acoustical Joint Sealant: Manufacturer's standard nonsag, paintable, nonstaining latex sealant complying with ASTM C 834. Product effectively reduces airborne sound transmission through perimeter joints and openings in building construction as demonstrated by testing representative assemblies according to ASTM E Products: Subject to compliance with requirements, provide one of the following : a. Accumetric LLC; BOSS 824 Acoustical Sound Sealant. b. Grabber Construction Products; Acoustical Sealant GSC. c. Pecora Corporation; AC-20 FTR. d. Specified Technologies, Inc.; Smoke N Sound Acoustical Sealant. e. USG Corporation; SHEETROCK Acoustical Sealant. E. Thermal Insulation: As specified in Division 07 Section "Thermal Insulation." F. Vapor Retarder: As specified in Division 07 Section "Thermal Insulation." PART 3 - EXECUTION 3.1 EXAMINATION A. Examine areas and substrates including welded hollow-metal frames and framing, with Installer present, for compliance with requirements and other conditions affecting performance. B. Examine panels before installation. Reject panels that are wet, moisture damaged, and mold damaged. C. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 APPLYING AND FINISHING PANELS, GENERAL A. Comply with ASTM C 840. GYPSUM BOARD Page 3 of 5

23 GYPSUM BOARD Axis Architecture + Interiors SECTION B. Install ceiling panels across framing to minimize the number of abutting end joints and to avoid abutting end joints in central area of each ceiling. Stagger abutting end joints of adjacent panels not less than one framing member. C. Install panels with face side out. Butt panels together for a light contact at edges and ends with not more than 1/16 inch of open space between panels. Do not force into place. D. Locate edge and end joints over supports, except in ceiling applications where intermediate supports or gypsum board back-blocking is provided behind end joints. Do not place tapered edges against cut edges or ends. Stagger vertical joints on opposite sides of partitions. Do not make joints other than control joints at corners of framed openings. E. Form control and expansion joints with space between edges of adjoining gypsum panels. F. Cover both faces of support framing with gypsum panels in concealed spaces (above ceilings, etc.), except in chases braced internally. 1. Unless concealed application is indicated or required for sound, fire, air, or smoke ratings, coverage may be accomplished with scraps of not less than 8 sq. ft. in area. 2. Fit gypsum panels around ducts, pipes, and conduits. 3. Where partitions intersect structural members projecting below underside of floor/roof slabs and decks, cut gypsum panels to fit profile formed by structural members; allow 1/4- to 3/8-inch- wide joints to install sealant. G. Isolate perimeter of gypsum board applied to non-load-bearing partitions at structural abutments, except floors. Provide 1/4- to 1/2-inch- wide spaces at these locations and trim edges with edge trim where edges of panels are exposed. Seal joints between edges and abutting structural surfaces with acoustical sealant. H. Attachment to Steel Framing: Attach panels so leading edge or end of each panel is attached to open (unsupported) edges of stud flanges first. I. Wood Framing: Install gypsum panels over wood framing, with floating internal corner construction. Do not attach gypsum panels across the flat grain of wide-dimension lumber, including floor joists and headers. Float gypsum panels over these members or provide control joints to counteract wood shrinkage. J. STC-Rated Assemblies: Seal construction at perimeters, behind control joints, and at openings and penetrations with a continuous bead of acoustical sealant. Install acoustical sealant at both faces of partitions at perimeters and through penetrations. Comply with ASTM C 919 and with manufacturer's written recommendations for locating edge trim and closing off sound-flanking paths around or through assemblies, including sealing partitions above acoustical ceilings. K. Install sound attenuation blankets before installing gypsum panels unless blankets are readily installed after panels have been installed on one side. 3.3 APPLYING TILE BACKING PANELS A. Glass-Mat, Water-Resistant Backing Panels: Comply with manufacturer's written installation instructions and install at locations indicated to receive tile. Install with 1/4-inch gap where panels abut other construction or penetrations. B. Where tile backing panels abut other types of panels in same plane, shim surfaces to produce a uniform plane across panel surfaces. 3.4 INSTALLING TRIM ACCESSORIES A. General: For trim with back flanges intended for fasteners, attach to framing with same fasteners used for panels. Otherwise, attach trim according to manufacturer's written instructions. GYPSUM BOARD Page 4 of 5