GIB Quiet Clip GIB CBI March Features and Benefits
|
|
- Lorin Small
- 6 years ago
- Views:
Transcription
1 CBI March 2002 GIB Quiet Clip Features and Benefits No special flooring systems required Easy fit Installation Significantly improves low frequency sound transmission Significantly improves low frequency impact insulation Superior, cost effective noise control for floor/ceiling systems Fully tested for use with GIB Noise Control Systems A reduction in low frequency sound such as bass stereo and footfall noise is clearly noticeable when the is installed correctly. NZ Patent Application Number
2 TECHNICAL INFORMATION PERFORMANCE COMPARISONS STC and IIC ratings The ability of a floor/ceiling to reduce noise is expressed as the Sound Transmission Class (STC) for airborne noise, and the Impact Insulation Class (IIC) for impact noise. Examples of airborne noise are people talking, the TV or stereo being played. Examples of impact noise are people walking, scratching chairs or items being dropped on a floor. STC The ISO standard laboratory test for airborne noise exposes a specimen to noises over a frequency range between 100 and 3150 Hz. On the basis of the noise reduction achieved over this range, a single figure STC rating is calculated. This single figure STC rating does not provide any information about the system s performance when exposed to any particular frequency. The laboratory test also does not consider the performance in the frequency range below 100 Hz, where base thumping noises are most annoying. The The performance of the may not be immediately evident from the single figure STC rating. However, low frequency noises in the Hz are dampened and will be experienced by occupants as much softer and more acceptable. Figure 1 compares the STC performance of the standard GIB Rondo Direct Fixed Clip with the. Airborne Sound Reduction Standard GIB Clip Frequency Hz Figure 1. Low frequency STC performance enhancement achieved by using the Notes for guidance The higher the bar, the better the performance a 3dB difference in any frequency is noticed by most people a 5dB difference is clearly noticeable IIC The ISO standard laboratory test for impact noise uses a tapping machine exposing a specimen to impact frequencies ranging from 100 to 3150 Hz. On the basis of the noise reduction achieved over this range, a single figure IIC rating is calculated. This single figure IIC rating does not provide any information about the system s performance against any particular frequency. The laboratory test also does not consider the performance in the frequency range below 100 Hz where footfall impact noise (walking) is most annoying. The Again the performance of the is not immediately apparent from the single figure IIC rating. However, Figure 2 shows that low frequency impact noises are dampened significantly. Occupants will experience the loudness of footfall noise in the frequency range from Hz as much softer and more acceptable. Impact Sound Received Standard GIB Clip Frequency Hz Figure 2. Low frequency IIC performance enhancement achieved by using the Notes for guidance The lower the bar, the better the performance a 3dB difference in any frequency is noticed by most people a 5dB difference is clearly noticeable
3 Residential Noise Control Floor/Ceiling System Timber Joists - GIB Quiet Zone Specification Loadbearing STC RW IIC Fire Resistance Lining Number Capability Rating Rating N/A LB *50 *50 *64 (See IIC below) N/A 1 x 13mm GIB Standard Floor Framing Floor joists shall comply with NZ 3604, be spaced at 600mm centres and have a depth of 200mm minimum alternatively use either Origin I-beams or CHH Hybeam HJ series joists designed for strength and serviceability, no less than 240mm deep and spaced at no more than 600mm. Nogs fixed on the flat to receive edges of flooring material shall be 100mm x 50mm minimum. Consult the beam manufacturer regarding construction of the solid blocking contained in the floor/ceiling to wall junctions. Flooring Minimum flooring shall be nominal 20mm particle board or minimum 17mm thick structural plywood fixed to the manufacturers instructions. and Battens The shall be fastened to the joists at maximum 1200mm centres (and no less than 900mm centres) to support the. The battens shall be spaced at 600mm centres maximum. It is important that these specific brands of batten and clips are used when specifying and installing GIB Noise Control Systems. Site tests have shown that other brands can have STC performances up to 10 STC points lower. Installing the Use 3 x 32mm x 8g GIB Grabber wafer head screws. Insert the first screw into the middle rubber grommet, tighten enough to hold the in place, adjust the clip to the correct height, insert the remaining two screws and tighten. the grommet is crushed. The screws should be tightened enough to allow the flexibility to remain in the connection between the grommet and the joists. Sound Control Infill Ceiling overlaid with R1.8 (75mm) pink Fibreglass batts. Alternatively, Autex R1.8 Greenstuf 95mm battens. Sheet are touch fitted. Ceiling Lining 1 layer of 13mm GIB Standard fixed at right angles to the steel battens. All sheet end butt joints shall occur on the battens. Sheet are touch fitted. Fastening the Lining Fasteners 25mm x 6g GIB Grabber Scavenger Head Drywall Self Tapping Screws Fasteners centres 200mm centres along each batten and along sheet end butt joints. Place fasteners no closer than 12mm to the sheet edges. Acoustic Sealant A bead of GIB Soundseal acoustic sealant is required around the ceiling perimeter. the grommet is crushed 1 x 13mm GIB Standard 1 x 13mm GIB Standard Light Fittings Use surface mounted light fittings. The penetration for the electric cable shall be packed with an acoustic sealant. Wall/Ceiling Junctions The internal angle between the ceiling and the walls are protected by GIB Cove adhered with GIB Cove adhesive or boxed corners (square stopped) filled and taped in accordance with the publication entitled GIB Living Solutions Site Guide. Jointing All fasteners heads stopped and all sheet joints tape reinforced and stopped in accordance with the publication entitled GIB Living Solutions Site Guide. Impact Insulation Class (IIC) A performance of IIC 39 is achieved by a bare floor A performance of IIC 40 is achieved with a 2mm thick cushion backed vinyl on particle board or structural plywood. A performance of IIC 64 is achieved with a 48oz hard twisted wool hessian backed carpet over a rubberwaffle underlay. * Note Estimated STC and IIC Performance and
4 Residential Noise Control Floor/Ceiling System Timber Joists - GIB Quiet Zone Upgrade Specification Loadbearing STC RW IIC Fire Resistance Lining Number Capability Rating Rating GBDFA 30c LB (See IIC below) 30/30/30 2 x 13mm GIB Standard Floor Framing Floor joists shall comply with NZ 3604, be spaced at 600mm centres and have a depth of 200mm minimum. Alternative Floor Framing Use either Origin I-beams or CHH Hybeam HJ series joists designed for strength and serviceability, no less than 240mm deep and spaced at no more than 600mm. Nogs fixed on the flat to receive edges of flooring material shall be 100mm x 50mm minimum. Consult the beam manufacturer regarding construction of the solid blocking contained in the floor/ceiling to wall junctions. Flooring Minimum flooring shall be nominal 20mm particle board or minimum 17mm thick structural plywood fixed to the manufacturers instructions. Note: To ensure the FRR is achieved, nogs are required behind tongue or adhesive fixed flooring sheet joints and Battens The shall be fastened to the joists at maximum 1200mm centres (and no less than 900mm centres) to support the. The battens shall be spaced at 600mm centres maximum. It is important that these specific brands of batten and clips are used when specifying and installing GIB Noise Control Systems. Site tests have shown that other brands can have STC performances up to 10 STC points lower. Installing the Use 3 x 32mm x 8g GIB Grabber wafer head screws. Insert the first screw into the middle rubber grommet, tighten enough to hold the in place, adjust the clip to the correct height, insert the remaining two screws and tighten. the grommet is crushed. The screws should be tightened enough to allow the flexibility to remain in the connection between the grommet and the joists. Sound Control Infill Ceiling overlaid with R1.8 (75mm) pink Fibreglass batts. Alternatively, Autex R1.8 Greenstuf 95mm battens. Sheet are touch fitted. Ceiling Lining 2 layers of 13mm GIB Standard fixed at right angles to the battens. Offset the joints of the outer layer by 600mm from those of the inner layer. All sheet end butt joints shall occur on the battens and are offset between the first and second layers. Sheets are touch fitted. Fastening the Lining Fasteners Inner layer - 25mm x 6g GIB Grabber Scavenger Head Drywall Self Tapping Screws Outer layer - 41mm x 6g screws as above Fasteners centres 200mm centres along each batten and along sheet end butt joints. Place fasteners no closer than 12mm to the sheet edges. the grommet is crushed 2 x 13mm GIB Standard and Joist 2 x 13mm GIB Standard Acoustic Sealant A bead of GIB Soundseal acoustic sealant is required around the ceiling perimeter. The outer lining is then bedded onto the bead. Light Fittings Use surface mounted light fittings. The penetration for the electric cable shall be packed with a fire rated sealant. Wall/Ceiling Junctions The internal angle between the ceiling and the walls are protected by GIB Cove adhered with GIB Cove adhesive or boxed corners (square stopped) filled and taped in accordance with the publication entitled GIB Living Solutions Site Guide. Jointing Inner unstopped Outer layer - all sheet fasteners heads stopped and all sheet joints tape reinforced and stopped in accordance with the publication entitled GIB Living Solutions Site Guide. Impact Insulation Class (IIC) A performance of IIC 46 is achieved by a bare floor A performance of IIC 47 is achieved with a 2mm thick cushion backed vinyl on particle board or structural plywood. A performance of IIC 71 is achieved with a 48oz hard twisted wool hessian backed carpet over a rubberwaffle underlay.
5 TECHNICAL INFORMATION PERFORMANCE COMPARISONS Inter-tenancy Noise Control Floor/Ceiling System Timber Joists Specification Loadbearing STC RW IIC Fire Resistance Lining Number Capability Rating Rating GBDFA 60c GBCJA 60a LB (See IIC below) Floor Framing Floor joists shall comply with NZ 3604, be spaced at 600mm centres and have a depth of 200mm minimum. Alternative Floor Framing Use either Origin I-beams or CHH Hybeam HJ series joists designed for strength and serviceability, no less than 240mm deep and spaced at no more than 600mm. Nogs fixed on the flat to receive edges of flooring material shall be 100mm x 50mm minimum. Consult the beam manufacturer regarding construction of the solid blocking contained in the floor/ceiling to wall junctions. Flooring Minimum flooring shall be nominal 20mm particle board or minimum 17mm thick structural plywood fixed to the manufacturers instructions. Note: To ensure the FRR is achieved, nogs are required behind tongue or adhesive fixed flooring sheet joints and Battens The shall be fastened to the joists at maximum 1200mm centres (and no less than 900mm centres) to support the. The battens shall be spaced at 600mm centres maximum. It is important that these specific brands of batten and clips are used when specifying and installing GIB Noise Control Systems. Site tests have shown that other brands can have STC performances up to 10 STC points lower. Installing the Use 3 x 32mm x 8g GIB Grabber wafer head screws. Insert the first screw into the middle rubber grommet, tighten enough to hold the in place, adjust the clip to the correct height, insert the remaining two screws and tighten. the grommet is crushed. The screws should be tightened enough to allow the flexibility to remain in the connection between the grommet and the joists. Sound Control Infill Ceiling overlaid with R1.8 (75mm) pink Fibreglass batts. Alternatively, Autex R1.8 Greenstuf 95mm battens. Sheet are touch fitted. Ceiling Lining 2 layers of 13mm GIB Noiseline fixed at right angles to the battens. Offset the joints of the outer layer by 600mm from those of the inner layer. All sheet end butt joints shall occur on the battens and are offset between the first and second layers. Sheets are touch fitted. Fastening the Lining Fasteners Inner layer - 25mm x 6g GIB Grabber Scavenger Head Drywall Self Tapping Screws Outer layer - 41mm x 6g screws as above Fasteners centres 200mm centres along each batten and along sheet end butt joints. Place fasteners no closer than 12mm to the sheet edges. 60/60/60 2 x 13mm GIB Noiseline the grommet is crushed 2 x 13mm GIB Noiseline and Joist 2 x 13mm GIB Noiseline Acoustic Sealant A bead of GIB Soundseal acoustic sealant is required around the ceiling perimeter. The outer lining is then bedded onto the bead. Light Fittings Use surface mounted light fittings. The penetration for the electric cable shall be packed with a fire rated sealant. Wall/Ceiling Junctions The internal angle between the ceiling and the walls are protected by GIB Cove adhered with GIB Cove adhesive or boxed corners (square stopped) filled and taped in accordance with the publication entitled GIB Living Solutions Site Guide. Jointing Inner unstopped Outer layer - all sheet fasteners heads stopped and all sheet joints tape reinforced and stopped in accordance with the publication entitled GIB Living Solutions Site Guide. Impact Insulation Class (IIC) A performance of IIC 47 is achieved by a bare floor A performance of IIC 50 is achieved with a 2mm thick cushion backed vinyl on particle board or structural plywood. A performance of IIC 72 is achieved with a 48oz hard twisted wool hessian backed carpet over a rubberwaffle underlay.
6 Installation Guide Lines and GIB Rondo Battens The shall be fastened to the joist at maximum 1200mm centres (and no less than 900mm centres) to support the GIB Rondo batten. The battens shall be spaced at 600mm centres maximum for linings 13mm thick, and at 450mm centres maximum for linings 10mm thick. the grommet is crushed. and It is important that these specific brands of batten and clips are used when specifying and installing GIB Noise Control Systems. Site tests have shown that other brands of metal clips and battens can perform up to 10 STC points below the tested brands above. Installing the Using 3 x 32mm x 8g GIB Grabber wafer head screws. Insert the first screw into the middle rubber grommet, tighten enough to hold the in place, adjust to the clip correct height and insert the remaining two screws and tighten up. GIB Noiseline Joist the grommet is crushed. The screws should be tightened enough to allow the flexibility to remain in the connection between the grommet and the joists. Substitution GIB Systems for Sound Control are not generic. GIB Noiseline It is important that only GIB branded components are used when specifying and installing GIB Sound Control Systems. Substitution is not in accordance with GIB Systems recommendations and must be at the risk of the owner, specifier or builder. If you wish to substitute then you must first ensure that the alternative proprietary brand supplier can provide documentary evidence of NZBC compliance, including structural, noise control IIC and STC durability and hazardous material. For further systems detail please refer to Winstone Wallboards Ltd. Please phone the GIB information Helpline
Intertenancy Barrier Systems for Terrace Homes
Intertenancy Barrier Systems for Terrace Homes Specification & Installation Manual CBI5113 NATIONAL SUPPORT VISIT: POST: Winstone Wallboards Limited 37 Felix Street, Penrose, Auckland 1061, New Zealand
More informationNoise Control Systems
Noise Control Systems Specification and installation manual CBI5113 SEPTEMBER 2017 NATIONAL SUPPORT VISIT: POST: Winstone Wallboards Limited 37 Felix Street, Penrose, Auckland 1061, New Zealand PO Box
More informationINTERTENANCY SYSTEMS 2018
KOROK INTERTENANCY SYSTEMS 2018 FOR TERRACED HOUSING AND APARTMENTS CBI 5113 FEB 2018 KOROK KOROK INTERTENANCY SYSTEMS 2018 FOR TERRACED HOUSING AND APARTMENTS SECURE, QUIET, FLEXIBLE. KOROK Intertenancy
More informationVolume II FWPRDC PN Maximising impact sound resistance of timber framed floor/ceiling systems. Page 183
Volume II FWPRDC PN04.05 Maximising impact sound resistance of timber framed floor/ceiling systems Page 183 Page 184 Table of Contents. 1 PROJECT OVERVIEW...13 1.1 INTRODUCTION...13 1.2 OVERVIEW OF THE
More informationSECTION D Masonry Wall Systems. Contents. Introduction. Design Considerations. Installation. Components. System Specifications.
SECTION D Wall Systems. Contents. SUBJECT Introduction Design Considerations Installation Components PAGE D2 D2 D4 D5 System Specifications Stud One Side Stud Both Sides Stud and Furring Channel Resilient
More informationGIB FIRE RATED SYSTEMS. Product. Scope. Building Regulations. Appraisal No. 289 [2018] Logo. Appraisal No. 289 (2018) BRANZ Appraisals
GIB FIRE RATED SYSTEMS This Appraisal replaces 289 (2012) dated 8 November 2012 s Technical Assessments of products for building and construction. Logo Winstone Wallboards Ltd P.O Box 12 256 Penrose Auckland
More information5.0 GIB PERFORMANCE SYSTEMS INSTALLATION
5.0 GIB PERFORMANCE SYSTEMS INSTALLATION The GIB Performance Systems section covers installation of GIB EzyBrace and GIB Aqualine Wet Area Systems. For other systems including 5.1 GIB BRACING SYSTEMS This
More informationGIB FIRE RATED SYSTEMS. Product. Scope. Building Regulations. Fire Rated Systems Specification and Installation Manual GIB. Appraisal No.
CBI 5113 OCT 2012 GIB Fire Rated Systems Specification and Installation Manual GIB FIRE RATED SYSTEMS This Appraisal replaces BRANZ Appraisal No. 289 (2006) dated 22 November 2006. Amended 02 June 2016.
More informationMaximising impact sound resistance of timber framed floor/ ceiling systems Volume 3
MARKET KNOWLEDGE & DEVELOPMENT Project number: PN4.5 Maximising impact sound resistance of timber framed floor/ ceiling systems Volume 3 This report can also be viewed on the FWPRDC website www.fwprdc.org.au
More informationSECTION E Ceiling Systems. Contents. Introduction. Design Considerations. Installation. Components. System Specifications. Floor/Ceiling Systems
SECTION E Ceiling Systems. Contents. SUBJECT Introduction Design Considerations Installation Components PAGE E2 E2 E4 E4 System Specifications Floor/Ceiling Systems Roof/Ceiling Systems E6 E12 Floor or
More informationAcoustical Characteristics of Carpet
CRI TECHNICAL BULLETIN Acoustical Characteristics of Carpet Carpet is an outstanding sound absorptive material. When properly selected, carpet absorbs airborne noise as efficiently as many specialized
More informationReverberation Control Systems
Reverberation Control Systems Design and Installation Manual for GIB Quietline and GIB-Tone Quiet tiles CBI 5311 NATIONAL SUPPORT VISIT: POST: Winstone Wallboards Limited 37 Felix Street, Penrose, Auckland
More informationNoise Control Systems Supplement
Noise Control Systems Supplement Issue Date September 2017 GIB Noise Control design notes SUPPLEMENT ISSUE DATE Polyester Sound Control Infill Sept 2017 Enviromental Noise March 2006 SEPTEMBER 2017 GIB
More informationPROMATECT hour walls
PROMATECT 100 2 hour walls 08 9445 8300 info@progressivematerials.com.au progressivematerials.com.au Partitions General Information Introduction Partitions and external walls are used to separate buildings,
More informationLOXO CLADDING SOUND INSULATION PERFORMANCE. Opinion on Acoustic Performance of. Loxo Cladding Systems Utilising Aerated Concrete.
LOXO CLADDING SOUND INSULATION PERFORMANCE Opinion on Acoustic Performance of Loxo Cladding Systems Utilising Aerated Concrete Rp001 2012195C 08 May 2012 Level 369 Cambridge Terrace PO Box 4071 Christchurch
More informationPROMAtect H 4 hour walls. progressivematerials.com.au
PROMAtect H 4 hour walls 08 9445 8300 info@progressivematerials.com.au progressivematerials.com.au Partitions General Information Introduction Partitions and external walls are used to separate buildings,
More informationCompliance Documents Training Series G6 Airborne & Impact Sound 2 LBP skills maintenance points Building Networks Ltd 2014 G6 Airborne and Impact Sound - 1 - Published: Version 1; October, 2009 2014 Building
More informationwet area systems Product BRANZ APPRAISAL No. 427 (2007) Scope Building Regulations
Product Appraisal No.427 [2007] 1.1 GIB Aqualine Wet Area Systems are for the interior lining of timber and steel frame walls and ceilings in wet areas such as bathrooms, laundries, kitchens and toilets
More informationSECTION B Steel Frame Wall Systems. Contents. Steel Stud Selection Tables. Introduction. Design Considerations. Installation.
SECTION B Steel Frame Wall Systems. Contents. SUBJECT Steel Stud Selection Tables Introduction Design Considerations Installation Components PAGE B2 B4 B4 B6 B7 System Specifications Single Stud Staggered
More informationGIB EZYBRACE SYSTEMS 2011
Product Appraisal No.294 [2011] 1.1 GIB EzyBrace Systems 2011 are a range of wall and ceiling bracing systems based on the use of GIB Braceline, GIB Standard and other GIB plasterboards. GIB EzyBrace Systems
More informationSingle frame acoustic separating wall system
GypWall QUIET SF GypWall QUIET SF Single frame acoustic separating wall system GypWall QUIET SF metal stud partition is a lightweight, non-loadbearing, single frame wall system. Subject to Local Authority
More informationPROMATECT 100 Solid Partitions
PROMATECT 100 Solid Partitions 08 9445 8300 info@progressivematerials.com.au progressivematerials.com.au Partitions General Information Introduction Partitions and external walls are used to separate buildings,
More informationExperimental setup. Each design was constructed and tested
Abstract Introduction Most residential buildings can be classified as either concrete-based or lightweight timber-based constructions. The lightweight systems have become popular because timber is a renewable
More informationJune Non - Residential New Build Partition walls
June 2010 Non - Residential New Build 4.6.3 Partition walls Non-residential new build 4.0 Non-residential New Build Partition Walls Contents Introduction find online page Solution optimiser and pathfinder
More informationStatus: Rev: Comments Date: Author: Reviewer:
ENGINEERED WOOD FLOORING ON SOUNDGUARD EXTREME UNDERLAY IIC OPINION Rp 005 2016596A 4 August 2016 84 Symonds Street PO Box 5811 Wellesley Street Auckland 1141 New Zealand T: +64 9 379 7822 F: +64 9 309
More informationJune Non - Residential Refurbishment Separating floors
June 2010 Non - Residential Refurbishment 5.6.2 Separating floors Non-residential refurbishment 5.0 Non-residential Refurbishment Separating Floors Contents Introduction find online page Solution optimiser
More information2.0 GIB PRODUCT RANGE
CBI 5113 AUGUST 2016 2.0 GIB PRODUCT RANGE 2.1 GIB SYSTEMS LITERATURE Because of the volume of information it is not feasible to include all the GIB systems publications in the GIB Site Guide. If you are
More informationJune Residential Refurbishment Separating floors
June 2010 Residential Refurbishment 3.6.2 Separating floors Residential refurbishment 3.0 Residential Refurbishment Separating Floors Contents Introduction find online page Solution optimiser and pathfinder
More informationContents. Timber framing to be installed in accordance with AS:1684 Metal framing to be installed in accordance with BCA Volume: 2
Contents BCA Codes 3 General 4 Fire Performances Thermal and Acoustic Insulation Wall Installation 4 Timber Frame Separation Walls 5 Steel Frame Separation Walls 6 External Fire Rated Walls 7 Floor Installation
More informationThis page was. intentionally. left blank
CONSTRUCTION Measurement of Airborne Sound Insulation of 8 Wall Assemblies Measurement of Airborne and Impact Sound Insulation of 29 Floor Assemblies Nordic Engineered Wood Report No. A1-006070.10 July
More informationIntertek Testing Services
Acoustical 3933 U.S. Rt. Cortland, NY 13045 Phone: 607-753-6711 Fax: 607-756-9891 Order No. J99031102-003 December 10, 1999 REPORT NO. J99031102-003 SOUND TRANSMISSION LOSS TEST AND CLASSIFICATION OF A
More informationFIRE RATING MATERIAL FIXING NOTES
FIRE RATING MATERIAL FIXING NOTES FIRE RATING MATERIAL FIXING NOTES... 1 External Wall Systems... 2 Non load bearing steel stud walls... 3 LOAD-BEARING STEEL STUD WALLS... 3 NON LOAD-BEARING TIMBER STUD
More informationSignatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.
ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor- Ceiling Assemblies Using
More informationH R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to URBAN SURFACES. Series/Model: Urban Surfaces Soundtec
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to URBAN SURFACES Series/Model: Urban Surfaces Soundtec Specimen Type: 152 mm Concrete Slab with Drop Ceiling Overall Size: 3048 mm
More informationPresented By: Jim O Neill. Acoustics
Presented By: Jim O Neill Acoustics Topics STC and IIC 101 Sound in floors Sound in walls Noise In Multifamily Measurements of Noise Two ASTM Standards STC Sound Transmission Classification Measurement
More information1. The subfloor must be structurally sound and able to withstand live and dead loads with a deflection limitation of L/360.
HARDWOOD FLOOR Read First These suggestions represent generally accepted procedures for successful installation of Maxxon Products. These instructions may be followed, modified or rejected by the owner,
More informationSubPrimo. subprimo. Acoustic insulation for timber & laminate flooring. Uniclass L5395:N372 EPIC E485:Y45. CI/SfB (43) T (P2)
Acoustic insulation for timber & laminate flooring Uniclass L5395:N372 CI/SfB EPIC E485:Y45 (43) T (P2) subprimo Introduction Introduction Sound Reduction Systems Ltd. (SRS) manufacture acoustic insulation
More informationSOUND INSULATION ASSESSMENT RANELAGH MULTI-DENOMINATIONAL SCHOOL, DUBLIN October 2014
SOUND INSULATION ASSESSMENT RANELAGH MULTI-DENOMINATIONAL SCHOOL, DUBLIN 6 22 October 2014 Project: Sound Insulation Assessment Ranelagh Multi-Denominational School, Dublin 6 7 Osborne Promenade Warrenpoint
More informationMETRA INTER- TENANCY WALL SYSTEM. Product. Scope. Appraisal No. 985 [2018] Appraisal No. 985 (2018) BRANZ Appraisals
METRA INTER- TENANCY WALL BRANZ Appraisals Technical Assessments of products for building and construction. Metra Panel Systems Limited P O Box 22 Huntly 3740 Tel: 07 828 2077 Fax: 07 828 9673 Freephone:
More informationAcoustic. . Absorbs sound reduces noise transmission between rooms for a quieter more relaxing home
Acoustic Application Pink Batts Silencer insulation is a lightweight flexible glass wool insulation product designed to: Provide acoustic insulation in internal walls and midfloors Fit easily into standard
More informationOpinion on Acoustic Performance of. Rockcote Systems Utilising Integra Aerated Concrete. 08 December 2010
Opinion on Acoustic Performance of Rockcote Systems Utilising Integra Aerated Concrete 08 December 2010 84 Symonds Street PO Box 5811 Wellesley Street Auckland 1141 New Zealand T: +64 9 379 7822 F: +64
More informationLISTING INFORMATION OF International Beams - IB Series Joists SPEC ID: 27316
LISTING INFORMATION OF International Beams - IB Series Joists SPEC ID: 27316 International Beams Inc. 2010 Boul. St-Elzear Quest Laval, QC H7L 3N4 CANADA This report is for the exclusive use of Intertek
More informationSignatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.
ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using
More informationPLYWOOD FLOATING FLOOR
PLYWOOD FLOATING FLOOR Read First These suggestions represent generally accepted procedures for successful installation of Enka Building Products. These instructions may be followed, modified, or rejected
More informationSOUND INSULATION TESTING IN DWELLINGS
SOUND INSULATION TESTING IN DWELLINGS Chris Dilworth, AWN Consulting This Presentation Discusses the standards by which we judge sound insulation performance. Presents the results of sound insulation tests
More informationAcoustic Testing of CLT and Glulam Floor Assemblies Nordic Engineered Wood Report No. A August 2016 CONSTRUCTION
CONSTRUCTION Acoustic Testing of CLT and Glulam Floor Assemblies Nordic Engineered Wood Report No. A1-008253.1 19 August 2016 The results in this report only apply to the specimen that was tested Page
More informationMetal Web Floor System
Metal Web Floor System Contents Contents Introduction and benefits 3 easi-joist definitions 4 easi-joist webs 5-6 Mechanical services 7 Loading and design 8 Floor stiffness 9 Internal non-loadbearing wall
More informationRESILIENT SOUND ISOLATION CLIPS
RESILIENT SOUND ISOLATION CLIPS For Wall & Floor Ceiling Assemblies RSIC-1 Resilient Sound Isolation Clip Isolation Clip RSIC-1 Isolation Clip Soundproofing Products SonexTM Ceiling & Wall Panels Sound
More information84 Symonds Street PO Box 5811 Wellesley Street Auckland 1141 New Zealand T: F:
84 Symonds Street PO Box 5811 Wellesley Street Auckland 1141 New Zealand T: +64 9 379 7822 F: +64 9 309 3540 www.marshallday.com DESIGN GUIDE Floors in buildings are often required to achieve certain levels
More informationKINETICS NOISE CONTROL TEST REPORT #AT001052
KINETICS NOISE CONTROL TEST REPORT #AT001052 KINETICS NOISE CONTROL PRODUCTS: o ISOMAX CLIPS ACOUSTICAL RATINGS: o STC 66 o IIC 44 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA
More informationGenieClip. Sound Isolation Clips. It s not magic, it s engineering. Impact and Airborne Sound Control
It s not magic, it s engineering. Impact and Airborne Sound Control GenieClip Sound Isolation Clips Patents: US 7895803, US 9121469, CA 2552516, AU 2007276677, CN 1011919, EPO Patent Pending GenieClip
More informationCreating perfect living spaces. Shaping spaces for living, with internal lining solutions that enhance lifestyles. Creating perfect living spaces
O7 Shaping spaces for living, with internal lining solutions that enhance lifestyles 171 Discover how we are working within the residential industry to facilitate differentiation, through new, innovative,
More informationFIRE PROTECTION. GTEC Shaftwall systems 244 GTEC Shaftwall Stairwell systems 248 GTEC Horizontal Shaftwall systems 249 GTEC Encasement systems 250
FIRE PROTECTION GTEC Shaftwall range uses a specially designed system to protect voids and shafts in buildings. It resists pressure changes and enables installation from one side of the shaft only. GTEC
More informationPlease Note: PhoneStar was previously branded as Phonewell
Soundproofing Floors Timber Joist or Concrete Floors Installation Instructions Acoustic Insulation Please Note: was previously branded as Phonewell There are two options to achieve noise reduction through
More informationSound Control Solutions in Floor/Ceiling Assemblies
Sound Control Solutions in Floor/Ceiling Assemblies Controlling sound becomes more important every day. At SAMfloors, it is our mission to provide elegant, functional sound control solutions to meet the
More informationrobustdetails E-FC-7 Separating Floor Concrete Separating Floors Concrete E-FC-7
DO Butt floor blocks tightly together Cover floor blocks with min 50mm concrete topping Ensure that concrete does not enter the cavity and bridge the two leaves of supporting wall blockwork - it is acceptable
More informationSilencer Rubber Underlayment
Silencer Rubber Underlayment Specifications Name: Silencer Rubber Color: Beige & Silver Type: Sound + Vapor Barrier Construction: High Density Rubber & foil barrier film Coverage: 100sqft Thickness: 2mm
More informationInternal walls. Creating perfect living spaces. Technical Advice Centre Tel:
Internal walls 174 Technical Advice Centre Tel: 0844 800 1991 Legislation and guidance - National Building Regulations Approved Document E Approved Document E (ADE) gives guidance on how to provide reasonable
More informationSelecting floors and ceilings
floors and ceilings email: bgtechnical.enquiries@bpb.com www.british-gypsum.com/health 89 floors and ceilings Introduction 9 Solutions - key systems 9 Solutions for concrete floors 9 - Dense slab 9 This
More informationPREDICTING SOUND INSULATION PERFORMANCE
Auckland Christchurch Kuala Lumpur Melbourne Sydney Wellington www.marshallday.com PREDICTING SOUND INSULATION PERFORMANCE USING SOUND INSULATION SOFTWARE TO PREDICT NON-ACHIEVEMENT OF PERFORMANCE STANDARDS
More informationBuilding a Quieter Home
Building a Quieter Home Your guide to building a peaceful and quiet home Design guidelines Renovation Solutions Creating a Home Theatre Room 2 PROTECTING YOUR PEACE & PRIVACY Our lifestyles and living
More informationGypWall TM ROBUST 4.4. GypWall ROBUST. Durable impact resistant partition system. Key facts. Sector Guide
GypWall TM ROBUST GypWall ROBUST is a high impact resistant partition system for use where a more durable structure is required. The system provides a lightweight, cost-effective, non-loadbearing partition
More informationSpecialists in Acoustic Flooring and House to Flat Conversions
Sound Solution Consultants Ltd Po Box 755 Capel St Mary Ipswich Suffolk IP9 2WF Tel No: 0845 5212096 Fax No: 0845 5212097 Email: mpconsultservice@aol.com Specialists in Acoustic Flooring and House to Flat
More informationC R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Forest rx
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: Forest rx Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File
More informationC06. S05. P02 P12 GypFloor silent
! This section includes updated information, added since it was first published in December 05. Last updated 6//06 C06. S05. P0 P GypFloor silent Including C06. S0. P0 P08 Floors and ceilings introduction
More informationC06. S05. P02 P12 GypFloor silent
! This section includes updated information, added since it was first published in December 05. Last updated 30/06/06 C06. S05. P0 P GypFloor silent Including C06. S0. P0 P08 Floors and ceilings introduction
More informationApril Section 4.3. Separating Floors
April 2012 Section Separating Floors Separating Floors Separating floors Separating floor design Mineral wool products offer substantial advantages when used as both sound absorbent and resilient layers
More informationrondo acoustic wall & ceiling systems manual
rondo acoustic wall & ceiling systems manual SEPTEMBER 2015 introduction This manual provides information on the performance of the Rondo range of acoustic products when incorporated in common installation
More informationH R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to AMORIM CORK COMPOSITES
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to AMORIM CORK COMPOSITES Series/Model: AcoustiCORK ECOx2 Sound Reduction Underlayment for LVT Plank Flooring Specimen Type: 152 mm
More informationInstruction and Safety Manual Resilient Sound Isolation Clips (SIC Clips)
SOUND ISOLATION CLIPS Installation Manual Instruction and Safety Manual Resilient Sound Isolation Clips (SIC Clips) SOUND ISOLATION CLIP SPECIFICATIONS Width...1.00 inch Height...1.06 inch Length...3.86
More informationSECTION GYPSUM BOARD SYSTEM
PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 09 29 00 GYPSUM BOARD SYSTEM A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 specification sections,
More informationFlanking Transmission at Joints in Multi-Family Dwellings. Phase 1: Effects of Fire Stops at Floor/Wall Intersections
Flanking Transmission at Joints in Multi-Family Dwellings. Phase 1: Effects of Fire Stops at Floor/Wall Intersections Nightingale, T.R.T. and Halliwell, R.E. IRC-IR-754 www.nrc.ca/irc/ircpubs Flanking
More informationPinkWood Ltd. Revised September 29, 2017
Fire-Rated Assemblies PR-S315 PinkWood Ltd. Revised September 29, 2017 Products: Series I-Joists PinkWood Ltd., 5929 6 th St. NE, Calgary, Alberta, Canada T2K 5R5 (403) 279-3700 www.pinkwood.ca 1. Basis
More informationRSIC-1 ACOUSTIC ASSEMBLY
RSIC-1 ACOUSTIC ASSEMBLY FLOOR/CEILING ASSEMBLY DIRECT FIX TO CONCRETE SLAB FCS5 DSWA FIIC 72 CONSTRUCTION * 3/8" Hard Wood flooring * 8" PT concrete slab Fire resistance ratings * R-8 insulation ANS/UL
More informationFloor Insulation Underlayment Section Sound Control Matting
Floor Insulation Underlayment Section 09618 Sound Control Matting Part I General 1.1 Summary A. Section includes a sound control material for achieving an STC and IIC rating in excess of 50 to meet building
More informationC R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Base 10
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: Base 10 Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File Result
More informationLABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF PIR ROOF PANELS (According to ISO )
Ref no: LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF PIR ROOF PANELS (According to ISO 10140 2) AUCKLAND UNISERVICES LIMITED a wholly owned company of THE UNIVERSITY OF AUCKLAND Report prepared
More informationKINETICS NOISE CONTROL TEST REPORT # AT001084
KINETICS NOISE CONTROL TEST REPORT # AT001084 KINETICS NOISE CONTROL PRODUCTS: o MODEL ISOGRID ACOUSTICAL RATINGS: o STC 63 o IIC 50 TESTING AGENCY & REPORT NUMBER: o NRC-CNRC o B-3463.6 KINETICS DRAWING
More informationRSIC-1 ACOUSTIC ASSEMBLY
RSIC-1 ACOUSTIC ASSEMBLY FLOOR/CEILING ASSEMBLY DIRECT FIX TO CONCRETE SLAB FCS3 DSWA FIIC 69 PAC INTERNATIONAL Inc. Toll Free 866-774-2100 Telephone 503-649-7700 CONSTRUCTION * Ceramic Tile * 1/4" James
More informationC R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: Expona
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to ECORE International Series/Model: Expona Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results
More informationC R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: QT4005
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: QT4005 Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File Result
More informationC R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to. ECORE International. Series/Model: QT4002
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to Series/Model: QT4002 Specimen Type: Floor/Ceiling Assembly Overall Size: 3023 mm by 3632 mm Summary of Test Results Data File Result
More informationSECTION GYPSUM BOARD SYSTEM
PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 09 29 00 GYPSUM BOARD SYSTEM A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 specification sections,
More informationFLOOR CEILING ASSEMBLY
FLOOR CEILING ASSEMBLY DIRECT FIX TO I JOIST FCW-ATI-E6968.08 CONSTRUCTION Sheet Vinyl Ecore Forest FX Plywood 5/8" Waterproof Membrane (15lb Felt) Plywood 5/8" I Joist 12" Deep @ 24" OC Insulation Nominal
More informationACOUSTICAL PERFORMANCE TEST REPORT
REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON 1MM REGUPOL SONUS SOUND CONTROL UNDERLAYMENT UNDER CERAMIC TILE SPECIMEN TYPE 23 mm Concrete Slab with
More informationPart E robustdetails. robustdetails. January 2017 Update Pack. Dear Colleague,
Part E Pack Dear Colleague, This is the first 2017 update to the Part E Robust Details Handbook. In this update pack, we have focussed on clarifying the situation on incorporating underfloor heating (UFH)
More informationStaggered stud acoustic partition system
C0 Partitions Staggered stud acoustic partition system All our systems are covered by SpecSure when using genuine Gyproc and Isover products is a non-loadbearing stud partition incorporating a single framework
More informationSPECIFICATION: CLASSIC PROGRESSIVE MOVABLE WALL SYSTEM DEMOUNTABLE STEEL STUD AND GYPSUM BOARD PARTITIONS
SPECIFICATION: CLASSIC PROGRESSIVE MOVABLE WALL SYSTEM DEMOUNTABLE STEEL STUD AND GYPSUM BOARD PARTITIONS PART 1 GENERAL 1.1 RELATED WORK SPECIFIED IN OTHER SECTIONS 1.2 DESCRIPTION OF SYSTEM A. GENERAL:
More informationFIRM-FILL SCM-400 can be installed under a FIRM-FILL Gypsum Concrete Floor Underlayment to produce an exceptional vibration isolation floor system.
Specify FILL SCM-400 for additional impact noise control when a thicker sound mat is needed. It helps achieve higher delta numbers than thinner mats. FILL SCM-400 is a cost-effective way to address Impact
More informationLABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF STEEL CLAD PIR WALL PANELS (According to ISO )
Ref no: LABORATORY MEASUREMENT OF AIRBORNE SOUND INSULATION OF STEEL CLAD PIR WALL PANELS (According to ISO 10140 2) AUCKLAND UNISERVICES LIMITED a wholly owned company of THE UNIVERSITY OF AUCKLAND Report
More informationGypWall Secure Systems
GypWall Secure Systems This is a lightweight, non load bearing security wall system, offering high resistance to determined attack. Key facts Minimal wall thickness Tested in accordance with SANS 10177:2
More informationA simplified approach to impact sound insulation rating without using a tapping machine
Acoustics 8 Paris A simplified approach to impact sound insulation rating without using a tapping machine M. Li and G. Dodd Acoustics Research Centre, School of Architecture, The University of Auckland,
More informationGypLyner (walls) Metal framed wall lining system. GypLyner.
GypLyner GypLyner (walls) Metal framed wall lining system GypLyner is a cost-effective, virtually independent metal frame drylining system for lining walls. General purpose and suitable for all internal
More informationHACKER SOUND MAT II, to create a quieter living environment while meeting demanding project specifications in multi-family construction.
HACKER SOUND MAT II HACKER SOUND MAT II, to create a quieter living environment while meeting demanding project specifications in multi-family construction. HACKER SOUND MAT II, a recycled rubber sound
More informationacoustics 101 The following is a brief tutorial that describes the use of a flooring underlayment as an acoustic barrier.
acoustics 101 The following is a brief tutorial that describes the use of a flooring underlayment as an acoustic barrier. 1 why use a floor underlayment? IT S WHAT S UNDERNEATH THAT COUNTS - BENEFITS OF
More informationInstallation Guide and Safety Manual Resilient Sound Isolation Clips (SIC Clips)
Installation Guide and Safety Manual Resilient Sound Isolation Clips (SIC Clips) SOUND ISOLATION CLIP SPECIFICATIONS Width...1.00 inch Height...1.06 inch Length...3.86 inch Weight....025 lbs Max Spacing...48
More informationENKASONIC FLOOR UNDERLAYMENT 9110
ENKASONIC FLOOR UNDERLAYMENT 9110 GS1197 Section 13080 SECTION 09618 SOUND CONTROL MATTING Part I General 1.1 Summary A. Section includes a sound control material for achieving an STC and IIC rating in
More informationStark Truss Company, Inc. Revised December 14, 2018
Fire-Rated Assemblies PR-S223 Stark Truss Company, Inc. Revised December 14, 2018 Products: SI-40, SI-60, and SI-80 Prefabricated Wood I-Joists Stark Truss Company, Inc. 8655 Chestnut Ridge Road, N.W.
More informationPart E robustdetails. robustdetails. September 2015 Update Pack. Dear Colleague,
Part E September 2015 Update Pack Dear Colleague, Thank you for subscribing to receive updates to the Part E Robust Details Handbook. The most significant amendment is to the Besblock wall, E-WM-26, which
More informationKINETICS NOISE CONTROL TEST REPORT #AT001067
KINETICS NOISE CONTROL TEST REPORT #AT001067 KINETICS NOISE CONTROL PRODUCTS: o FLM- NEOPRENE PAD ACOUSTICAL RATINGS: o STC 69 o IIC 61 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA
More information