1 Minnesota Health Care Engineers Association Life Safety Code Potpourri Friday, May 1, 2015 Presenter: Bob Dehler, P.E., Engineering Program Manager, Minnesota Department of Health

2 Minnesota Department of Health Engineering Services Section - Bob Dehler, P.E. Minnesota Department of Health Engineering Services Section

3 Today s Topics Engineering Services Project Submittal Process Barriers in Healthcare Life Safety Plan Requirements Occupancies Suites Gift Shops Minnesota Department of Health Engineering Services Section

4 Engineering Services Project Submittal Process What do we need? Complete plan submittal form Plan review fee Full set of signed pdf plan Fully reviewed by submitter prior Full set of signed hard copies of plan Minnesota Department of Health Engineering Services Section

5 Engineering Services Project Submittal Process Plan submittal form Ensure construction type and cost included Cross reference project cost with fee schedule

6 Engineering Services Project Submittal Process Plan review fee Plan review fee correlated to construction cost Be very careful to get accurate cost and ensure it is in the range in the statute Sometimes revised submittals are sent in because cost is not in line with fee

7 Engineering Services Project Submittal Process PDF plan Full set of pdf plans Can submit: CD, thumb drive, to Have architect/engineer review set before submission to MDH. Many times sheet(s) not properly certified by licensed engineer or architect. Master plumbers and master electricians may not submit plans to MDH

8 Engineering Services Project Submittal Process Hard copy of plans Architect to review every sheet for proper certification

9 Engineering Services Project Submittal Process Failure to provide any one item will delay your project from being completely entered in our system Any time construction activity takes place in a healthcare facility, plans should be submitted for review and approval The main exception is interior finish replacement Remember, we review plans to help the facility. Not be a pain to the facility or engineer/architect Please do not send MDH all drawing changes throughout construction. Only changes that affect licensure and certification requirements. If a change is sent to MDH, additional plan review fees may be required

10 Barriers in Healthcare What is a smoke partition? Generally a building code term, not in chapter 18 or 19 Building code requires the smoke partition to extend from floor to deck above and life safety code allows termination at drop ceiling. Life Safety Code Corridor walls shall form a barrier to limit the transfer of smoke. Allows termination at drop ceiling. Life safety code requires all doors in smoke partitions to have closers and clearances must meet NFPA 80. Not an appropriate term on life safety plans.

11 Barriers in Healthcare Smoke barrier Wall that extends from outside wall to outside wall and floor to floor/roof. These barriers shall be continuous through all concealed spaces CMS is looking at this requirement and have found non-compliant smoke barriers to roof requires smoke barriers in healthcare to have a 1-hour rating and doors must be rated for 20 minutes or be constructed of 1-¾ solid wood. WARNING If your life safety plans call out 1 hour smoke barrier walls, you need rated doors in the openings, not just 1-3/4 solid wood doors

12 Barriers in Healthcare Fire resistance rating and fire barrier The time that materials or assemblies have withstood a fire exposure as established in accordance with the test procedure of NFPA 251, Standard methods of Test of Fire Endurance of Building Construction and Materials Fire barriers have one of the following fire resistance ratings: 2-hour fire resistance rating 1-hour fire resistance rating ½-hour fire resistance rating (lath and plaster or ½ gypsum on both sides of studs)

13 Barriers in Healthcare Limit the transfer of smoke Corridor walls in new healthcare must limit the transfer of smoke Corridor walls in existing healthcare that are protected with automatic sprinkler systems may limit the transfer of smoke Can end at lay-in ceiling (check building code) Doors must resist passage of smoke with positive latching. Max 1 undercut per Max door gaps from frame ¼ (non-sprinklered) and ½ (sprinklered) S&C 07-18

14 Barriers in Healthcare Smoke Wall? Term heard a lot. Not defined in building code or life safety code Fire Wall? Building code term not required in life safety code. A fire resistance rated wall with structural stability under fire conditions to allow collapse of the wall on either side without collapse of both sides

15 Life Safety Plan Requirements Building construction year, construction type and occupancy Areas of building sprinklered Locations of all hazardous areas Locations of all smoke barriers Suite boundaries with size (sf) and exiting Locations, size and exiting of designated smoke compartments Locations of chutes and shafts (ratings) Locations and direction of any horizontal exits Locations of all exits Other required elements from AHJ s

16 Example of Life Safety Plan

17 Occupancies Hospital and CAH life safety code occupancy classification may be classified as other occupancies other than healthcare S&C Letter explains the requirements for classification If mixed occupancy in one building (without proper separation) then most stringent occupancy classification applies An example could be assembly in healthcare may have more stringent exiting requirements

18 Occupancies Healthcare Occupancy Provide sleeping accommodations, Provide housing on a 24 hour basis and Patients mostly incapable of self preservation A CMS-certified hospital or CAH does not need to have four or more inpatients at all times in order to be classified as a Health Care Occupancy. Occupancy classification must be determined regardless of the number of patients served at a hospital s or CAH s component facility.

19 Occupancies Ambulatory Health Care Occupancy Does not provide sleeping accommodations, Facility does not provide housing on a 24 hour basis and Patients mostly incapable of self preservation (provides anesthesia services) Be aware that CMS does not consider whether or not a patient has been rendered incapable of taking action for self-preservation by the facility; rather, the only consideration is whether the patient is capable or incapable of self-preservation. CMS does not consider the number of patients treated when determining an AHC occupancy classification

20 Occupancies Business Occupancy Does not provide sleeping accommodations, Facility does not provide housing or treatment on a 24 hour basis, Facility does not provide anesthesia; and Patients are mostly capable of self-preservation A patient may be incapable of self-preservation due to many factors, including, but not limited to, age, physical or mental disability, medical or therapeutic interventions, medication reactions, etc.

21 Sweet! - I mean Suite Suites are essentially large rooms with rooms inside Benefits of suites include: Hallways in suites do not have to meet corridor requirements Park equipment or carts in suite hallway Latching of doors inside suite not required but exterior

22 Suites Common Features Suite perimeter walls and doors abutting all interior space should meet corridor wall and door requirements Hazardous areas may not be an intervening room. Unless whole suite is protected as hazardous Interior walls in suite do not need to extend to deck above but must be non-combustible or limited combustible Minimum hallway width is 36 inches clear (chapter 7) Max travel distance to exit; 150 feet is building is not sprinkled and 200 feet if building is sprinklered Constant staff supervision required in sleeping suites Doors in suites for treatment/exam must be 41.5 clear Generally, sleeping suites not appropriate for nursing homes

23 Suites Maximum suite size Sleeping Suite 5,000 square feet Non-Sleeping Suite 10,000 square feet

24 Suites Intervening rooms within suites Sleeping Suite You may not pass through more than 1 intervening room within the suite to reach the corridor Non-Sleeping Suite You may not pass through more than 2 intervening rooms within the suite to reach the corridor

25 Suites Max travel distance to corridor Sleeping Suite You must get to corridor within 100 feet (1 intervening room) Non-Sleeping Suite You must get to corridor within 100 feet (1 intervening room) or 50 feet (2 intervening rooms)

26 Suites Number of exits to corridor Sleeping Suite 2 remote means of egress required when suite is over 1,000 square feet Non-Sleeping Suite 2 remote means of egress required when suite is over 2,500 square feet

27 Suites Potential Issues Found Outside the Suite When Suites are Used Are new excessive dead end corridors created? Has the new suite blocked access to a required exit?

28 Suites

29 Suites

30 Suites

31 Suites

32 Suites

33 Suites

34 Gift Shops New Gift Shops Must meet NFPA 101, Gift shops that are used for the storage and display of combustibles in quantities considered hazardous must be protected as hazardous (1-hour construction). Basically considered storage room storing combustibles Gift shops not considered hazardous and having separately protected storage may be: Open to the corridor if the gift shop does not exceed 500sf. Separated from the corridor with non-fire rated walls

35 Gift Shops Who determines if the gift shop is a hazardous area? The Joint Commission The Center for Medicare & Medicaid Services (CMS) The state department of health The state fire marshal The local fire inspector The facilities insurance carrier The facility safety officer All of the AHJ s make their own interpretation if the gift shop is hazardous. If one AHJ determines that the gift shop is hazardous the gift shop must be protected with 1-hour construction

36 Gift Shops Most gift shops are full of combustibles, such as greeting cards, clothing, stuffed toys, packaging, plastics, etc. In order to avoid any issues for new construction, protect gift shop with 1-hour construction Granted, you could have a protected storage room but who moves combustibles from gift shop to storage room during times the gift shop is closed?

37 Thank you for having me here today

38 QUESTIONS

LIFE SAFETY 101. Architecture Interior Design Planning Sustainable Design

LIFE SAFETY 101. Architecture Interior Design Planning Sustainable Design LIFE SAFETY 101 Drew Underwood, AIA, ACHA Senior Healthcare Principal TMPartners, PLLC 211 Franklin Road, Suite 200 Brentwood, TN 37027 615-523-5234 aunderwood@tmpartners.com Architecture Interior Design

More information

Centennial Hills Skilled Nursing Facility Fire Protection Report July 13, 2016 Revised September 15, 2016 JBA Project No

Centennial Hills Skilled Nursing Facility Fire Protection Report July 13, 2016 Revised September 15, 2016 JBA Project No We Bring Buildings to Life www.jbace.com Centennial Hills Skilled Nursing Facility Fire Protection Report July 13, 2016 Revised September 15, 2016 JBA Project No. 16.0667.000 At the request of Yihong Liu

More information

Brad Keyes, CHSP LIFE SAFETY CODE. The New. How to Prepare in Advance

Brad Keyes, CHSP LIFE SAFETY CODE. The New. How to Prepare in Advance Brad Keyes, CHSP The New LIFE SAFETY CODE How to Prepare in Advance The following is an excerpt from The New Life Safety Code : How to Prepare in Advance by Brad Keyes, CHSP. A new edition of the Life

More information

Minnesota Healthcare Engineers Association, Fall Conference. Bob Dehler, P.E. Engineering Program Manager September 14, 2017

Minnesota Healthcare Engineers Association, Fall Conference. Bob Dehler, P.E. Engineering Program Manager September 14, 2017 Minnesota Healthcare Engineers Association, Fall Conference Bob Dehler, P.E. Engineering Program Manager September 14, 2017 Categories of Rehabilitation Work in Healthcare Facilities Bob Dehler, P.E. robert.dehler@state.mn.us

More information

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council Copyright This presentation is protected

More information

FCIA Barrier Management Series. Barrier Management Policies

FCIA Barrier Management Series. Barrier Management Policies FCIA Barrier Management Series Barrier Management Policies Objective Keep Buildings Safe Barriers are for Safety DIIM Properly Designed and Specified Tested and Listed Systems Directories, Tables Specified

More information

Knowledge Objectives (3 of 3)

Knowledge Objectives (3 of 3) Building Systems Knowledge Objectives (1 of 3) Identify construction types in commercial and residential structures. Explain fire behavior as it relates to the method of construction. Discuss the structural

More information

Barrier Management. FCIA Barrier Management Series Barrier Management Policies

Barrier Management. FCIA Barrier Management Series Barrier Management Policies Barrier Management FCIA Barrier Management Series Barrier Management Policies Objective Keep Buildings Safe Barriers are for Safety DIIM Properly Designed and Specified Tested and Listed Systems Directories,

More information

The Building Codes A.R.E. Building Design and Construction Exam Prep

The Building Codes A.R.E. Building Design and Construction Exam Prep Know Thy Codes! The Building Codes Building Codes The Code of Hammurabi 4000bc Developed 19 th and 20 th c. Codes define what you can and can t do Allowable area and height based on degree of danger Fire

More information

&02.1. Level 3 Alterations. Level 3 Alterations shall comply with Sections & and &

&02.1. Level 3 Alterations. Level 3 Alterations shall comply with Sections & and & &01 GENERAL To be developed. All of the exceptions have to be coordinated. &02 SPECIAL USE AND OCCUPANCY &02.1. Level 3 Alterations. Level 3 Alterations shall comply with Sections &02.1.1 and &02.1.2.

More information

The Lexington Division of Fire and Emergency Services. Fire Chief Robert G. Hendricks

The Lexington Division of Fire and Emergency Services. Fire Chief Robert G. Hendricks The Lexington Division of Fire and Emergency Services Fire Chief Robert G. Hendricks The Code of Hammurabi 229. If a builder builds a house for someone, and does not construct it properly, and the house

More information

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings. John Buddy Showalter, PE VP, Technology Transfer American Wood Council

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings. John Buddy Showalter, PE VP, Technology Transfer American Wood Council Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings John Buddy Showalter, PE VP, Technology Transfer American Wood Council Copyright This presentation is protected by US and International

More information

FCIA Webinar Gypsum Wall Patching

FCIA Webinar Gypsum Wall Patching FCIA Webinar Gypsum Wall Patching Firestop Contractors International Association Hillside, IL +1-708-202-1108 - office Bill McHugh bill @ fcia.org Nestor Sanchez, USG Corp. nsanchez@usg.com DIIM Firestopping

More information

2015 IBC Exit Systems

2015 IBC Exit Systems Objectives 2015 IBC Exit Systems Based on the 2015 International Building Code Upon completion, participants will be better able to: Determine those means of egress components that are defined as exits

More information

Educational Occupancies such as schools, and day care centers (more than 12 children).

Educational Occupancies such as schools, and day care centers (more than 12 children). State Fire Marshal Approval Your project may require approval from the Maine Office of the State Fire Marshal. Below is some information regarding Construction Permits and Barrier Free Permits. Other permits

More information

Comparison of the life safety elements of the 1997 UBC and the IBC 2000.

Comparison of the life safety elements of the 1997 UBC and the IBC 2000. Comparison of the life safety elements of the 1997 UBC and the IBC 2000. Introduction The Building Performance Research Institute s mission is primarily one of education on building safety and performance.

More information

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council Copyright This presentation is protected

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Detention and

More information

City of Des Moines. Permit and Development Center 602 Robert D Ray Drive Des Moines, IA Phone: Fax:

City of Des Moines. Permit and Development Center 602 Robert D Ray Drive Des Moines, IA Phone: Fax: City of Des Moines Permit and Development Center 602 Robert D Ray Drive Des Moines, IA 50309 Phone: 515-283-4200 Fax: 515-283-4270 This Code Analysis Form must be completed and returned with the Building

More information

9/20/2016 4:01 PM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

9/20/2016 4:01 PM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement of 28 9/20/2016 4:01 PM Second Revision No. 5502-NFPA 101-2016 [ New Section after 36.2.1.5 ] 36.2.1.6 Grab Bars for Bathtubs, Bathtub-Shower Combinations, and Showers. 36.2.1.6.1 Where bathtubs, bathtub-shower

More information

2012 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata)

2012 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata) ELEVENTH PRINTING (Updated January 10, 2017) 406.4 Public parking garages. Parking garages other than private parking garages, shall be classified as public parking garages and shall comply with the provisions

More information

(Statute, Rule, FBC, Industry) FBC 406.3, see also FBC No provisions in FBC or FS

(Statute, Rule, FBC, Industry) FBC 406.3, see also FBC No provisions in FBC or FS Florida Specific Amendment Code Reference NFPA 101 Open Parking Structure. A parking structure that, at each parking level, has wall openings open to the atmosphere, for an area of not less than 1.4 ft2

More information

VERTICAL OPENINGS STUDY GROUP REPORT TO CTC MEETNG CHICAGO, IL - OCTOBER 13-14, 2011 CODE CHANGES

VERTICAL OPENINGS STUDY GROUP REPORT TO CTC MEETNG CHICAGO, IL - OCTOBER 13-14, 2011 CODE CHANGES VERTICAL OPENINGS STUDY GROUP REPORT TO CTC MEETNG CHICAGO, IL - OCTOBER 13-14, 2011 CODE CHANGES The following is the Study Group report that was considered by the CTC at its October 13-14, 2011 meeting.

More information

2015 IBC Update. Copyright 2014 International Code Council #1000PDF15 1

2015 IBC Update. Copyright 2014 International Code Council #1000PDF15 1 Goal 2015 IBC Update Based on the International Building Code (IBC ) The goal is to familiarize building officials, fire officials, plans examiners, inspectors, design professionals, contractors, and others

More information

Applying the Building Code During Design

Applying the Building Code During Design Applying the Building Code During Design A Step-By-Step Process AIA Learning Units The Salt Lake City CSI Chapter is a Registered Provider with The American Institute of Architects Continuing Education

More information

FS , 712, 713, 714

FS , 712, 713, 714 VERTICAL OPENINGS STUDY GROUP REPORT TO CTC MEETNG CHICAGO, IL JUNE 28-29, 2012 PUBLIC COMMENTS CTC Code Change Proposal FS50-12 was Approved as Modified as shown below - No public comments for the Group

More information

Barrier Management Systems. ASHE Region 2 Radisson Valley Forge May 13, 2014

Barrier Management Systems. ASHE Region 2 Radisson Valley Forge May 13, 2014 Barrier Management Systems ASHE Region 2 Radisson Valley Forge May 13, 2014 DIIM Barriers are for Safety DIIM Properly Designed and Specified Tested and Listed Systems Directories, Tables Professional

More information

Updated references to SEI/ASCE 7 to the 2016 edition once it is available.

Updated references to SEI/ASCE 7 to the 2016 edition once it is available. Committee Input No. 8008-NFPA 5000-2015 [ Global Input ] Updated references to SEI/ASCE 7 to the 2016 edition once it is available. Submitter Information Verification Submitter Full Name: Tracy Vecchiarelli

More information

Project Address Applicant: (Please Print) Plan review Engineer: Phone: Date

Project Address Applicant: (Please Print) Plan review Engineer: Phone: Date BUILDING AND SAFETY Tenant Improvement Checklist Project Address Applicant: (Please Print) Plan review Engineer: Phone: Date APPLICATION The following items will be required at the permit counter before

More information

Advanced Studies of the International Building Code. Presented by Steve Thomas, Colorado Code Consulting, LLC

Advanced Studies of the International Building Code. Presented by Steve Thomas, Colorado Code Consulting, LLC Advanced Studies of the International Building Code Presented by Steve Thomas, Colorado Code Consulting, LLC Advanced Studies of the International Building Code Instructor Steve Thomas, CBO President,

More information

UCC Permit Application Procedures

UCC Permit Application Procedures How do I apply for a permit? UCC Permit Application Procedures 1. Please complete the CodeMaster Pan Review Application 2. Please provide the scope of work description and/or construction documents/plans.

More information

2012 IBC Exit Systems

2012 IBC Exit Systems Accreditation Based on the 2012 International Building Code The International Code Council has been accredited as an Authorized Provider by the International Association for Continuing Education and Training

More information

UNDERSTANDING THE MASS TIMBER CODE PROPOSALS. A Guide for Building Officials

UNDERSTANDING THE MASS TIMBER CODE PROPOSALS. A Guide for Building Officials UNDERSTANDING THE MASS TIMBER CODE PROPOSALS A Guide for Building Officials 1 Background on ICC Ad Hoc Committee on Tall Wood Buildings The Board of the International Code Council (ICC), the developer

More information

High Piled Combustible Storage Guideline

High Piled Combustible Storage Guideline Moreno Valley High Piled Combustible Storage Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 5, 2017 Rev: 7-28-16 City of Moreno Valley Fire Department Page 1 of 19 High Piled Storage

More information

COMMERCIAL TENANT IMPROVEMENT PERMIT APPLICATION

COMMERCIAL TENANT IMPROVEMENT PERMIT APPLICATION COMMERCIAL TENANT IMPROVEMENT PERMIT APPLICATION OFFICIAL USE ONLY Date: Permit #: Received by: For Staff Use Only: OFD ELEC Planning SITE LOCATION Site Address: Tax Parcel Number: TYPE OF WORK Building

More information

Analysis of Changes for the 5 th Edition (2014) of the Florida Codes

Analysis of Changes for the 5 th Edition (2014) of the Florida Codes Analysis of Changes for the 5 th Edition (2014) of the Florida Codes Changes to the Florida Building Code, Existing Building This Analysis of Changes for the 5 th Edition (2014) of the Florida Codes is

More information

SUMMARY OF FIRE SPRINKLER REQUIREMENTS FOR ALTERATIONS TO EXISTING BUILDINGS 2015 I-Codes

SUMMARY OF FIRE SPRINKLER REQUIREMENTS FOR ALTERATIONS TO EXISTING BUILDINGS 2015 I-Codes SUMMARY OF FIRE SPRINKLER REQUIREMENTS FOR ALTERATIONS TO EXISTING BUILDINGS 2015 I-Codes SCOPE: The City of Lawrence requirements for application of current code provisions. This shall apply to alterations

More information

CALIFORNIA BUILDING PLANS EXAMINER CONTENT OUTLINE 01. GENERAL ADMINISTRATION 3 % Project Administration 3%

CALIFORNIA BUILDING PLANS EXAMINER CONTENT OUTLINE 01. GENERAL ADMINISTRATION 3 % Project Administration 3% CALIFORNIA BUILDING PLANS EXAMINER CONTENT OUTLINE EXAM ID: I6 80 multiple-choice questions 3-1/2-hour time limit Open book 01. GENERAL ADMINISTRATION 3 % 0101. Project Administration 3% Verify that plans,

More information

COMMUNITY & DEVELOPMENT SERVICES 840 Northgate Drive, Richland, WA Phone: Fax:

COMMUNITY & DEVELOPMENT SERVICES 840 Northgate Drive, Richland, WA Phone: Fax: WORKSHEET FOR COMMERCIAL PLAN REVIEWS THIS WORKSHEET MUST BE SIGNED (AT END OF DOCUMENT) BY THE ARCHITECT OR ENGINEER OF RECORD FOR THE ENTIRE PROJECT (SEC. 106.3.4) FOR ALL COMMERCIAL OR MIXED-USE BUILDINGS

More information

WON-DOOR CORPORATION Won-Door FireGuard Applications

WON-DOOR CORPORATION Won-Door FireGuard Applications WON-DOOR CORPORATION Won-Door FireGuard Applications A Code Analysis WON-DOOR CORPORATION Won-Door FireGuard Applications A Code Analysis THE INTERNATIONAL BUILDING CODE is widely recognized in the United

More information

Commercial Plans Application Checklist

Commercial Plans Application Checklist Botetourt County, Virginia Development Services Construction Compliance 5 West Main Street, Suite 100 Fincastle, Virginia 24090 Phone: (540) 473-8248 Fax: (540) 473-2018 www.botetourtva.gov Commercial

More information

APPLICATION NUMBER:, TAX MAP KEY: STREET ADDRESS:, PRPOJECT: APPLICANT:, PHONE NO: MAILING ADDRESS:, FAX NO:

APPLICATION NUMBER:, TAX MAP KEY: STREET ADDRESS:, PRPOJECT: APPLICANT:, PHONE NO: MAILING ADDRESS:, FAX NO: COUNTY OF KAUAI BUILDING DIVISION, DEPARTMENT OF PUBLIC WORKS 4444 RICE STREET, SUITE 175, LIHUE, HAWAII 96766 Telephone: (808) 241-6655 Fax Number: (808) 241-6806 BUILDING CODE COMMERCIAL CHECKLIST APPLICATION

More information

This worksheet must be signed by the architect or engineer of record for the entire project for commercial or mixed-use buildings.

This worksheet must be signed by the architect or engineer of record for the entire project for commercial or mixed-use buildings. Application - City of Oxnard WORKSHEET FOR COMMERCIAL PLAN REVIEWS This worksheet must be signed by the architect or engineer of record for the entire project for commercial or mixed-use buildings. Note:

More information

FIRE-RESISTANCE-RATED CONSTRUCTION

FIRE-RESISTANCE-RATED CONSTRUCTION CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION BC 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated

More information

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU TENANT IMPROVEMENT GROUP B FIRE PLAN REVIEW CHECKLIST

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU TENANT IMPROVEMENT GROUP B FIRE PLAN REVIEW CHECKLIST INFORMATION CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU TENANT IMPROVEMENT GROUP B FIRE PLAN REVIEW CHECKLIST DATE: PROJECT NO.: EXPIRATION DATE: STATUS: Corrections

More information

Village of Glen Ellyn Basement Remodeling Project Guidelines

Village of Glen Ellyn Basement Remodeling Project Guidelines Village of Glen Ellyn Basement Remodeling Project Guidelines Existing unfinished basement space is often remodeled to create more habitable (living, sleeping, eating, dining) space in a home. Building

More information

City of Roanoke. Commercial Permit Submittal Guidelines

City of Roanoke. Commercial Permit Submittal Guidelines City of Roanoke Commercial Permit Submittal Guidelines These guidelines are for information purposes only. The contractor is obligated to comply with all adopted codes and ordinances BUILDING INSPECTIONS

More information

The Building Code for Rookies

The Building Code for Rookies The Building Code for Rookies Or Basic Steps for Using the 7 Ohio Building Code Chapters - Or All the building code stuff you forgot to ask about in college and probably didn t have time for anyway AIA

More information

COMMERCIAL BUILDING PLAN REVIEW CHECKLIST

COMMERCIAL BUILDING PLAN REVIEW CHECKLIST Department of Urban Planning & Codes Enforcement City of Coatesville - 1 City Hall Place - Coatesville, Pennsylvania 19320 Phone: 610.384.0300 Fax: 610.384.6051 COMMERCIAL BUILDING PLAN REVIEW CHECKLIST

More information

Application for a Building Permit Commercial Work Building Commissioner 37 Main Street Charlton, MA

Application for a Building Permit Commercial Work Building Commissioner 37 Main Street Charlton, MA Paid Amount: Date: Check Number: Initials 1. Owner, Applicant Information Application for a Building Permit Work Building Commissioner 37 Main Street Charlton, MA 01507 508-248-2241 Date: Approved by:

More information

2009 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata)

2009 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata) TWELFTH PRINTING (Updated December 6, 2016) Note for 706.5.1: This is an erratum in the 8 th, 9 th, 10 th and 11 th printing only. The reference is correct in other editions. 706.5.1 Exterior walls. Where

More information

PLAN SUBMITTAL REQUIREMENTS - ARCHITECTURAL

PLAN SUBMITTAL REQUIREMENTS - ARCHITECTURAL FIRE DEPARTMENT 10573 E Stockton Blvd. Elk Grove, CA 95624 (916) 405-7100 Fax (916) 685-6622 www.yourcsd.com PLAN SUBMITTAL REQUIREMENTS - ARCHITECTURAL I Purpose To advise architects, engineers and contractors

More information

Company Overview. Significant Code Changes Massachusetts State Building Code 9 th Edition (2015 International Code)

Company Overview. Significant Code Changes Massachusetts State Building Code 9 th Edition (2015 International Code) Significant Code Changes Massachusetts State Building Code 9 th Edition (2015 International Code) Company Overview R.W. Sullivan Engineering (RWS) was established in 1945 and currently has 95 employees.

More information

CODE ANALYSIS REPORT SECOND FLOOR

CODE ANALYSIS REPORT SECOND FLOOR CODE ANALYSIS REPORT SECOND FLOOR 384 DWIGHT STREET HOLYOKE, MA Prepared by Dietz & Company Architects, Inc. 17 Hampden Street Springfield, MA March 2014 INTRODUCTION The following report is a preliminary

More information

2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES)

2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) 2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Reproduce the following data on the building plans sheet 1 or 2) Name of Project: Address:

More information

2009 IBC/IFC Photoluminescent Signs & Pathway Marking Systems Frequently Asked Questions

2009 IBC/IFC Photoluminescent Signs & Pathway Marking Systems Frequently Asked Questions 2009 IBC/IFC Photoluminescent Signs & Pathway Marking Systems Frequently Asked Questions 1. What is the difference between IBC & IFC? a. IBC International Building Code covers new construction b. IFC International

More information

EGRESS AZMIR SULTANA NICOLAS MIMU SAKUMA EDWIN VEGA CHAMORRO

EGRESS AZMIR SULTANA NICOLAS MIMU SAKUMA EDWIN VEGA CHAMORRO EGRESS AZMIR SULTANA NICOLAS CHAMORRO MIMU SAKUMA EDWIN VEGA DEFINITIONS NC ACCESSIBLE MEANS OF EGRESS. A continuous and unobstructed way of egress travel from any accessible point in a building or facility

More information

Code Change No: FS43-06/07

Code Change No: FS43-06/07 CODE CHANGES RESOURCE COLLECTION INTERNATIONAL MECHANICAL CODE PART III IBC MEANS OF EGRESS Approved as Submitted Committee Reason: The revised language in Sections 1021.3 and 1022.2. would provide consistency

More information

CHAPTER 6 TYPES OF CONSTRUCTION

CHAPTER 6 TYPES OF CONSTRUCTION CHAPTER 6 TYPES OF CONSTRUCTION SECTION 61 GENERAL 61.1 Scope. The provisions of this chapter shall control the classification of buildings as to type of construction. SECTION 62 CONSTRUCTION CLASSIFICATION

More information

A New Path Forward for Tall Wood Construction: Code Provisions and Design Steps

A New Path Forward for Tall Wood Construction: Code Provisions and Design Steps A New Path Forward for Tall Wood Construction: Code Provisions and Design Steps Dallas Wood Design Symposium Ricky McLain, PE, SE Senior Technical Director Tall Wood WoodWorks Wood Products Council Ricky.McLain@Woodworks.org

More information

INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS

INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS CHAPTER 8 INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS SECTION 801 GENERAL 801.1 Scope. The provisions of this chapter shall govern furniture and furnishings, interior finishes, interior trim,

More information

Building Codes and Ordinances ARC 227

Building Codes and Ordinances ARC 227 Building Codes and Ordinances ARC 227 Week 6 Fire Resistive Construction 03.02.10 Instructor: Rick Staub, AIA Email: staub@pointonearchitects.com Phone: 860-434-7707 Fire Resistive Construction Passive

More information

Common Plan Review Rejection Reasons

Common Plan Review Rejection Reasons Common Plan Review Rejection Reasons Submitted plans must contain sufficient information for plan reviewers to be able to verify that the proposed construction complies with the Virginia Uniform Statewide

More information

EXETER TOWNSHIP HOOD AND DUCT SYSTEMS FOR COMMERCIAL KITCHENS

EXETER TOWNSHIP HOOD AND DUCT SYSTEMS FOR COMMERCIAL KITCHENS HOOD AND DUCT SYSTEMS FOR COMMERCIAL KITCHENS POLICY STATEMENT This policy applies to NEW Hood and Duct systems. The Authority Having Jurisdiction will not waive major criteria in the applicable standards

More information

COMMERCIAL PLAN SUBMITTAL GUIDELINES JAN 2018

COMMERCIAL PLAN SUBMITTAL GUIDELINES JAN 2018 COMMERCIAL PLAN SUBMITTAL GUIDELINES JAN 2018 CONSTRUCTION CODES The City of Colleyville has adopted and enforces the following codes which are applicable to building construction activities within the

More information

Chapter 4 Test. Directions: Write the correct letter on the blank before each question.

Chapter 4 Test. Directions: Write the correct letter on the blank before each question. Chapter 4 Test Name: Date: Directions: Write the correct letter on the blank before each question. Objective 1: Describe the impact of fire on common building materials. 1. Which of the following is the

More information

Common Plan Review Rejection Reasons

Common Plan Review Rejection Reasons (CPHD) (ISD) Common Plan Review Rejection Reasons Submitted plans must contain sufficient information for plan reviewers to be able to verify that the proposed construction complies with the Virginia Uniform

More information

BUILDING DIVISION 120 Malabar Road, S.E., Palm Bay, FL Phone: (321) Fax: (321)

BUILDING DIVISION 120 Malabar Road, S.E., Palm Bay, FL Phone: (321) Fax: (321) BUILDING DIVISION 120 Malabar Road, S.E., Palm Bay, FL 32907 Phone: (321) 953-8924 Fax: (321) 953-8925 CUSTOMER SERVICE INFORMATION ON COMMERCIAL PLAN REVIEW REQUIRED DOCUMENTS MUST BE SUBMITTED AT TIME

More information

Name of Project: Address: Zip Code Owner/Authorized Agent: Phone # ( ) - Owned By: Select one Code Enforcement Jurisdiction: Select one

Name of Project: Address: Zip Code Owner/Authorized Agent: Phone # ( ) -  Owned By: Select one Code Enforcement Jurisdiction: Select one 2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Reproduce the following data on the building plans sheet 1 or 2) Name of Project: Address:

More information

Name of Project: Address: Zip Code Owner/Authorized Agent: Phone # ( ) - Owned By: Select one Code Enforcement Jurisdiction: Select one

Name of Project: Address: Zip Code Owner/Authorized Agent: Phone # ( ) -  Owned By: Select one Code Enforcement Jurisdiction: Select one 2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Reproduce the following data on the building plans sheet 1 or 2) Name of Project: Address:

More information

www.safti.com 888.653.3333 202 IBC 76 TABLES 76.3 Marking Rated Glazing Assemblies 76.5 Opening Assemblies, Ratings and Markings (previously 75.4) 76.6 Window Assembly Ratings (previously 75.5) These tables

More information

Learning Objectives. Copyright Materials MULTI STORY WOOD FRAMED BUILDINGS. Prepared for Wood Products Council. Presented by James E. Churchill, P.E.

Learning Objectives. Copyright Materials MULTI STORY WOOD FRAMED BUILDINGS. Prepared for Wood Products Council. Presented by James E. Churchill, P.E. NONSTRUCTURAL PROVISIONS FOR MULTI STORY WOOD FRAMED BUILDINGS 2010 CALIFORNIA BUILDING CODE (CBC ) Prepared for Wood Products Council WoodWorks Presented by James E. Churchill, P.E. Churchill Engineering,

More information

INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS

INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS CHAPTER 8 INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS SECTION 801 GENERAL 801.1 Scope. The provisions of this chapter shall govern interior finish, interior trim, furniture, furnishings, decorative

More information

Session: 2018 IBC Essentials Building Planning

Session: 2018 IBC Essentials Building Planning Session: 2018 IBC Essentials Building Planning 2018 IBC Essentials Building Planning Based on the 2018 International Building Code (IBC ) Description This seminar focuses on the basic concepts pertaining

More information

CSI. Spec/Build it Right & Barrier Management Policies FCIA 2017

CSI. Spec/Build it Right & Barrier Management Policies FCIA 2017 FCIA @ CSI Spec/Build it Right & Barrier Management Policies FCIA 2017 TOTAL FIRE PROTECTION Effective Compartmentation Fire Barriers, Fire Walls/Floors, Smoke Barriers Firestopping, Fire Dampers, Swinging

More information

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA CITY OF DANA POINT COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 33282 Golden Lantern, Suite 209 Dana Point, CA 92629 949 248-3594 www.danapoint.org B005 COM STRUCT 2016 CALIFORNIA CODES CODE CYCLE 01/01/2017

More information

TOWN OF PERINTON 1350 TURK HILL ROAD. FAIRPORT, NEW YORK (585) , Fax: (585) ,

TOWN OF PERINTON 1350 TURK HILL ROAD. FAIRPORT, NEW YORK (585) , Fax: (585) , BUILDING PERMIT REQUIREMENTS FOR BASEMENT REMODELING 1. Provide two copies of a detailed floor plan and elevation drawing, see sample drawings on page 9 and 10. Include materials, sizes, supports, heating,

More information

Commercial Plan Review: Exempt Buildings. Plan review by a Minnesota Building Official-Limited Presented by: Peter Villard

Commercial Plan Review: Exempt Buildings. Plan review by a Minnesota Building Official-Limited Presented by: Peter Villard Commercial Plan Review: Exempt Buildings Plan review by a Minnesota Building Official-Limited Presented by: Peter Villard Some of the content material is; Disclaimers Reproduced from the 2012 International

More information

INTERNATIONAL BUILDING CODE GENERAL

INTERNATIONAL BUILDING CODE GENERAL INTERNATIONAL BUILDING CODE GENERAL G1-09/10 202, 419.1 Proposed Change as Submitted Proponent: Maureen Traxler representing Washington Association of Building Officials Technical Code Development Committee

More information

INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS

INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS CHAPTER 8 INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS SECTION 801 GENERAL 801.1 Scope. The provisions of this chapter shall govern furniture and furnishings, interior finishes, interior trim,

More information

2015 International Mechanical Code Errata (Portions of text and tables not shown are unaffected by the errata)

2015 International Mechanical Code Errata (Portions of text and tables not shown are unaffected by the errata) PIPING MATERIAL 1 ST PRINTING (September 1, 2015) CHAPTER 3 GENERAL REGULATIONS TABLE 305.4 PIPING SUPPORT SPACING a MAXIMUM HORIZONTAL SPACING (feet) MAXIMUM VERTICAL SPACING (feet) ABS pipe 4 10 c Aluminum

More information

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD.

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD. Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD. Included are selected sections of codes taken directly from: 1997 Uniform

More information

2012 IBC Inspection of Fire-resistance Rated Walls

2012 IBC Inspection of Fire-resistance Rated Walls Accreditation 2012 IBC Inspection of Fire-resistance Rated Walls Based on the 2012 International Building Code (IBC ) The International Code Council has been accredited as an Authorized Provider by the

More information

NYC Technical Bulletin

NYC Technical Bulletin Building Owners Architects Engineers Quality Managers Safety Professionals Construction Industry NYC Technical Bulletin 2010-020 Special Inspection Requirements for Fire Resistant Rated Construction Life

More information

2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES)

2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) 2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Reproduce the following data on the building plans sheet 1 or 2) Name of Project: Address:

More information

Municipal Code of Chicago CHAPTER EXIT REQUIREMENTS

Municipal Code of Chicago CHAPTER EXIT REQUIREMENTS Municipal Code of Chicago CHAPTER 13-160 EXIT REQUIREMENTS 13-160-010 General provisions. 13-160-020 Definitions. 13-160-030 Exit types - Requirements. 13-160-040 Exit types - Above or below grade. 13-160-050

More information

Essentials of Fire Fighting

Essentials of Fire Fighting Essentials of Fire Fighting 6 th Edition Firefighter I Chapter 4 Building Construction Learning Objective 1 Describe the impact of fire on common building materials. Replace with manual graphic on slide

More information

Action Concept. Lumps CTL, solid and Glue Lam under heavy timber. I don't have any idea on arguments G 181 H O D

Action Concept. Lumps CTL, solid and Glue Lam under heavy timber. I don't have any idea on arguments G 181 H O D Final Action on 2018 International Building Code Group A Proposals Market Impact: H=High, M=Moderate, L=Low, N=None Position: O=Oppose, S=Support, MO=Mild Opposition, MS=Mild Support, N = None Action:

More information

CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY DRAFT. FLORIDA BUILDING CODE BUILDING, 5th EDITION (2014) 4.1

CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY DRAFT. FLORIDA BUILDING CODE BUILDING, 5th EDITION (2014) 4.1 CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,

More information

INTERNATIONAL CODE INTERPRETATIONS

INTERNATIONAL CODE INTERPRETATIONS 2012 INTERNATIONAL CODE INTERPRETATIONS PREFACE The 2012 International Codes promulgated by the International Code Council (ICC ) comprise a comprehensive set of model regulations for the construction

More information

BBS MEMO. Ohio Board of Building Standards August 3, Tussing Road, P.O. Box 4009, Reynoldsburg, Ohio

BBS MEMO. Ohio Board of Building Standards August 3, Tussing Road, P.O. Box 4009, Reynoldsburg, Ohio BBS MEMO Ohio Board of Building Standards August 3, 2015 6606 Tussing Road, P.O. Box 4009, Reynoldsburg, Ohio 43068-9009 Temporary Structures and Tents Temporary structures such as tents and membrane structures

More information

* RESIDENTIAL PLAN REVIEW *

* RESIDENTIAL PLAN REVIEW * CITY OF DES MOINES, IOWA COMMUNITY DEVELOPMENT DEPARTMENT PERMIT AND DEVELOPMENT CENTER 602 Robert D. Ray Drive DES MOINES, IOWA 50309 Phone: 515.283.4200 Facsimile: 515.283.4270 Based on the scope of

More information

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,

More information

Shaft Wall Solutions for Wood-Frame Structures. Ricky McLain, PE, SE WoodWorks Wood Products Council Charlotte WSF, November 2, 2017

Shaft Wall Solutions for Wood-Frame Structures. Ricky McLain, PE, SE WoodWorks Wood Products Council Charlotte WSF, November 2, 2017 Shaft Wall Solutions for Wood-Frame Structures Ricky McLain, PE, SE WoodWorks Wood Products Council Charlotte WSF, November 2, 2017 Course Description It is fairly common for light wood-frame commercial

More information

CITY OF ANDERSON BUILDING AND CODES 601 South Main Street

CITY OF ANDERSON BUILDING AND CODES 601 South Main Street CITY OF ANDERSON BUILDING AND CODES 601 South Main Street Plan Review Notes (STREET ADDRESS) ANDERSON, SC Plan Review Number: Building Plans prepared by: Plans Signed by: Project Name: Plans Received:

More information

INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS

INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS November 2018 Contents 1. Introduction... 1 2. Ontario Building Code and Second Dwelling Units... 1 3. How Do I Make My Secondary Dwelling Unit

More information

2003 International Residential Building Code

2003 International Residential Building Code 2003 International Residential Building Code Section R305 Ceiling Height Habitable rooms, hallways, corridors, bathrooms, toilet rooms, laundry rooms and basements shall have a ceiling height of not less

More information

Shaft Wall Solutions for Wood-Frame Structures. Ricky McLain, PE, SE WoodWorks Wood Products Council Boston & Waltham Workshops, December 6 & 7, 2017

Shaft Wall Solutions for Wood-Frame Structures. Ricky McLain, PE, SE WoodWorks Wood Products Council Boston & Waltham Workshops, December 6 & 7, 2017 Shaft Wall Solutions for Wood-Frame Structures Ricky McLain, PE, SE WoodWorks Wood Products Council Boston & Waltham Workshops, December 6 & 7, 2017 Shaft Walls Shaft Walls Form Shaft Enclosures The purpose

More information

INFORMATIONAL HANDOUT FOR FINISHING A BASEMENT

INFORMATIONAL HANDOUT FOR FINISHING A BASEMENT 7100 147 th Street West Telephone (952) 953-2588 Apple Valley, MN 55124-9016 Fax (952) 953-2515 www.cityofapplevalley.org INFORMATIONAL HANDOUT FOR FINISHING A BASEMENT 1. Submit plan showing the proposed

More information

UBC. (1997 Edition) (p.1-116) 2-hr. shaft required for

UBC. (1997 Edition) (p.1-116) 2-hr. shaft required for Protection of Shaft Enclosures (Exit Stairs) Protection of Shaft Enclosures (Other Shafts) Comparison on Fire Safety Provisions* (Revised 2/28/03) (S) = Small difference in fire protection, (M) = Moderate

More information