1 Project: Barrabool Hills Shopping Centre Subject: Environmental Noise Addressee: Lascorp Development Group (Aust) Pty Ltd Issued To: Rob Harris Date: 4 September 2012 Reference: Prepared by: David Dolly (Director) B.App.Sc. M.A.A.S AAAC Member of the Association of Australian Acoustical Consultants

2 Acoustic Consulting Australia Pty Ltd. Page 2 of 13 CONTENTS 1.0 INTRODUCTION AND CONSULTING SCOPE PROJECT DETAIL AND NOISE SENSITIVE AREAS Noise Sensitive Locations STATUTORY NOISE LIMITS State Environment Protection Policy Noise Limits Calculated for this Site ENVIRONMENTAL NOISE CONTROL FOR PLANT & EQUIPMENT Refrigeration and Air Conditioning Condensers Air Conditioning & Refrigeration Compressors & Air Handling Unit Plant Room Plant Room Forced Ventilation Small Roof Mounted Fans Specialty Retail Shops - Air Conditioning Units ENVIRONMENTAL NOISE CONTROL FOR THE LOADING DOCK CONCLUSION... 12

3 Acoustic Consulting Australia Pty Ltd. Page 3 of Introduction and Consulting Scope This report addresses the environmental noise control design requirements for the proposed retail development at the site at the corner of Province Boulevard and Stoneleigh Crescent in Barrabool. This report relates to this particular project and must not be applied to any other project without prior consultation with Acoustic Consulting Australia Pty Ltd as project designs and conditions can vary from project to project causing variation in acoustic performance and advice. This report addresses the range of noise sources that are associated with a proposed development of this type and makeup. These noise sources include operational noise from mechanical plant and equipment (ventilation, air conditioning and refrigeration) as well as noise form loading dock activities. 2.0 Project Detail and Noise Sensitive Areas The development involves the establishment of new buildings on the subject site as well as new plant and equipment to serve the major tenancy (a supermarket) and smaller specialty retail stores. Refrigeration and air conditioning plant is to be predominantly located at the roof level of the proposed buildings. Some of this equipment will operate on a 24 hour basis. Some of the equipment will be located on an open roof platform while other plant will be located in a dedicated plant room established at roof/mezzanine level. 2.1 Noise Sensitive Locations The site is located adjacent to residential and abuts a church to the east. Overall, the noise sensitive locations applicable to this evaluation are shown in the plan below. It is noted that the topography of this local areas varies significantly several residences will be or are elevated and will look across that the roof of the new store. Residences represented by R1 are at a lower elevation. Many of these residences are not existing; however construction in this well locality is underway. Residences represented by R2 will be at a similar or greater elevation; however this may vary depending on the location and type of future dwellings. This land is currently divided up for residential development.

4 Acoustic Consulting Australia Pty Ltd. Page 4 of 13 Diagram 1: Key Compliance Locations 3.0 Statutory Noise Limits 3.1 State Environment Protection Policy The Environment Protection Authority (EPA) set limits on the level of noise, which a commercial operation can emit to a residential area. The limits are determined by applying the procedures set out in the State Environment Protection Policy No. N-1 (SEPP N-1). The SEPP N-1 policy is technically applicable only in the Melbourne Metropolitan area; however this policy is used directly in rural town centres where ambient noise levels can be typical of a suburban setting.

5 Acoustic Consulting Australia Pty Ltd. Page 5 of 13 Based on our site assessment work we believe that it would be appropriate to apply the assessment methods described by the SEPP N-1 policy at this site. According to the SEPP N-1 Policy criteria, the noise level limits are calculated for each residence location individually and take account of the following factors. (i) (ii) (iii) The time of day (day, evening or night). The proportions of land zoned for residential, industrial and commercial use in the immediate local area. The background noise level, which would occur at the residence if activities associated with the commercial premises were not occurring. 3.2 Noise Limits Calculated for this Site In this case the permissible noise levels have been determined based on background noise measurements made in the area of the residences R1 to R3 and current land use zoning information obtained from the Department of Planning and Community Development. The permissible noise levels are as follows: Table 1 SEPP N-1 Permissible Noise Levels for R1, R2 and R3 Permissible Noise Level, db(a) Week Day (7am to 6pm) Saturday (7am-1pm) Weekday (6pm-10pm) Saturday (1pm-10pm) Sunday (7am-10pm) All Days (10pm-7am) The permissible levels must be met outside the residential dwelling not greater than 10m from a habitable room. It should also be noted that the evening permissible noise limit calculation procedure is also applied to Saturday (1pm to 6pm) as well as Sunday and Public Holidays (7am to 6pm). 4.0 Environmental Noise Control for Plant & Equipment 4.1 Refrigeration and Air Conditioning Condensers Base on previous projects it is anticipated that up to 4 air-cooled condenser will be installed onto the roof mounted platform. It is understood that the platform be placed as shown below:

6 Acoustic Consulting Australia Pty Ltd. Page 6 of 13 Diagram 2: Location of Platform for Air Cooled Condensers Based on current supermarket design approaches it is anticipated that condenser fans will be driven by variable speed fans and that condensers will be Buffalo Trident LDV-NQ or LDV-SQ type or equivalent EC alternative. Preliminary calculations have been made based on three medium size condensers (8 fans) and one large condenser (10 fans). One of the medium size condensers is assumed for the air conditioning system. The following has been determined in relation to noise control: It is recommended that each refrigeration condenser meet a noise level specification of 62dB(A) at a reference distance of 3m when operating at full daytime load. This level would be achieved via model type and size selection. The noise rating must be reduced to 56dB(A) at 3m during the night period by capping the fan speed as required (likely to be 70% of full speed).

7 Acoustic Consulting Australia Pty Ltd. Page 7 of 13 Localised acoustic screening will be required along the west, south and east sides of the platform to achieve adequate noise control to all existing and future residences at and around locations R1 and R3. The mezzanine plant room can be used to achieve acoustic screening to then north (R2) provided that the top of the parapet wall is not less than 1200mm above the top of the tallest condenser. The plant room wall facing into the condenser deck area will require as sound absorptive finish to control sound reflection in the directions of R1 and R3. This lining will comprise of a 75mm thick acoustic insulation faced with a Melinex liner (20micron thick) and a perforated metal finish (11% open). The extent of this lining will be determined during the detailed design stages. The screens must extend to a height of not less than 1000mm above the top of the condenser fans. The screens must completely eliminate line of site to any condenser from any residence on the residential zone development. The anticipated screening extent is as follows: Diagram 3: Acoustic screening layout The main screens should be constructed as indicated in Diagram 3 (below). A 0.6mm custom orb could be used as an alternative to the cladding shown. Screens should extend down to the top of the platform; the platform can be open below the screen to allow air to flow to the condensers however the gap must be screened as shown schematically below:

8 Acoustic Consulting Australia Pty Ltd. Page 8 of 13 Diagram 4: Acoustic screening design concept Important: The height of the sub screen (below the platform) and the main screen will vary depending on direction and final platform elevation and this should be reviewed during the detailed design phase of the project. The sub screen must extend to a height of not less than 1000mm above the top of the platform. The screening system should be reviewed once the platform elevation and plant layout on the platform are confirmed. 4.2 Air Conditioning & Refrigeration Compressors & Air Handling Unit The air conditioning and refrigeration compressor units must be located inside the dedicated and acoustically treated plant room. It is anticipated that the air conditioning air handling unit would similar be placed in the plant room or on the external platform. 4.3 Plant Room For the purpose of this evaluation allowance has been made for a typical supermarket store compressor room and air handling unit installation including a plant room ventilation system. The plant room must include the following designs: Roof: Metal decking on thermal insulation with a 1x13mm plasterboard ceiling.

9 Acoustic Consulting Australia Pty Ltd. Page 9 of 13 Walls: Masonry (150 Precast Concrete Panel) or light weight system having a Sound Reduction index (R w ) of not less than R w 60. Doors: Any door between the plant room and the exterior must be a 40mm thick (solid timber core) doors fitted with acoustic seals rated to R w 30. Ventilation Openings to the plant room will require acoustic rating in the form of a 300 or 600mm thick acoustic louvre (depending on the final location). Louvres should be placed on the south side of the plantroom where escaping noise will be attenuated by the acoustic screening around the condenser deck. Some of the above may be varied during the design development phase as the noise control requirements will depend on the final layout of the plant room. 4.4 Plant Room Forced Ventilation The plant room ventilation fans should be located within the plant room. Roof mounted fans should not be used for the plant room at this site. The fans must meet a noise level rating of 62dB(A) at a distance of 1m outside the intake and/or exhaust point. A 1400mm long sound attenuator should be allowed for between each fan (supply and exhaust) and plant room envelope penetration. The acoustic performance of these sound attenuators will need to be determined during the detailed design phase once the fan selections are made. The intake and exhaust points could be via the east wall or roof but should not be via the west, north or south walls. 4.5 Small Roof Mounted Fans We refer to the following equipment times typically included in a supermarket: Chicken Hood O/A Fan Meat Prep O/A Fan Bakery Hood O/A Fan Stock room exh Fan x 2 Chicken Hood Exh Fan Meat Prep Exh Fan Bakery Hood Exh fan Donut Hood Exh Fan Dishwasher Exh Fan Seafood Prep Fan Toilet Exh Fan Small air conditioning condensers Liquor Air conditioning Unit

10 Acoustic Consulting Australia Pty Ltd. Page 10 of 13 The following are recommended to achieve compliance with noise limits: I. Fans may be located on or just above the store roof. II. III. IV. No fans should be within 15m of the northern, western or southern edge of the building. No fan should be placed on the loading dock roof. All fans must be reviewed upon selection to determine if dedicated sound attenuation is required (i.e. possible screening or repositioning). The selection of quieter slow running fans is recommended for this project. Fans will be required to meet a specification of 55dB(A) at a horizontal distance of 3m unless otherwise agreed based on fan position and acoustic screening provision. 4.6 Specialty Retail Shops - Air Conditioning Units These are anticipated to be small split system air conditioning systems that will operate only during normal business hours. Based on the proposed locations for the small stores and preliminary calculations it is likely that modest noise control (e.g. Acoustic screens) will be needed to control noise emitted to the south and west. A further review should be initiated once equipment details are available. 5.0 Environmental Noise Control for the Loading Dock The proposed location for the loading dock necessitates some very specific noise control recommendations: Recommendations: A. Deliveries to the store should be restricted to the period 7am to 10pm. No deliveries should be permitted outside these hours. This curfew would apply to all delivery trucks. B. The roof over the loading dock should be extended as indicated in diagram 5 (below). The roof will of traditional metal deck construction; however a sound absorptive soffit is recommended to the soffit. This insulation lining would be a 75mm thick, 24kg/m 3 density acoustic grade insulation with a perforated foil facing. The insulation must be exposed to the loading dock noise and so must not be clad over with plasterboard or similar. The northern wall along the loading dock/truck bay should extend to match the extent of the roof and must extend to the roof line. No gaps should be permitted between the head of this wall and the underside of the roof.

11 Acoustic Consulting Australia Pty Ltd. Page 11 of 13 Diagram 5: Loading Dock and Boundary Noise Control Treatment C. The all trucks (large and small) should be unloaded in the screened and roofed zone. D. It is recommended that a 2.1m tall acoustic fence be constructed along the northern site boundary as indicated above: This fencing height recommended is shown to scale in the diagram above. The fence should be constructed using the design shown in diagram 6 (below) and must take account of the following: The design must ensure that all gaps and openings are eliminated. The fence must remain gap and opening free over time. Alternative materials such as compressed cement sheet, masonry, thick plywood can all be considered for the acoustic fencing. Compressed cement sheeting should be at least 10mm thick and must be sealed at panel joints. Ply should be at least 30mm thick and must also be sealed at the joints.

12 Acoustic Consulting Australia Pty Ltd. Page 12 of 13 Diagram 6: Acoustic Fence Construction Note: Double storey residences should not be permitted at residential lots adjacent to the fence to avoid overlooking of the acoustic fence to the loading dock. If double storey residences are to be permitted then some acoustic upgrade work would be recommended for upstairs bedrooms/living spaces of the dwellings concerned. 6.0 Conclusion Environmental noise associated with air conditioning, refrigeration and ventilation plant proposed at the subject site has been considered.

13 Acoustic Consulting Australia Pty Ltd. Page 13 of 13 It is concluded that noise emissions can comply with the statutory noise limits described this report provided that the noise controls described are implemented. A curfew on delivery times is recommended along with acoustic fencing and roofing to attenuate truck movement noise and noise from truck unloading. David Dolly Acoustic Consulting Australia Pty Ltd

Acoustic Consulting Australia PtyLtd. I Consultants on Noise and Vibration P0 Box 332

Acoustic Consulting Australia PtyLtd. I Consultants on Noise and Vibration P0 Box 332 Pg 'P. Acoustic Consulting Australia PtyLtd. I Consultants on Noise and Vibration P0 Box 332 Heidelberg i#i..wr. David, u.,0 Victoria 3054 Phone 0412 375 234 Email: acausteblgpond.corn ABN 49 095 932 092

More information

Acoustic Design Criteria

Acoustic Design Criteria Apartment Acoustics Apartment Buildings Acoustic Design Criteria Building Code of Australia: - Intertenancy walls and floors - Corridor walls and doors - Floor impact isolation - Lift, stair and core walls

More information

442 CHELTENHAM ROAD KEYSBOROUGH. Noise Control Considerations. Prepared for Bridport Property Group Level 1, 170 Bridport Street, Albert Park VIC 3206

442 CHELTENHAM ROAD KEYSBOROUGH. Noise Control Considerations. Prepared for Bridport Property Group Level 1, 170 Bridport Street, Albert Park VIC 3206 442 CHELTENHAM ROAD KEYSBOROUGH Noise Control Considerations Prepared for Bridport Property Group Level 1, 170 Bridport Street, Albert Park VIC 3206 Ref. 11649-1ng.docx 22 December 2014 TABLE OF CONTENTS

More information

MECHANICAL PLANT FOR COMMERCIAL BUILDINGS

MECHANICAL PLANT FOR COMMERCIAL BUILDINGS MECHANICAL PLANT FOR COMMERCIAL BUILDINGS Excessive noise from the operation of mechanical plant can disturb residents, disrupt sleep, interfere with normal daily activities and significantly impact on

More information

Proposed Childcare and Café within SHA Development, Girven Road, Mount Maunganui - Noise Assessment

Proposed Childcare and Café within SHA Development, Girven Road, Mount Maunganui - Noise Assessment 14 June 2016 Momentum Planning and Design Tauranga Dear Sir, Re: Attention: Richard Coles 1.0 Dear Sir Re: Proposed Childcare and Café within SHA Development, Girven Road, Mount Maunganui - Noise Assessment

More information

CARRYING OUT NOISE ASSESSMENTS FOR PROPOSED SUPERMARKET DEVELOPMENTS

CARRYING OUT NOISE ASSESSMENTS FOR PROPOSED SUPERMARKET DEVELOPMENTS Acoustics 2008 Geelong, Victoria, Australia 24 to 26 November 2008 Acoustics and Sustainability: How should acoustics adapt to meet future demands? CARRYING OUT NOISE ASSESSMENTS FOR PROPOSED SUPERMARKET

More information

Roma to Brisbane Pipeline Dalby Compressor Station Upgrade Environmental Management Plan. Appendix 8. Noise Assessment

Roma to Brisbane Pipeline Dalby Compressor Station Upgrade Environmental Management Plan. Appendix 8. Noise Assessment Roma to Brisbane Pipeline Dalby Compressor Station Upgrade Environmental Management Plan Appendix 8 Noise Assessment PR104962-1 Rev 0; June 2011 PR104962-1 Rev 0; June 2011 Roma to Brisbane Pipeline Dalby

More information

Day Night Day Night Day Night Residential site and amphitheatre Green Non residential site boundary Red

Day Night Day Night Day Night Residential site and amphitheatre Green Non residential site boundary Red Plant Areas External plant must meet the following noise suppression requirement as adopted by the Landlord: 1. Air handling units 45db measured at 3metres from source. 2. Heat rejection plant 45db measured

More information

Sound and Vibration Consulting Engineers ABN

Sound and Vibration Consulting Engineers ABN ABN 44 133 737 443 www.acousticconsulting.com.au Acoustic Consulting Engineers Pty Ltd PO Box 3450 PUTNEY NSW 2112 Telephone: +61 (0) 2 8006 5560 Facsimile: +61 (0) 2 8006 5559 info@acousticconsulting.com.au

More information

Section 10 Residential Zone

Section 10 Residential Zone 231 Section 10 Residential Zone Proposed Draft Amendments to Section 10: Residential Note: new text to be added to the District Plan is shown as coloured underlined and text to be removed is shown in coloured

More information

Technical Supplement. Internal Fire and Acoustic Rated Floor Solution INTERIORS

Technical Supplement. Internal Fire and Acoustic Rated Floor Solution INTERIORS Technical Supplement Internal Fire and Acoustic Rated Floor Solution INTERIORS Australia June 2017 Make sure your information is up to date. When specifying or installing James Hardie products, ensure

More information

8. Appendix F Acoustic Assessment

8. Appendix F Acoustic Assessment 8. Appendix F Acoustic Assessment HFT Ltd 06-Jun-2017 Assessment of Noise Effects Mixed Industrial Development at 28 Inlet Road, Takanini Mixed Industrial Development at 28 Inlet Road, Takanini Client:

More information

Status: Rev: Comments Date: Author: Reviewer:

Status: Rev: Comments Date: Author: Reviewer: MB ASSESSMENT OF NOISE EFFECTS Rp 002 R02 2016907 3 May 2018 84 Symonds Street PO Box 5811 Wellesley Street Auckland 1141 New Zealand T: +64 9 379 7822 F: +64 9 309 3540 www.marshallday.com Project: MB

More information

Contents. Timber framing to be installed in accordance with AS:1684 Metal framing to be installed in accordance with BCA Volume: 2

Contents. Timber framing to be installed in accordance with AS:1684 Metal framing to be installed in accordance with BCA Volume: 2 Contents BCA Codes 3 General 4 Fire Performances Thermal and Acoustic Insulation Wall Installation 4 Timber Frame Separation Walls 5 Steel Frame Separation Walls 6 External Fire Rated Walls 7 Floor Installation

More information

appendix 19 acoustic insulation requirements

appendix 19 acoustic insulation requirements appendix 19 acoustic insulation requirements AP19.1 Airport Effects Control Overlay Ap19.1.i The provisions in Tables 1 and 2 are the minimum measures which are an approved method of complying with the

More information

Building regulations now in force

Building regulations now in force BCA Section J: Guide to compliance Publication date July 2008 Building regulations now in force BCA SECTION J: Mandatory energy efficiency measures for non-residential construction The new BCA Section

More information

UC Press Building 2120 Berkeley Way Berkeley, CA

UC Press Building 2120 Berkeley Way Berkeley, CA CONSTRUCTION NOISE REDUCTION PROGRAM FOR: UC Press Building 2120 Berkeley Way Berkeley, CA RGD Project #: 17-057 PREPARED FOR: Berkeley Way, LLC 1958A University Ave. Berkeley, CA 94704 PREPARED BY: Harold

More information

LOTS 2 & 3 ANKETELL ROAD, ANKETELL SUBDIVISION ACOUSTIC ASSESSMENT FOR TERRANOVIS

LOTS 2 & 3 ANKETELL ROAD, ANKETELL SUBDIVISION ACOUSTIC ASSESSMENT FOR TERRANOVIS Rochdale Holdings Pty Ltd A.B.N. 85 009 049 067 trading as: HERRING STORER ACOUSTICS Suite 34, 11 Preston Street, Como, W.A. 6152 P.O. Box 219, Como, W.A. 6952 Telephone: (08) 9367 6200 Facsimile: (08)

More information

Noise Feasibility Study Proposed Residential Development, 361 Tanbark Road Niagara-on-the-Lake, Ontario

Noise Feasibility Study Proposed Residential Development, 361 Tanbark Road Niagara-on-the-Lake, Ontario Noise Feasibility Study Proposed Residential Development, 361 Tanbark Road Niagara-on-the-Lake, Ontario Prepared for: Blythwood Homes Inc. 7058 Ridgewood Crescent Niagara Falls, Ontario L2J 3H1 Prepared

More information

WAIKATO POWER PLANT SH31, KAWHIA ROAD OTOROHANGA ASSESSMENT OF NOISE EFFECTS

WAIKATO POWER PLANT SH31, KAWHIA ROAD OTOROHANGA ASSESSMENT OF NOISE EFFECTS 1/355 Manukau Road Epsom, Auckland 1023 PO Box 26283 Epsom, Auckland 1344 T: 09 638 8414 E: hegley@acoustics.co.nz WAIKATO POWER PLANT SH31, KAWHIA ROAD OTOROHANGA ASSESSMENT OF NOISE EFFECTS Report No

More information

FACT SHEET 1 SOUND INSULATION GUIDELINES. Key Issues and Considerations. Sound Absorption and Sound Insulation

FACT SHEET 1 SOUND INSULATION GUIDELINES. Key Issues and Considerations. Sound Absorption and Sound Insulation SOUND INSULATION GUIDELINES If you are purchasing or renovating a home in the inner city it is important to consider acoustic design. Good acoustic design will reduce noise from services, external areas

More information

Noise Feasibility Study EMGO (North Oakville I) Ltd., Town of Oakville, Ontario

Noise Feasibility Study EMGO (North Oakville I) Ltd., Town of Oakville, Ontario Noise Feasibility Study EMGO (North Oakville I) Ltd., Town of Oakville, Ontario For Emgo (North Oakville I) Ltd. 2173 Turnberry Road Burlington, ON L7M 4P8 Prepared by Victor Garcia, BASc Reviewed by Sheeba

More information

Design. Boral CinemaZone Fact Sheet. Windows. Acoustic sealants. Sound absorptive panels. Ventilation. Floor coverings. The vision.

Design. Boral CinemaZone Fact Sheet. Windows. Acoustic sealants. Sound absorptive panels. Ventilation. Floor coverings. The vision. Windows Like doorways, windows can be a significant source of sound leakage. For maximum isolation, windows should either be removed or built over internally - leaving the house facade unaffected. If natural

More information

Stationary Noise Feasibility Study. The Shops of Tenth Line. Ottawa, Ontario

Stationary Noise Feasibility Study. The Shops of Tenth Line. Ottawa, Ontario Stationary Noise Feasibility Study The Shops of Tenth Line Ottawa, Ontario REPORT: GWE13-040 Stationary Noise Prepared For: Jeff Parks 225 Metcalfe Street Ottawa, Ontario K2P 1P9 Prepared By: Thomas Couper,

More information

Noise Impact Assessment

Noise Impact Assessment Noise Impact Assessment December 2016 Prepared by SRL Technical Services Ltd Telephone +44(0)1787 247595 Website www.srltsl.com London, Birmingham, Manchester, Sudbury Quality Assurance Project Title Document

More information

ATTACHMENT 2 DRC Page 1 of 13

ATTACHMENT 2 DRC Page 1 of 13 Page 1 of 13 CLEAR GLASS 7' - 6" SPANDREL GLASS CLEAR GLASS SOLID PHENOLIC PANEL MEAT PREP 206 EMPLOYEE LOCKERS 181 VARIES 8' - 1" 2' - 9" 3' - 1" 2' - 8" 2' - 5" 0'-0" 19' - 6" SECTION @ SOUTH WALL Scale:

More information

O. NOISE. 1. Existing Conditions. 2. Future without the Proposed Project

O. NOISE. 1. Existing Conditions. 2. Future without the Proposed Project O. NOISE 1. Existing Conditions Existing ambient noise conditions at the Project Site reflect surrounding land uses. As described previously (see Chapter 3.A, Land Use, Zoning and Public Policy), predominant

More information

External Steel Stud and Top Hat Walls. Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185

External Steel Stud and Top Hat Walls. Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185 Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185 GENERAL REQUIREMENTS 185 FRAMING 185 PLASTERBOARD LAYOUT 189 PLASTERBOARD FIXING 190 EXTERIOR

More information

Noise Feasibility Study Proposed Residential Building 103 Dundas Street West Oakville, Ontario

Noise Feasibility Study Proposed Residential Building 103 Dundas Street West Oakville, Ontario Noise Feasibility Study Proposed Residential Building 103 Dundas Street West Oakville, Ontario Prepared for: 103 Dundas Corporation Attn: Zaki Wahbeh 2184 Providence Road Oakville, ON L6H 6Z2 Prepared

More information

Assessing external noise impacts for apartments

Assessing external noise impacts for apartments Assessing external noise impacts for apartments Planning Practice Note 83 AUGUST 2017 This practice note gives guidance about the operation of Clause 55.07-6 (Noise impacts) and Clause 58.04-3 (Noise impacts)

More information

NOISE IN HIGH RISE BUILDINGS

NOISE IN HIGH RISE BUILDINGS NOISE IN HIGH RISE BUILDINGS Ross H. Palmer CPEng RPEQ Principal Palmer Acoustics (Australia) Pty Ltd ross@palmeracoustics.com Noise in high rise buildings has traditionally not been considered an issue,

More information

Noise Assessment Report

Noise Assessment Report Noise Assessment Report 176 Greenfield Avenue Prepared for: TC United Group Prepared by: Stantec Consulting Ltd. February 8, 2016 NOISE ASSESSMENT REPORT Introduction February 8, 2016 Table of Contents

More information

Christchurch City Plan Proposed Plan Change

Christchurch City Plan Proposed Plan Change Resource Management Act 1991 52 Christchurch City Plan Proposed Plan Change Note 1: The proposed rules in this Plan Change will have no legal effect under Section 9 and Clause 10(5) of Schedule 1 of the

More information

contents 1 introduction general requirements building design guidelines... 2

contents 1 introduction general requirements building design guidelines... 2 138 rix road, building design guidelines hansen partnership pty ltd 1 contents 1 introduction... 2 2 general requirements... 2 3 building design guidelines... 2 building siting and site cover... 2 front

More information

Noise Feasibility Study Stacked Townhouse Development Glenashton Drive (Block 55) Oakville, Ontario

Noise Feasibility Study Stacked Townhouse Development Glenashton Drive (Block 55) Oakville, Ontario Noise Feasibility Study Stacked Townhouse Development Glenashton Drive (Block 55) Oakville, Ontario Prepared for: Nathan Jamieson, P.Eng Senior Principal, Community Development Stantec Consulting Ltd 300W

More information

Great Ocean Rd Ice Creamery

Great Ocean Rd Ice Creamery Great Ocean Rd Ice Creamery BCA Section J - JV3 Compliance Report Revision: 01 Job No: 2171 Date: 7 July 2015 ADP Consulting Pty Ltd Level 10, 10 Queens Rd, Melbourne Vic 3004 www.adpconsulting.com.au

More information

1 18 August 2017 Version 2 (Noise and vibration)

1 18 August 2017 Version 2 (Noise and vibration) Table 8-6 s (Noise and Vibration only) EES Evaluation Noise and Vibration Health, amenity and environmental quality to minimise adverse air quality, noise and vibration effects on the health and amenity

More information

Understanding Energy Codes

Understanding Energy Codes NRCA University Webinar October 17, 2013 Understanding Energy Codes presented by Mark S. Graham Associate Executive Director, Technical Services National Roofing Contractors Association Some background

More information

FIRE RATING MATERIAL FIXING NOTES

FIRE RATING MATERIAL FIXING NOTES FIRE RATING MATERIAL FIXING NOTES FIRE RATING MATERIAL FIXING NOTES... 1 External Wall Systems... 2 Non load bearing steel stud walls... 3 LOAD-BEARING STEEL STUD WALLS... 3 NON LOAD-BEARING TIMBER STUD

More information

EFA BASELINE DESIGNS ACOUSTICS STRATEGY. Acoustic Design of Schools

EFA BASELINE DESIGNS ACOUSTICS STRATEGY. Acoustic Design of Schools EFA BASELINE DESIGNS ACOUSTICS STRATEGY Acoustic Design of Schools Contents 1. Introduction... 3 2. The Baselinee Design Solutions... 4 2.1 Control of reverberation... 4 2.1.1 Classbases... 4 2.1.2 Dining/atrium

More information

Manufacturing Facilities Proposal

Manufacturing Facilities Proposal Manufacturing Facilities Proposal Construction proposal To assist business owners with expansion projects, Wisconsin Public Service has compiled information and renderings of common building types in business

More information

CRANBOURNE LANDFILL. Environmental Noise Assessment. Rp ML. 10 May 2013

CRANBOURNE LANDFILL. Environmental Noise Assessment. Rp ML. 10 May 2013 CRANBOURNE LANDFILL Environmental Noise Assessment Rp 001 2012351ML 10 May 2013 4/46 Balfour St Chippendale NSW 2008 T: +612 9282 9422 Fax: +612 9281 3611 www.marshallday.com Project: CRANBOURNE LANDFILL

More information

The use of layered recycled aggregate concrete barriers in targeting urban noise

The use of layered recycled aggregate concrete barriers in targeting urban noise The use of layered recycled aggregate concrete barriers in targeting urban noise Z. A. Krezel 1, K. J. McManus 1 & G. E. Harding 2 1 School of Engineering and Science, Swinburne University of Technology,

More information

Approved Document E Technical Design Report

Approved Document E Technical Design Report Approved Document E Technical Design Report Report No 15692 Date 15 th April 2013 Sound Solution Consultants Ltd. Ref 15692 Page 1 Client: Site Address Brighton Our Report Ref:15692 Table of Contents 1.

More information

Noise Assessment Report Riverside Drive Phase I

Noise Assessment Report Riverside Drive Phase I Noise Assessment Report - 2887 Riverside Drive Phase I Project # 160401333 Prepared for: Youth Services Bureau Prepared by: Stantec Consulting Ltd. Introduction Table of Contents 1.0 INTRODUCTION... 1

More information

Stationary Noise Assessment. Car Dealership Strandherd Drive. Ottawa, Ontario

Stationary Noise Assessment. Car Dealership Strandherd Drive. Ottawa, Ontario Stationary Noise Assessment Car Dealership Strandherd Drive Ottawa, Ontario REPORT: GWE14-114 - Noise Prepared For: Lewis Treimstra 1805 Woodward Drive Ottawa, Ontario K2C 0P9 Prepared By: Michael Lafortune,

More information

Noise October 22, Noise Existing Conditions. Noise Characteristics

Noise October 22, Noise Existing Conditions. Noise Characteristics 3.7 3.7.1 Existing Conditions Characteristics The noise analysis contained in this section of the DEIS has been conducted in accordance with the New York State Department of Environmental Conservation

More information

Examination paper, both A3 plain and A3 tracing, are provided. Use as appropriate.

Examination paper, both A3 plain and A3 tracing, are provided. Use as appropriate. Candidate Number : Room Number : Seat Number : HKIA / ARB Professional Assessment 2008 Paper 7a CONSTRUCTION DETAILS & DOCUMENTATION (20 marks out of 100 marks of Paper 7) 18 December 2008 4:00 pm 6:00

More information

City of High Point Airport Overlay District Noise Level Reduction Design Standards

City of High Point Airport Overlay District Noise Level Reduction Design Standards City of High Point Airport Overlay District Noise Level Reduction Design Standards Part A. Residential Design Standards for Zone 3 I. NOISE LEVEL REDUCTION (NLR) REQUIREMENT FOR ZONE 3. The City of High

More information

A Handbook of thermal bridging details incorporating aircrete blocks

A Handbook of thermal bridging details incorporating aircrete blocks A Handbook of thermal bridging details incorporating aircrete blocks Book 1 Thermal bridging solutions for external wall partial fill cavity details and full fill party wall details Prepared for the Aircrete

More information

beaconsfield gardenia estate stages 1 & 2

beaconsfield gardenia estate stages 1 & 2 beaconsfield gardenia estate stages 1 & 2 building design guidelines prepared by hansen partnership pty ltd on behalf of banriar investments pty ltd february, 2016 urban planning I urban design I landscape

More information

Noise Control Systems Supplement

Noise Control Systems Supplement Noise Control Systems Supplement Issue Date September 2017 GIB Noise Control design notes SUPPLEMENT ISSUE DATE Polyester Sound Control Infill Sept 2017 Enviromental Noise March 2006 SEPTEMBER 2017 GIB

More information

Noise Feasibility Study Proposed Residential Development Old Barber House 5155 Mississauga Road City of Mississauga, Ontario

Noise Feasibility Study Proposed Residential Development Old Barber House 5155 Mississauga Road City of Mississauga, Ontario Noise Feasibility Study Proposed Residential Development Old Barber ouse 5155 Mississauga Road City of Mississauga, Ontario Prepared for: City Park (Old Barber) omes Inc. 950 Nashville Road Kleinburg,

More information

RE: AIRCRAFT NOISE ASSESSMENT 42 AND 44 REES JAMES ROAD, RAYMOND TERRACE

RE: AIRCRAFT NOISE ASSESSMENT 42 AND 44 REES JAMES ROAD, RAYMOND TERRACE 21 October 2016 Ref: 161323/6778 McCloy Raymond Terrace Pty Ltd P.O. Box 2214 Dangar NSW 2309 RE: AIRCRAFT NOISE ASSESSMENT 42 AND 44 REES JAMES ROAD, RAYMOND TERRACE This letter report presents the results

More information

SECTION 4 - NOISE INTRODUCTION

SECTION 4 - NOISE INTRODUCTION SECTION 4 - NOISE INTRODUCTION The Noise Element of the General Plan is a planning document, which is intended to provide a policy framework within which potential noise impacts may be addressed in the

More information

PROPOSED CHILDCARE 11 CRYERS ROAD, HIGHBROOK ASSESSMENT OF NOISE

PROPOSED CHILDCARE 11 CRYERS ROAD, HIGHBROOK ASSESSMENT OF NOISE 1/355 Manukau Road Epsom, Auckland 1023 PO Box 26283 Epsom, Auckland 1344 T: 09 638 8414 E: hegley@acoustics.co.nz PROPOSED CHILDCARE 11 CRYERS ROAD, HIGHBROOK ASSESSMENT OF NOISE Report No 16295 Prepared

More information

Exterior Wall Solutions Building Shell

Exterior Wall Solutions Building Shell A strong, water tight and thermally insulated building shell will ensure the buildings sustainability of usage over time. The Exterior Shell is the most important factor of protection to ensure that the

More information

JV PROPERTIES, LLC (AQUA GLASS/MASCO) 320 INDUSTRIAL ROAD ADAMSVILLE, MCNAIRY COUNTY, TN Approximately 511,807 square feet

JV PROPERTIES, LLC (AQUA GLASS/MASCO) 320 INDUSTRIAL ROAD ADAMSVILLE, MCNAIRY COUNTY, TN Approximately 511,807 square feet (AQUA GLASS/MASCO) 320 INDUSTRIAL ROAD ADAMSVILLE, MCNAIRY COUNTY, TN 38310 SIZE: GROUND: NUMBER OF BUILDINGS: NUMBER OF FLOORS: Approximately 511,807 square feet Approximately 59 acres, mostly level with

More information

Noise Control Case Studies TIM WIENS CONESTOGA-ROVERS & ASSOCIATES

Noise Control Case Studies TIM WIENS CONESTOGA-ROVERS & ASSOCIATES Noise Control Case Studies TIM WIENS CONESTOGA-ROVERS & ASSOCIATES A bit about your speaker Presentation Overview 1. Some Case Studies 2. Mystery 3. Drama 4. Danger Environmental Noise Impact an Overview

More information

Building Standards Department. Guide to Building Permits Understanding the Different Building Permit Types and their Submission Requirements

Building Standards Department. Guide to Building Permits Understanding the Different Building Permit Types and their Submission Requirements Guide to Building Permits Understanding the Different Building Permit Types and their Submission Requirements Building Standards March 2018 CONTENTS BUILDING PERMIT APPLICATIONS... 2 GENERAL INFORMATION...

More information

3.5.1 Outdoor Living Areas (OLAs) Indoor Sound Levels... 8

3.5.1 Outdoor Living Areas (OLAs) Indoor Sound Levels... 8 RWDI was retained by Manor Park Management to conduct a traffic noise feasibility study as part of the Site Plan Approval (SPA) for the proposed development, to be located at the northwest corner of Vanier

More information

Fire Safety and Performance of Wood in Multi-Residential and Commercial Buildings. Boris Iskra Forest & Wood Products Australia

Fire Safety and Performance of Wood in Multi-Residential and Commercial Buildings. Boris Iskra Forest & Wood Products Australia Fire Safety and Performance of Wood in Multi-Residential and Commercial Buildings Boris Iskra Forest & Wood Products Australia This Presentation 1. Fire Hazard Properties Building Code of Australia Volume

More information

APPENDIX E EXAMPLE AIRPORT OVERLAY DISTRICT REGULATIONS

APPENDIX E EXAMPLE AIRPORT OVERLAY DISTRICT REGULATIONS APPENDIX E EXAMPLE AIRPORT OVERLAY DISTRICT REGULATIONS AIRPORT NOISE OVERLAY DISTRICTS The following Airport Noise Overlay Districts are intended to provide regulations governing land uses and development

More information

NORTHERN RESIDENTIAL ZONE

NORTHERN RESIDENTIAL ZONE Chapter 7 NORTHERN RESIDENTIAL ZONE INTRODUCTION This chapter contains rules managing land uses in the. boundaries of this zone are shown on the planning maps. The All rules apply throughout the unless

More information

A CASE STUDY ON COST/BENEFIT ASSESSMENT OF ROAD TRAFFIC NOISE AMELIORATION WITHIN AND OUTSIDE THE ROAD RESERVE

A CASE STUDY ON COST/BENEFIT ASSESSMENT OF ROAD TRAFFIC NOISE AMELIORATION WITHIN AND OUTSIDE THE ROAD RESERVE A CASE STUDY ON COST/BENEFIT ASSESSMENT OF ROAD TRAFFIC NOISE AMELIORATION WITHIN AND OUTSIDE THE ROAD RESERVE Douglas, P. (1)*, De Silva, S. (1), Chen, L. (1) and Peters, J. (2) (1) RMIT University, Melbourne,

More information

Noise Assessment Report

Noise Assessment Report Noise Assessment Report 19 & 23 Bachman Terrace Prepared for: Tega Homes Prepared by: Stantec Consulting Ltd. June 5, 2015 NOISE ASSESSMENT REPORT Table of Contents 1.0 INTRODUCTION... 1 1.1 PURPOSE OF

More information

InterHome SEPARATING WALL SYSTEM FOR MULTI-RESIDENTIAL CONSTRUCTION

InterHome SEPARATING WALL SYSTEM FOR MULTI-RESIDENTIAL CONSTRUCTION InterHome SEPARATING WALL SYSTEM FOR MULTI-RESIDENTIAL CONSTRUCTION B Contents DISCLAIMER Products manufactured and systems designed by Knauf are produced in accordance with the Building Code of Australia

More information

NEWS LETTER MARCH 27, 2009

NEWS LETTER MARCH 27, 2009 PLANNING, BUILDING & DEVELOPMENT SERVICES DEPARTMENT 580-1 Street S.E. Medicine Hat, Alberta T1A 8E6 Telephone: 529-8374 FAX 502-8038 1 NEWS LETTER MARCH 27, 2009 GENERAL As you are probably aware there

More information

fireseal Party Wall Design Guide CLASS 1 BUILDINGS PARTY WALL DESIGN GUIDE PAGE 1

fireseal Party Wall Design Guide CLASS 1 BUILDINGS PARTY WALL DESIGN GUIDE PAGE 1 fireseal Party Wall Design Guide CLASS 1 BUILDINGS PARTY WALL DESIGN GUIDE PAGE 1 1.0 INTRODUCTION CONTENTS The stability of a building in a fire depends upon the performance of all the component parts

More information

Environmental Noise Impact Assessment. Crag Digital Energy Centre

Environmental Noise Impact Assessment. Crag Digital Energy Centre 4 Turlough Gardens, Fairview, Dublin 3 Phone : +353 (0)1 8376693 www.acoustic-designs.com Environmental Noise Impact Assessment Crag Digital Energy Centre Author : Dr. Peter Hill Date : September 2017

More information

Roadway Traffic Noise Assessment Montreal Road. Ottawa, Ontario

Roadway Traffic Noise Assessment Montreal Road. Ottawa, Ontario Roadway Traffic Noise Assessment 807-825 Montreal Road Ottawa, Ontario REPORT: GWE15-086-TRAFFIC NOISE Prepared For: Anthony Nicolini 183 Michael Cowpland Drive Ottawa, Ontario K2M 0M3 Prepared By: Michael

More information

Fire safety issues with balconies

Fire safety issues with balconies Fire safety issues with balconies By Ciara Holland, Martin Shipp and David Crowder of BRE Global Introduction BRE Global carries out fire investigation activities on behalf of the Department for Communities

More information

Suspended timber upper floors

Suspended timber upper floors Exposed Soffit Floors Exposed soffit Exposed soffit design Many clients perceive that rooms above exposed upper floors will be cold. However, it is possible to achieve very high levels of thermal insulation

More information

RESIDENTIAL BUILDING PLAN APPROVAL PROCEDURE

RESIDENTIAL BUILDING PLAN APPROVAL PROCEDURE RESIDENTIAL BUILDING PLAN APPROVAL PROCEDURE 1. Prior to the commencement on any lot, of any building work whatsoever, including outbuildings, fencing, external renovations, air-conditioners or any other

More information

NOISE CONTROL STUDY FOR PHOENIX HOMES 3654 & 3658 JOCKVALE ROAD APRIL 28, 2011 REV 1 TABLE OF CONTENTS 1.0 INTRODUCTION BACKGROUND...

NOISE CONTROL STUDY FOR PHOENIX HOMES 3654 & 3658 JOCKVALE ROAD APRIL 28, 2011 REV 1 TABLE OF CONTENTS 1.0 INTRODUCTION BACKGROUND... NOISE CONTROL STUDY PHOENIX HOMES 3654 & 3658 JOCKVALE ROAD APRIL 28, 2011 REV 1 NOISE CONTROL STUDY FOR PHOENIX HOMES 3654 & 3658 JOCKVALE ROAD APRIL 28, 2011 REV 1 TABLE OF CONTENTS 1.0 INTRODUCTION...

More information

The most economical solutions can be obtained by using our load span tables, and where applicable dimensioning software for roof optimisation.

The most economical solutions can be obtained by using our load span tables, and where applicable dimensioning software for roof optimisation. Roof Decking: RD60 Firth Steels manufacture and supply various types of structural roof deck profiles, each characterised by the depth of each profile which lends itself in its design to various characteristics

More information

Stationary Noise Feasibility Assessment. 315 Chapel Street Ottawa, Ontario

Stationary Noise Feasibility Assessment. 315 Chapel Street Ottawa, Ontario Stationary Noise Feasibility Assessment 315 Chapel Street Ottawa, Ontario REPORT: GWE17-002 - Stationary Noise Prepared For: Leanne Moussa Allsaints 10 Blackburn Avenue K1N 6P8 Ottawa, Ontario Prepared

More information

NOISE IMPACT ASSESSMENT FOR SITE PLAN APPROVAL 47 HAVELOCK STREET OTTAWA, ON. REVISED with ADDENDUM for ROOFTOP OUTDOOR LIVING AREA

NOISE IMPACT ASSESSMENT FOR SITE PLAN APPROVAL 47 HAVELOCK STREET OTTAWA, ON. REVISED with ADDENDUM for ROOFTOP OUTDOOR LIVING AREA NOISE IMPACT ASSESSMENT FOR SITE PLAN APPROVAL 47 HAVELOCK STREET OTTAWA, ON. REVISED with ADDENDUM for ROOFTOP OUTDOOR LIVING AREA REPORT PREPARED FOR SURFACE DEVELOPMENTS 61 FOREST HILL AVE. OTTAWA,

More information

QLDC PROPOSED DISTRICT PLAN [PART THREE] AUGUST 2015 BUSINESS MIXED USE

QLDC PROPOSED DISTRICT PLAN [PART THREE] AUGUST 2015 BUSINESS MIXED USE 16 QLDC PROPOSED DISTRICT PLAN [PART THREE] AUGUST 2015 16 b usiness mix ed use BUSINESS MIXED USE QLDC PROPOSED DISTRICT PLAN [PART THREE] AUGUST 2015 16 business mixed use 16.1 Purpose The intention

More information

260,000 SF Building Profile

260,000 SF Building Profile Expanding Your Development & Investment Perspectives 260,000 SF Building Profile Precast & Brick Exterior Finish 245,000 SF Production/Warehouse 7,500 SF Office & 7,500 SF Mezzanine 50 x 50 Bays, 24 Clear

More information

7 BUSINESS 1, 1A 2, 3, 3A, 4, 5, 6 AND H

7 BUSINESS 1, 1A 2, 3, 3A, 4, 5, 6 AND H 7 BUSINESS 1, 1A 2, 3, 3A, 4, 5, 6 AND H (HERITAGE) ZONES 7.1 ZONE STATEMENTS 7.1.1 BUSINESS 1 AND 1A ZONES - (INNER COMMERCIAL) The Business 1 and 1A Zones represent the inner commercial area of Oamaru

More information

INSPECT DIRECT Pty Ltd

INSPECT DIRECT Pty Ltd Web Page: www.inspectdirect.com.au INSPECT DIRECT Pty Ltd Property Address: Sample.Dilapidation.Report Victoria Building Status / Dilapidation Report This is not a Pest Inspection The Building Status /

More information

SUBURBAN RESIDENTIAL. QLDC PROPOSED DISTRICT PLAN [PART THREE] DECISIONS VERSION 7 lower density SUBURBAN residential

SUBURBAN RESIDENTIAL. QLDC PROPOSED DISTRICT PLAN [PART THREE] DECISIONS VERSION 7 lower density SUBURBAN residential 7 LOWER DENSITY SUBURBAN RESIDENTIAL 7.1 Zone Purpose The Lower Density Suburban Residential Zone is the largest residential zone in the District. The District Plan includes such zoning that is within

More information

GAF EnergyGuard Polyiso Wall Sheathing

GAF EnergyGuard Polyiso Wall Sheathing From: Technical Services May 15, 2013 GAF EnergyGuard Polyiso Wall Sheathing GAF s EnergyGuard Polyiso Wall Sheathing is intended to be installed on residential construction only. Application types include:

More information

Expanding Your Development & Investment Perspectives 159,000 SF Building Profile

Expanding Your Development & Investment Perspectives 159,000 SF Building Profile Expanding Your Development & Investment Perspectives 159,000 SF Building Profile Metal & EIFS Exterior Finish 150,000 SF Production/Warehouse 4,500 SF Office & 4,500 SF Mezzanine 50 x 50 Bays, 24 Clear

More information

Datasheet. Thermal Benefits of Solid Construction

Datasheet. Thermal Benefits of Solid Construction > Datasheet > Thermal Benefits of Solid Construction Introduction Recently, attention has been focussed on environmental issues, and, in particular, energyefficient construction. Building designers are

More information

AIR BARRIER DESIGN PRINCIPLES AN OVERVIEW.

AIR BARRIER DESIGN PRINCIPLES AN OVERVIEW. AIR BARRIER DESIGN PRINCIPLES AN OVERVIEW www.stromatech.com AIR BARRIER DESIGN PRINCIPLES Building Regulations Approved Document Parts L1A & L2A currently requires that new buildings have to achieve a

More information

typical section 1:50 Important:

typical section 1:50 Important: 00 Typical ventilated facade installation mounted with top hat channels onto external walls, awning soffit and fascia. 00 Wall panels are shown in varying heights, having open joints for ventilation of

More information

Appendix G: Noise Supporting Information

Appendix G: Noise Supporting Information City of Livermore Sunset Crossing Project/Catalina Crossing Project Draft EIR Appendix G: Noise Supporting Information FirstCarbon Solutions H:\Client (PN-JN)\1728\17280002\3 - Draft EIR\edit-wp\17280002

More information

Sound Intensity Measurements for Ranking Noise Transmission Through Building Envelope Elements

Sound Intensity Measurements for Ranking Noise Transmission Through Building Envelope Elements Proceedings of Acoustics 2012 - Fremantle 21-23 November 2012, Fremantle, Australia Sound Intensity Measurements for Ranking Noise Transmission Through Building Envelope Elements Jeremy Taylor Savery &

More information

INTERIOR ENVIRONMENT

INTERIOR ENVIRONMENT CHAPTER 12 INTERIOR ENVIRONMENT > SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter shall govern ventilation, temperature control, lighting, yards and courts, sound transmission, room dimensions,

More information

Speech Privacy outcomes from Green star Design and As-Built v1.1 rating tool

Speech Privacy outcomes from Green star Design and As-Built v1.1 rating tool Speech Privacy outcomes from Green star Design and As-Built v1.1 rating tool Philip Setton 1 and David Yates 1 1 WSP Parsons Brinckerhoff, Melbourne Australia ABSTRACT The Green Building Council has consolidated

More information

Contact Details: Phone Fax . Work Description: New Building Extensions Refurbishment Change of Use. Yes No Method:

Contact Details: Phone Fax  . Work Description: New Building Extensions Refurbishment Change of Use. Yes No Method: BCA Section J- Energy Efficiency Deemed- to- Satisfy Provisions Assessment Sheet 1. Project Overview Client Name: Address: Contact Person: Contact Details: Phone Fax Email Project: Work Description: New

More information

Note:

Note: Email: sales@koolwall.com.au JANUARY 2009 ISSUE Note: When installing the koolwall panel system, please ensure you are using a copy of the most recently published edition of the installation manual. If

More information

Noise Analysis for Latitude II City of Escondido, California

Noise Analysis for Latitude II City of Escondido, California Noise Analysis for Latitude II City of Escondido, California Project #560401-0100b June 23, 2015 Prepared For: NCA Developments 14 Corporate Plaza, Suite 100 Laguna Hills, CA 92660 Prepared By: Matt B.

More information

REP Fotenn Bank Phase 1 Feasibility Noise Study with Building Component AmendmentPage 1 of 21

REP Fotenn Bank Phase 1 Feasibility Noise Study with Building Component AmendmentPage 1 of 21 REP Fotenn 890-900 Bank Phase 1 Feasibility Noise Study with Building Component AmendmentPage 1 of 21 2018-02-28 Emilie Coyle, M.Pl Planner Fotenn Planning + Design 223 McLeod St, Ottawa, ON K2P 0Z8 Office:

More information

Wall Linings. As well as complete dry lining solutions we also provide fast-drying parge coat to ensure airtightness,

Wall Linings. As well as complete dry lining solutions we also provide fast-drying parge coat to ensure airtightness, Wall Linings Our versatile range of wall lining systems makes it easy to produce a high-quality, high-performance finished wall regardless of the background. Whether your priority is acoustic control,

More information

A Handbook of thermal bridging details incorporating aircrete blocks

A Handbook of thermal bridging details incorporating aircrete blocks A Handbook of thermal bridging details incorporating aircrete blocks Book 2 Thermal bridging solutions for external wall full fill cavity details Prepared for the Aircrete Products Association by the BBA

More information

TOWN OF HAGUE GUIDELINES FOR PERMIT APPLICATION

TOWN OF HAGUE GUIDELINES FOR PERMIT APPLICATION TOWN OF HAGUE GUIDELINES FOR PERMIT APPLICATION Town of Hague Building Inspector: Dale Wagner Home #: 306-225-2265 Cell #: 306-241-4741 Fill all part of the permit application including the date and signature.

More information

Acoustic Advisory Service and Noise Management Incentive Scheme Operating Guidelines

Acoustic Advisory Service and Noise Management Incentive Scheme Operating Guidelines Acoustic Advisory Service and Noise Management Incentive Scheme Operating Guidelines Approved: Council endorsement (13 September 2016) Owner: Trim: Associate Director, Planning and Development 8203 7756

More information