PHILMONT WAREHOUSE BUILDING PRELIMINARY STRUCTURAL ASSESSMENT
|
|
- Teresa Mosley
- 5 years ago
- Views:
Transcription
1 PHILMONT WAREHOUSE BUILDING PRELIMINARY STRUCTURAL ASSESSMENT Prepared for: GATTER ARCHITECTS 111 MAIN ST. PHILMONT, NY Prepared by: TACONIC ENGINEERING, DPC PO BOX 272 CHATHAM, NY TACONIC #:13016 DATE: MAY 2013
2 TABLE OF CONTENTS I. INTRODUCTION II. III. IV. DESCRIPTION OF EXISTING STRUCTURAL COMPONENTS STRUCTURAL ASSESSMENT SUMMARY PHOTO SUMMARY APPENDIX A BUILDING SECTION
3 PHILMONT WAREHOUSE BUILDING MAY 2013 PRELIMINARY STRUCTURAL ASSESSMENT PAGE No. 3 I. INTRODUCTION As requested, Taconic Engineering has conducted an overall structural assessment of the Philmont warehouse building on Elm St ext. in the village of Philmont NY. The focus of the assessment was to determine the structural configuration of the building, outline areas of concern, and provide preliminary recommendations for repair in areas where warranted. It should be understood, due to concealed nature of many components the review was conducted on a broad scale and does not fully address all problems that may exist with the building. The purpose of the assessment was to determine the general state of the exposed components and brings to light any major issues that may exist. Additionally, this report does not evaluate the building for code compliance pertaining to life and safety issues, nor does it address potential modifications that would be required of the building should the change in use classification occur. A site visit was conducted on April 23rd, The assessment was strictly visual in nature. No material testing or destructive evaluation was performed to compile the report. The report is broken down into four parts. Part II of this report outlines the existing configuration and physical description of each structural component. Part III outlines problems observed along with preliminary recommendations for corrective action. Part IV is a photo summary of the building and issues observed. A section of the building construction is attached for reference.
4 PHILMONT WAREHOUSE BUILDING MAY 2013 PRELIMINARY STRUCTURAL ASSESSMENT PAGE No. 4 II. DESCRIPTION OF EXISTING STRUCTURAL COMPONENTS The building consists of one large open space of ± 71 x40 or approx. 2,840 ft². The space has a height of ± 22 from slab to bottom of trusses. Based on the construction techniques it appears to be built in the late 19 th century and was likely constructed as a support facility for the neighboring mills. A narrative summary of the structural components of the building is provided below. 1. Foundation Stone masonry Stone footings presumed 2. Floor Construction Concrete slab on grade 3. Wall construction Brick masonry construction (3) (4) wythe. 4. Roof Heavy Timber Trusses Wood Decking 2X8 presumed Metal Roofing Panels
5 PHILMONT WAREHOUSE BUILDING MAY 2013 PRELIMINARY STRUCTURAL ASSESSMENT PAGE No. 5 III. ASSESSMENT SUMMARY In general, the structural composition of the building was found to be in fair condition. Major items of concern were observed and are indicated below in bold text. These items pertain to load bearing elements and may lead to life safety issues should corrective action not be taken. The remaining items are minor in scale however, should be addressed during the renovation process to ensure the long term integrity of the structure. Summaries of the issues observed with each structural component of the building are provided below. As indicated, items of greater concern are indicated by bold text. A structural photo summary is included in Appendix A to aid in the description process and section of the building is shown in appendix B. The following items are the major issues discovered during the assessment. 1. Deteriorated wood sheathing & truss members. 2. Failed metal roof system. 3. Grade elevation and drainage of the east elevation. With decay in the trusses and sheathing and leaks in the roof significant improvements must be made to the roof system during the restoration process. The walls and foundation in general are in good condition with no major structural concerns. The current 200 amp electrical service may need to be upgraded depending on the HVAC system chosen for restored space. No water or sewer service was noted for the building. No environmental assessment was conducted however a phase 1 should be considered based on the past industrial use of the facility. Although reinforcement and repair is required the structure was found to be stable and sound. No issue was discovered that should preclude the restoration or reuse of the building.
6 PHILMONT WAREHOUSE BUILDING MAY 2013 PRELIMINARY STRUCTURAL ASSESSMENT PAGE No. 6 A. ROOF 1. As part of the assessment process a scissor lift was utilized to inspect the individual timber trusses that frame the roof system. Due interference with stored items in the space not all portions of the trusses were accessible and additional issues may exist. Following is a summary of the issues observed at each of the truss members identified on the locator sketch above. a. White mildew was noted on the on truss #1. Pick tests revealed no apparent decay. b. The top cord of truss #2 was wet. Pick testing resulted in penetration of ¼ in several locations c. Pick testing the bottom cord of truss #2 at the east web bearing location resulted in >2 penetration. d. The web bolt at truss #3 is loose. e. Sheathing decay was noted between the web members of the east side of truss #4. f. Wet sawdust was noted near the ridge of truss #5 indicating possible burrowing insects and leaks of the roof system. g. The bottom cord of truss #6 has extensive checking which may require reinforcement. *Although strength analysis and reinforcement design is beyond the scope of this assessment, repair of the decayed members would likely involve epoxy resin repairs. In addition it should be noted the concealed tops of the upper cord members likely have extensive decay which should be revealed, assessed and repaired during the roof replacement process below. 2. The current corrugated metal roofing is failing in several locations and complete replacement is recommended. Water infiltration and
7 PHILMONT WAREHOUSE BUILDING MAY 2013 PRELIMINARY STRUCTURAL ASSESSMENT PAGE No. 7 associated decay of wood members was noted in several areas. This style of metal roof is connected with screws penetrating the panel and sealed with a rubber grommet gasket. As the gasket material breaks down the roof is no longer water tight at the penetration point. Due to the extent of renovation proposed a more permanent roof system is recommended. 3. The roof sheathing appears to be T&G planking. Cursory review indicates a thickness greater than 3 is required to support current snow loading requirements. The thickness, species, and condition of the sheathing must be reviewed during the roof replacement. 4. Sheet metal soffits have been installed around the building, likely to prevent birds from nesting in these areas. Restoration of the soffits may be desired during the renovation process.
8 PHILMONT WAREHOUSE BUILDING MAY 2013 PRELIMINARY STRUCTURAL ASSESSMENT PAGE No. 8 B. Brick Masonry Walls 1. The grade on the east side of the building extends above the foundation and up along the brick masonry wall. The bricks below grade are subject to degradation from the wet condition below grade. In addition the bricks are permeable and moist condition was noted along the inside of the west wall. Although the brick in this area did not appear soft future degradation is expected and the moist condition is not acceptable for a finished space. Excavation of the east side is recommended down to the stone foundation with the brick to be assessed and covered with an impermeable membrane. Proper drainage should be designed and installed with the area backfilled and graded as desired. 2. There is a vertical crack in the north end of the west wall extending from the top of the wall to the bottom. The crack appears to extend through the wall as it is apparent on both sides. The crack is likely due to differential foundation settlement. Although the crack appears stable now crack monitors should be installed and reviewed to determine if the separation is progressing. Depending on results of the monitoring remediation would involve repointing or reinforcing by stitching or epoxy injecting the crack. 3. The mortar of the exterior brick masonry is deteriorated and or missing in several locations. Extensive repointing of the brick masonry is required. Depending on the aesthetic requirements of the finished walls complete joint grinding and repointing may be required. The worse areas are noted on the locator sketch above.
9 PHILMONT WAREHOUSE BUILDING MAY 2013 PRELIMINARY STRUCTURAL ASSESSMENT PAGE No There is a small crack above the top west window of the rear wall. This crack appears minor and should be repointed and monitored for future movement. 5. The windows of the south wall are partially in filled. These areas should be opened for windows again or the infill completed to provide a continuous wall surface. 6. An area along the top center of the east wall is missing bricks and requires repair and infill brick masonry to provide a continuous wall surface
10 PHILMONT WAREHOUSE BUILDING MAY 2013 PRELIMINARY STRUCTURAL ASSESSMENT PAGE No. 10 C. Foundation / Floor Slab 1. Several cracks were noted in the concrete slab floor of the building. Depending on the design requirements for the new space the current floor should be replaced or covered. 2. Several burrow holes were noted along the perimeter of the building. These holes should be filled and measures taken to eradicate the animals. 3. A drain in the center of the floor day lights through the south wall of the building. This drain should be removed and the penetration sealed. 4. The sump hole in the north west corner of the slab should be filled.
11 IV. PHILMONT WAREHOUSE BUILDING PHOTO SUMMARY TACONIC #: North Elevation West Elevation South Elevation 1
12 East Elevation Interior looking south Interior looking North 2
13 Fungal decay on timber truss Pick test penetration Wet sawdust at ridge 3
14 Severe checking Corrugated metal roof Plank sheathing 4
15 Tin metal soffit Grade above bickline Moist interior wall 5
16 Cracked masonry wall Deteriorated brick and mortar to repair and repoint Crack above rear window 6
17 Incomplete infill Wall masonry to repair Cracked floor slab 7
18 Burrow holes under foundation Interior floor drain Exterior floor drain discharge 8
19
Groundwater Seepage. Causes of Basement Seepage and Leaks Hydrostatic Pressure
Groundwater Seepage The following guide can be used by you and your crews when assessing seepage at a property. Bear in mind that this guide is not all-inclusive, and should be used in a supplementary
More informationCarroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage
Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage The following list of code requirements is intended to assist you in complying with the Code of Public
More informationNathan Clifford School Building Conditions Assessment Report
Nathan Clifford School Building Conditions Assessment Report Submitted To: The City of Portland April 12, 2013 Prepared By: Winton Scott Architects Becker Structural Engineers, Inc. Conditions Assessment
More informationExterior Elevated Elements Inspection Guidelines
Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code
More informationStructural Condition Assessment
108 6 th Street, Garland, Texas Engineering Report Date: September 29, 2016 RLG No. : 16729 Prepared for: Mr. Jeff D. Bulls III AIA 3030 LBJ Freeway, Suite 1220 Dallas, TX 75234 PM: Harold F. Phillips
More informationSTRUCTURAL CONDITION ASSESSMENT
STRUCTURAL CONDITION ASSESSMENT ALLEN JAY ROCK GYM 1201 FAIRFIELD ROAD HIGH POINT, NC Prepared for: Prepared by: Guilford County Schools 617 West Market Street Greensboro, NC Adrian S. Durham, PE, SE,
More informationSTRUCTURAL BUILDING CONDITION SURVEY
STRUCTURAL BUILDING CONDITION SURVEY Our Project No. 140565 Prepared For: Mayfair Hotel Development Corporation Date: 3 December 2014; Revised: 15 December 2014 15 December 2014 Mayfair Hotel Development
More informationROOME & GUARRACINO, LLC Consulting Structural Engineers 48 Grove Street Somerville, MA Tel: Fax:
ROOME & GUARRACINO, LLC Consulting Structural Engineers 48 Grove Street Somerville, MA 02144 Tel: 617.628.1700 Fax: 617.628.1711 March 3, 2016 Mr. Jeff Hoover, Principal Tappe Architects, 6 Edgerly Place
More informationFEMA P-593 STEP-BY STEP PRESCRIPTIVE RETROFIT FOR CRIPPLE WALL BRACING & ANCHORAGE TO FOUNDATION
INTRODUCTION Objective of provisions: The provisions of IEBC Appendix Chapter A3 are intended to reduce hazard of earthquake-induced damage (IEBC A301.1). These provisions are not intended to eliminate
More informationEast Lyme Middle School EAST LYME MIDDLE SCHOOL
Description: N EAST LYME MIDDLE SCHOOL The school consists of a multi story building with lower, main and upper level floors. The typical floor framing for the main and upper levels is wide flange steel
More informationEidem Farm Brooklyn Park, MN
Eidem Farm Brooklyn Park, MN East Farm House Structural Condition Assessment Prepared By 1 0 0 P O R T L A N D A V E N U E S O U T H, S U I T E 1 0 0 M I N N E A P O L I S, M I N N E S O T A 5 5 4 0 1
More informationSTRUCTURAL ASSESSMENT OBSERVATION REPORT
Consulting Engineers THORSON BAKER & Associates, Inc. 3030 West Streetsboro Road (330) 659-6688 phone Richfield, Ohio 44286 (330) 659-6675 fax www.thorsonbaker.com STRUCTURAL ASSESSMENT OBSERVATION REPORT
More informationFIELD COPY ATTACHMENT
FIELD COPY ATTACHMENT The released plans for the project must be on site and available to the inspectors at all times. No inspection will be done without the released field plans. If you have any questions,
More informationIntroduction. LLB wishes to thank the Trustees, Director and Building Committee of the Gleason Public Library for their assistance and guidance.
1 E x e c u t i v e s u m m a r y Introduction Architect Lerner Ladds + Bartels and engineers Simpson Gumpertz & Heger were selected to provide services to investigate and determine the causes of deterioration
More informationSTRUCTURAL EVALUATION
SMELTER BUILDINGS STRUCTURAL EVALUATION Resolution Copper Mining, LLC West Plant Area September 7, 2016 Safety Share Preventable Motor Vehicle Accidents 1. Aim High in Steering. 2. Get The Big Picture.
More informationSubject: Amphitheater School District Reroofing Projects Amphi High School, Building 900 Roof Evaluation SCI Project Number:
27 June 2016 Mr. Shane Chism, AIA Breckenridge Group 4625 E. Fort Lowell Road Tucson, Arizona 85712 Subject: Amphitheater School District Reroofing Projects Amphi High School, Building 900 Roof Evaluation
More informationStructural Inspection
General: Background: An inspection and structural analysis have been performed for the purpose of evaluating the buildings structural systems and components. A full set of structural drawings was utilized
More informationACCESSORY BUILDING. Building Permit Requirements: (must be completed before submitting application)
ACCESSORY BUILDING Before your application can be deemed complete and ready for processing you will need the following: (Please hand in entire application package including this cover sheet) Zoning- check
More informationAtlas-Helical & ATLAS RESISTANCE PIERS. LOOK OUT! New House Headed South!
Atlas-Helical & ATLAS RESISTANCE PIERS CASE STUDY 110-9 Atlas-Helical Slab s and Atlas Resistance s are Used to Restore and Stabilize a New House Atlanta, Georgia Installed by: Atlas s of Atlanta Alpharetta,
More informationEXECUTIVE SUMMARY INTRODUCTION Terms of Reference Building Description Documents Reviewed SUMMARY OF FIELD DATA 4
Abbott Place Wood Framed Window Condition Assessment May 30, 2012 TABLE OF CONTENTS EXECUTIVE SUMMARY 1 1.0 INTRODUCTION 2 1.1 Terms of Reference 2 1.2 Building Description 3 1.3 Documents Reviewed 3 2.0
More informationSite Bldg Fiscal Yr System Sub-System. Verde Valley Site site 2014/15 Parking Paving. Verde Valley Site site 2014/15 Sidewalks
Site Bldg Fiscal Yr System Sub-System Site site 2014/15 Parking Paving Site site 2014/15 Sidewalks Skill Center L 2015/16 Architectural Partitions Site Site 2015/16 Parking Striping Arc Center M 2014/15
More informationNo structural deficiencies were observed to the west exterior elevation.
August 9, 2016 Ms. Jennifer Spencer, AIA, NCARB Gary W. Anderson Architects 200 Prairie Street, Suite 201 Rockford, IL 61107 Subject: Structural Observations 227 North Wyman Street Rockford, IL Dear Ms.
More informationSparks Engineering, Inc. S T R U C T U R A L E V A L U A T I O N, D E S I G N A N D T E S T I N G
Sparks Engineering, Inc. S T R U C T U R A L E V A L U A T I O N, D E S I G N A N D T E S T I N G February 29, 2008 Ms. Leslie Wolfenden Save Austin's Cemeteries PO Box 41814 Austin, TX 78704 (512) 917-1666
More informationJAY E. BUTLER, being first duly sworn deposes and states as follows: 1. I am a Professional Engineer licensed in the State of New York.
SUPREME COURT OF THE STATE OF NEW YORK COUNTY OF NEW YORK In the Matter of DEVELOP DON T DESTROY BROOKLYN; Index No. DANIEL GOLDSTEIN; ATLANTIC AVENUE BETTERMENT ASSOCIATION; RJI No. FORT GREENE ASSOCIATION;
More informationWEATHERTIGHTNESS (INVASIVE MOISTURE TESTING) ASSESSMENT
WEATHERTIGHTNESS (INVASIVE MOISTURE TESTING) ASSESSMENT 1 INTRODUCTION Inspection Date: 24 TH August 2016 Job No:47126 Property Inspected: 1-51 Watford Street Christchurch Weather Conditions: Fine Prepared
More informationRepair methods of the roofing structures. Mon
Repair methods of the roofing structures Mon 29.02.2016 Course Content Introduction & Conservation The use of ICT for condition assessment of structures Repair of fire damage Repair methods of the roofing
More informationBUILDING A NEW HOME. Construction Permit Tips For Home Owners
BUILDING A NEW HOME Construction Permit Tips For Home Owners This publication provides guidelines for constructing a detached singlefamily home. The code requirements herein are not all inclusive and should
More informationSt. Mark s Presbyterian Church
St. Mark s Presbyterian Church Hawkins County, Tennessee Preservation Assessment and Recommendations St. Mark s Presbyterian Church Hawkins County, Tennessee Historic Overview, Needs Assessment, and Recommendations
More informationSECTION 39 - MANHOLES TABLE OF CONTENTS
Section SECTION 39 - MANHOLES TABLE OF CONTENTS Page 39-1 GENERAL... 39.1 39-2 CONCRETE MANHOLES... 39.1 39-2.01 NOT USED... 39.1 39-2.02 Concrete Storm Drain Manholes... 39.1 39-3 SADDLE SEWER MANHOLES...
More informationMoonlight Architecture, Inc. Architecture Interior Design Site Planning
Moonlight Architecture, Inc. Architecture Interior Design Site Planning 22 May 2018 18057 Mr. Michael J. Petit de Mange, County Administrator Kent County Levy Court 555 Bay Road Dover, DE 19901 RE: Facilities
More information2/23/2009 R15-R20R20
Foundations What is important to know about foundations? You (probably) won t design it What are the components that make up a properly designed and built foundation? Determine whether house has a good
More informationMondol Fabrics Ltd. Nayapara,kasimpur, Gazipur ( N, E0) 8th March 2014
Mondol Fabrics Ltd Nayapara,kasimpur, Gazipur (23.990028N, 90.317336E0) 8th March 2014 1 2 Observations 3 Column Stresses in Toilet Area North of Building Cursory calculations indicate that column size
More informationRECREATIONAL EAGLE CENTER METAL ROOF ASSESSMENT AND SOLUTION
RECREATIONAL EAGLE CENTER METAL ROOF ASSESSMENT AND SOLUTION Recreational Eagle Center (00550) La Crosse, WI DSF Project No. 07H1E SEG Project No. 10975 Prepared for Division of State Facilities 101 E.
More informationREPORT OF BUILDING INSPECTIONS TECOLUCA, EL SALVADOR. Prepared by: Global Village Engineers
REPORT OF BUILDING INSPECTIONS TECOLUCA, EL SALVADOR Prepared by: Global Village Engineers 23 JANUARY, 2001 23 January 2001 Senor Carlos Cortez Hernandez Alcaldia Municipal de Tecoluca San Vicente, El
More informationTOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit:
TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION 355-7575 Ext. 395 Needed to Obtain Permit: 1. Building Permit Application, and/or residential plumbing permit application, as applicable, to be
More informationEASTERN HIGH SCHOOL. Site Plan East Capitol Street, N.E., Washington, DC INITIAL YEAR BUILT 1923
INITIAL YEAR BUILT 1923 BUILDING AREA 288,800 SF CURRENT PROGRAM CAPACITY 1,425 ENROLLMENT 2008 565 WARD 6 PROPOSED PROGRAM CAPACITY 1,100 Site Plan EASTERN - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationStone and Masonry Veneer
Stone and Masonry Veneer R703.7 Stone and masonry veneer, general. Stone and masonry veneer shall be installed in accordance with this chapter, Table R703.4 and Figure R703.7. These veneers installed over
More informationSEATTLE CENTRAL COLLEGE BROADWAY PERFORMANCE HALL SEATTLE, WASHINGTON STRUCTURAL EVALUATION FOR PREPARED BY PCS STRUCTURAL SOLUTIONS
STRUCTURAL EVALUATION FOR SEATTLE CENTRAL COLLEGE BROADWAY PERFORMANCE HALL SEATTLE, WASHINGTON PREPARED BY PCS STRUCTURAL SOLUTIONS NOVEMBER 1, 2017 17-733 TABLE OF CONTENTS Page I. PREFACE ii II. EXECUTIVE
More informationRadon Resistant New Construction. Topic 8 - Audio 64
Topic 8 - Audio 64 EPA Map of Radon Zones Designations drawn in by county boundary to match code jurisdictions Indicates the potential for a short-term measurement in the lowest portion of the home to
More informationIntroduction. This Part One will address; Type 1 Fire Resistive and Type 2 Noncombustible buildings.
Introduction This Part One will address; Type 1 Fire Resistive and Type 2 Noncombustible buildings. The future presentations, will cover; Type 3 Ordinary Type 4 Heavy Timber and Type 5 Wood Frame buildings.
More informationBWA ENVIRONMENTAL CONTROL BOARD (ECB) APPLICATION
BWA ENVIRONMENTAL CONTROL BOARD (ECB) APPLICATION To: The Environmental Control Board I propose to: (please check all that apply) * Repaint my home/garage. Color samples are submitted herewith and are
More informationLEWIS ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1962 BUILDING AREA 49,500 SF CURRENT PROGRAM CAPACITY 550 ENROLLMENT 2008 288 WARD 1 PROPOSED PROGRAM CAPACITY 450 Site Plan LEWIS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5
More informationThe Ashland Project. Total Area: 1,778 Sq.Ft. 3 Bedroom, 2 Bath, 2 Car Garage
The Ashland Project Total Area: 1,778 Sq.Ft. 3 Bedroom, 2 Bath, 2 Car Garage The garage and bedroom extend from the front of this three bedroom home, drawing you visually into the entryway. Brick and stucco
More informationGAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT
GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT STRUCTURAL FOR CUSTOMS HOUSE JULY 2014 i P a g e Table of Contents 1. INTRODUCTION 3 1.1 Design Criteria and Specifications..
More informationThe Inspection Process. Waxhaw N.C.
The Inspection Process In Waxhaw N.C. This information is provided by the Waxhaw Enforcement Division to assist you in the progression of your project. Nothing in this document should be considered "Code"
More informationCITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures
CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE - 268-5161 Residential Accessory Structures This information has been compiled for the benefit of any person
More informationCity of Westerville Guide to Commercial Inspections
City of Westerville Guide to Commercial Inspections FOOTINGS - After the excavation, with the form work and any required reinforcing steel in place. All footings shall have loose soil removed, reinforcing
More information2019 IAQA Annual Meeting
Daniel Stih, CMC. CIEC Healthy Living Spaces Stanley Yeskolski CIEC, CMC Investigative Inspection Services Inc. 2 Purpose The presentation will provide a over view of: Installation Details Problem Areas
More informationCALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE 01. GENERAL ADMINISTRATION 6% Project Administration 1%
CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE EXAM ID: I1 80 multiple-choice questions 3-1/2-hour time limit Open book 01. GENERAL ADMINISTRATION 6% 0101. Project Administration 1% Verify that
More informationINSPECT DIRECT Pty Ltd
Web Page: www.inspectdirect.com.au INSPECT DIRECT Pty Ltd Property Address: Sample.Dilapidation.Report Victoria Building Status / Dilapidation Report This is not a Pest Inspection The Building Status /
More informationKORA_Req._for_Eng._Studies_on_Stouffer_Apts. KU Reference No
000130 1 PURPOSE: Professional Engineering Consultants, P.A. (PEC) was engaged by University of Kansas Design & Construction Management to perform an assessment of Stouffer Place Apartment Building 20
More informationDetached Garages and Building Permits. 1 and 2 Family Dwellings
Detached Garages and Building Permits 1 and 2 Family Dwellings Why do I need a permit? The City of Minneapolis adopts the State of Minnesota Building Code (MNSBC) and its associated state statutes and
More informationNational Property Inspections
Monday, August 22, 2011 Inspector Joe Smith 548-254-3658 Page 1 of 33 GENERAL INFORMATION GENERAL CONDITIONS AT TIME OF INSPECTION : No Property Occupied : Property Faces : North South East þ West Year(s)
More informationA Design Review of Waterproofing Codes
A Design Review of Waterproofing Codes Section 1807 of Chapter 18 of the International Building Code addresses waterproofing under the section title of Dampproofing and Waterproofing. The section defines
More informationConditions Report St. John s Episcopal Church Youngstown, NY. June Hamilton Houston Lownie Architects Siracuse Consulting Engineers
Conditions Report St. John s Episcopal Church Youngstown, NY June 2009 Lownie Architects Siracuse Consulting Engineers St. John s Episcopal Church Main & Chestnut Streets Youngstown, NY 14174 Conditions
More informationCHAPTER VI. -- FOUNDATION REPAIR & DAMP PROOFING TABLE OF CONTENTS
CHAPTER VI. -- FOUNDATION REPAIR & DAMP PROOFING TABLE OF CONTENTS 30.50 (1.) Application for Building Permit 30.50 (2.) Best Management Standards for Foundation Repair 30.50 (3.) Definitions 30.50 (4.)
More informationEstimated Cost Ranges for Completing Residential Flood Protection Projects
Estimated Ranges for Completing Residential Flood Protection Projects Introduction to the Home Flood Protection Program The Home Flood Protection Program is an educational service designed to help homeowners
More informationWhat s Gray, Gets Hard, and Holds Up Your Home?
Concrete Foundation Association of North America 1 THE Resource for Contractors, Producers, Engineers and Suppliers in the Concrete Foundation Industry Mission Statement To unite, in common organization,
More informationPrepared By. Accent Building Sciences Inc. For
ROOF LEAK INVESTIGATION & CONDITION ASSESSMENT REPORT For Toronto, Ontario Prepared By Accent Building Sciences Inc. For Client# 40105 Date: November 11, 2003 November 2003 Roof Leak Investigations & Condition
More informationMr. Eric Ryffel, Manager October 5, 2015 Sanibel Beach Club 626 Nerita Street Sanibel Island, Florida 33957
TRC Worldwide Engineering Restoration & Inspection, LLC 11926 Fairway Lakes Drive Fort Myers, Florida 33913 Phone: (239) 939-1414 F: (239) 278-4289 www.trcww.com C.O.A. No. 30761 Mr. Eric Ryffel, Manager
More informationKEVIN BURNS BUILDING INSPECTIONS REGISTERED BUILDER PRE-PURCHASE VISUAL STRUCTURAL INSPECTION REPORT No. 822
KEVIN BURNS BUILDING INSPECTIONS REGISTERED BUILDER 6163 PRE-PURCHASE VISUAL STRUCTURAL INSPECTION REPORT No. 822 CLIENT: Talavera PROPERTY ADDRESS: Mindarie DATE: 20 April 2017 TIME: 9.00am WEATHER: Fine
More informationProperty Condition Assessment. Summary Report
www.real-estate-inspections.com Property Condition Assessment Summary Report Subject Property Prepared for: Client in Detroit File Number: 05-15-005 Inspector: Craig Milliken, PE CPM Real Estate Inspections,
More informationLithia Dodge East 5500 L St. Omaha, NE
Lithia Dodge East 5500 L St. Omaha, NE Perimeter Photos Failed Joints at North Rear Wall Control Joints Look Good Inadequate Downspout Elbows Erosion Along Wall Minor Efflorescence Roof Section Photos
More informationGroup Eight Engineering Limited
Group Eight Engineering Limited Structural Mechanical Electrical 499 King Street East, Suite 200 Hamilton, ON L8N 1E1 Consulting Engineers Tel: (905) 525-6069 Fax: (905) 528-7310 E-Mail: info@group8eng.com
More informationSTUCCO FAILURES and REMEDIATION Roger G. Morse AIA
STUCCO FAILURES and REMEDIATION Roger G. Morse AIA Morse Zehnter Associates Rensselaer Technology Park 165 Jordan Road Troy, NY 12180 rgmorse@mzaconsulting.com Florida Environment Hot Humid High ground
More informationCCIM Central Canada Chapter. Richard Weldon, P.Eng., LEED AP Carson Dunlop Weldon & Associates Ltd. October 5,
Minimizing Risk When Purchasing or Leasing CCIM Central Canada Chapter Richard Weldon, P.Eng., LEED AP Carson Dunlop Weldon & Associates Ltd. October 5, 2010 www.cdwengineering.com Who We Are CDW is a
More informationProperty Condition Assessment
Property Condition Assessment Pewaukee, WI 53072 Inspection Date: 1/6/15 Prepared For: Report Number: Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar Dr. Pewaukee, WI 53072
More informationSITE AND BUILDING INSPECTION CHECKLIST
PARISH BUILDING Page 1 of 6 SITE AND GROUNDS DATE INIT COMMENTS DATE INIT COMMENTS Ramps & Provisions for Handicap Designated parking spaces for Handicap Has soil dropped or heaved Is there standing water
More information04/05/2014. Introductions. Agenda. Heritage Adaptive Reuse: A Catalyst for Revitalization
Heritage Adaptive Reuse: A Catalyst for Revitalization Susan Spencer Lewin, OAA, CS&P Architects Scott Weir, OAA, ERA Architects Introductions Susan Spencer Lewin, CS&P Architects Scott Weir, ERA Architects
More informationEMERGENCY MANAGEMENT PREPAREDNESS AND ASSISTANCE TRUST FUND ARC 4496 Evaluation Questionnaire
EMERGENCY MANAGEMENT PREPAREDNESS AND ASSISTANCE TRUST FUND ARC 4496 Evaluation Questionnaire Additional Instructions and Clarifications 1. Please review ARC 4496 before beginning the project identification
More information0103 Plan Reading 4% Read plans to verify the project conforms with the code, approved plans, and construction documents.
Certification: Commercial Building Inspector Exam ID: B2 Scope: A Commercial Building Inspector will be responsible for performing inspections of structures to determine compliance with the various Building
More informationEvaluation, Restoration and Protection of Sandstone Façade on a Historic Building The Boston Building Denver, CO Presenter: Leo Whiteley
Circa 1910 Evaluation, Restoration and Protection of Sandstone Façade on a Historic Building The Boston Building Denver, CO Presenter: Leo Whiteley Boston Loft Building History On Southeast corner of 17
More informationRESIDENTIAL BUILDING PLAN REQUIREMENTS
CITY OF MANSFIELD BUREAU OF BUILDING AND CODES 30 NORTH DIAMOND STREET 3RD FLOOR MANSFIELD, OHIO 44902 Phone (419) 755-9688 Fax (419) 755-9453 www.ci.mansfield.oh.us RESIDENTIAL BUILDING PLAN REQUIREMENTS
More informationSchool Assessment Report
School Assessment Report School: Humphries Elementary School Report: Nov 17, 2015 Condition Assessment: Suitability Assessment: Generated: 11/17/2015 10:35:17 AM FOR OFFICIAL USE ONLY Final School Assessment
More informationARCHITECTURAL EXPANSION JOINT PRE-INSTALLATION INSPECTION
Date Project Name Location (city/state) Project Address Installer: Architect /Engineering Firm: General Contractor: Your Name: Contact Person: Contact Person: Phone: Phone: Phone: Mobile: Mobile: Mobile
More informationRESIDENTIAL BUILDING PERMIT GUIDE FOR MULTI-FAMILY DWELLINGS
RESIDENTIAL BUILDING PERMIT GUIDE FOR MULTI-FAMILY DWELLINGS New Construction, Addition, or Alteration All plans submitted must be prepared, sealed, and signed by a Registered Nebraska Design Professional
More informationSECTION 39 - MANHOLES TABLE OF CONTENTS 39-1 GENERAL PRECAST CONCRETE MANHOLES
Section SECTION 39 - MANHOLES TABLE OF CONTENTS 39-1 GENERAL... 39-1 39-2 PRECAST CONCRETE MANHOLES... 39-1 39-2.01 Precast Concrete Storm Drain Manholes... 39-1 39-3 SADDLE MANHOLES... 39-2 39-3.01 Saddle
More informationARTICLE 12 INTERNATIONAL RESIDENTIAL CODE 2012 International Residential Code Modification Summary (Statutory Authority: 1976 Code Section )
8-1200. International Residential Code. ARTICLE 12 INTERNATIONAL RESIDENTIAL CODE 2012 International Residential Code Modification Summary (Statutory Authority: 1976 Code Section 6-9-40) NOTE-This article
More informationCALIFORNIA BUILDING PLANS EXAMINER CONTENT OUTLINE 01. GENERAL ADMINISTRATION 3 % Project Administration 3%
CALIFORNIA BUILDING PLANS EXAMINER CONTENT OUTLINE EXAM ID: I6 80 multiple-choice questions 3-1/2-hour time limit Open book 01. GENERAL ADMINISTRATION 3 % 0101. Project Administration 3% Verify that plans,
More informationCITY OF HAGERSTOWN PLANNING & CODE ADMINISTRATION DEPARTMENT. Submittal Requirements
CITY OF HAGERSTOWN PLANNING & CODE ADMINISTRATION DEPARTMENT 1 East Franklin Street Phone: 301-790-4163 Third Floor Hagerstown, MD 21740 Fax: 301-791-2650 BUILDING PERMIT APPLICATION FOR RESIDENTIAL ACCESSORY
More informationBUILDING SURVEYOR S INSPECTION REPORT OLD CO-OP BAKERY SUBSTATION - WEST CALDER FOR COMMUNITY DEVELOPMENT TRUST WEST CALDER.
BUILDING SURVEYOR S INSPECTION REPORT OF OLD CO-OP BAKERY SUBSTATION - WEST CALDER FOR COMMUNITY DEVELOPMENT TRUST WEST CALDER Prepared by SEPTEMBER 2017 Accessibility Statement In accordance with the
More informationChristchurch City Council
36 Lichfield Street Detailed Engineering Evaluation Quantitative Assessment Report Christchurch City Council 36 Lichfield Street Kathmandu/Rexel Building Detailed Engineering Evaluation Quantitative Assessment
More informationToronto Community Housing Executive Summary 2016/2017. BCA Report. Sample House High FCI
BCA Report Porfolio Development Size Construction TCHC - All Op Units Scattered Units (CHU 20),005 Sq.Ft. 925 Floor Above Grade 2 Divisional Units Page of 43 Description This dwelling unit is a detached
More informationMasonry Study. Club House and Jr. Club House Pequot Yacht Club Southport, Connecticut 03-44
Club House and Jr. Club House Southport, Connecticut 03-44 669 Harbor Road Southport, Connecticut 06890 Architect: Martin A. Benassi, AIA Architect Two Broadway Hamden, CT 06518 Date: Table of Contents
More informationArts Center- Building needs
Arts Center- Building needs Built in 1928 Last renovated in 1986 Priority 1- fascia repair Loose, rotting and missing fascia needs to be replaced to prevent water intrusion. There are seven different pieces
More informationFundamentals of Building Construction: Materials and Methods
Fundamentals of Building Construction: Materials and Methods Allen, Edward ISBN-13: 9780470074688 Table of Contents Preface. Chapter 1: Making Buildings. Learning to Build. Sustainability. The Work of
More informationAdministrative Changes
Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings
More informationvia only:
July 22, 2011 via email only: lschultz@mcmproperty.com The Board of Directors of The Solace Condominium c/o Ms. Linda Schultz, Condominium Manager MCM Property Management Ltd. 200 1010 8 th Avenue SW Calgary,
More informationGUIDELINES FOR RETAINING WALLS 4-0 IN HEIGHT OR LESS
GUIDELINES FOR RETAINING WALLS 4-0 IN HEIGHT OR LESS Version 2014-11-11 Prepared by: Building Development Division Department of Development Services 5 County Complex Ct. Suite 120 Prince William, VA 22192
More informationSCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC Permit Requirements
SCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC. 320-226.5189 www.101developmentresources.com While every attempt has been made to insure the correctness of this handout, no guarantees are made to its accuracy
More informationSTRUCTURAL ASSESSMENT SURVEY REPORT
Level 6, River Park House, 225 High Road, Wood Green, London N22 8HQ Tel: 020 8489 5504 Fax: 020 8489 5229 Email: building.control@haringey.gov.uk www.haringey.gov.uk Head of Building Control Robert McIver
More informationStructural Conditions Assessment of Current Lapeer District Schools Administration Building 250 Second Street, Lapeer, Michigan
November 2, 2015 Melissa A. Malcolm Library Director Lapeer District Library 201 Village West Dr S Lapeer, MI 48446 RE: Structural Conditions Assessment of Current Lapeer District Schools Administration
More informationLimited Exterior Masonry Assessment Roosevelt Elementary School
Limited Exterior Volume 2 of 2 November 29. 2007 Produced for: Medford Public Schools Medford, Oregon In Consultation with: 710 NE 21 st Avenue, Suite 200, Portland, Oregon 97232 P: 503.517.0283 F: 503.517.0285
More informationU.S. EDITION RESIDENTIAL CONSTRUCTION DETAILS SAMPLE. A visual guide to construction detailing. Emma Walshaw
RESIDENTIAL CONSTRUCTION DETAILS U.S. EDITION A visual guide to construction detailing Emma Walshaw Contents INTRODUCTION 4 PRINCIPLES OF CONSTRUCTION DETAILING 6 FOUNDATIONS 9 PRINCIPLES OF FOUNDATION
More informationStucco Moisture Inspection Report
Website:www.ibgoodinspector.com E-Mail:support@ibgoodinspector.com January 11, 2006 Stucco Moisture Inspection Report Property Address 123 Our Street OurTown, USA 12345 Report Ordered By: Mr. & Mrs. Client
More informationIncluded in our report are our visual observations, recommendations for follow-up evaluation, and conceptual repair recommendations.
Ms. Pamela J. Irwin Community Management Associates 384 Ralph McGill Blvd Atlanta, GA 30312 Re: Phase I Condition Assessment Central City Condominiums Pool Deck Atlanta, Georgia Walter P Moore Project
More informationStructural Inspection Report
Revision: Issue 2 Date: 23 rd June 2014 Cherry Pvt. Ltd. Florence Fashions Ltd. Ultimate Ltd. Chandand Fashion Ltd. Joy Fashion Ltd. Structural Inspection Report Authors: Adrian Ryan, Cathal Mac an tsearraigh
More informationcomponent was performing its intended function; installation and condition were appropriate for age and use.
April 23, 2012 Dear Home Seller, On April 6, 2012, Cities Inspection Service, Inc. completed a home inspection of the property located at 123 Oak Drive, Somewhere, Minnesota for you. Doug Hastings did
More informationNote on the assessment:
EXCERPTS Note on the assessment: The following is an excerpt from the book Post-disaster shelter: 10 Designs, IFRC, 2013. Inclusion of this design is for information purposes and does not necessarily imply
More informationSt. Charles Community Unit School District 303
St. Charles Community Unit School District 303 Mold Conditions Report For Norris Recreation Center August 2, 2012 By ATS&R Planners/Architects/Engineers Report by: David M. Maroney AIA / NCARB Architect
More information