LISTING INFORMATION OF International Beams - IB Series Joists SPEC ID: 27316

Size: px
Start display at page:

Download "LISTING INFORMATION OF International Beams - IB Series Joists SPEC ID: 27316"

Transcription

1 LISTING INFORMATION OF International Beams - IB Series Joists SPEC ID: International Beams Inc Boul. St-Elzear Quest Laval, QC H7L 3N4 CANADA This report is for the exclusive use of Intertek s Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is authorized to permit copying or distribution of this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to the sample tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. International Beams Inc Rev: Mar :52AM Uncontrolled Copy Page 1 of 12

2 IB400, IB600, IB800 and IB900 I Joists are installed in place of conventional 2x10 and 2x12 joists using traditional framing tools and fasteners. With long lengths, I-joists are used in multiple span applications, thus reducing cutting, overlapping and material waste at the job site. The wide flanges provide a larger gluing and nailing surface for floor and roof sheathing. These lightweight joists will not twist, warp, or shrink and are more uniform in their dimensions than solid lumber. IB400, IB600, IB800 and IB900 I Joists are available in lengths up to 52 feet. IB400, IB600, IB800 and IB900 I Joists are available in depths ranging from 9-1/2 to 24 inches deep. RATINGS Standard Rating Design Number ASTM E hour IB/WIJ ASTM E 119 and CAN/ULC S minutes IBI/MWP ASTM E 119 and CAN/ULC S101 1 hour IBI/MWP ASTM E 119 and CAN/ULC S101 1 hour IBI/MWP hour IBI/MWP ASTM E 119 and CAN/ULC S101 ASTM E 119 and CAN/ULC S101 1 hour IBI/MWP hours IBI/MWP ASTM E 119 and CAN/ULC S101 Attribute Value Criteria CAN / ULC S101 (2007) Criteria ASTM E119 (2012a) CSI Code Shop-Fabricated Structural Wood Fire Resistance 2 Hour Fire Resistance 1 Hour Fire Rating Fire Resistance 45 Minute Fire Rated Intertek Services Certification Listed or Inspected LISTED Listing Section PREFABRICATED JOISTS, COLUMNS & OPEN WEB TRUSSES Listing Section ROOF/CEILING, FLOOR/CEILING, BEAM & COLUMN ASSEMBLIES Report Number ; ; , SAT-001 EEV, SAT-002, Spec ID International Beams Inc Rev: Mar :52AM Uncontrolled Copy Page 2 of 12

3 DRAWING INDEX IB/WIJ IBI/MWP IBI/MWP IBI/MWP IBI/MWP IBI/MWP IBI/MWP International Beams Inc Rev: Mar :52AM Uncontrolled Copy Page 3 of 12

4 IB/WIJ Rough Carpentry Shop Fabricated Structural Wood Wood I Joists Design Number IB/WIJ Loaded Floor / Ceiling Assembly International Beams, Inc. IB600 OSB Web I Joist ASTM E Fire Resistance Rating 1 hour Superimposed Load 51 PSF 1. TOPPING (Optional, Not Shown): Lightweight concrete, minimum density 110 pound per square foot (pcf), minimum compressive strength 3000 pound per square inch (psi) or proprietary gypsum/cement/sand topping, minimum density 100 pcf, minimum compressive strength 1000 psi. Minimum topping thickness for lightweight concrete or proprietary gypsum/cement/sand topping is 3/4 in. Date Revised: February 27, 2012 Project No: SAT-002 with joists (Item 2) spacing 24 in. on center (OC). 2. CERTIFIED COMPANY: International Beams, Inc. CERTIFIED PRODUCT: IB I Joist CERTIFIED MODEL: IB600, IB800 or IB 900 Intertek International Beams Inc Rev: Mar :52AM Uncontrolled Copy Page 4 of 12

5 IB/WIJ (page 2 of 3) Rough Carpentry Shop Fabricated Structural Wood Wood I Joists WOOD JOISTS: Use minimum 14 in., 1-1/2 in. x 2-1/2 in. flange, 3/8 in. thick OSB web I Joists spaced a maximum of 24 in. OC. Fasten I Joists to rim board with 2-3/8 in. long by in. smooth shank nails. Fasten 1 nail through the rim board into the end of each flange, and one on each side of the joist web into the bearing plate (Not Shown). 3. SUB-FLOORING: Use nominal 23/32 in. thick tongue and groove OSB subfloor sheathing. Apply a minimum 1/8 in. bead of adhesive with the following requirements along the top of all the joists and in the flooring grooves: meets ASTM D 3498 Standard Specification for Adhesives for Field- Gluing Plywood to Lumber Framing for Floor Systems, meets American Plywood Association specifications AFG-01 and tested and approved for HUD-FHA application per specification UMB No. 60. Secure OSB using 8d 2-1/2 in. common nails spaced 6 in. OC around the perimeter and at the butted edges and 12 in. OC at interior members. 4. SOUND ISOLATION CLIP (OPTIONAL): GenieClip, UL Classified. 1-5/8 in. wide x 15/16 in. high x 2-/12 in. long spaced maximum 48 in. on centre along the length of the furring channels (Item 5). GenieClip shall be used with furring channel matching the specifications noted as required for GenieClip in Item 5 of this Design Listing. Each GenieClip must be fastened to the Wood Joist (Item 2) using a minimum 2 in. Hi-Lo drywall screw through the center grommet. 5. FURRING: Use one of the following options: i. Install 1/2 in. deep nominal 25 GA galvanized steel single leg (RC-1) or minimum 1/2 in. deep x 2-1/2 in. wide hat shaped (RC-2) channels spaced 16 in. OC and applied perpendicular to the Wood Joists (Item 2). Secure furring channels to the bottom flange of each of the Wood Joists (Item 2) using minimum 1-1/4 in. long Type W screws Date Revised: February 27, 2012 Project No: SAT-002 ensuring two screws are installed in the bottom flange of each wood joist (Item 2). When required for length, overlap the channel a minimum 6 in. and secure using a 1-1/4 in. Type W screw. ii. FOR USE WITH GENIECLIP (OPTIONAL): Install 7/8 in. deep x 2-1/2 in. face width, minimum nominal 25 GA galvanized steel spaced 16 in. OC applied perpendicular to wood joists (Item 2). Furring channels must have hemmed edges. 6. GYPSUM BOARD: Install 2 layers of 1/2 in. or 5/8 in. thick proprietary Type X gypsum board UL-Classified (Type C) for application in fire-rated construction, installed with the long edge of the base layer perpendicular to the Furring Channel (Item 4), and the face layer sheets with butt joints offset. Attach gypsum board using one of the methods below. Install 1/2 in. thick gypsum board using method i or ii, but when using 5/8 in. thick gypsum board, only method i may be used. After gypsum board is attached, apply vinyl or casein, dry or premixed joint compound to the exposed face of gypsum wallboard in two coats to all exposed fastener heads and gypsum wallboard joints. Embed a minimum 2 in. wide paper, plastic, or fiberglass tape in first layer of compound over joints in gypsum wallboard. i. Attach base layer to Furring Channel (Item 4) using 1 in. Type S drywall screws spaced 12 in. OC, 1-1/2 in. from the sides and 3/8 in. from butt joints. Attach face layer to the resilient channels (through the base layer) using 1-5/8 in. Type S drywall screws spaced 8 in. OC, 1-1/2 in. from the sides. Install face layer with joints offset 24 in. from those of the base layer in 2 directions (at the sides and ends of the panels). Attach face layer to the base layer using 1-1/2 in. Type G laminating screws spaced 8 in. OC at butt joints. Install screws just short of flush with the surface. Intertek International Beams Inc Rev: Mar :52AM Uncontrolled Copy Page 5 of 12

6 IB/WIJ (page 3 of 3) Rough Carpentry Shop Fabricated Structural Wood Wood I Joists ii. Attach base layer of gypsum board to Furring Channel (Item 4) using minimum 1-1/4 in. Type S screws spaced 12 in. OC, 1-1/2 in. from the sides and 3/8 in. from butt joints. Attach face layer to the resilient channels (through the base layer) using 1-5/8 in. Type S screws spaced 12 in. OC, 1-1/2 in. from the sides. Install face layer with joints offset 24 in. from those of the base layer in 2 directions (at the sides and ends of the panels). Attach face layer to the base layer using 1-1/2 in. Type G laminating screws spaced 12 in. OC at butt joints. Install screws just short of flush with the surface. 7. INSULATION: Use insulation with a thickness ranging from 3-1/2 in. thick (R13) to 9-1/2 in. thick (R30) unfaced glass fiber insulation batts conforming to ASTM C518. Install insulation using one of the below methods: ii. installed, insulation wire stays (Not Shown) are required and are to be spaced at a maximum of 12 in. OC perpendicular to the I-Joists in the plenum cavity. Use 6-1/4 in. thick insulation or greater. When installed, insulation wire stays are not required. Install insulation over the Furring (Item 4) and Gypsum Board (Item 5). Pressfit insulation between the bottom flanges of the Wood Joists (Item 2). Install insulation with ends butted over or between the Furring (Item 4). iii. When needed, install insulation directly underneath the sub-flooring (Item 3) and hold insulation in place using insulation wire stays installed per the manufacturer s specifications or spaced maximum 12 in. OC, whichever is more conservative. i. Use less than 6-1/4 in. thick insulation. When insulation is Date Revised: February 27, 2012 Project No: SAT-002 Intertek International Beams Inc Rev: Mar :52AM Uncontrolled Copy Page 6 of 12

7 IBI/MWP International Beams Inc. June 23, 2009 Project No COQ-004 Revised: January 27, 2015 DESIGN NO. IBI/MWP ASSEMBLY RATING: 120 MINUTE FLOOR/CEILING ASSEMBLY 1 Floor Topping (optional): Lightweight concrete or proprietary topping. Sub-Flooring: Min. 5/8 in. thick plywood or Oriented Strand Board (OSB) installed 2 perpendicular to joists, with end joints staggered. Min. sheathing thickness (based on framing spacing) and fastener schedules shall comply with the Code. Structural Members: International Beams Inc. (IB) Series I-joists having a min. depth of 3 9-1/2 in., installed at 24 in. on center (oc) max.. Insulation (optional): When installed, insulation shall be installed above the joist flanges 4 and supported by stay wires spaced 16 in. oc. Resilient Channels: Min in. thick (28 GA) galvanized steel resilient channels, attached perpendicular to joists using one 1-5/8 in. long drywall screw. Resilient channels 5 spaced 16 in. oc. (channels installed after the first layer of gypsum board and is used to support the second and third layers of gypsum wallboard). 6. Gypsum Wallboard: Three layers of min. 5/8 inch thick Type C gypsum wallboard as follows: 6a. Wallboard Base Layer: Base layer of wallboard installed perpendicular to the joists and directly attached to the bottom flange using 1-5/8 in. Type S drywall screws at 12 in. oc. End joints of wallboard centered on bottom flange and staggered a min. of one joist spacing. 6b. Wallboard Middle Layer: Middle layer of wallboard attached to channels using 1 inch Type S drywall screws spaced 12 in. oc with the long dimension of wallboard 6 perpendicular to channels. Edge joints shall be centered between the joists. End joints staggered a min. of one channel spacing and offset from the edge joints in the base layer a min. of one channel spacing. 6c. Wallboard Face Layer: Face layer of wallboard attached to channels through middle layer using 1-5/8 in. Type S drywall screws spaced 8 in. oc. in the field and on the edge with a min. 3/4 in. edge distance. Edge joints of face layer of wallboard offset a distance equal to the joist spacing from those of middle layer. End joints of face layer of wallboard staggered a min. of one channel spacing with respect to the middle layer end joint. Finish System (not shown): Face layer joints covered with tape and coated with joint 7 compound. Screw heads covered with joint compound. International Beams Inc Rev: Mar :52AM Uncontrolled Copy Page 7 of 12

8 IBI/MWP International Beams Inc. July 17, 2009 Project No COQ-004 Revised: January 27, 2015 DESIGN NO. IBI/MWP FLOOR/CEILING ASSEMBLY RATING: 45 Minutes 1 Floor Topping (optional): Lightweight concrete or proprietary topping. Sub-Flooring: Min. 5/8 in. thick plywood or Oriented Strand Board (OSB) installed 2 perpendicular to joists, with end joints staggered. Min. sheathing thickness (based on framing spacing) and fastener schedules shall comply with the Code. Structural Members: International Beams Inc. (IB) Series I-joists having a minimum depth 3 of 9-1/2 in., installed at 24 in. on center (oc) max.. 5. Resilient Channels: Min in. thick (28 gauge) galvanized steel resilient channel attached perpendicular to the bottom flange of the joists with one 1-5/8 inch Type W screw. 4 Channels spaced 16 inches on center max.. Additional channels are required at gypsum board end joints so that each board is attached to a separate channel. These additional channels shall extend to the next joist on each side of the board end joint. 6. Gypsum Wallboard: Min. 5/8 in. thick Type X gypsum wallboard installed with long dimension perpendicular to resilient channels and fastened to each channel with min. 1-1/8 5 in. long Type S drywall screws. Fasteners spaced 12 in. oc. in the field, 8 in. oc at wallboard end joints, and 1-1/2 in. from panel edges and ends. Edge joints shall be centered on joists. End joints of wallboard staggered a min. of one channel spacing. Insulation (optional): When installed, insulation shall be supported above the top flange 6 by stay wires spaced 16 in. oc. Finish System (not shown): Face layer joints covered with tape and coated with joint 7 compound. Screw heads covered with joint compound. International Beams Inc Rev: Mar :52AM Uncontrolled Copy Page 8 of 12

9 IBI/MWP International Beams Inc. July 17, 2009 Project No COQ-004 Revised: January 27, 2015 DESIGN NO. IBI/MWP FLOOR/CEILING ASSEMBLY RATING: 60 Minutes 1 Floor Topping (optional): Lightweight concrete or proprietary topping. Sub-Flooring: Min. 5/8 in. thick plywood or Oriented Strand Board (OSB) installed 2 perpendicular to joists, with end joints staggered. Min. sheathing thickness (based on framing spacing) and fastener schedules shall comply with the Code. Structural Members: International Beams Inc. (IB) Series I-joists having a min. depth of 9 3 ½ inches, installed at 24 in. on center (oc) max.. (Min. 1-1/2 in. by 3-1/2 in. flange dimensions) Insulation: Min. 1-1/2 in. thick mineral wool insulation batts 2.5 pcf (min.), friction fitted 4 between the bottom flanges of the joists and supported by resilient channels. Ends of batts shall be centered over resilient channels and tightly butted. Resilient Channel: Min in. thick (28 GA) galvanized steel resilient channels, attached perpendicular to joists using one 1-5/8 in. long Type W screw. Resilient channels 5 spaced a max. of 16 in. oc. Additional channels are required at gypsum board end joints so that each board is attached to a separate channel. These additional channels shall extend to the next joist on each side of the board end joint. Gypsum Board: Min. 5/8 in. thick Type C gypsum wallboard installed with long dimension perpendicular to resilient channels and fastened to each channel with min. 1-1/8 in. long 6 Type S drywall screws. Fasteners spaced 12 in. oc in the field, 8 in. oc at wallboard end joints, and 1-1/2 in. from panel edges and ends. Edge joints shall be centered between joists. End joints shall be staggered one channel spacing. Finish System (not shown): Face layer joints covered with tape and coated with joint 7 compound. Screw heads covered with joint compound. International Beams Inc Rev: Mar :52AM Uncontrolled Copy Page 9 of 12

10 IBI/MWP International Beams Inc. July 17, 2009 Project No COQ-004 Revised: March 20, 2015 DESIGN NO. IBI/MWP FLOOR/CEILING ASSEMBLY RATING: 60 Minutes 1 Floor Topping (optional): Lightweight concrete or proprietary topping. Sub-Flooring: Min. 5/8 in. thick plywood or Oriented Strand Board (OSB) installed 2 perpendicular to joists, with end joints staggered. Min. sheathing thickness (based on framing spacing) and fastener schedules shall comply with the Code. Structural Members: International Beams Inc. (IB) Series I-joists having a minimum depth of 3 9 1/2 in., installed at 24 in. on center (oc) max. Insulation (optional): When installed, insulation shall be supported by stay wires spaced 16 4 in. on center (oc). Resilient Channel (optional): Min in. thick (28 GA) galvanized steel resilient channel attached perpendicular to the bottom flange of the joists with one 1-5/8 in. Type W screw. 5 Channels spaced a max. of 16 in. oc. The max. channel spacing may be increased to 24 in. oc when joists are spaced a max. of 16 in. oc Gypsum Board: Two layers of min. 1/2 in. thick Type X gypsum wallboard attached with the long dimension perpendicular to the resilient channels (or joists) as follows: 6a. Wallboard Base Layer: Base layer of wallboard attached to resilient channels (or joists) using 1-1/4 in. type S drywall screws at 12 in. oc. When resilient channels are installed, edge joints shall be centered on joists. End joints of wallboard shall be centered on a resilient channel (or joist) staggered a min. of one channel (or joist) spacing. 6 6b. Wallboard Face Layer: Face layer of wallboard attached to resilient channels (or joists) through base layer using 1-5/8 in. Type S drywall screws spaced 12 in. oc in the field and 8 in. oc at the end joints. Edge joints of wallboard face layer shall be offset a min. distance equal to one joist spacing, from those of the base layer. End joints shall be offset from base layer joints by a min. of 24 in. and shall be centered in-between channel (or joist) spacing. Additionally, wallboard face layer is attached to base layer with 1-1/2 in. Type G drywall screws spaced 8 in.oc, placed 1-1/2 in. from face layer end joints. Finish System (not shown): Face layer joints covered with tape and coated with joint 7 compound. Screw heads covered with joint compound. International Beams Inc Rev: Mar :52AM Uncontrolled Copy Page 10 of 12

11 IBI/MWP International Beams Inc. July 17, 2009 Project No COQ-004 Revised: January 27, 2015 DESIGN NO. IBI/MWP FLOOR/CEILING ASSEMBLY RATING: 60 Minutes 1 Floor Topping (optional): Lightweight concrete or proprietary topping. Sub-Flooring: Min. 5/8 in. thick plywood or Oriented Strand Board (OSB) installed 2 perpendicular to joists, with end joints staggered. Minimum sheathing thickness (based on framing spacing) and fastener schedules shall comply with the Code. Structural Members: International Beams Inc. (IB) Series I-joists having a minimum depth of 3 9-1/2 in., installed at 24 in. on center (oc) max.. Insulation: Min. 2 in. thick mineral wool insulation batts 3.5 pcf (min.), friction fitted 4 between the bottom flanges of the joists and supported by wood setting strip edges. Ends of batts shall be centered over resilient channels and tightly butted. Resilient Channel: Min in. thick (28 GA) galvanized steel resilient channel attached perpendicular to the bottom flange of the joists with one 1-1/8 in. drywall screw. Channels 5 spaced a max. of 16 in. oc. Additional channels are required at gypsum board end joints so that each board is attached to a separate channel. These additional channels shall extend to the next joist on each side of the board end joint. Gypsum Board: Min. 5/8 in. thick Type C gypsum wallboard installed with long dimension perpendicular to resilient channels and fastened to each channel with min. 1-1/8 in. long 6 Type S drywall screws. Fasteners spaced 7 in. oc and 1-1/2 in. from panel edges and ends. Edge joints shall be centered between joists. End joints shall be staggered one channel spacing. Wood Setting Strips (not shown): Minimum 1x4 (nominal) wood setting strips attached with 7 1-1/2 in. long Type W screws at 24 in. oc. along the bottom flange of joist creating a ledge to support insulation. Finish System (not shown): Face layer joints covered with tape and coated with joint 8 compound. Screw heads covered with joint compound. International Beams Inc Rev: Mar :52AM Uncontrolled Copy Page 11 of 12

12 IBI/MWP International Beams Inc. June 23, 2009 Project No COQ-004 Revised: January 27, 2015 DESIGN NO. IBI/MWP ROOF/CEILING ASSEMBLY RATING: 60 Minutes Roof Covering System: Insulation and roof covering materials intended for built-up covering which provides Class A, B, or C covering on combustible wood decks for fire resistant assemblies equivalent to the assembly. Sheathing: Min. 1/2 in. thick plywood or Oriented Strand Board (OSB) installed perpendicular to joists, with end joints staggered. Min. sheathing thickness (based on framing spacing) and fastener schedules shall comply with the Code. Structural Members: International Beams Inc. (IB) Series I-joists having a min. depth of 9-1/2 in., installed at 24 in. on center (oc) max.. (Min. 1-1/2 in. by 3-1/2 in. flange dimensions) Insulation: Min. 1-1/2 in. thick mineral wool insulation batts 2.5 pcf (min.), friction fitted between the bottom flanges of the joists and supported by resilient channels. Ends of batts shall be centered over resilient channels and tightly butted. Resilient Channel: Min in. (28 GA) thick galvanized steel resilient channels, attached perpendicular to joists using 1-5/8 in. long Type W screws. Resilient channels spaced a max. of 16 in. oc.. Additional channels are required at gypsum board end joints so that each board is attached to a separate channel. These additional channels shall extend to the next joist on each side of the board end joint. Gypsum Board: Min. 5/8 in. thick Type C gypsum wallboard installed with long dimension perpendicular to resilient channels and fastened to each channel with min. 1-1/8 in. long Type S screws. Fasteners spaced 12 in. oc in the field, 8 in. oc at wallboard end joints, and 1-1/2 in. from panel edges and ends. Edge joints shall be centered between joists. End joints shall be staggered one channel spacing. Finish System (not shown): Face layer joints covered with tape and coated with joint compound. Screw heads covered with joint compound. International Beams Inc Rev: Mar :52AM Uncontrolled Copy Page 12 of 12

LISTING INFORMATION OF Mitek Design No. MCI/WI SPEC ID: MiTek Canada, Inc. 100 Industrial Road Bradford, ON L3Z 3G7 Canada

LISTING INFORMATION OF Mitek Design No. MCI/WI SPEC ID: MiTek Canada, Inc. 100 Industrial Road Bradford, ON L3Z 3G7 Canada LISTING INFORMATION OF Mitek Design No. MCI/WI 60-02 SPEC ID: 27680 MiTek Canada, Inc. 100 Industrial Road Bradford, ON L3Z 3G7 Canada This report is for the exclusive use of Intertek s Client and is provided

More information

LISTING INFORMATION OF Weyerhaeuser - TJI Joists SPEC ID: 26948

LISTING INFORMATION OF Weyerhaeuser - TJI Joists SPEC ID: 26948 LISTING INFORMATION OF Weyerhaeuser - TJI Joists SPEC ID: 26948 Weyerhaeuser NR Company 33663 Weyerhaeuser Way S PO Box 9777, WTC 1K5 Federal Way, WA 98063 This report is for the exclusive use of Intertek

More information

Stark Truss Company, Inc. Revised December 14, 2018

Stark Truss Company, Inc. Revised December 14, 2018 Fire-Rated Assemblies PR-S223 Stark Truss Company, Inc. Revised December 14, 2018 Products: SI-40, SI-60, and SI-80 Prefabricated Wood I-Joists Stark Truss Company, Inc. 8655 Chestnut Ridge Road, N.W.

More information

PinkWood Ltd. Revised September 29, 2017

PinkWood Ltd. Revised September 29, 2017 Fire-Rated Assemblies PR-S315 PinkWood Ltd. Revised September 29, 2017 Products: Series I-Joists PinkWood Ltd., 5929 6 th St. NE, Calgary, Alberta, Canada T2K 5R5 (403) 279-3700 www.pinkwood.ca 1. Basis

More information

Boise Cascade Company Revised June 25, 2018

Boise Cascade Company Revised June 25, 2018 Fire-Rated Assemblies PR-S255 Boise Cascade Company Revised June 25, 2018 Products: GPI, WI, and BSI I-Joists Boise Cascade Company, 1000 North Park Drive, Roxboro, North Carolina 27573 (336) 599-1000

More information

Appendix D. -Weyerhaeuser Fire Rated Assembly Listings-

Appendix D. -Weyerhaeuser Fire Rated Assembly Listings- Appendix D -Weyerhaeuser Fire Rated Assembly Listings- Table of Contents Assembly Description Reference Standard/Criteria FJ-1 TJI Joist 1 hour fire resistance rated floor and roof assembly. ASTM-E119

More information

AUTHORIZATION TO MARK

AUTHORIZATION TO MARK AUTHORIZATION TO MARK This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) Covered section when made in accordance with the conditions set

More information

LISTING INFORMATION OF ClarkDietrich Wall Assembly Design No. CD/WA SPEC ID: 26053

LISTING INFORMATION OF ClarkDietrich Wall Assembly Design No. CD/WA SPEC ID: 26053 LISTING INFORMATION OF ClarkDietrich Wall Assembly Design No. CD/WA 120-03 SPEC ID: 26053 ClarkDietrich Building Systems 9100 Centre Pointe Drive, Suite 210 West Chester, OH 45069 This report is for the

More information

LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 8" Thick 3 Hour Fire Rated Panels SPEC ID: 29868

LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 8 Thick 3 Hour Fire Rated Panels SPEC ID: 29868 LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 8" Thick 3 Hour Fire Rated Panels SPEC ID: 29868 Metl-Span, A Division of NCI Group, Inc. 1720 Lakepointe Drive, Suite 101 Lewisville, TX 75057 This report

More information

LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 4" Thick 1 Hour Fire Rated Wall Panels SPEC ID: 29555

LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 4 Thick 1 Hour Fire Rated Wall Panels SPEC ID: 29555 LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 4" Thick 1 Hour Fire Rated Wall Panels SPEC ID: 29555 Metl-Span, A Division of NCI Group, Inc. 1720 Lakepointe Drive, Suite 101 Lewisville, TX 75057 This

More information

LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 6" Thick 2-hour Fire Rated Panels SPEC ID: 29771

LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 6 Thick 2-hour Fire Rated Panels SPEC ID: 29771 LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 6" Thick 2-hour Fire Rated Panels SPEC ID: 29771 Metl-Span, A Division of NCI Group, Inc. 1720 Lakepointe Drive, Suite 101 Lewisville, TX 75057 This report

More information

LISTING INFORMATION OF International Fireproof Technology Inc. - Joint Systems SPEC ID: 43848

LISTING INFORMATION OF International Fireproof Technology Inc. - Joint Systems SPEC ID: 43848 LISTING INFORMATION OF International Fireproof Technology Inc. - Joint Systems SPEC ID: 43848 International Fireproof Technology Inc. 17528 Von Karman Avenue Irvine, CA 92614 This report is for the exclusive

More information

LISTING INFORMATION OF ClarkDietrich Steel 'H' Stud and 'U' Track Fire-resistance-rated Area Separation Wall Assemblies SPEC ID: 26662

LISTING INFORMATION OF ClarkDietrich Steel 'H' Stud and 'U' Track Fire-resistance-rated Area Separation Wall Assemblies SPEC ID: 26662 LISTING INFORMATION OF ClarkDietrich Steel 'H' Stud and 'U' Track Fire-resistance-rated Area Separation Wall Assemblies SPEC ID: 26662 ClarkDietrich Building Systems 9100 Centre Pointe Drive, Suite 210

More information

REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: September 14, 2012 REVISED DATE: N/A

REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: September 14, 2012 REVISED DATE: N/A TEST REPORT REPORT NUMBER: 100595243SAT-005 ORIGINAL ISSUE DATE: September 14, 2012 REVISED DATE: N/A EVALUATION CENTER 16015 Shady Falls Road Elmendorf, TX 78112 Phone: (210) 635-8100 Fax: (210) 635-8101

More information

Page 2 of 5 1. Flooring Systems The flooring system shall consist of one of the following: System No. 1 Subflooring Nom 23/32 in. thick wood structura

Page 2 of 5 1. Flooring Systems The flooring system shall consist of one of the following: System No. 1 Subflooring Nom 23/32 in. thick wood structura Page 1 of 5 Page Bottom Design No. L577 BXUV.L577 Fire-resistance Ratings - ANSI/UL 263 Design/System/Construction/Assembly Usage Disclaimer Authorities Having Jurisdiction should be consulted in all cases

More information

LISTING INFORMATION OF CCI Manufacturing Inc. - HiBAR SPEC ID: CCI Manufacturing Inc Ave. Edmonton, AB T5V 1K5 Canada

LISTING INFORMATION OF CCI Manufacturing Inc. - HiBAR SPEC ID: CCI Manufacturing Inc Ave. Edmonton, AB T5V 1K5 Canada LISTING INFORMATION OF CCI Manufacturing Inc. - HiBAR SPEC ID: 30390 CCI Manufacturing Inc. 16355-130 Ave Edmonton, AB T5V 1K5 Canada This report is for the exclusive use of Intertek s Client and is provided

More information

LISTING INFORMATION OF SIPA - Structural Insulated Panels (SIPs) SPEC ID: Structural Insulated Panel Association (SIPA) P.O.

LISTING INFORMATION OF SIPA - Structural Insulated Panels (SIPs) SPEC ID: Structural Insulated Panel Association (SIPA) P.O. LISTING INFORMATION OF SIPA - Structural Insulated Panels (SIPs) SPEC ID: 32805 Structural Insulated Panel Association (SIPA) P.O. Box 39848 Fort Lauderdale, FL 33339 This report is for the exclusive use

More information

BXUV.L576 - Fire Resistance Ratings - ANSI/UL 263. Fire Resistance Ratings - ANSI/UL 263

BXUV.L576 - Fire Resistance Ratings - ANSI/UL 263. Fire Resistance Ratings - ANSI/UL 263 Page 1 of 7 Page Bottom BXUV.L576 Fire Resistance Ratings - ANSI/UL 263 Fire Resistance Ratings - ANSI/UL 263 See General Information for Fire Resistance Ratings - ANSI/UL 263 Design No. L576 August 15,

More information

DIVISION: FINISHES SECTION: ACOUSTIC TREATMENT REPORT HOLDER: HOMASOTE COMPANY

DIVISION: FINISHES SECTION: ACOUSTIC TREATMENT REPORT HOLDER: HOMASOTE COMPANY 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1374 Reissued 06/2017 This report is subject to renewal 06/2018. DIVISION: 09 00

More information

Design No. M507. Design No. M507

Design No. M507. Design No. M507 1 of 5 3/17/2015 6:22 PM Design No. M507 BXUV.M507 Fire Resistance Ratings - ANSI/UL 263 Page Bottom Design/System/Construction/Assembly Usage Disclaimer Authorities Having Jurisdiction should be consulted

More information

Design No. U415 BXUV.U415 Fire-resistance Ratings - ANSI/UL 263. Design No. U415

Design No. U415 BXUV.U415 Fire-resistance Ratings - ANSI/UL 263. Design No. U415 Design No. U415 BXUV.U415 Fire-resistance Ratings - ANSI/UL 263 Page Bottom Design/System/Construction/Assembly Usage Disclaimer Authorities Having Jurisdiction should be consulted in all cases as to the

More information

REPORT HOLDER: KINETICS NOISE CONTROL 6300 IRELAN PLACE DUBLIN, OHIO EVALUATION SUBJECT: KINETICS NOISE CONTROL WAVE HANGER

REPORT HOLDER: KINETICS NOISE CONTROL 6300 IRELAN PLACE DUBLIN, OHIO EVALUATION SUBJECT: KINETICS NOISE CONTROL WAVE HANGER 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3207 Reissued 10/2016 This report is subject to renewal 10/2018. DIVISION: 09 00 00 FINISHES

More information

Design No. L565. Design No. L565

Design No. L565. Design No. L565 1 of 5 3/17/2015 6:18 PM Design No. L565 BXUV.L565 Fire Resistance Ratings - ANSI/UL 263 Page Bottom Design/System/Construction/Assembly Usage Disclaimer Authorities Having Jurisdiction should be consulted

More information

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1 FIRESTOP JOINT SPRAY CFS-SP WB SILICONE JOINT SPRAY CFS-SP SIL F-RATING 2-HR. 2-HR. T-RATING -HR. -HR. APPLICATION THICKNESS PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table /8" WET FILM (/6"

More information

UL Design System HW-D-1012 continued

UL Design System HW-D-1012 continued UL System No. HW-D-1012 Assembly Ratings 1, 2 and 3 Hr (See Item 2) Nominal Joint Width 3 in. Class II and III Movement Capabilities 100% Compression or Extension Page 1 of 5 1. Floor Assembly The fire-rated

More information

Duct Wrap Flexible Wraps

Duct Wrap Flexible Wraps Design No. 3MU/ 60-01 December 23, 2010 VENTILATION DUCT PROTECTION 3M Company 3M Fire Barrier Duct Wraps: 615 and 615+ 3M Fire Barrier Sealants: Water-Tight 1000-NS Silicone, Water-Tight 1003-SL Silicone

More information

FLOOR CEILING ASSEMBLY

FLOOR CEILING ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO SOLID WOOD JOIST FCWT RAL IN09-012 Toll Free (866) 774-2100 WWW.PAC-INTL.COM Fire Resistance Ratings CONSTRUCTION 3/8" HARDWOOD FLOORING VAPOR BARRIER 3/4 LT WT CONCRETE

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP-APPLIED WOOD COATINGS SECTION: SHEATHING REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP-APPLIED WOOD COATINGS SECTION: SHEATHING REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1365 Reissued 04/2018 This report is subject to renewal 04/2020. DIVISION: 06 00

More information

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No October 15, REPORT NO CRT-002d3

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No October 15, REPORT NO CRT-002d3 REPORT ACCREDITATION UNDER NVLAP 3933 US ROUTE 11 CORTLAND, NEW YORK 13045 Order No. 3166866 October 15, 2013 REPORT NO. 3166866CRT-002d3 IMPACT SOUND TRANSMISSION TEST AND CLASSIFICATION OF LAMINATE FLOORING

More information

BXUV.L521 - Fire Resistance Ratings - ANSI/UL 263. Fire Resistance Ratings - ANSI/UL 263

BXUV.L521 - Fire Resistance Ratings - ANSI/UL 263. Fire Resistance Ratings - ANSI/UL 263 Page 1 of 8 Page Bottom BXUV.L521 Fire Resistance Ratings - ANSI/UL 263 Fire Resistance Ratings - ANSI/UL 263 See General Information for Fire Resistance Ratings - ANSI/UL 263 Design No. L521 November

More information

NATIONAL GYPSUM COMPANY 2-Hour Area Separation Wall System

NATIONAL GYPSUM COMPANY 2-Hour Area Separation Wall System 0 00/NGC NATIONAL GYPSUM COMPANY -Hour Wall System The -Hour is a -hour fire wall consisting of in. (0. mm) light-gauge steel H-Studs that secure two layers of in. (. mm) shaftliner panels friction-fit

More information

CEYDC.R25563 Nonmetallic Plumbing System Components Listed for Fire Resistance

CEYDC.R25563 Nonmetallic Plumbing System Components Listed for Fire Resistance INFO 33, page 1 CEYDC.R25563 Nonmetallic Plumbing System Components Listed for Fire Resistance HEATLINK GROUP INC R25563 4603E 13TH ST NE CALGARY, AB T2E 6M3 CANADA Types Purelink PEXa, Heatlink PEXa and

More information

LEGACY REPORT. (800) (562) A Subsidiary of the International Code Council

LEGACY REPORT.   (800) (562) A Subsidiary of the International Code Council ICC-ES Legacy Report ER-5885 Reissued March 2004 www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council Legacy report on the 1997 Uniform Building Code, the 2000 International

More information

FIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079") WET FILM ± 7.5 ± 5

FIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079) WET FILM ± 7.5 ± 5 Design No. CEJ 27 P (HI/JS 20-05) Table. CONCRETE FLOOR ASSEMBLY: Max. two-hour rated concrete floor assembly made from either lightweight or normal weight concrete with a density of 00-50 pcf, with a

More information

ATI Evaluation Service A Division of Architectural Testing Certification Services

ATI Evaluation Service A Division of Architectural Testing Certification Services ATI Evaluation Service A Division of Architectural Testing Certification Services PCA-125 Subject to Renewal: 06/27/2018 Issued: 06/28/2017 Visit www.ati-es.com for current status Page 1 of 16 Framecad

More information

BXUV.U415 - Fire Resistance Ratings - ANSI/UL 263. Fire Resistance Ratings - ANSI/UL 263

BXUV.U415 - Fire Resistance Ratings - ANSI/UL 263. Fire Resistance Ratings - ANSI/UL 263 Page 1 of 7 Page Bottom BXUV.U415 Fire Resistance Ratings - ANSI/UL 263 Fire Resistance Ratings - ANSI/UL 263 See General Information for Fire Resistance Ratings - ANSI/UL 263 Design No. U415 July 30,

More information

DIVISION: FINISHES SECTION: ACOUSTIC TREATMENT REPORT HOLDER: ECORE INTERNATIONAL, INC.

DIVISION: FINISHES SECTION: ACOUSTIC TREATMENT REPORT HOLDER: ECORE INTERNATIONAL, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1522 Reissued 09/2016 This report is subject to renewal 09/2018. DIVISION: 09 00

More information

ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015.

ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015. A Subsidiary of the International Code Council DIVISION:

More information

PFC-5804* Reissued February 1, Filing Category: DESIGN Wood

PFC-5804* Reissued February 1, Filing Category: DESIGN Wood PFC-50* Reissued February 1, 2003 ICBO Evaluation Service, Inc. 530 Workman Mill Road, Whittier, California 9001 www.icboes.org Filing Category: DESIGN Wood PACIFIC WOODTECH CORPORATION PWI JOISTS PACIFIC

More information

LISTING INFORMATION OF Dryvit - Category 2 OUTSULATION NC EIFS Wall Systems SPEC ID: 29344

LISTING INFORMATION OF Dryvit - Category 2 OUTSULATION NC EIFS Wall Systems SPEC ID: 29344 LISTING INFORMATION OF Dryvit - Category 2 OUTSULATION NC EIFS Wall Systems SPEC ID: 29344 Dryvit Systems Canada 129 Ringwood Drive Stouffville, ON L4A 8C1 Canada This report is for the exclusive use of

More information

ICBO Evaluation Service, Inc Workman Mill Road, Whittier, California *Revised April 2003

ICBO Evaluation Service, Inc Workman Mill Road, Whittier, California *Revised April 2003 PFC-5804* Reissued February 1, 2003 ICBO Evaluation Service, Inc. 5360 Workman Mill Road, Whittier, California 90601 www.icboes.org Filing Category: DESIGN Wood PACIFIC WOODTECH CORPORATION PWI JOISTS

More information

Design No. L551. Design No. L551

Design No. L551. Design No. L551 1 of 7 3/17/2015 6:13 PM Design No. L551 BXUV.L551 Fire Resistance Ratings - ANSI/UL 263 Page Bottom Design/System/Construction/Assembly Usage Disclaimer Authorities Having Jurisdiction should be consulted

More information

FIRE DESIGN & INSTALLATION GUIDE

FIRE DESIGN & INSTALLATION GUIDE FIRE DESIGN & INSTALLATION GUIDE EWP FDIG US 06/02/2015 r 02/08/2018 2 Boise Cascade EWP Product Profiles BCI Joists and VERSA-LAM Beams Western (White City, OR) BCI Joists and VERSA-LAM Beams Eastern

More information

RSIC ACOUSTIC ASSEMBLY

RSIC ACOUSTIC ASSEMBLY RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD OPEN WEB TRUSS TFCSW RAL IN09-045 STC 56 IIC 73 CONSTRUCTION Carpet and Pad 3/4 T&G OSB Subfloor 11-1/4" Deep Open Web Truss @ 24" OC R-11

More information

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance Pei Evaluation Service is an accredited ISO Standard 17065 Product Certifier, accredited by the IAS. This Assembly Evaluation Report represents a product that Pei ES has Evaluated. This Assembly Evaluation

More information

ESR-1405 Reissued November 1, 2013 This report is subject to renewal December 1, 2015.

ESR-1405 Reissued November 1, 2013 This report is subject to renewal December 1, 2015. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-1405 Reissued November 1, 2013 This report is subject to renewal December 1, 2015. A Subsidiary of the International Code Council

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD I JOISTS REPORT HOLDER: REDBUILT LLC

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD I JOISTS REPORT HOLDER: REDBUILT LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2994 Reissued 08/2017 This report is subject to renewal 08/2019. DIVISION: 06 00

More information

RSIC ACOUSTIC ASSEMBLY

RSIC ACOUSTIC ASSEMBLY RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD OPEN WEB TRUSS TFCSW RAL IN09-044 STC 54 IIC 52 CONSTRUCTION Hardwood Flooring 1/16" Foam Underlayment 3/4 T&G OSB Subfloor 11-1/4" Deep

More information

RSIC ACOUSTIC ASSEMBLY

RSIC ACOUSTIC ASSEMBLY RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO SOLID WOOD JOIST FCWT RAL IN08-016 CONSTRUCTION Sheet Vinyl 1/2 Wood Underlayment 5/8 Plywood Subfloor (*L513 3/4 Ply) 2" X 10" Solid Wood Joist

More information

SECTION GYPSUM BOARD PART 1 - GENERAL

SECTION GYPSUM BOARD PART 1 - GENERAL SECTION 09250 - GYPSUM BOARD PART 1 - GENERAL 1.01 DESCRIPTION: A. Work under this section is subject to requirements of the Contract Documents including the General Conditions and Supplementary Conditions

More information

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued October 1, Legacy report on the 1997 Uniform Building Code

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued October 1, Legacy report on the 1997 Uniform Building Code LEGACY REPORT Reissued October 1, 2007 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office # 900 Montclair

More information

Code Compliance Research Report CCRR-0231

Code Compliance Research Report CCRR-0231 Code Compliance Research Report CCRR-0231 Issue Date: 09-01-2015 Revision Date: 10-01-2018 Renewal Date: 09-01-2019 DIVISION: 09 00 00 FINISHES Section: 09 24 00 Portland Cement Plastering REPORT HOLDER:

More information

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board. 1.2 RELATED WORK A. Installation of steel framing members for walls, partitions,

More information

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance Pei Evaluation Service is an accredited ISO Standard 17065 Product Certifier, accredited by the IAS. This Assembly Evaluation Report represents a product that Pei ES has Evaluated. This Assembly Evaluation

More information

R-Matte Plus-3: Insulation for the Building Envelope

R-Matte Plus-3: Insulation for the Building Envelope Attic and Crawl Space Applications R-Matte Plus-3 may be applied to the interior face of stud walls or roof rafters within attics and crawl spaces to provide a layer of continuous insulation (ci). Simply

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: EVALUATION SUBJECT: STRUCTURAL PANELS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: EVALUATION SUBJECT: STRUCTURAL PANELS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2182 Reissued 08/2018 This report is subject to renewal 06/2019. DIVISION: 06 00

More information

SECTION GYPSUM BOARD ASSEMBLIES

SECTION GYPSUM BOARD ASSEMBLIES PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 09260 - A. Metal stud wall framing. Denoted on drawings as "metal studs". B. Metal channel ceiling framing. C. Acoustic insulation and sealant. D. Cementitious

More information

FIRE DESIGN & INSTALLATION GUIDE

FIRE DESIGN & INSTALLATION GUIDE FIRE DESIGN & INSTALLATION GUIDE EWP FDIG 03/09/2011 2 EWP Product Profiles BCI Joists and VERSA-LAM Beams Western (White City, OR) BCI Joists and VERSA-LAM Beams Eastern (Lena, LA) ALLJOIST (St. Jacques,

More information

REPORT HOLDER: GYPSUM ASSOCIATION 962 WAYNE AVENUE, SUITE 620 SILVER SPRING, MARYLAND EVALUATION SUBJECT:

REPORT HOLDER: GYPSUM ASSOCIATION 962 WAYNE AVENUE, SUITE 620 SILVER SPRING, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 338 Reissued 02/208 This report is subject to renewal 02/209. DIVISION: 09 00 00

More information

WALL ASSEMBLIES. PHILLIPS MANUFACTURING CO. - Omaha, NE USA DESIGN NO. PMC/WA DESIGN NO. PMC/WA 60-01

WALL ASSEMBLIES. PHILLIPS MANUFACTURING CO. - Omaha, NE USA DESIGN NO. PMC/WA DESIGN NO. PMC/WA 60-01 WALL ASSEMBLIES PHILLIPS MANUFACTURING CO. - Omaha, NE USA DESIGN NO. PMC/WA 60-01 DESIGN NO. PMC/WA 60-01 1. Steel Framing Members (Floor, Sides, and Ceiling Runners)*: 'J'-shaped runner, minimum 2-1/2"

More information

Installation. Resilmount A237R. Installation Instructions. Furring channel sound isolation clip

Installation. Resilmount A237R. Installation Instructions. Furring channel sound isolation clip Resilmount A237R Furring channel sound isolation clip Installation Instructions Another Quality Building Product Installation A237R SPECIFICATIONS Width: 1-3/8 eight (including rubber): 1-1/16 Length:

More information

REPORT HOLDER: GYPSUM ASSOCIATION 6525 BELCREST ROAD #480 HYATTSVILLE, MARYLAND EVALUATION SUBJECT:

REPORT HOLDER: GYPSUM ASSOCIATION 6525 BELCREST ROAD #480 HYATTSVILLE, MARYLAND EVALUATION SUBJECT: 0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-338 Reissued 02/206 This report is subject to renewal 02/207. DIVISION: 09 00 00 FINISHES SECTION:

More information

FOR: CEMCO - California Expanded Metal Products Co. Sound Transmission Loss Test

FOR: CEMCO - California Expanded Metal Products Co. Sound Transmission Loss Test FOR: CEMCO - California Expanded Metal Products Co. Sound Transmission Loss Test Industry, CA ON: Bare 1 Inch Thick USG LEVELROCK Brand CSD Floor Underlayment on USG LEVELROCK SRM-25 Sound Mat on CEMCO

More information

SECTION GYPSUM BOARD

SECTION GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Gypsum board screw attached to wood framing and furring members, joint treatment, and accessories. 2. Installation of

More information

GenieMat FF. Floating Floor Systems for Airborne & Impact Sound and Vibration Isolation. It s not magic, it s engineering. Impact Sound Control

GenieMat FF. Floating Floor Systems for Airborne & Impact Sound and Vibration Isolation. It s not magic, it s engineering. Impact Sound Control It s not magic, it s engineering. Impact Sound Control GenieMat FF Floating Floor Systems for Airborne & Impact Sound and Vibration Isolation Patents: US 8240430, US8556029, CA 2500956, CA 2503420 GenieMat

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD I-JOISTS REPORT HOLDER: APA- THE ENGINEERED WOOD ASSOCIATION

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD I-JOISTS REPORT HOLDER: APA- THE ENGINEERED WOOD ASSOCIATION 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1405 Reissued 12/2017 This report is subject to renewal 12/2019. DIVISION: 06 00

More information

When demanding consistent quality, specify FIRM-FILL SCM-250 to assist in achieving highly improved IIC sound performance in multifamily

When demanding consistent quality, specify FIRM-FILL SCM-250 to assist in achieving highly improved IIC sound performance in multifamily When demanding consistent quality, specify FILL to assist in achieving highly improved sound performance in multifamily construction. FILL is an integral component of a well designed floor/ ceiling assembly.

More information

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel

More information

TYPICAL BEARING WALL FRAMING

TYPICAL BEARING WALL FRAMING BASIC WOOD FRAMING City of Grand Rapids Building Safety Division 218-326-7601 www.grandrapidsmn.org This handout is intended only as a guide and is based in part on the 2007 Minnesota State Building Code,

More information

1 Exam Prep Application and Finishing of Gypsum Board GA Tabs and Highlights

1 Exam Prep Application and Finishing of Gypsum Board GA Tabs and Highlights 1 Exam Prep Application and Finishing of Gypsum Board GA-216-2013 Tabs and s These 1 Exam Prep Tabs are based on the Gypsum Association GA-216-2013 Application and Finishing of Gypsum Panel Products. Each

More information

DIVISION: CONCRETE SECTION: CEMENTITIOUS WOOD FIBER DECKS DIVISION: FINISHES SECTION: ACOUSTIC ROOM COMPONENTS

DIVISION: CONCRETE SECTION: CEMENTITIOUS WOOD FIBER DECKS DIVISION: FINISHES SECTION: ACOUSTIC ROOM COMPONENTS 0 ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org Most Widely Accepted and Trusted ESR-1112 Reissued 05/2017 Revised 08/2018 This report is subject to renewal 05/2019.

More information

STEEL STUD, TRIMS AND ACCESSORIES FOR DRYWALL CONSTRUCTION MONTREAL TORONTO CALGARY EDMONTON VANCOUVER THE STRENGTH WITHIN

STEEL STUD, TRIMS AND ACCESSORIES FOR DRYWALL CONSTRUCTION MONTREAL TORONTO CALGARY EDMONTON VANCOUVER THE STRENGTH WITHIN STEEL STUD, TRIMS AND ACCESSORIES FOR DRYWALL CONSTRUCTION MONTREAL TORONTO CALGARY EDMONTON VANCOUVER THE STRENGTH WITHIN STEEL STUD AND TRACK FOR DRYWALL PARTITIONS TAKE ADVANTAGE OF THE SAVINGS IN TIME

More information

138 H-STUD AREA SEPARATION WALL SYSTEM

138 H-STUD AREA SEPARATION WALL SYSTEM H-STUD AREA SEPARATION WALL SYSTEM The fire-protection of gypsum-based Area Separation Walls is demonstrated in dramatic fashion by the results of this actual townhouse fire in which the two-hour fire-rated

More information

HIGH PERFORMANCE FIRE RETARDANT TREATED WOOD PRODUCTS

HIGH PERFORMANCE FIRE RETARDANT TREATED WOOD PRODUCTS TM HIGH PERFORMANCE FIRE RETARDANT TREATED WOOD PRODUCTS Innovators of high performance fire retardant products Class A Rated Fire Retardant Treated Wood Products TM Certified and Listed with Accredited

More information

1 Exam Prep Application and Finishing of Gypsum Board GA Tabs and Highlights

1 Exam Prep Application and Finishing of Gypsum Board GA Tabs and Highlights 1 Exam Prep Application and Finishing of Gypsum Board GA-216-2016 Tabs and s These 1 Exam Prep Tabs are based on the Gypsum Association GA-216-2016 Application and Finishing of Gypsum Panel Products. Each

More information

SECTION GYPSUM BOARD

SECTION GYPSUM BOARD SECTION 09250 GYPSUM BOARD PART 1GENERAL 1.1 SUMMARY A. Related Documents: General and Supplementary Conditions of the Contract, Division 1 - General Requirements, and Drawings are collectively applicable

More information

The System U.S. Patent No. 5,913,788

The System U.S. Patent No. 5,913,788 The System U.S. Patent No. 5,913,788 UL System No. HW-D-0027 2 Hour Rated Assembly (Metal Decking) UL System No. HW-D-0028 1 Hour Rated Assembly (Metal Decking) UL System No. HW-D-0208 1 Hour Rated Assembly

More information

SECTION R614 STRUCTURAL INSULATED PANEL WALL CONSTRUCTION

SECTION R614 STRUCTURAL INSULATED PANEL WALL CONSTRUCTION Section R614 Add new section to read as shown: (RB34-06/07) SECTION R614 STRUCTURAL INSULATED PANEL WALL CONSTRUCTION R614.1 General. Structural insulated panel (SIP) walls shall be designed in accordance

More information

ICC-ES Evaluation Report Reissued February 1, 2011 This report is subject to re-examination in one year.

ICC-ES Evaluation Report Reissued February 1, 2011 This report is subject to re-examination in one year. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-1826 Reissued February 1, 2011 This report is subject to re-examination in one year. A Subsidiary of the International Code Council

More information

Code Compliance Research Report CCRR 0232

Code Compliance Research Report CCRR 0232 Code Compliance Research Report CCRR 0232 Issued: 01 06 2016 Revised: 01 03 2018 Renewal Due: 01 06 2019 DIVISION: 06 17 00 WOOD, PLASTICS & COMPOSITES Section: 06 17 33 Wood I - Joists International Beams

More information

GYPSUM BOARD AND PLASTER

GYPSUM BOARD AND PLASTER CHAPTER 25 SECTION 2501 GENERAL 2501.1 Scope. 2501.1.1 General. Provisions of this chapter shall govern the materials, design, construction and quality of gypsum board, lath, gypsum plaster and cement

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: ENERCEPT, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: ENERCEPT, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1780 Reissued 11/2017 This report is subject to renewal 11/2019. DIVISION: 06 00

More information

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 11

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 11 07 21 16 Blanket Insulation Page 1 of 11 Unifrax I LLC Design No. UNI/BI 120-14 FIRE RESISTANT GREASE DUCT FyreWrap Elite 1.5 Duct Insulation ASTM E 2336-16 and ICC-ES Acceptance Criteria for Grease Duct

More information

SECTION CEMENTITIOUS WOOD FIBER DECKS

SECTION CEMENTITIOUS WOOD FIBER DECKS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 03 51 13 CEMENTITIOUS WOOD FIBER DECKS SPEC WRITE NOTES: 1. Delete between // // if not applicable to project. 2. Also delete any other item or paragraph not applicable

More information

BXUV.L548 - Fire Resistance Ratings - ANSI/UL 263. Fire Resistance Ratings - ANSI/UL 263

BXUV.L548 - Fire Resistance Ratings - ANSI/UL 263. Fire Resistance Ratings - ANSI/UL 263 Page 1 of 8 Page Bottom BXUV.L548 Fire Resistance Ratings - ANSI/UL 263 Fire Resistance Ratings - ANSI/UL 263 See General Information for Fire Resistance Ratings - ANSI/UL 263 Design No. L548 December

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS MARSHA L. BROWN PRESIDENT HELENA JUBANY VICE-PRESIDENT VAN AMBATIELOS VICTOR H. CUEVAS ELENORE A. WILLIAMS CITY OF LOS ANGELES CALIFORNIA ANTONIO R. VILLARAIGOSA

More information

ESR-1882 Reissued February 1, 2013 This report is subject to renewal February 1, 2014.

ESR-1882 Reissued February 1, 2013 This report is subject to renewal February 1, 2014. ICC-ES Evaluation Report www.icc-es.org (800) -8 () 99-0 ESR-88 Reissued February, 0 This report is subject to renewal February, 0. A Subsidiary of the International Code Council DIVISION: 0 00 00 WOOD,

More information

Report on Structural Stability of Engineered Lumber in Fire Conditions

Report on Structural Stability of Engineered Lumber in Fire Conditions Report on Structural Stability of Engineered Lumber in Fire Conditions Prepared by: Project Number: 07CA42520 File Number: NC9140 Underwriters Laboratories Inc. 333 Pfingsten Road, Northbrook, IL 60062

More information

NATIONAL GYPSUM COMPANY 3-Hour Area Separation Wall System

NATIONAL GYPSUM COMPANY 3-Hour Area Separation Wall System -Hour Wall System The -hour Wall System is a -hour fire wall consisting of two layers of in. (. mm) shaftliner panels friction-fit between in. (0. mm) light-gauge steel H-Studs and a layer of /" Fire-Shield

More information

Table R (1) Allowable Spans and Loads for Wood Structural Panels for Roof and Subfloor. Sheathing and Combination Subfloor Underlayment

Table R (1) Allowable Spans and Loads for Wood Structural Panels for Roof and Subfloor. Sheathing and Combination Subfloor Underlayment City of Republic - Community Development Department Roof and Subfloor Sheathing Spans Revision Date: January 2017 Table R503.2.1.1(1) Allowable Spans and Loads for Wood Structural Panels for Roof and Subfloor

More information

SECTION GYPSUM BOARD ASSEMBLIES

SECTION GYPSUM BOARD ASSEMBLIES PART 1 - GENERAL 1.1 SUMMARY SECTION 09 21 16 A. Provide gypsum board assemblies as shown and specified. Work includes: 1. Walls, partitions, and soffits, including metal framing systems. 2. Acoustical

More information

SECTION THERMAL INSULATION

SECTION THERMAL INSULATION PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 21 13 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

CONTRACT NUMBER: W912DQ-08-C % CORRECTED DESIGN 28 JULY 2008

CONTRACT NUMBER: W912DQ-08-C % CORRECTED DESIGN 28 JULY 2008 SECTION 092900 - GYPSUM BOARD 1.1 SUMMARY A. This Section includes the following: 1. Interior gypsum board. 2. Tile backing panels. B. Related Sections include the following: 1. Division 06 Section "Rough

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD I-JOISTS REPORT HOLDER: PACIFIC WOODTECH CORPORATION

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD I-JOISTS REPORT HOLDER: PACIFIC WOODTECH CORPORATION 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1225 Reissued 10/2017 This report is subject to renewal 10/2019. DIVISION: 06 00

More information

INSTALLATION GUIDE GUIDE TO ASC ISO-WALL CONSTRUCTION SYSTEM APPLICATION ISO-WALL SYSTEM. ASC Iso-Wall System Includes: Materials Required:

INSTALLATION GUIDE GUIDE TO ASC ISO-WALL CONSTRUCTION SYSTEM APPLICATION ISO-WALL SYSTEM. ASC Iso-Wall System Includes: Materials Required: ISO-WALL SYSTEM ACOUSTIC SCIENCES CORPORATION INSTALLATION GUIDE ASC Iso-Wall System Includes: 4" x 4" WallDamp Squares 1-1/2" x 48" WallDamp Strips 1-1/2" x 3" WallDamp RC Pads (optional) drc-1 (Damped

More information

SECTION GYPSUM BOARD & SHEATHING SYSTEMS

SECTION GYPSUM BOARD & SHEATHING SYSTEMS PART 1!GENERAL! 1.01! SECTION INCLUDES SECTION 09260 GYPSUM BOARD & SHEATHING SYSTEMS! Metal stud wall framing. Metal channel ceiling framing.! Gypsum board.! Sheathing.! Taped and sanded joint treatment.!

More information

FIGURE R502.2 FLOOR CONSTRUCTION

FIGURE R502.2 FLOOR CONSTRUCTION CHAPTER 5 FLOORS 11 I SECTION R501 GENERAL R501.1 Application. The provisions of this chapter shall control the design and construction of the floors for all buildings including the floors of attic spaces

More information

LISTING INFORMATION OF Dryvit - Category 1 OUTSULATION EIFS Wall Systems SPEC ID: 29311

LISTING INFORMATION OF Dryvit - Category 1 OUTSULATION EIFS Wall Systems SPEC ID: 29311 LISTING INFORMATION OF Dryvit - Category 1 OUTSULATION EIFS Wall Systems SPEC ID: 29311 Dryvit Systems Canada 129 Ringwood Drive Stouffville, ON, L4A 8A2 Canada This report is for the exclusive use of

More information

ESR-1826 Reissued May 1, 2009 This report is subject to re-examination in one year.

ESR-1826 Reissued May 1, 2009 This report is subject to re-examination in one year. ICC-ES Evaluation Report ESR-1826 Reissued May 1, 2009 This report is subject to re-examination in one year. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council

More information