DIVISION 7 THERMAL AND MOISTURE CONTROL

Size: px
Start display at page:

Download "DIVISION 7 THERMAL AND MOISTURE CONTROL"

Transcription

1 DIVISION 7 THERMAL AND MOISTURE CONTROL BUSHEY FEIGHT MORIN ARCHITECTS INC. 473 NORTH POTOMAC STREET HAGERSTOWN, MARYLAND FAX:

2 SECTION THERMAL INSULATION PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Foam-plastic board insulation. 2. Glass-fiber blanket insulation. 3. Mineral-wool blanket insulation. 4. Vapor retarders. 1.2 SUBMITTALS A. Product Data: For each type of product indicated. B. Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, for each product. C. Research/Evaluation Reports: For foam-plastic insulation, from ICC-ES. 1.3 QUALITY ASSURANCE A. Surface-Burning Characteristics: As determined by testing identical products according to ASTM E 84 by a qualified testing agency. Identify products with appropriate markings of applicable testing agency. 1.4 DELIVERY, STORAGE, AND HANDLING A. Protect insulation materials from physical damage and from deterioration due to moisture, soiling, and other sources. Store inside and in a dry location. Comply with manufacturer's written instructions for handling, storing, and protecting during installation. B. Protect foam-plastic board insulation as follows: 1. Do not expose to sunlight except to necessary extent for period of installation and concealment. 2. Protect against ignition at all times. Do not deliver foam-plastic board materials to Project site before installation time. 3. Quickly complete installation and concealment of foam-plastic board insulation in each area of construction. PART 2 PRODUCTS 2.1 FOAM-PLASTIC BOARD INSULATION (RIGID INSUL) A. Extruded-Polystyrene Board Insulation: ASTM C 578, of type and minimum compressive strength indicated below, with maximum flame-spread and smoke-developed indexes of 75 and 450, respectively, per ASTM E Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. DiversiFoam Products. b. Dow Chemical Company (The). c. Owens Corning. Wash. Co. Administration Complex THERMAL INSULATION

3 d. Pactiv Building Products. e. Or approved equal. 2. Type X, 15 psi. B. Unfaced Wall Insulation Drainage Panels: Extruded-polystyrene board insulation complying with ASTM C 578, Type IV, 25-psi minimum compressive strength; unfaced; fabricated with shiplap or channel edges and with one side having grooved drainage channels. 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. DiversiFoam Products. b. Dow Chemical Company (The). c. Pactiv Building Products. d. Or approved equal. C. Foil-Faced, Polyisocyanurate Board Insulation: ASTM C 1289, Type I, Class 2, with maximum flame-spread and smoke-developed indexes of 75 and 450, respectively, per ASTM E Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. Atlas Roofing Corporation. b. Dow Chemical Company (The). c. Rmax, Inc. d. Or approved equal. D. Adhesive for Bonding Insulation: Product with demonstrated capability to bond insulation securely to substrates without damaging insulation and substrates. 2.2 GLASS-FIBER BLANKET INSULATION A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. CertainTeed Corporation. 2. Johns Manville. 3. Owens Corning. 4. Or approved equal. B. Unfaced, Glass-Fiber Blanket Insulation: ASTM C 665, Type I; with maximum flamespread and smoke-developed indexes of 25 and 50, respectively, per ASTM E 84; passing ASTM E 136 for combustion characteristics. C. Foil-Faced, Glass-Fiber Blanket Insulation: ASTM C 665, Type II (non-reflective faced), Class C (faced surface not rated for flame propagation); Category 1 (membrane is a vapor barrier). D. Sustainability Requirements: Provide glass-fiber blanket insulation as follows: 1. Free of Formaldehyde: Insulation manufactured with 100 percent acrylic binders and no formaldehyde. 2. Low Emitting: Insulation tested according to ASTM D 5116 and shown to emit less than 0.05-ppm formaldehyde THERMAL INSULATION Wash. Co. Administration Complex

4 2.3 MINERAL-WOOL BLANKET INSULATION (SOUND ATTENUATION) A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. Fibrex Insulations Inc. 2. Owens Corning. 3. Thermafiber. 4. Or approved equal. B. Unfaced, Mineral-Wool Blanket Insulation: ASTM C 665, Type I (blankets without membrane facing); consisting of fibers; with maximum flame-spread and smokedeveloped indexes of 25 and 50, respectively, per ASTM E 84; passing ASTM E 136 for combustion characteristics. 2.4 VAPOR RETARDERS A. Polyethylene Vapor Retarders: ASTM D 4397, 6 mils thick, with maximum permeance rating of 0.13 perm. B. Vapor-Retarder Tape: Pressure-sensitive tape of type recommended by vapor-retarder manufacturer for sealing joints and penetrations in vapor retarder. C. Vapor-Retarder Fasteners: Pancake-head, self-tapping steel drill screws; with fender washers. D. Single-Component Nonsag Urethane Sealant: ASTM C 920, Type I, Grade NS, Class 25, Use NT related to exposure, and Use O related to vapor-barrier-related substrates. E. Adhesive for Vapor Retarders: Product recommended by vapor-retarder manufacturer and has demonstrated capability to bond vapor retarders securely to substrates indicated. 2.5 INSULATION FASTENERS A. Adhesively Attached, Spindle-Type Anchors: Plate welded to projecting spindle; capable of holding insulation of specified thickness securely in position indicated with selflocking washer in place. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. AGM Industries, Inc.; Series T TACTOO Insul-Hangers. b. Gemco; Spindle Type. c. Or approved equal. 2. Plate: Perforated, galvanized carbon-steel sheet, inch thick by 2 inches square. 3. Spindle: Copper-coated, low-carbon steel; fully annealed; inch in diameter; length to suit depth of insulation indicated. B. Adhesively Attached, Angle-Shaped, Spindle-Type Anchors: Angle welded to projecting spindle; capable of holding insulation of specified thickness securely in position indicated with self-locking washer in place. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Gemco; 90-Degree Insulation Hangers. b. Or approved equal. 2. Angle: Formed from inch- thick, perforated, galvanized carbon-steel sheet with each leg 2 inches square. 3. Spindle: Copper-coated, low-carbon steel; fully annealed; inch in diameter; length to suit depth of insulation indicated. Wash. Co. Administration Complex THERMAL INSULATION

5 C. Insulation-Retaining Washers: Self-locking washers formed from inch- thick galvanized-steel sheet, with beveled edge for increased stiffness, sized as required to hold insulation securely in place, but not less than 1-1/2 inches square or in diameter. 1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. AGM Industries, Inc.; RC150. b. Gemco; R-150. c. Or approved equal. 2. Protect ends with capped self-locking washers incorporating a spring steel insert to ensure permanent retention of cap in the following locations: a. Where indicated. PART 3 EXECUTION 3.1 PREPARATION A. Clean substrates of substances that are harmful to insulation or vapor retarders, including removing projections capable of puncturing vapor retarders, or that interfere with insulation attachment. 3.2 INSTALLATION, GENERAL A. Comply with insulation manufacturer's written instructions applicable to products and applications indicated. B. Install insulation that is undamaged, dry, and unsoiled and that has not been left exposed to ice, rain, or snow at any time. C. Extend insulation to envelop entire area to be insulated. Cut and fit tightly around obstructions and fill voids with insulation. Remove projections that interfere with placement. D. Provide sizes to fit applications indicated and selected from manufacturer's standard thicknesses, widths, and lengths. Apply single layer of insulation units to produce thickness indicated unless multiple layers are otherwise shown or required to make up total thickness. 3.3 INSTALLATION OF BELOW-GRADE INSULATION A. On vertical footing and foundation wall surfaces, set insulation units using manufacturer's recommended adhesive according to manufacturer's written instructions. 1. If not otherwise indicated, extend insulation a minimum of 24 inches below exterior grade line. 3.4 INSTALLATION OF CAVITY-WALL INSULATION A. Foam-Plastic Board Insulation: Install pads of adhesive spaced approximately 24 inches o.c. both ways on inside face, and as recommended by manufacturer. Fit courses of insulation between wall ties and other obstructions, with edges butted tightly in both directions. Press units firmly against inside substrates. 1. Supplement adhesive attachment of insulation by securing boards with two-piece wall ties designed for this purpose and specified in Division 04 Section "Unit Masonry." THERMAL INSULATION Wash. Co. Administration Complex

6 3.5 INSTALLATION OF INSULATION FOR FRAMED CONSTRUCTION A. Apply insulation units to substrates by method indicated, complying with manufacturer's written instructions. If no specific method is indicated, bond units to substrate with adhesive or use mechanical anchorage to provide permanent placement and support of units. B. Glass-Fiber or Mineral-Wool Blanket Insulation: Install in cavities formed by framing members according to the following requirements: 1. Use insulation widths and lengths that fill the cavities formed by framing members. If more than one length is required to fill the cavities, provide lengths that will produce a snug fit between ends. 2. Place insulation in cavities formed by framing members to produce a friction fit between edges of insulation and adjoining framing members. 3. Maintain 3-inch clearance of insulation around recessed lighting fixtures not rated for or protected from contact with insulation. 4. For metal-framed wall cavities where cavity heights exceed 96 inches, support unfaced blankets mechanically and support faced blankets by taping flanges of insulation to flanges of metal studs. 5. Vapor-Retarder-Faced Blankets: Tape joints and ruptures in vapor-retarder facings, and seal each continuous area of insulation to ensure airtight installation. a. Exterior Walls: Set units with facing placed toward interior of construction. C. Miscellaneous Voids: Install insulation in miscellaneous voids and cavity spaces where required to prevent gaps in insulation using the following materials: 1. Loose-Fill Insulation: Compact to approximately 40 percent of normal maximum volume equaling a density of approximately 2.5 lb/cu. ft. 2. Spray Polyurethane Insulation: Apply according to manufacturer's written instructions. 3.6 INSTALLATION OF INSULATION IN CEILINGS FOR SOUND ATTENUATION A. Where glass-fiber blankets are indicated for sound attenuation above ceilings, install blanket insulation over entire ceiling area in thicknesses indicated. Extend insulation 48 inches up either side of partitions. 3.7 INSTALLATION OF INSULATION FOR CONCRETE SUBSTRATES A. Install board insulation on concrete substrates by adhesively attached, spindle-type insulation anchors as follows: 1. Fasten insulation anchors to concrete substrates with insulation anchor adhesive according to anchor manufacturer's written instructions. Space anchors according to insulation manufacturer's written instructions for insulation type, thickness, and application indicated. 2. Apply insulation standoffs to each spindle to create cavity width indicated between concrete substrate and insulation. 3. After adhesive has dried, install board insulation by pressing insulation into position over spindles and securing it tightly in place with insulation-retaining washers, taking care not to compress insulation below indicated thickness. 4. Where insulation will not be covered by other building materials, apply capped washers to tips of spindles. 3.8 INSTALLATION OF CURTAIN-WALL INSULATION A. Install board insulation in curtain-wall construction where indicated on Drawings according to curtain-wall manufacturer's written instructions. Wash. Co. Administration Complex THERMAL INSULATION

7 1. Hold insulation in place by securing metal clips and straps or integral pockets within window frames, spaced at intervals recommended in writing by insulation manufacturer to hold insulation securely in place without touching spandrel glass. Maintain cavity width of dimension indicated between insulation and glass. 2. Install insulation where it contacts perimeter fire-containment system to prevent insulation from bowing under pressure from perimeter fire-containment system. 3.9 INSTALLATION OF VAPOR RETARDERS A. Place vapor retarders on side of construction indicated on Drawings. Extend vapor retarders to extremities of areas to protect from vapor transmission. Secure vapor retarders in place with adhesives or other anchorage system as indicated. Extend vapor retarders to cover miscellaneous voids in insulated substrates, including those filled with loose-fiber insulation. B. Seal vertical joints in vapor retarders over framing by lapping no fewer than two studs. 1. Fasten vapor retarders to wood framing at top, end, and bottom edges; at perimeter of wall openings; and at lap joints. Space fasteners 16 inches o.c. Before installing vapor retarders, apply urethane sealant to flanges of metal framing including runner tracks, metal studs, and framing around door and window openings. Seal overlapping joints in vapor retarders with vapor-retarder tape according to vapor-retarder manufacturer's written instructions. Seal butt joints with vapor-retarder tape. Locate all joints over framing members or other solid substrates. 2. Firmly attach vapor retarders to metal framing and solid substrates with vaporretarder fasteners as recommended by vapor-retarder manufacturer. C. Seal joints caused by pipes, conduits, electrical boxes, and similar items penetrating vapor retarders with vapor-retarder tape to create an airtight seal between penetrating objects and vapor retarders. D. Repair tears or punctures in vapor retarders immediately before concealment by other work. Cover with vapor-retarder tape or another layer of vapor retarders PROTECTION A. Protect installed insulation and vapor retarders from damage due to harmful weather exposures, physical abuse, and other causes. Provide temporary coverings or enclosures where insulation is subject to abuse and cannot be concealed and protected by permanent construction immediately after installation. END OF SECTION THERMAL INSULATION Wash. Co. Administration Complex

8 SECTION REINFORCED SINGLE-PLY MEMBRANE ROOFING PART 1 - GENERAL CONDITIONS 1.1 DESCRIPTION A. Scope: To install a mechanically fastened Sarnafil roofing membrane with flashings, and other items to comprise a roofing system. B. Related Work: The work includes but is not necessarily limited to General Conditions, Supplementary Conditions, Sections in Division 1 of Specifications and the installation of: 1. Wood Blocking 2. Insulation 3. Fasteners 4. Roof Membrane 5. Roof Membrane Flashings 6. Walkways 7. Metal Flashings 8. Sealants and Adhesives C. Upon successful completion of work, the following warranties may be obtained: 1. Sarnafil's Warranty 2. Roofing Contractor's Warranty 1.2 QUALITY ASSURANCE A. Use adequate numbers of skilled workmen who are thoroughly trained and experienced in the necessary crafts and who are completely familiar with the specified requirements and the methods needed for proper performance of the work of this section. B. This roofing system shall be applied only by a contractor authorized by Sarnafil prior to bid. C. Upon completion of the installation, and the delivery to Sarnafil by the contractor of a certification that all work has been done in strict accordance with the contract specifications and Sarnafil's requirements. An inspection shall be made by a representative of Sarnafil to observe the roofing system. D. There shall be no deviation made from the contract specification or the approved shop drawings without prior written approval by the owner, the owner's representative and Sarnafil. E. All work shall be completed by personnel trained and authorized by Sarnafil. 1.3 CODE REQUIREMENTS A. The roofing contractor shall submit evidence that the proposed roofing system will meet the identified requirement of the following recognized code approval or testing agencies. These requirements are minimum standards and no roofing work shall commence without written documentation of the system's compliance, as required in the "Submittals" section of this specification. 1 Factory Mutual Research Laboratories, Norwood, Massachusetts a. F.M. Class I system acceptance b. F.M. I-90 wind uplift resistance 2. Underwriters Laboratories, Chicago, IL a U.L. Class A membrane Wash. Co. Administration Complex REINFORCED SINGLE-PLY MEMBRANE ROOFING

9 1.4 SUBMITTALS A. After the bid and prior to issuing the contract, the roofing contractor shall submit to the owner's representative the following: 1. Copies of specification. 2. Samples of each material to be used in the roof system including each component manufacturer's literature. 3. Written approval by the insulation manufacturer (as applicable) for use and performance of the product in the proposed system. 4. Specimen copy of Sarnafil's warranty. 5. Specimen copy of contractor's warranty 6. Dimensioned shop drawings which shall include: a. outline of roof and roof size; b. profile details of flashing methods for penetrations and terminations; c. technical acceptance from Sarnafil. 7. Certification that system specifications meets all identified code and insurance requirements. 1.5 PRODUCT DELIVERY, STORAGE AND HANDLING A. All products delivered to the job site shall be in the original unopened containers or wrappings. B. Handle all materials to prevent damage. Place all materials on pallets and fully protected from moisture. C. Membrane rolls shall be stored lying down on pallets, and fully protected from moisture with clean canvas tarpaulins. D. Bonding adhesives shall be stored at temperatures above 40Ε F. E. All flammable materials shall be stored in a cool, dry area away from sparks and open flames. Follow precautions outlined on container or supplied by material manufacturer/supplier. F. All materials which are determined damaged by the owner's representative and Sarnafil are to be removed from the job site and replaced at no cost to the owner. 1.6 JOB CONDITIONS A. Only as much of the new roofing as can be made weather tight each day, including all flashings, and metal work shall be installed. B. All work shall be scheduled and executed without exposing the interior building areas to the effects of inclement weather. The existing building and its contents shall be protected against all risks. C. The roofing contractor shall run pullout tests of fasteners to verify condition of deck/substrate and confirm pullout values. D. All surfaces to receive new insulation, membrane or flashings shall be thoroughly dry. Should surface moisture occur, the contractor shall provide the necessary equipment to dry the surface prior to application. E. All new and temporary construction, including equipment and accessories, shall be secured in such a manner, at all times, as to preclude wind blow-off or damage REINFORCED SINGLE-PLY Wash. Co. Administration Complex MEMBRANE ROOFING

10 F. Temporary waterstops shall be installed at the end of each day's work, and shall be removed before proceeding with next day's work. Waterstops shall be compatible with all materials and shall not emit dangerous or incompatible fumes. G. The contractor is cautioned that certain Sarnafil membranes are incompatible with asphalt, coal tar and oil-based materials and cements. Creosote and penta-based materials are also incompatible. Such materials should not come in contact with Sarnafil membranes at any time. If such contacts occur, the material shall be cut out and discarded. The contractor should consult Sarnafil with respect to material compatibility, precautions, and recommendations. H. Arrange work sequence to avoid use of newly-constructed roofing for storage, walking surface, and equipment movement. Where such access is absolutely required, the contractor shall provide all necessary protection and barriers to segregate the work area and to prevent damage to adjacent areas. Both plywood and polyester felt protection shall be provided for all new and existing roof areas which receive traffic during construction. I. Prior to and during application, all dirt, debris and dust shall be removed from surfaces either by vacuuming, sweeping, blowing with compressed air and/or similar methods. J. All roofing, insulation, flashings and metal work removed for construction shall be immediately taken off the site to a legal dumping area authorized to receive such materials. Any hazardous materials such as asbestos or materials containing asbestos fibers shall be disposed of in accordance with applicable City, State and Federal requirements. K. The contractor shall follow all safety regulations as recommended by OSHA. L. The contractor should take care during application and storage that overloading of deck and structure does not occur. M. Liquid materials such as solvents and adhesives shall be stored and used away from open flames, sparks and excessive heat. N. Contaminants, such as grease, fats, oils, and solvents, shall not be allowed to come into contact with the roofing membrane. O. Contractor shall verify that all roof drain lines are unblocked before starting work. Report any such blockages to the owner's representative in writing. P. If any unusual or concealed condition is discovered, stop work and notify owner immediately in writing. Q. Site clean-up, including both interior and exterior building areas which have been affected by construction, shall be completed daily to the owner's satisfaction. R. All landscaped areas affected by construction activities shall be raked clean and replanted to the owner s satisfaction. 1.7 BIDDING REQUIREMENTS A. Pre-Bid Conference: A pre-bid conference shall be held with a representative of the owner and all involved trades to discuss all aspects of the project. The contractor's field representative or roofing foreman for the work shall be in attendance. B Site Visit: Bidders shall visit the site and carefully examine the areas in question as to conditions which may affect proper execution of the work. All dimensions and quantities shall be determined or verified by the contractor. No claims for extra costs will be allowed because of lack of full knowledge of the existing conditions. Wash. Co. Administration Complex REINFORCED SINGLE-PLY MEMBRANE ROOFING

11 1.8 WARRANTIES A. Sarnafil's 20-Year Material and Labor Warranty: Upon successful completion of the work and receipt of final payment, the Sarnafil, Inc. 20-year No Dollar Limit (NDL) warranty shall be issued. B. Roofing Contractor's Warranty: The roofing contractor shall supply the owner with a minimum five-year workmanship warranty. In the event any work related to roofing, flashings, or metal work is found to be defective or otherwise not in accordance with the contract documents within two years of substantial completion, the roofing contractor shall remove and replace at not cost to the owner. The contractor's warranty obligation shall run directly to the owner, and a copy shall be sent to Sarnafil. PART 2 - PRODUCTS 2.2 GENERAL A. The components of the Sarnafil Mechanically Fastened Roof System are to be products of Sarnafil Inc. B. Components to be used that are other than those supplied or manufactured by Sarnafil may be submitted for review and acceptance by Sarnafil. Sarnafil's acceptance of any other product is only for chemical compatibility with Sarnafil products. The specifications, installation instructions, limitations, and/or restrictions of the respective manufacturers must be reviewed by the owner or the owner s representative for acceptability for use with Sarnafil products. 2.3 APPROVED MEMBRANE SYSTEMS A. Sarnafil Inc.: Sarnafil S327L, 60 mil nominal (.060 ) thickness, polyester reinforced membrane with an acrylic coating to repel dirt. 2.4 MEMBRANE A. Membrane shall conform to ASTM D4434 (latest revision) Standard for poly (vinyl chloride) sheet roofing. Classification Type III. B. As manufactured, membrane shall conform to the following physical properties: Sarnafil ASTM Tropical Physical Parameters Test Method Properties overall thickness mm (inches) D (0.060) breaking strength, min. (1bf./in.) D elongation at break, % D751 20% seam strength, % of breaking strength D751 80% retention of properties after heat aging D REINFORCED SINGLE-PLY Wash. Co. Administration Complex MEMBRANE ROOFING

12 tensile strength, % of original D751 95% elongation, % of original D751 90% tear resistance (1 bf.) D low temperature (-40Ε F) D2136 pass accelerated weathering test (Xenon) D ,000 hours cracking (7X magnification) -- none discoloration (observed) -- negligible crazing (7X magnification) -- none linear dimensional change % D % weight change after immersion in water, max. % D % 2.5 ACCESSORY PRODUCTS A. Accessory products shall be supplied by the membrane manufacturer or approved by them for use with the roofing system. 2.6 RELATED MATERIALS A. Wood Nailers: Treated wood nailers shall be installed at the perimeter of the entire roof and around such other roof projections and penetrations as specified on project drawings. Height of nailers shall be matched to that of the insulation thickness being used. 1. Wood nailers shall conform to Factory Mutual's Loss Prevention Data All wood shall have a maximum moisture content of 19% by weight on a dry weight basis stainless steel fasteners shall be used with ACQ treated wood. B. Plywood: When bonding directly to plywood, or laying roofing membrane directly over plywood, a minimum standard 1/2 smooth surfaced exterior grade plywood with exterior grade glue shall be used. 1. Plywood shall have a maximum moisture content of 19% by weight on a dry weight basis. 2.7 INSULATION A. Where specified or required, insulation shall be installed as a separation layer over the existing substrate and/or to obtain the desired thermal value. 1. Insulation shall be a Factory Mutual Class 1 fire rated, I-90 uplift approved insulation board. 2. Insulation shall meet all identified code/insurance requirements. 3. Insulation shall be compatible with and accepted by the roofing membrane manufacturer. B. Insulation shall be Sarnatherm isocyanurate or approved equal. C. Total insulation thickness shall be a minimum of 4 to be installed in two layers of 2 insulation board. Wash. Co. Administration Complex REINFORCED SINGLE-PLY MEMBRANE ROOFING

13 2.8 ACCEPTED FASTENERS FOR ATTACHMENT OF INSULATION AND SARNAFIL MEMBRANE A. The following fastener is approved for steel deck construction: 1. Sarnafastener self-tapping screws and plates as supplied by Sarnafil, Inc. 2.9 WALKWAYS A. Walkways shall consist of SarnaTred SEALANTS AND PITCH POCKET FILLERS A. Silcaflex 1a shall be used where caulk is required. B. Sarnafiller as provided by Sarnafil shall be the only accepted Pitch Pocket Filler ROOF EDGE A. Terminedge or coping as manufactured by W.P. Hickman Company..063 aluminum in Kynar Finish with color as selected by Architect MISCELLANEOUS FASTENERS AND ANCHORS A. All fasteners shall be of the same type as metal being secured. In general all fasteners, anchors, nails, straps, shall be of zinc or cadmium plated steel, galvanized, or stainless steel. All fasteners and anchors shall have a minimum embedment of 1-1/4 and shall be approved for such use by the fastener manufacturer. Fasteners for attachment of metal to wood blocking shall be annular ring nails. Fasteners for attachment of metal to masonry shall be expansion type fasteners. All fasteners shall meet Factory Mutual Standard 4470 for corrosion resistance. PART 3 - EXECUTION 3.1 GENERAL A. The roofing contractor shall coordinate the installation so that each area is made watertight at the end of each work period. 3.2 DECK PREPARATION A. The roof deck and existing roof construction must be structurally sound to provide support for the new roof system. The structure and deck must be capable of withstanding expected wind uplift forces created at fastening points. Sarnafil requires fastener pullout tests to verify deck condition and confirm fastener pullout values. B. FM approved steel decks (22 ga. minimum). The roof deck construction shall conform to Factory Mutual's recommendations outlined in their Loss Prevention Data Sheet SUBSTRATE PREPARATION A. A proper substrate shall be provided to receive the Sarnafil Membrane in a mechanically attached system. B. The roofing contractor shall inspect the roofing surface for defects such as excessive surface roughness, contaminated surfaces, structurally unsound substrates, etc., that will adversely affect the quality of work REINFORCED SINGLE-PLY Wash. Co. Administration Complex MEMBRANE ROOFING

14 C. The substrate shall be clean, smooth, dry, free of flaws, sharp edges, loose and foreign material, oil and grease. Roofing shall not start until all defects have been corrected. D. All roof surfaces shall be free of water, ice and snow. 3.4 WOOD NAILERS A. Install continuous treated wood nailers at the perimeter of the entire roof and around roof projections and penetrations as specified on project drawings. B. Nailers shall be anchored to resist a minimum force of 175 pounds per lineal foot in any direction. A 1/2 space shall be provided between nailer lengths. Individual nailer lengths shall not be less than 3 long. Fasteners spacing shall be a maximum of 3 o.c. Fasteners shall be installed within 6 of each end. Spacing and fastener embedment shall conform to Factory Mutual Loss Prevention Data C. Thickness shall be as required to match substrate or insulation height. D. Any existing woodwork which is to be reused shall be firmly anchored in place (shall resist a minimum force of 175 pounds per lineal foot in any direction) and free of rot. Only woodwork designated to be reused in detail drawings shall be left in place and all other woodwork shall be removed. 3.5 INSULATION INSTALLATION A. General Criteria: Insulation shall be installed according to insulation manufacturer's instructions. 1. Insulation shall be neatly cut to fit around penetrations and projections. 2. Install tapered insulation in accordance with insulation manufacturer's shop drawings. 3. Install tapered insulation around drains creating a drain sump. 4. Do not install more insulation board than can be covered with Sarnafil membrane by the end of the day, or onset of inclement weather. 5. Mechanical Attachment: Insulation shall be mechanically fastened to the deck with accepted fasteners and plates at a minimum rate of one fastener for every 8 sq. ft. a. FM I-90 Approved Perimeter Fastening Pattern Insulation panels which fall in the perimeter and corner areas of the building shall be fastened at a minimum rate of six fasteners for every 4 foot x 8 foot insulation panel, or according to the insulation manufacturer's requirements, whichever is more stringent. b. Fasteners are to be installed in accordance with fastener manufacturer's recommendations. Fasteners are to have minimum penetration into structural deck recommended by fastener manufacturer and Sarnafil. c. Use fastener tools with a depth locator as recommended or supplied by fastener manufacturer to ensure proper installation. d. Sarnafil requires pullout tests be done to verify deck condition and actual pullout values, on reroofing projects. e. For mechanical attachments of insulation to wood or lumber decks, the fasteners shall achieve a 1 minimum penetration into the deck. B. Two layers of insulation shall be mechanically fastened to the deck with accepted fasteners and plates. Insulation shall be laid in parallel courses with end joints staggered. The second layer of insulation shall be laid transverse to the first layer, with joints staggered at least 6 from those of the first layer. 3.6 INSTALLATION OF SARNAFIL MEMBRANE A. The surface of the insulation or substrate shall be inspected prior to installation of the Sarnafil roof membrane. The substrate shall be clean, dry and smooth with no excessive surface roughness, contaminated surfaces, or unsound surfaces such as broken, delaminated or Wash. Co. Administration Complex REINFORCED SINGLE-PLY MEMBRANE ROOFING

15 damaged insulation boards. 1. Sarnafasteners and Sarnadiscs placed in overlap method of attachment. B. General: Sarnafil membrane is to be attached with Sarnafasteners and Sarnadiscs according to Sarnafil's specifications and details. 1. Membrane overlaps shall be shingled with the flow of water where possible. C. Perimeter and Corners: Over the properly installed and prepared substrate surface, two Sarnafil half sheets are to be installed around the entire perimeter edge. An overlap line has been provided to ensure proper overlap. Sarnadiscs are to be held back a minimum of 1 from the edge of the Sarnafil membrane. Fasteners shall be installed according to manufacturer's instructions. Fasteners shall be installed using fastener manufacturer's recommended fastening tools with dept locators. 1. Hot-air weld overlaps according to Sarnafil's recommendations. D. Interior - Field Sheets: Over the properly installed and prepared substrate surface the standard-sized Sarnafil membrane is to be unrolled. An inch overlap line has been provided to ensure sufficient overlap. Sarnafil plates and screws or anchors are to be installed along the edge of the membrane. Sarnadiscs are to be held back a minimum of 1" from the edge of the Sarnafil membrane. Fasteners shall be installed according to the manufacturer's instructions. Fasteners shall be installed using the fastener manufacturer's recommended fastening tools with depth locators. 1. Hot-air welded overlaps according to Sarnafil's recommendations. E. Securement Around Perimeter and Rooftop Penetrations: Around all perimeters, at the base of walls, drains, curbs, vent pipes, or any other roof penetrations, Sarnafasteners and Sarnadiscs shall be installed. Fasteners shall be installed according to the manufacturer's instructions. Fasteners shall be installed using the fastener manufacturer's recommended fastening tools with depth locators. 1. Sarnafil membrane flashings shall extend 3 past the Sarnadiscs and be hot-air welded to the Sarnafil deck sheet. 2. Two perimeter half sheets run parallel to the outside edge, continued into the corner to the outside edge. Sarnafasteners XP and Sarnadiscs XP spaced 12 o.c. in the overlaps. Interior sheets to be fastened with Sarnafasteners XP and Sarnadiscs XP spaced 12 o.c. in the overlaps. 3.7 HOT-AIR WELDING OF LAP AREAS A. General: Adjacent sheets shall be welded in accordance with Sarnafil's written instructions. All side and end lap joints shall be hot-air welded. Lap area shall be a minimum of 3" wide when machine welding, and a minimum of 4 wide when hand welding. 1. Welding equipment shall be provided by or approved by Sarnafil. All mechanics intending to use the equipment shall have successfully completed a course of instruction provided by a Sarnafil representative prior to welding. 2. All surfaces to be welded shall be clean according to Sarnafil recommendations, and dry. No adhesive shall be present within the lap areas. B. Hand Welding: Hand welded seams shall be completed in three stages. Equipment shall be allowed to warm up for at least one minute prior to start of welding. 1. The lap shall be tack welded every 3 to hold the seam in place. NOTE: WHEN HAND WELDING LAPS OF MECHANICALLY ATTACHED FIELD AND PERIMETER SHEETS, TACK WELDING IS NOT ADVISABLE, USE WEIGHTS OR METAL TRACKS TO HOLD THE SEAM IN PLACE FOR WELDING. 2. The back edge of the lap shall be welded with a thin, continuous weld to prevent loss of hot air during the final welding REINFORCED SINGLE-PLY Wash. Co. Administration Complex MEMBRANE ROOFING

16 3. The hot air nozzle shall be inserted into the lap, at a 45 degree angle. Once the proper welding temperature has been reached and the material starts to flow, and the roller shall be applied at a right angle to the welding gun and pressed lightly. For straight laps, the 1-1/2 wide nozzle shall be used. For corners and compound connections, the ¾ wide nozzle shall be used. C. Machine Welding: Machine welded seams may be achieved by the use of Sarnafil's various automatic welding equipment. When using this equipment, the manufacturer's instructions shall be followed and local codes for electric supply, grounding and over current protection observed. The automatic welding machines require 218 to 230 volts at amps. The use of a portable generator is recommended. D. Quality Control of Welded Seams: All completed welded seams shall be checked after cooling for continuity using a rounded screwdriver or other suitable blunt object by the roofing contractor. Visible evidence that welding is proceeding acceptably is smoke during the welding operation, shiny membrane surfaces, and an uninterrupted flow of black material from the edge of completed joints. On-site evaluation of welded seams shall be made daily by the contractor to locations as directed by the owner's representative or Sarnafil's representative. Two inch wide cross-section samples shall be taken three times a day minimum through completed seams. Correct welds display failure from shearing of the membrane prior to separation of the weld. Each test cut shall be patched by the contractor at no extra charge to the owner. E. 15 wide metal tracks must be used over the deck sheet and under the machine to avoid wrinkles. 3-8 WALKWAY INSTALLATION A. Walkways shall be provided for regular maintenance of rooftop equipment and for roof areas subject to foot traffic. B. SarnaTred Installation: Roofing membrane to receive SarnaTred shall be clean and dry. 1. Chalk lines on deck sheet to indicate location of SarnaTred. 2. SarnaTred shall be unrolled and positioned within chalk lines. 3. Hot-air weld the perimeter of the SarnaTred to the Sarnafil deck sheet. Check all welds with a rounded screwdriver. Reweld any inconsistencies. 3.9 MEMBRANE FLASHINGS A. All flashings shall be installed concurrently with the roof membrane as the job progresses. No temporary flashings shall be allowed without the prior written approval of the project manager and Sarnafil. Approval shall only be for specific locations on specific dates. Flashings shall be adhered to compatible, dry smooth, and solvent-resistant surfaces. B. Sarnacol 2170 Contact Adhesive: Over the properly installed and prepared substrate surface, Sarnacol 2170 adhesive shall be applied using approved solvent-resistant ¾ nap paint rollers. The adhesive shall be applied at a rate of approximately 1-1/2 to 2-1/2 gallons per 100 sq. ft. of surface depending upon substrate. The adhesive shall be applied in smooth, even coatings with no holidays, globs, puddles or similar irregularities. Only an area which can be completely covered in the same day's operations shall be coated with adhesive. The surface with adhesive coating shall be allowed to dry completely prior to installing the membrane. Note: Drying time increases with cooler temperatures. Also, the contractor is cautioned against work on days of high humidity because of extremely slow evaporation of the solvent. The Contractor shall check with the Sarnafil technical representative prior to roof operations on such days. Wash. Co. Administration Complex REINFORCED SINGLE-PLY MEMBRANE ROOFING

17 1. When the surface is dry, the Sarnafil flashing membrane is cut to a workable length and the underside shall be evenly coated with Sarnacol 2170 adhesive at a rate of ½ gallon per 100 sq. ft. When the adhesive has dried sufficiently to produce strings when touched with a dry finger, the coated membrane shall be rolled onto the previously-coated substrate being careful to avoid wrinkles. Do not allow adhesive on the underside of the Sarnafil membrane to completely dry. The amount of membrane that can be coated with adhesive before applying to substrate will be determined by ambient temperature, humidity, and manpower. Adjacent sheets shall be overlapped a minimum of 4. Sarnafil flashings shall extend 5 onto the roofing membrane. The bonded sheet shall be pressed firmly in place with a hand roller. 2. No bonding adhesives shall be applied in lap areas that are to be welded to flashings or adjacent sheets. All sheets shall be applied in the same manner, lapping all sheets as required by welding techniques. C. Sarnafil's requirements and recommendations and the specifications shall be followed. All material submittals shall have been accepted by Sarnafil prior to installation. D. All flashings shall extend a minimum of 8 above roofing level unless previously accepted by owner's representative and Sarnafil. E. All flashing membranes shall be adhered to substrates. All interior and exterior corners and miters shall be cut and hot-air welded into place. No bituminous elements shall be in contact with the Sarnafil membrane. F. All flashings shall be hot-air welded at their joints and at their connections with the roof membrane. G. All flashing membranes shall be mechanically fastened along the top edge through tin discs spaced a maximum of 1 foot o.c., or predrilled metal strips. Expansion pins with nylon sheaths set in predrilled holes shall be used to secure flashings to masonry and concrete surfaces. H. Sarnafil flashings shall be terminated according to Sarnafil recommended details METAL FLASHINGS A. Metal details, fabrication practices and installation methods shall conform to the applicable requirements of the following: 1. Factory Mutual Loss Prevention Data Sheet 1-49 (latest issue). 2. Sheet Metal and Air Conditioning Contractors National Association (SMACNA), (latest issue). B. Metal, other than Sarnaclad metal, is not covered under the Sarnafil warranty. C. Complete all metal work in conjunction with roofing and flashings so that a watertight condition exists daily. D. Metal shall be installed to provide adequate resistance to bending and allow for normal thermal expansion and contraction. E. Metal joints shall be watertight. F. Metal flashings shall have a 4 minimum nailing flange and shall be fastened into solid wood blocking with fasteners of the same type with two rows of annular ring nails, 4 o.c., staggered. Fasteners shall penetrate the wood nailer a minimum of 1-1/4. G. Continuous metal hook strips are required if Sarnaclad metal fascia exceeds 5 in width. Hook strip is to be fastened 12 o.c. into wood nailer or masonry wall REINFORCED SINGLE-PLY Wash. Co. Administration Complex MEMBRANE ROOFING

18 3.11 TEMPORARY CUT-OFF A. All flashings shall be installed concurrently with the roof membrane in order to maintain a watertight condition as the work progresses. When a break in the day's work occurs in the central area of a roof, a temporary waterstop shall be constructed to provide a 100% watertight seal. When work on the new system is suspended, the stagger of the insulation joints shall be maintained by installing partial fillers. The new membrane shall be carried into the waterstop. The waterstop shall be sealed to the deck and/or substrate so that water will not be allowed to travel under the new or existing roofing. The edge of the membrane shall be sealed in a continuous heavy application of roof cement of 6 girth. When work resumes, the contaminated PVC membrane shall be cut out. All sealant, contaminated membrane, insulation fillers, etc. shall be removed from the work area and disposed of off site. None of these materials shall be used in the new work. B. If inclement weather occurs while a temporary waterstop is in place, the contractor shall provide the labor necessary to monitor the situation to maintain a watertight condition. C. If any water is allowed to enter under the newly-completed roofing, the affected area shall be removed and replaced at the contractor's expense COMPLETION A. Prior to demobilization from the site, the work shall be reviewed by the owner/project manager and contractor. All defects noted, non-compliance with the specifications or the recommendations of Sarnafil shall be itemized in a punch list. These items must be corrected immediately by the contractor prior to demobilization to the satisfaction of the owner/project manager and Sarnafil. B. All warranties, as required in Part 1 of this specification shall be submitted for approval prior to final payment. END OF SECTION Wash. Co. Administration Complex REINFORCED SINGLE-PLY MEMBRANE ROOFING

19 SECTION SHEET METAL FLASHING AND TRIM PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Manufactured and formed through-wall flashing and counterflashing, reglets, fascia, and other fabricated sheet metal items as required by Contract Documents. 1.2 PERFORMANCE REQUIREMENTS A. General: Sheet metal flashing and trim assemblies as indicated shall withstand wind loads, structural movement, thermally induced movement, and exposure to weather without failure due to defective manufacture, fabrication, installation, or other defects in construction. Completed sheet metal flashing and trim shall not rattle, leak, or loosen, and shall remain watertight. B. Thermal Movements: Provide sheet metal flashing and trim that allows for thermal movements from ambient and surface temperature changes. 1. Temperature Change (Range): 120 deg F, ambient; 180 deg F, material surfaces. 1.3 SUBMITTALS A. Product Data: For each type of product indicated. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for each manufactured product and accessory. B. Shop Drawings: Show fabrication and installation layouts of sheet metal flashing and trim, including plans, elevations, expansion-joint locations, and keyed details. Distinguish between shop- and field-assembled work. Include the following: 1. Identification of material, thickness, weight, and finish for each item and location in project. 2. Details for forming sheet metal flashing and trim, including profiles, shapes, seams, and dimensions. 3. Details for joining, supporting, and securing sheet metal flashing and trim, including layout of fasteners, cleats, clips, and other attachments. Include pattern of seams. 4. Details of termination points and assemblies, including fixed points. 5. Details of edge conditions, including crickets and counterflashings as applicable. 6. Details of special conditions. 7. Details of connections to adjoining work. 8. Detail formed flashing and trim at a scale of not less than 3 inches per 12 inches. C. Samples for Initial Selection: For each type of sheet metal flashing, trim, and accessory indicated with factory-applied color finishes involving color selection. D. Samples for Verification: For each type of exposed finish required, prepared on Samples of size indicated below: Wash. Co. Administration Complex SHEET METAL FLASHING AND TRIM

20 1. Sheet Metal Flashing: 12 inches long by actual width of unit, including finished seam and in required profile. Include fasteners, cleats, clips, closures, and other attachments. 2. Trim, Metal Closures, Expansion Joints, Joint Intersections, and Miscellaneous Fabrications: 12 inches long and in required profile. Include fasteners and other exposed accessories. 3. Accessories and Miscellaneous Materials: Full-size Sample. E. Qualification Data: For qualified fabricator. F. Maintenance Data: For sheet metal flashing, trim, and accessories to include in maintenance manuals. G. Warranty: Sample of special warranty. 1.4 QUALITY ASSURANCE A. Fabricator Qualifications: Shop that employs skilled workers who custom fabricate sheet metal flashing and trim similar to that required for this project and whose products have a record of successful in-service performance. B. Sheet Metal Flashing and Trim Standard: Comply with SMACNA's "Architectural Sheet Metal Manual" unless more stringent requirements are specified or shown on Contract Drawings. C. Conform to applicable requirements of Section 01351, Sustainable Project Requirements. 1.5 DELIVERY, STORAGE, AND HANDLING A. Do not store sheet metal flashing and trim materials in contact with other materials that might cause staining, denting, or other surface damage. Store sheet metal flashing and trim materials away from uncured concrete and masonry. B. Protect strippable protective covering on sheet metal flashing and trim from exposure to sunlight and high humidity, except to the extent necessary for the period of sheet metal flashing and trim installation. 1.6 WARRANTY A. Special Warranty on Finishes: Manufacturer's standard form in which manufacturer agrees to repair finish or replace sheet metal flashing and trim that shows evidence of deterioration of factory-applied finishes within specified warranty period. 1. Exposed Panel Finish: Deterioration includes, but is not limited to, the following: a. Color fading more than 5 Hunter units when tested according to ASTM D b. Chalking in excess of a No. 8 rating when tested according to ASTM D c. Cracking, checking, peeling, or failure of paint to adhere to bare metal. 2. Finish Warranty Period: 10 years from date of Substantial Completion SHEET METAL FLASHING Wash. Co. Administration Complex AND TRIM