1 December 3, 2012 TO: PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS SUBJECT: Proposed Acceptance Criteria for Intumescent Fire-resistant Coatings Field-applied to Prefabricated Wood I-Joists, Subject (MO/MB). Dear Colleague: We are seeking your comments on the enclosed proposal for a new acceptance criteria, which is being posted for 30 days of public comment on the ICC-ES web site. Public comments will be considered in preparing a revised draft of the criteria, which we hope to present at a future Evaluation Committee hearing. The proposed new criteria establishes performance testing for evaluating intumescent fire-resistant coatings field-applied to prefabricated wood I-joists. The criteria is limited to the application noted in Section 1.2. Field application of the intumescent fire-resistant coating will need special inspection as noted in Section 6.8 of the criteria. Documentation on the application and field testing of the intumescent fireresistant coating after application is required as noted in Section Use of the intumescent fire-resistant coatings field-applied to prefabricated wood I- joists will need to be authorized by the manufacturer of the wood I-joists, and testing conducted for each manufacturer as needed. The intumescent fire-resistant coating will need to be noted in the prefabricated wood I-joist evaluation report. Refer to Sections 3.2 and 6.0. Performance testing of the intumescent fire-resistant coatings is noted in Section 4.0 of the criteria and includes full-scale fire testing of pre-fabricated wood I-joists, durability of the coating, effects on mechanical properties, and corrosion effects of the coating. If it is of interest, please review the draft criteria and send us your comments at the earliest opportunity. At the end of the 30-day comment period, we will post on our web site the correspondence we have received. To submit your comments, please use the form on the web site and attach any letters or other materials. If you would like an explanation of the alternate criteria process, under which we are soliciting comments, this too is available on the ICC-ES web site.

2 2 Please do not try to communicate directly with any Evaluation Committee member about a criteria under consideration, as committee members cannot accept such communications. Thank you for your interest and your contributions. If you have any questions, please contact me at (800) , extension 5685, or Michael Beaton, Senior Vice- President, at extension You may also reach us by at es@icc-es.org. Yours very truly, MPO/bc Encl. cc: Evaluation Committee Michael O Reardon, P.E. Regional Manager

3 (800) (562) A Subsidiary of the International Code Council PROPOSED ACCEPTANCE CRITERIA FOR INTUMESCENT FIRE- RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS AC450 Proposed December 2012 PREFACE Evaluation reports issued by ICC Evaluation Service, LLC (ICC-ES), are based upon performance features of the International family of codes. (Some reports may also reference older code families such as the BOCA National Codes, the Standard Codes, and the Uniform Codes.) Section of the International Building Code reads as follows: The provisions of this code are not intended to prevent the installation of any materials or to prohibit any design or method of construction not specifically prescribed by this code, provided that any such alternative has been approved. An alternative material, design or method of construction shall be approved where the building official finds that the proposed design is satisfactory and complies with the intent of the provisions of this code, and that the material, method or work offered is, for the purpose intended, at least the equivalent of that prescribed in this code in quality, strength, effectiveness, fire resistance, durability and safety. ICC-ES may consider alternate criteria for report approval, provided the report applicant submits data demonstrating that the alternate criteria are at least equivalent to the criteria set forth in this document, and otherwise demonstrate compliance with the performance features of the codes. ICC-ES retains the right to refuse to issue or renew any evaluation report, if the applicable product, material, or method of construction is such that either unusual care with its installation or use must be exercised for satisfactory performance, or if malfunctioning is apt to cause injury or unreasonable damage. NOTE: The Preface for ICC-ES acceptance criteria was revised in July 2011 to reflect changes in policy. Acceptance criteria are developed for use solely by ICC-ES for purpose of issuing ICC-ES evaluation reports..

4 Page 2 December 2012 PROPOSED ACCEPTANCE CRITERIA FOR INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS INTRODUCTION 1.1 Purpose: The purpose of this criteria is to establish requirements for an intumescent fire-resistant coating field-applied to prefabricated wood I-joists to be recognized in an ICC Evaluation Service LLC. (ICC-ES), evaluation report under the 2012, 2009 and 2006 International Residential Code (IRC). The basis of recognition is IRC Section R Applicable code sections are listed in Section 1.2. The reason for the development of this criteria is that the code does not address the use of field-applied intumescent fire-resistant coatings for the uses described in Section Scope: This acceptance criteria is limited to intumescent fire-resistant coatings field-applied to prefabricated wood I-joists in new construction, utilized for fire protection of floors where recognition is sought for establishment of equivalent fire performance to the materials described in Exception 4 to Section R501.3 of the 2012 IRC. 1.3 Codes and Referenced Standards: Codes: , 2009 and 2006 International Residential Code ( IRC), International Code Council , 2009 and 2006 International Building Code ( IBC), International Code Council , 2009 and 2006 International Fire Code ( IFC), International Code Council.

5 FOR INTUMESCENT FIRE-RESISTANT COATINGS Page , 2009 and 2006 International Existing Building Code (IEBC), International Code Council ASTM International, ASTM D (-05 for the 2009 IRC, -04 for the 2006 IRC), Standard Specification for Establishing and Monitoring Structural Capacities of Prefabricated Wood I-joists ICC-ES Acceptance Criteria: ICC-ES Acceptance Criteria for Prefabricated Wood I-Joists (AC14) ICC-ES Acceptance Criteria for Corrosion-resistant Fasteners and Evaluation of Corrosion effects of Wood Treatment Chemicals (AC257) ICC-ES Acceptance Criteria for Surface-applied Fire-retardant Coatings (AC363). 1.4 Definitions: Intumescent Fire-resistant Coatings: Refer to Section 202 of the 2012 IBC Prefabricated Wood I-joist: Refer to Section of AC14 and Sections 3.1 and 3.2 of this criteria. 2.0 BASIC INFORMATION 2.1 General: The following information shall be submitted: Product Description: Complete information concerning material specifications, and the manufacturing process Application Instructions: The instructions shall include the following items: Application of the intumescent fire-resistant coating is limited to interior assemblies and must occur once the structure is dried-in (having a sustained humidity of less than 80 percent). The coating must be applied prior to installation of mechanical, electrical or plumbing components.

6 FOR INTUMESCENT FIRE-RESISTANT COATINGS Page The contractor shall be trained and qualified in the proper application procedures by the intumescent fire-resistant coating manufacturer before starting the first application Application and/or installation details for the intumescent fire-resistant coating The frequency of thickness measurements with a wet film gauge during the application of each coat necessary to ensure uniform thickness Details of the surface preparation of the material Minimum ambient temperature before and after application Product handling and storage requirements Restrictions or limitations on use Packaging and Identification: A description of the field identification of the intumescent fire-resistant coating shall be submitted. Identification provisions shall include the evaluation report holder s name and address, the evaluation report number and the name of the product Field Tests: The intumescent fire-resistant coating manufacturer shall identify the methods used to verify the presence and quality of workmanship of the intumescent fire-resistant coating during and after application, in accordance with the relevant methods described in the National Fireproofing Contractor s Association 400 Field Quality Assurance Procedure for Application of Mastic and Thin-Film Intumescent Fireresistive Coatings. 2.2 Testing Laboratories: Testing laboratories shall comply with Section 2.0 of the ICC-ES Acceptance Criteria for Test Reports (AC85) and Section 4.2 of the ICC-ES Rules of Procedure for Evaluation Reports.

7 FOR INTUMESCENT FIRE-RESISTANT COATINGS Page Test Reports: Test reports shall comply with AC Product Sampling: Products shall be sampled in accordance with Section 3.1 of AC TEST AND PERFORMANCE REQUIREMENTS 3.1 Fire Protection of Floors: Where recognition is sought for establishment of equivalent fire performance to the materials described in Exception 4 to Section R501.3 of the 2012 IRC, testing and analysis must be conducted in accordance with Section 4.0 of this criteria. 3.2 Substrates: Documentation shall be submitted to demonstrate that the prefabricated wood I-joists to which the intumescent fire-resistant coating is to be applied, comply with Section R of the IRC. The documentation shall consist of a current ICC-ES evaluation report on the prefabricated wood I-joists. Use of intumescent fire-resistant coatings with prefabricated wood I-joists noted above must be authorized by the I-joist manufacturer. Testing shall be conducted for each manufacturer. Recognition of the intumescent fire-resistant coating shall be described within the prefabricated wood I-joist manufacturer s evaluation report and the intumescent coating manufacturer s evaluation report. 4.0 TEST METHODS 4.1 Fire Protection of Floors: Where recognition is sought for a field-applied intumescent fire-resistant coating to establish equivalent fire performance to the materials described in Exception 4 of Section R501.3 of the 2012 IRC, the test shall meet the requirements and conditions of Sections A4.4.1, A , A and A4.4.3 of AC14. Durability, mechanical properties and corrosion effects testing shall be conducted in accordance with Sections 4.2, 4.3 and 4.4 of this criteria.

8 FOR INTUMESCENT FIRE-RESISTANT COATINGS Page Conditions of Acceptance: The fire performance test shall meet the requirements and conditions of Sections A of AC Durability of Intumescent Fire-resistant Coatings: The intumescent fireresistant coating shall be evaluated to ensure that environmental exposure does not affect the fire performance. Specimens shall consist of the minimum thickness of proposed web stock, with dimensions of 4 feet by 4 feet (1.2 m by 1.2 m). The coating shall be applied to each specimen in accordance with the manufacturer s quality documentation, except that it shall be applied only to one side (same side for all specimens). A minimum of 3 shall be used as matched control specimens (coated, but not subjected to the exposure condition). The remaining specimens shall be subjected to the exposure condition as described in Item a. The exposed specimens and control specimens shall be tested in accordance with Item b. a. Exposure Condition Evaluate effect of elevated temperature: A minimum of 3 specimens shall be conditioned in accordance with ASTM D5664 (temperature at 150 ± 4 F and relative humidity 50% for 108 ± 3 days). b. Intermediate Scale Calorimeter (ICAL) Tests: Each specimen shall be exposed to a uniform heat flux on the protected face using the radiant panel configuration described ASTM E1623 with an energy input of 50 kw/m2. The burn-through time, which is defined as the time elapsed between the start of the test and the time at which sustained flaming (i.e., the existence of flame on or over the surface of the specimen for periods of at least 5 seconds) appears on the unexposed side of the specimen, shall be recorded for each specimen. Due to potential artificial edge effects introduced by the sample holder where surface flames may curl around the specimen edges or heat transfer from the return

9 FOR INTUMESCENT FIRE-RESISTANT COATINGS Page edges of the metal holder may be higher than in the field of the specimen, flaming within 5 inches of the edges of the unexposed specimen shall be allowed. These flames can be extinguished using a suitable means that will not affect the field of the unexposed specimen surface The average burn-through time for the exposed specimens shall be at least 90% of the average burn-through time for the control group. If the exposure condition results in an average burn-through time less than 90% of the average burn-through time for the control group, I-joist specimens may be subjected to the durability exposure condition and tested in accordance with Section 4.1. Conditions of Acceptance: The requirements of the durability exposure condition are deemed to comply when the test result satisfies the requirements of A of AC Effect of Intumescent Fire-Resistant Coatings on Mechanical Properties: Intumescent fire-resistant coatings field-applied to prefabricated wood I-joists shall be subjected to testing to ensure that the I-joist mechanical properties are not affected by fire protection materials. One of the following two test programs shall be followed: a. Flange stiffness, flange tension, flange compression, and I-joist shear shall be evaluated per ASTM D5055. b. I-joist stiffness, moment and shear shall be evaluated per ASTM D Evaluations shall be based on the comparison between a control group (unprotected) and a matched group (protected) with each group comprised of not less than 20 specimens when flange materials are tested or not less than 10 specimens when I-joist

10 FOR INTUMESCENT FIRE-RESISTANT COATINGS Page specimens are tested. The following conditioning environments shall be evaluated separately for both control and matched groups: a. Ambient: Condition based on an as-manufactured condition. b. Elevated Temperature: Condition both protected and control groups in accordance with ASTM D5664 (temperature at 150 ± 4 F and relative humidity 50% for 108 ± 3 days) The average mechanical property of the matched group (protected) under each conditioning environment shall not be less than the 95% lower confidence bound on the average mechanical property of the control group (unprotected) under the same conditioning environment, as calculated as follows: M m M c (1 t V ) N where: Mm Mc = average mechanical property (stiffness or strength) of matched group (protected) for the conditioning environment listed in this Section, = average mechanical property (stiffness or strength) of the control group (unprotected) for the same conditioning environment as Mm, t = student t statistic with 95 % confidence (see Table 1 of ASTM D2915); t = for 20 specimens (19 degrees of freedom) or t = for 10 specimens (9 degrees of freedom),

11 FOR INTUMESCENT FIRE-RESISTANT COATINGS Page V N = coefficient of variation for the mechanical property of the control group at the conditioning environment; V 0.2 (when V is greater than 0.2, use 0.2 in the calculation), and = sample size for the control group; N 20 when flange materials are tested or N 10 when I-joist specimens are tested. Conditions of Acceptance: The mechanical properties testing shall indicate that the coating has no effect on the performance of a coated I-joist, or a proper reduction factor shall be applied. 4.4 Corrosion Testing for Intumescent Fire-resistant Coatings: Corrosion effects of fire protection materials on fasteners, if any, shall be evaluated in accordance with the provisions of AC257 that are applicable to evaluations of corrosion effects of wood treatment chemicals, with the following exceptions and conditions: Instead of evaluating the corrosion effects of a treatment chemical, the corrosion effects of the fire protection material shall be evaluated. Thus, the provisions relating to AWPA Use Categories do not apply. Those provisions relating to minimum retention levels do not apply unless the fire protection is in the form of a woodpenetrating treatment chemical Control (benchmark) materials shall consist of unprotected prefabricated wood I-joist materials from the same type of materials (i.e., flange and web materials) on which the corrosion tests are performed The control and protected materials shall both be tested with steel coupons meeting ASTM A653 with a G60 coating designation The control and protected materials shall be tested under Exposure Condition 5 (Dry Use).

12 FOR INTUMESCENT FIRE-RESISTANT COATINGS Page Conditions of Acceptance: The corrosion effect of the fire protection materials on a fastener complying with Section R of the 2012 and 2009 IBC, and Section R319.3 of the 2006 IRC, shall not be significantly greater than that of the control materials (without the fire protective material), as determined in accordance with Section AC QUALITY CONTROL 5.1 Intumescent fire-resistant coatings shall be produced at plants under an approved quality control program, with inspections conducted by an inspection agency accredited by the International Accreditation Service (IAS) or otherwise acceptable to ICC-ES. 5.2 Quality documentation complying with the ICC-ES Acceptance Criteria for Quality Documentation (AC10) shall be submitted for each facility manufacturing or labeling products that are recognized in the ICC-ES evaluation report. 5.3 A qualifying inspection shall be conducted at each manufacturing facility when required by the ICC-ES Acceptance Criteria for Inspections and Inspection Agencies (AC304). 5.4 Field Inspection and Report Requirements: Field inspections and reporting shall include the following: Installation shall be by applicators approved by the intumescent fire-resistant coating manufacturer as being qualified to perform such installations. A list containing the names and addresses of approved applicators shall be maintained and shall be made available to code officials or ICC-ES upon request An installation card or certificate provided by the intumescent fire-resistant coating manufacture shall be completed by the applicator shall be and available for review by the code official at the completion of each project.

13 FOR INTUMESCENT FIRE-RESISTANT COATINGS Page A report on the special inspection shall be provided to the code official in accordance with Section 6.8 of this criteria, when required. 6.0 EVALUATION REPORT RECOGNITION Intumescent fire-resistant coatings field-applied to prefabricated wood I-joists evaluated under this criteria are limited to wood I-joist manufacturer's that have authorized the use of the coating and reference to the intumescent fire-resistant coating I shall be included in the wood I-joist manufacturer s ICC-ES evaluation report. The wood I-joist evaluation report shall include the following information: 6.1 The evaluation report shall describe the field tests required in Section of this acceptance criteria, and shall include a condition of use that the field test will be performed by the applicator when requested by the code official. 6.2 The evaluation report shall include a sample installation card or certificate as required by Section of this acceptance criteria. 6.3 The evaluation report shall specify if the coating is required to be maintained or renewed; the frequency of maintenance or renewal; and that the maintenance or renewal is subject to the approval of the fire official in accordance with International Fire Code (IFC) Section The evaluation report shall specify the conditions under which intumescent fireresistant coatings may be overcoated with paint. 6.5 The evaluation report shall include a condition of use that use of the coating is limited to exposed interior locations having a sustained humidity of less than 80 percent. 6.6 The evaluation report shall specify the substrate, thickness of coating and cure time for which performance has been established.

14 FOR INTUMESCENT FIRE-RESISTANT COATINGS Page The evaluation report shall include a condition of use stating that application of the intumescent fire-resistant coating is limited to use on surfaces facing the interior of the building that the coating must be applied once the structure is dried-in as defined herein, to interior assemblies; and that the coating must be applied prior to installation of mechanical, electrical or plumbing components. 6.8 The evaluation report shall include requirements for special inspection and a condition of use that special inspection shall be provided when determined to be necessary by the code official in accordance with Sections and (using the relevant methods prescribed in AWCI Technical Manual 12-B) of the 2012 IBC, Section of the 2009 IBC or Section of the 2006 IBC, as applicable.

June 7, 2012 PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES

June 7, 2012 PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES June 7, 2012 TO: PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES SUBJECT: Revisions to the Acceptance Criteria for Metallic HVAC Duct Enclosure Assemblies, Subject AC179-0612-R1 (MB/CA) Dear Colleague:

More information

April 2, 2018 PARTIES INTERESTED IN CROSS LAMINATED TIMBER PANELS USED AS COMPONENTS IN FLOOR AND ROOF DECKS

April 2, 2018 PARTIES INTERESTED IN CROSS LAMINATED TIMBER PANELS USED AS COMPONENTS IN FLOOR AND ROOF DECKS April 2, 2018 TO: PARTIES INTERESTED IN CROSS LAMINATED TIMBER PANELS USED AS COMPONENTS IN FLOOR AND ROOF DECKS SUBJECT: Proposed Revisions to the ICC-ES Acceptance Criteria for Cross-laminated Timber

More information

June 1, 2017 PARTIES INTERESTED IN POST-TENSIONING ANCHORAGES AND COUPLERS OF PRESTRESSED CONCRETE

June 1, 2017 PARTIES INTERESTED IN POST-TENSIONING ANCHORAGES AND COUPLERS OF PRESTRESSED CONCRETE June 1, 2017 TO: PARTIES INTERESTED IN POST-TENSIONING ANCHORAGES AND COUPLERS OF PRESTRESSED CONCRETE SUBJECT: Proposed Revisions to the Acceptance Criteria for Post-Tensioning Anchorages and Couplers

More information

February 1, SUBJECT: Proposed Revisions to the Acceptance Criteria for Staples, Subject AC R1 (EL/JF)

February 1, SUBJECT: Proposed Revisions to the Acceptance Criteria for Staples, Subject AC R1 (EL/JF) February 1, 2018 TO: PARTIES INTERESTED IN STAPLES SUBJECT: Proposed Revisions to the Acceptance Criteria for Staples, Subject AC201-0218-R1 (EL/JF) Dear Colleague: We are seeking your comments on proposed

More information

July 23, 2010 PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION

July 23, 2010 PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION July 23, 2010 TO: SUBJECT: PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION Revisions to the Acceptance Criteria for Reflective Foil Insulation, Subject AC02-0610-R1 (LS/RB) Dear Madam or Sir: In June

More information

December 1, 2014 PARTIES INTERESTED IN STRUCTURAL WOOD-BASED PRODUCTS

December 1, 2014 PARTIES INTERESTED IN STRUCTURAL WOOD-BASED PRODUCTS December 1, 2014 TO: PARTIES INTERESTED IN STRUCTURAL WOOD-BASED PRODUCTS SUBJECT: Proposed Revision to the ICC-ES Acceptance Criteria for Structural Wood-Based Products, Subject AC47-1214-R2-2 (JF/PC)

More information

June 9, 2008 PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS

June 9, 2008 PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect June 9, 2008 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS SUBJECT: Acceptance Criteria for Termite-resistant

More information

February 1, 2018 PARTIES INTERESTED IN DECK BOARD SPAN RATINGS AND GUARDRAIL SYSTEMS (GUARDS AND HANDRAILS)

February 1, 2018 PARTIES INTERESTED IN DECK BOARD SPAN RATINGS AND GUARDRAIL SYSTEMS (GUARDS AND HANDRAILS) February 1, 2018 TO: SUBJECT: PARTIES INTERESTED IN DECK BOARD SPAN RATINGS AND GUARDRAIL SYSTEMS (GUARDS AND HANDRAILS) Proposed Revisions to the ICC-ES Acceptance Criteria for Deck Board Span Ratings

More information

June 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION

June 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION June 1, 2010 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION SUBJECT: Proposed Revisions to the Acceptance Criteria for Reflective Foil Insulation, Subject AC02-0610-R1 (LS/RB)

More information

June 1, 2012 PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS

June 1, 2012 PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS June 1, 2012 TO: PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS SUBJECT: Proposed Revisions to the Acceptance Criteria for Cold-formed Steel Framing Members, Subject AC46-0612-R1 (WM/DM) Dear

More information

October 3, Section 1.2 Scope and Section 6.6 were revised to clarify interior and exterior construction types allowed.

October 3, Section 1.2 Scope and Section 6.6 were revised to clarify interior and exterior construction types allowed. October 3, 2016 TO: PARTIES INTERESTED IN EVALAUTION REPORTS ON FIBER- REINFORCED POLYMER (FRP) COMPOSITE COLUMNS USED AS AXIAL LOAD-BEARING AND NONLOAD-BEARING ARCHITECTURAL AND DECORATIVE COLUMNS SUBJECT:

More information

June 1, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS

June 1, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS June 1, 2009 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS SUBJECT: Proposed Revisions to the Acceptance Criteria for Wood-based Studs, Subject AC202-0609-R1

More information

June 22, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON COMPOSITE COLD-FORMED LIGHT GAGE STEEL AND CONCRETE MASONRY LINTELS

June 22, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON COMPOSITE COLD-FORMED LIGHT GAGE STEEL AND CONCRETE MASONRY LINTELS June 22, 2009 TO: SUBJECT: PARTIES INTERESTED IN EVALUATION REPORTS ON COMPOSITE COLD-FORMED LIGHT GAGE STEEL AND CONCRETE MASONRY LINTELS Acceptance Criteria for Composite Cold-formed Light Gage Steel

More information

August 1, Removed reference to the standard edition from Sections and

August 1, Removed reference to the standard edition from Sections and August 1, 2018 TO: PARTIES INTERESTED IN SPRAYED FIRE-RESISTANT MATERIALS (SFRMs), INTUMESCENT FIRE-RESISTANT COATINGS AND MASTIC FIRE-RESISTANT COATINGS USED TO PROTECT STRUCTURAL STEEL MEMBERS SUBJECT:

More information

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) AC191 Approved May 2008 Effective June 1, 2008 Previously approved February 2008, October 2007,

More information

Originally Issued: 04/24/2018 Valid Through: 04/30/ Design

Originally Issued: 04/24/2018 Valid Through: 04/30/ Design INTERNATIONAL FIREPROOF TECHNOLOGY, INC ADDITIONAL LISTEE: INTERNATIONAL CARBIDE TECHNOLOGY CO., LTD DC5040 FIELD APPLIED INTUMESCENT COATINGS CSI Section: 09 96 43 Fire-Retardant Coatings 1.0 RECOGNITION

More information

April 18, 2018 PARTIES INTERESTED IN ADHERED PORCELAIN TILE WALL CLADDING SYSTEM

April 18, 2018 PARTIES INTERESTED IN ADHERED PORCELAIN TILE WALL CLADDING SYSTEM April 18, 2018 TO: SUBJECT: PARTIES INTERESTED IN ADHERED PORCELAIN TILE WALL CLADDING SYSTEM Proposed Acceptance Criteria for Adhered Porcelain Tile Wall Cladding System, Subject (YM/DO) Hearing Information:

More information

The Rehabilitation of Existing Building Drains and Building Sewers by the

The Rehabilitation of Existing Building Drains and Building Sewers by the Inversion or Pulled-in-Place Method and Curing of Resin-impregnated Tube Page 1 of 7 www.icc-es.org/pmg (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council PROPOSED PMG LISTING

More information

February 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON ROOF UNDERLAYMENTS FOR USE IN SEVERE CLIMATE AREAS

February 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON ROOF UNDERLAYMENTS FOR USE IN SEVERE CLIMATE AREAS February 1, 2010 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON ROOF UNDERLAYMENTS FOR USE IN SEVERE CLIMATE AREAS SUBJECT: Proposed Revisions to the Acceptance Criteria for Roof Underlayments for Use

More information

October 12, Yours very truly, Gary G. Nichols, P.E., SECB Vice President. GGN/md Enclosure Evaluation Committee

October 12, Yours very truly, Gary G. Nichols, P.E., SECB Vice President. GGN/md Enclosure Evaluation Committee October 12, 2010 TO: SUBJECT: PARTIES INTERESTED IN EVALUATION REPORTS ON STAY-IN-PLACE, FOAM PLASTIC INSULATING CONCRETE FORM (ICF) SYSTEMS FOR SOLID CONCRETE WALLS Revisions to the Acceptance Criteria

More information

PMG LISTING CRITERIA FOR STRUCTURAL ADHESIVE JOINING SYSTEMS FOR FITTINGS PREFACE

PMG LISTING CRITERIA FOR STRUCTURAL ADHESIVE JOINING SYSTEMS FOR FITTINGS PREFACE www.icc-es.org/pmg (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council PMG LISTING CRITERIA FOR STRUCTURAL ADHESIVE JOINING SYSTEMS FOR FITTINGS Approved March 2009 (Editorially

More information

ACCEPTANCE CRITERIA FOR THREADED HIGH-STRENGTH STEEL BARS FOR CONCRETE REINFORCEMENT PREFACE

ACCEPTANCE CRITERIA FOR THREADED HIGH-STRENGTH STEEL BARS FOR CONCRETE REINFORCEMENT PREFACE www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR THREADED HIGH-STRENGTH STEEL BARS FOR CONCRETE REINFORCEMENT AC237 Approved June 2009

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: APPLIED FIREPROOFING REPORT HOLDER: FLAMEOFF COATINGS, INC. EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: APPLIED FIREPROOFING REPORT HOLDER: FLAMEOFF COATINGS, INC. EVALUATION SUBJECT: 0 ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org Most Widely Accepted and Trusted ESR 3874 Reissued 11/2018 This report is subject to renewal 11/2019. SECTION: 07 81 00

More information

ACCEPTANCE CRITERIA FOR ROOF UNDERLAYMENT FOR USE IN SEVERE CLIMATE AREAS PREFACE

ACCEPTANCE CRITERIA FOR ROOF UNDERLAYMENT FOR USE IN SEVERE CLIMATE AREAS PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR ROOF UNDERLAYMENT FOR USE IN SEVERE CLIMATE AREAS AC48 Approved January 2000 Effective February 1, 2000 (Editorially revised

More information

PMG LISTING CRITERIA FOR PERT-AL-PERT PIPE AND FITTINGS FOR REFRIGERATION APPLICATIONS LC1039. Approved Date: November 2015 PREFACE

PMG LISTING CRITERIA FOR PERT-AL-PERT PIPE AND FITTINGS FOR REFRIGERATION APPLICATIONS LC1039. Approved Date: November 2015 PREFACE www.icc-es.org/pmg (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council PMG LISTING CRITERIA FOR PERT-AL-PERT PIPE AND FITTINGS FOR REFRIGERATION APPLICATIONS Approved Date: November

More information

December 1, 2011 PARTIES INTERESTED IN ALTERNATE DOWEL-TYPE THREADED FASTENERS

December 1, 2011 PARTIES INTERESTED IN ALTERNATE DOWEL-TYPE THREADED FASTENERS December 1, 2011 TO: PARTIES INTERESTED IN ALTERNATE DOWEL-TYPE THREADED S SUBJECT: Proposed Revisions to the Acceptance Criteria for Alternate Dowel-type Threaded Fasteners, Subject AC233-1211-R1 (EL/JS)

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: APPLIED FIREPROOFING REPORT HOLDER: CARBOLINE COMPANY

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: APPLIED FIREPROOFING REPORT HOLDER: CARBOLINE COMPANY 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 973 Reissued /207 This report is subject to renewal /208. DIVISION: 07 00 00 THERMAL

More information

ACCEPTANCE CRITERIA FOR POLYMER-BASED AND POLYMER-MODIFIED EXTERIOR AND INTERIOR WALL CLADDING

ACCEPTANCE CRITERIA FOR POLYMER-BASED AND POLYMER-MODIFIED EXTERIOR AND INTERIOR WALL CLADDING www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR POLYMER-BASED AND POLYMER-MODIFIED EXTERIOR AND INTERIOR WALL CLADDING AC92 Approved

More information

The purpose of this memo is to respond to the comments received in response to the May 1, 2007, staff letter and the revised criteria.

The purpose of this memo is to respond to the comments received in response to the May 1, 2007, staff letter and the revised criteria. ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect #19 To: From: ICC-ES Evaluation Committee Brian Gerber, S.E., and Irni Yani Date: June 1, 2007 Subject: Revisions to the Proposed Acceptance Criteria

More information

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER AC51 Approved February 2008 Effective March 1, 2008 (Editorially

More information

March 6, 2012 PARTIES INTERESTED IN THE DETERMINATION OF FORMALDEHYDE EMISSIONS OF COMPOSITE WOOD PRODUCTS

March 6, 2012 PARTIES INTERESTED IN THE DETERMINATION OF FORMALDEHYDE EMISSIONS OF COMPOSITE WOOD PRODUCTS March 6, 2012 TO: SUBJECT: PARTIES INTERESTED IN THE DETERMINATION OF FORMALDEHYDE EMISSIONS OF COMPOSITE WOOD PRODUCTS Revisions to the Environmental Criteria for Determination of Formaldehyde Emissions

More information

ACCEPTANCE CRITERIA FOR EXPANSION BOLTS IN STRUCTURAL STEEL CONNECTIONS (BLIND-BOLTS) PREFACE

ACCEPTANCE CRITERIA FOR EXPANSION BOLTS IN STRUCTURAL STEEL CONNECTIONS (BLIND-BOLTS) PREFACE www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR EXPANSION BOLTS IN STRUCTURAL STEEL CONNECTIONS (BLIND-BOLTS) AC437 Approved October

More information

Session: Approving and Selecting Building Products with Confidence - What To Look for in Evaluation Reports

Session: Approving and Selecting Building Products with Confidence - What To Look for in Evaluation Reports Session: Approving and Selecting Building Products with Confidence - What To Look for in Evaluation Reports Approving and Selecting Building Products with Confidence - What To Look for in Evaluation Reports

More information

DIVISION: FINISHES SECTION: FIRE RETARDANT COATINGS REPORT HOLDER: FIRE RETARDANT COATINGS OF TEXAS, LLC

DIVISION: FINISHES SECTION: FIRE RETARDANT COATINGS REPORT HOLDER: FIRE RETARDANT COATINGS OF TEXAS, LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3872 Reissued 10/2017 This report is subject to renewal 10/2019. DIVISION: 09 00

More information

ACCEPTANCE CRITERIA FOR METAL COMPOSITE MATERIAL (MCM) PREFACE

ACCEPTANCE CRITERIA FOR METAL COMPOSITE MATERIAL (MCM) PREFACE www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR METAL COMPOSITE MATERIAL (MCM) AC25 Approved October 2010 (Editorially revised August

More information

DIVISION: CONCRETE SECTION: MAINTENANCE OF CONCRETE REPORT HOLDER: STRUCTURAL TECHNOLOGIES, LLC

DIVISION: CONCRETE SECTION: MAINTENANCE OF CONCRETE REPORT HOLDER: STRUCTURAL TECHNOLOGIES, LLC 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3606 Reissued 01/2018 This report is subject to renewal 01/2019. DIVISION: 03 00

More information

February 1, 2016 PARTIES INTERESTED IN EXTERIOR ULTRA-HIGH PERFORMANCE CONCRETE THIN WALL CLADDING PANELS

February 1, 2016 PARTIES INTERESTED IN EXTERIOR ULTRA-HIGH PERFORMANCE CONCRETE THIN WALL CLADDING PANELS February 1, 2016 TO: PARTIES INTERESTED IN EXTERIOR ULTRA-HIGH PERFORMANCE CONCRETE THIN WALL CLADDING PANELS SUBJECT: Proposed Revisions to the Acceptance Criteria for Exterior Ultra-high Performance

More information

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER PREFACE

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER AC51 Approved February 2008 Effective March 1, 2008 Previously approved October 2007, January 2001,

More information

August 31, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON ACCESS FLOORS

August 31, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON ACCESS FLOORS August 31, 2010 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON ACCESS FLOORS SUBJECT: Proposed Revisions to the Acceptance Criteria for Access Floors, Subject AC300-1010-R1 (EL/BG) Dear Madam or Sir:

More information

ICC-ES Evaluation Report Reissued December 1, 2011 This report is subject to renewal in two years.

ICC-ES Evaluation Report Reissued December 1, 2011 This report is subject to renewal in two years. ICC-ES Evaluation Report www.icc-es.org (800) -687 (6) 699-0 ESR-09 Reissued December, 0 This report is subject to renewal in two years. A Subsidiary of the International Code Council DIVISION: 07 00 00

More information

Originally Issued: 2/12/2016 Revised: 07/28/2017 Valid Through: 2/28/2018

Originally Issued: 2/12/2016 Revised: 07/28/2017 Valid Through: 2/28/2018 EVALUATION SUBJECT: FOAMSULATE 50 AND FOAMSULATE 210 SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION REPORT HOLDER: Accella Polyurethane Systems 100 Enterprise Drive Cartersville, GA 30120 (770) 607-0755

More information

PMG LISTING CRITERIA FOR MULTILAYER PIPE AND FITTINGS ASSEMBLY FOR REFRIGERANT APPLICATIONS LC1036

PMG LISTING CRITERIA FOR MULTILAYER PIPE AND FITTINGS ASSEMBLY FOR REFRIGERANT APPLICATIONS LC1036 www.icc-es-pmg.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council PMG LISTING CRITERIA FOR MULTILAYER PIPE AND FITTINGS ASSEMBLY FOR REFRIGERANT APPLICATIONS LC1036 August

More information

Originally Issued: 03/31/2017 Valid Through: 04/30/2018

Originally Issued: 03/31/2017 Valid Through: 04/30/2018 ALLEGHENY STRUCTURAL COMPONENTS, INC. OPEN JOIST 2000 WOOD TRUSSES CSI Sections: 06 11 00 Wood Framing 06 11 13 Engineered Wood Products 06 17 00 Shop Fabricated Structural Wood 06 17 53 Shop-Fabricated

More information

Originally Issued: 04/17/2015 Valid Through: 04/30/2016

Originally Issued: 04/17/2015 Valid Through: 04/30/2016 EVALUATION SUBJECT: Foamsulate 50-NIB Spray-Applied Polyurethane Foam Plastic Insulation REPORT HOLDER: Premium Spray Products 1255 Kennestone Circle, Suite 200 Marietta, Georgia 30066 www.premiumspray.com

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CHEMICAL BROTHERS INTERNATIONAL, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CHEMICAL BROTHERS INTERNATIONAL, LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3458 Reissued 11/2016 This report is subject to renewal 11/2017. DIVISION: 07 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: APPLIED FIREPROOFING REPORT HOLDER: ISOLATEK INTERNATIONAL

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: APPLIED FIREPROOFING REPORT HOLDER: ISOLATEK INTERNATIONAL 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1092 Reissued 12/2015 This report is subject to renewal 12/2016. DIVISION: 07 00 00 THERMAL

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION DIVISION: AIR BARRIERS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION DIVISION: AIR BARRIERS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2717 Reissued 07/2017 This report is subject to renewal 07/2019. DIVISION: 07 00

More information

December 1, 2014 PARTIES INTERESTED IN WATER-RESISTIVE BARRIERS

December 1, 2014 PARTIES INTERESTED IN WATER-RESISTIVE BARRIERS December 1, 2014 TO: PARTIES INTERESTED IN WATER-RESISTIVE BARRIERS SUBJECT: Proposed Revisions to the Acceptance Criteria for Water-resistive Barriers, Subject AC38-1214-R1 (ST/GH) Dear Colleague: You

More information

PMG LISTING CRITERIA FOR PRESS-CONNECTION FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS PREFACE

PMG LISTING CRITERIA FOR PRESS-CONNECTION FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS PREFACE Title???? Page 1 of 1 www.icc-es.org/pmg (800) 42-6587 (562) 699-054 A Subsidiary of the International Code Council PMG LISTING CRITERIA FOR PRESS-CONNECTION FITTINGS FOR POTABLE WATER TUBE AND RADIANT

More information

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES 1.0 INTRODUCTION INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR COMPOSITE STEEL SHEET AND NONCOMBUSTIBLE SHEATHING PANELS EC 012-2016

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CHEMICAL BROTHERS INTERNATIONAL, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CHEMICAL BROTHERS INTERNATIONAL, LLC 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3458 Reissued 11/2016 This report is subject to renewal 11/2017. DIVISION: 07 00 00 THERMAL

More information

DIVISION: THERMAL AND MOISTURE SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION

DIVISION: THERMAL AND MOISTURE SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2668 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 07 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER: 0 ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org Most Widely Accepted and Trusted ESR-4099 Reissued 07/2018 Revised 08/2018 This report is subject to renewal 07/2019.

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2600 Reissued 02/2017 This report is subject to renewal 02/2018. DIVISION: 07 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2668 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 07 00

More information

ACCEPTANCE CRITERIA FOR WATER-RESISTIVE BARRIERS PREFACE

ACCEPTANCE CRITERIA FOR WATER-RESISTIVE BARRIERS PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR WATER-RESISTIVE BARRIERS AC38 Approved June 2004 Effective July 1, 2004 Previously approved July 2000, September 1990 PREFACE

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: RHINO LININGS CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: RHINO LININGS CORPORATION 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2100 Reissued 02/2017 This report is subject to renewal 02/2018. DIVISION: 07 00

More information

AC178. June (Effective July 1, 2003) Previously issued April 2001 PREFACE

AC178. June (Effective July 1, 2003) Previously issued April 2001 PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect INTERIM CRITERIA FOR INSPECTION AND VERIFICATION OF CONCRETE AND AC178 June 2003 (Effective July 1, 2003) Previously issued April 2001 PREFACE Legacy

More information

Code Compliance Research Report CCRR 0232

Code Compliance Research Report CCRR 0232 Code Compliance Research Report CCRR 0232 Issued: 01 06 2016 Revised: 01 03 2018 Renewal Due: 01 06 2019 DIVISION: 06 17 00 WOOD, PLASTICS & COMPOSITES Section: 06 17 33 Wood I - Joists International Beams

More information

PMG LISTING CRITERIA FOR PUSH-FIT FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS LC1009

PMG LISTING CRITERIA FOR PUSH-FIT FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS LC1009 www.icc-es.org/pmg (800) 42-6587 (562) 699-054 A Subsidiary of the International Code Council PMG LISTING CRITERIA FOR PUSH-FIT FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS Approved April

More information

October 1, SUBJECT: Proposed Revisions to the Acceptance Criteria for Walking Decks, Subject AC R1 (WU/CA).

October 1, SUBJECT: Proposed Revisions to the Acceptance Criteria for Walking Decks, Subject AC R1 (WU/CA). October 1, 2012 TO: PARTIES INTERESTED IN WALKING DECKS SUBJECT: Proposed Revisions to the Acceptance Criteria for Walking Decks, Subject AC39-1012-R1 (WU/CA). Dear Colleague: We are seeking your comments

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3470 Reissued 03/2018 This report is subject to renewal 03/2019. DIVISION: 07 00

More information

April 18, 2018 PARTIES INTERESTED IN FIBER REINFORCED PLASTIC (FRP) MODULAR WALL SYSTEMS

April 18, 2018 PARTIES INTERESTED IN FIBER REINFORCED PLASTIC (FRP) MODULAR WALL SYSTEMS April 18, 2018 TO: PARTIES INTERESTED IN FIBER REINFORCED PLASTIC (FRP) MODULAR WALL SYSTEMS SUBJECT: Proposed Revisions to the Acceptance Criteria for Fiber Reinforced Plastic (FRP) Modular Wall Systems,

More information

ESR-2847 Reissued September 1, 2013 This report is subject to renewal September 1, 2015.

ESR-2847 Reissued September 1, 2013 This report is subject to renewal September 1, 2015. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-2847 Reissued September 1, 2013 This report is subject to renewal September 1, 2015. A Subsidiary of the International Code Council

More information

Originally Issued: 11/06/2017 Valid Through: 11/30/2018

Originally Issued: 11/06/2017 Valid Through: 11/30/2018 ACCELLA POLYURETHANE SYSTEMS, LLC. SEALTITE CC+ SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION CSI Section: 07 21 00 Thermal Insulation 1.0 RECOGNITION insulations described in this report have been

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD I JOISTS REPORT HOLDER: STARK TRUSS COMPANY, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD I JOISTS REPORT HOLDER: STARK TRUSS COMPANY, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 2 6587 (562) 699 05 www.icc es.org ESR 2919 Reissued 11/2017 This report is subject to renewal 11/2019. DIVISION: 06 00 00 WOOD,

More information

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR THE TESTING AND ANALYSIS OF STEEL SHEET SHEATHING FOR WOOD AND COLD FORMED STEEL LIGHT

More information

April 1, 2015 PARTIES INTERESTED IN FLEXIBLE FLASHING MATERIALS

April 1, 2015 PARTIES INTERESTED IN FLEXIBLE FLASHING MATERIALS April 1, 2015 TO: PARTIES INTERESTED IN FLEXIBLE FLASHING MATERIALS SUBJECT: Proposed Revisions to the Acceptance Criteria for Flexible Flashing Materials, Subject AC148-0415-R1 (ST/YM) Dear Colleague:

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: NATURAL POLYMERS, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: NATURAL POLYMERS, LLC 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3136 Reissued 06/2017 This report is subject to renewal 06/2018. DIVISION: 07 00

More information

ACCEPTANCE CRITERIA FOR PREFABRICATED WOOD SHEAR PANELS PREFACE

ACCEPTANCE CRITERIA FOR PREFABRICATED WOOD SHEAR PANELS PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR PREFABRICATED WOOD SHEAR PANELS AC130 Approved October 2007 Effective November 1, 2007 Previously approved February 2004,

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC. 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2600 Reissued 02/2017 This report is subject to renewal 02/2018. DIVISION: 07 00 00 THERMAL

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER: 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 2717 Reissued 07/2015 This report is subject to renewal 07/2017. DIVISION: 07 00 00 THERMAL

More information

Originally Issued: 09/07/2016 Revised: 09/28/2018 Valid Through: 09/30/2019

Originally Issued: 09/07/2016 Revised: 09/28/2018 Valid Through: 09/30/2019 130 WELSCO RD. SMACKOVER, AR 71762 (870) 725-3902 www.spiderlath.com REINFORCING FIBERGLASS MESH WITH A MULTI-FUNCTION STRIP SYSTEM CSI Sections: 09 22 36 Lath 1.0 RECOGNITION SpiderLath Reinforcing Fiberglass

More information

ICC-ES Evaluation Report. ESR-3102 Reissued July 1, 2013 This report is subject to renewal August 1, 2015.

ICC-ES Evaluation Report. ESR-3102 Reissued July 1, 2013 This report is subject to renewal August 1, 2015. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-3102 Reissued July 1, 2013 This report is subject to renewal August 1, 2015. A Subsidiary of the International Code Council DIVISION:

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3883 Reissued 08/2017 This report is subject to renewal 04/2018. DIVISION: 07 00

More information

Originally Issued: 03/21/2014 Revised: 04/12/2018 Valid Through: 03/31/2019

Originally Issued: 03/21/2014 Revised: 04/12/2018 Valid Through: 03/31/2019 EVALUATION SUBJECT: NO-BURN PLUS, PLUS THB, PLUS XD, PLUS MIH, ORIGINAL, ORIGINAL MIH, WOOD GARD AND WOOD GARD MIH. REPORT HOLDER: No-Burn, Inc. 1392 High Street Wadsworth, Ohio 44281 (800) 989-8577 www.noburn.com

More information

Project Address: Name of Person Completing Form:

Project Address: Name of Person Completing Form: Statement of Inspections This form is provided as a way to list aspects of the project that require special inspection and testing in accordance with IBC Sections 107.1, 1704, and 1705 and define duties

More information

Joint Evaluation Report ICC-ES (800) (562)

Joint Evaluation Report ICC-ES (800) (562) 0 Joint Evaluation Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 ESR-1336 Reissued 09/2016 This report is subject to renewal 09/2018. DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION:

More information

ICC-ES Evaluation Report Reissued September 1, 2011 This report is subject to renewal in two years.

ICC-ES Evaluation Report Reissued September 1, 2011 This report is subject to renewal in two years. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-1336 Reissued September 1, 2011 This report is subject to renewal in two years. A Subsidiary of the International Code Council

More information

April 2, 2012 PARTIES INTERESTED IN EXPANSION ANCHORS IN MASONRY ELEMENTS

April 2, 2012 PARTIES INTERESTED IN EXPANSION ANCHORS IN MASONRY ELEMENTS April 2, 2012 TO: PARTIES INTERESTED IN EXPANSION ANCHORS IN MASONRY ELEMENTS SUBJECT: Proposed Revisions to the Acceptance Criteria for Expansion Anchors in Masonry Elements, Subject AC01-0412-R1 (JHW/AHG)

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: THERMOSEAL LLC EVALUATION SUBJECT:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: THERMOSEAL LLC EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 4137 Reissued 06/2018 This report is subject to renewal 06/2019. DIVISION: 07 00

More information

Originally Issued: 05/03/2013 Revised: 06/06/2016 Valid Through: 05/31/2017

Originally Issued: 05/03/2013 Revised: 06/06/2016 Valid Through: 05/31/2017 EVALUATION SUBJECT: AA-2 VAPOR SHIELD, M-SHIELD, SILVER SHIELD RADIANT BARRIER, FSK SHIELD, RBI SHIELD AND VR PLUS SHIELD REPORT HOLDER: Fi-Foil Company, Inc. P.O. Box 800 612 Bridgers Ave. West Auburndale,

More information

Originally Issued: 02/11/2011 Revised: 02/23/2018 Valid Through: 02/28/2019

Originally Issued: 02/11/2011 Revised: 02/23/2018 Valid Through: 02/28/2019 MITEK USA, INC. USP HOLDOWN AND TENSION-TIE CONNECTORS CSI Section: 06 05 23 Wood, Plastic and Composite Fastenings 1.0 RECOGNITION MiTek USA, Inc. USP holdown and tension-tie connectors recognized in

More information

Originally Issued: 11/04/2016 Revised: 11/28/2017 Valid Through: 11/30/2018

Originally Issued: 11/04/2016 Revised: 11/28/2017 Valid Through: 11/30/2018 HUBER ENGINEERED WOODS ZIP SYSTEM R-SHEATHING CSI Section: 06 12 00 Structural Panels 06 16 00 Sheathing 1.0 RECOGNITION ZIP System R-Sheathing panels, manufactured by Huber Engineered Woods, LLC, were

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: ICYNENE, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: ICYNENE, INC. 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3500 Reissued 01/2016 This report is subject to renewal 01/2017. DIVISION: 07 00 00 THERMAL

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: SPRAY FOAM POLYMERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: SPRAY FOAM POLYMERS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3225 Reissued 08/2017 This report is subject to renewal 07/2018. DIVISION: 07 00

More information

Deer Ridge Consulting, Inc.

Deer Ridge Consulting, Inc. Deer Ridge Consulting, Inc. Code Compliance Research Report 505 Deer Ridge Lane Ararat, VA 24053 Office: 276-755-9162 Fax: 866-441-1054 www.deer-ridge-consulting.com Subject: NCFI 12-008 Spray Polyurethane

More information

PROPOSED ICC-ES EVALUATION GUIDELINE FOR VOLATILE ORGANIC COMPOUND (VOC) CONTENT AND EMISSIONS OF PAINTS AND COATINGS PUBLIC COMMENT DRAFT

PROPOSED ICC-ES EVALUATION GUIDELINE FOR VOLATILE ORGANIC COMPOUND (VOC) CONTENT AND EMISSIONS OF PAINTS AND COATINGS PUBLIC COMMENT DRAFT PROPOSED ICC-ES EVALUATION GUIDELINE FOR VOLATILE ORGANIC COMPOUND (VOC) CONTENT AND EMISSIONS OF PAINTS AND COATINGS PUBLIC COMMENT DRAFT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 PROPOSED

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 4073 Issued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: THE SPRAY MARKET, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: THE SPRAY MARKET, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 4195 Issued 12/2017 This report is subject to renewal 06/2018. DIVISION: 07 00 00

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP FABRICATED WOOD TRUSSES REPORT HOLDER: BARRETTE STRUCTURAL DISTRIBUTION, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP FABRICATED WOOD TRUSSES REPORT HOLDER: BARRETTE STRUCTURAL DISTRIBUTION, INC. 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 43 6587 (56) 699 0543 www.icc es.org ESR 999 Reissued 0/07 This report is subject to renewal 0/08. DIVISION: 06 00 00 WOOD, PLASTICS AND

More information

IAPMO UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR JOIST HANGERS AND MISCELLANEOUS CONNECTORS

IAPMO UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR JOIST HANGERS AND MISCELLANEOUS CONNECTORS IAPMO UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR JOIST HANGERS AND MISCELLANEOUS CONNECTORS EC 002-2017 (Adopted June 2007, Revised August 2017) 1.0 INTRODUCTION 1.1 Purpose: The purpose of this

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP FABRICATED WOOD TRUSSES REPORT HOLDER: BARRETTE STRUCTURAL DISTRIBUTION, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP FABRICATED WOOD TRUSSES REPORT HOLDER: BARRETTE STRUCTURAL DISTRIBUTION, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1035 Reissued 11/2017 This report is subject to renewal 04/2018. DIVISION: 06 00

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PLASTICS SECTION: PLASTIC DECKING REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PLASTICS SECTION: PLASTIC DECKING REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2497 Reissued 01/2018 This report is subject to renewal 01/2019. DIVISION: 06 00

More information

June 25, 2012 PARTIES INTERESTED IN SPRAY-APPLIED FOAM PLASTIC INSULATION

June 25, 2012 PARTIES INTERESTED IN SPRAY-APPLIED FOAM PLASTIC INSULATION June 25, 2012 TO: PARTIES INTERESTED IN SPRAY-APPLIED FOAM PLASTIC INSULATION SUBJECT: Revisions to the Acceptance Criteria for Spray-applied Foam Plastic Insulation, Subject AC377-0612-R1 (SF/MB) Dear

More information

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES 1.0 INTRODUCTION INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR COMPOSITE STEEL SHEET AND NONCOMBUSTIBLE SHEATHING PANELS EC 012-2013

More information

Originally Issued: 08/03/2017 Revised: 02/01/2019 Valid Through: 08/31/2019

Originally Issued: 08/03/2017 Revised: 02/01/2019 Valid Through: 08/31/2019 ACCELLA POLYURETHANE SYSTEMS, LLC. 100 Enterprise Drive Cartersville, GA 30120 Phone: (770) 607-0755 www.accellapolyurethane.com BAYSEAL CC X AND BAYSEAL CC XP SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION

More information

June 19, 2012 PARTIES INTERESTED IN SCREW FOUNDATION SYSTEMS

June 19, 2012 PARTIES INTERESTED IN SCREW FOUNDATION SYSTEMS June 19, 2012 TO: PARTIES INTERESTED IN SCREW FOUNDATION SYSTEMS SUBJECT: Acceptance Criteria for Screw Foundation Systems (SFSs), Subject AC443-0612-R1 (DZ/KS)] Dear Colleague: We are enclosing the new

More information

Originally Issued: 12/09/2014 Revised: 10/01/2018 Valid Through: 11/30/ Design:

Originally Issued: 12/09/2014 Revised: 10/01/2018 Valid Through: 11/30/ Design: ROYAL BUILDING PRODUCTS 135 Bear Creek Road Marion, Virginia 24354 (276)783-8161 www.royalbuildingproducts.com ZURI CELLULAR PVC DECKING CSI Section: 06 53 00 Plastic Decking 1.0 RECOGNITION Zuri Cellular

More information

ATI Evaluation Service A Division of Architectural Testing Certification Services

ATI Evaluation Service A Division of Architectural Testing Certification Services ATI Evaluation Service A Division of Architectural Testing Certification Services Subject to Renewal: 04/08/2014 Issued: 04/08/2013 Visit www.ati-es.com for current status Revision: 11/11/2013 Page 1 of

More information