2012 IBC Assembly Means of Egress. Based on the 2012 International Building Code

Size: px
Start display at page:

Download "2012 IBC Assembly Means of Egress. Based on the 2012 International Building Code"

Transcription

1 2012 IBC Assembly Means of Egress Based on the 2012 International Building Code

2 Overview This seminar deals with those means of egress provisions of the IBC that are intended to address the concerns related to assembly uses in buildings.

3 Overview Largest life-safety losses and building disasters have occurred within assembly occupancies. Some of the most notable losses in the United States include: Iroquois Theater (fire), Chicago, At least 605 dead Rhythm nightclub (fire), Natchez, Mississippi, dead Coconut Grove nightclub (fire), Boston, dead

4 Overview Most of these fires were found to have several common issues, many of which involve the means of egress system: Overcrowding. Locked or blocked exits. Flammable decorations or interior finishes. Lack of or inoperable sprinkler systems. People trying to get out the same way they entered. Failure to follow existing fire codes. Failure to exit promptly after the fire started. Using elevators during the fire.

5 Description This seminar will cover the aspects related to the means of egress in assembly uses including: classification of assembly buildings and spaces, general egress requirements in Chapter 10, special egress provisions of Section 1028, ICC 300 Standard for Bleachers, Folding and Telescopic Seating, and Grandstands, and selected additional provisions.

6 Classification of Assembly Buildings and Spaces

7 Overview The first step in addressing the significant hazards associated with assembly uses is their proper occupancy classification. Occupancy classifications allows the minimum standard provisions of Chapter 1 to be applied appropriately.

8 Overview The code makes a distinction between use and occupancy. Use describes the function of the room or building Occupancy is the code s approach to regulating various uses based on their hazard level Use is occasionally applied, such as: Occupant load determination Section 1028 Assembly Means of Egress provisions Occupancy is the primary consideration for provisions throughout the IBC.

9 Classification (302) Section of the IBC requires that all structures or portions of structures be classified into one or more of the occupancy groups listed in Chapter 3 of the code. Occupancies are classified according to the structure s purpose and function. Assembly spaces to be classified as Group A, except: Smaller spaces classified as Group B or possibly same as major occupancy Areas associated with Group E occupancies

10 Group A Classification (303) Group A assembly occupancies cover a number of uses and building types. Theaters Nightclubs Restaurants Art galleries Libraries Airport terminals Places of worship Arenas Stadiums Primary condition for classification as assembly space is DENSITY of occupants

11 Assembly Group A (303) Section thru Pages Assembly Group A Assembly Group A Assembly Group A Assembly Group A Assembly Group A-5.

12 Business Group B (304) Sections and allow small assembly spaces to be classified as a Group B occupancy. Code official must make decisions regarding the classification of certain uses to determine if they are appropriately classified as a Group B or a Group A-3 occupancy.

13 Small Assembly Spaces ( ) Section , Page 41 A building or tenant space used for assembly purposes with an occupant load of less than 50 is to be classified as a Group B occupancy.

14 Small Assembly Spaces ( ) Section , Page 41 A room or space accessory to another occupancy with less than 50 occupants or less than 750 square feet is to be classified as: Part of that occupancy, or Group B

15 Assembly Associated with Group E Occupancies ( ) Section allows rooms used for assembly purposes associated with a Group E occupancy to be classified as portions of the Group E.

16 Classification Example #1 Meeting Rooms 40 Occupants 40 Occupants Folding Door

17 Classification Example #2 Meeting Rooms 40 Occupants 40 Occupants

18 Classification Example #3 Restaurant 40 Occupants 40 Occupants

19 General Means of Egress Requirements in Chapter 10

20 General (Chapter 10) In evaluating a means of egress in assembly uses, there is a process that should be followed: General provisions of Chapter 10 are initially evaluated, beginning with the determination of occupant loads. Section 1028 is then utilized specifically where applicable. As Section 1028 is a more specific set of provisions, the requirements take precedence over those in Chapter 10 where conflicts occur. ICC-300 is applied for those seating systems that are not considered as building elements.

21 Occupant Load (1004) The determination of occupant load is critical in the evaluation of required fire and life safety systems for all buildings, however its application relating to assembly uses is even more important: Occupancy classification Design of the means of egress system Required fire protection features

22 Occupant Load (1004) Determine the occupant load of the assembly space or of the area served by a specific component in the egress system. The requirements for assembly spaces are not unique in this aspect, but a quick review of the general code requirements is appropriate.

23 Areas Without Fixed Seating (1004) 2012 IBC Table , Page 24 Assembly rooms are typical regulated as net floor area. Net floor area allows deductions for corridors, restrooms, wall thicknesses, and similar nonoccupiable areas.

24 Areas with Fixed Seating (1004.4) Occupant load is determined by counting the number of fixed seats. If the seating does not have dividing arms, the occupant load is determined as follows: One person for each 18 inches (457 mm) of seating length (general requirement). One person for each 24 inches (610 mm) of booth seat length where seating is in a booth.

25 Additional Occupant Load Provisions (1004) Remember that general egress provisions of Section 1004 also address: Cumulative occupant loads Where egressing through intervening rooms, areas or spaces Where egressing from adjacent levels such as mezzanines or stories Allowing increased occupant loads Outdoor areas Multiple occupancies or use of space for multiple uses

26 Posting of Occupant Load (1004.3) Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space.

27 Posting of Occupant Load (1004.3) In multipurpose assembly rooms without fixed seats, such as those used for both classroom and dining purposes, it is appropriate to show each of those occupant loads on the sign. This establishes the appropriate occupant load for each use and helps prevent overcrowding conditions.

28 Posting of Occupant Load (1004.3)

29 Minimum Width Based on Component (1005.2) All means of egress components must meet the minimum width requirements established throughout Chapter 10, including: Doorways Aisles Corridors Stairways 32 inches 36 inches 44 inches (serving 50 or more) 44 inches (serving 50 or more)

30 Minimum Capacity Based on Occupant Load (1005.3) All means of egress components must also meet the minimum capacity requirements established in Section : Stairways: 0.3 inches per occupant 0.2 inches per occupant is used for fully sprinklered buildings also provided with an emergency voice/alarm communication system Other than stairways: 0.2 inches per occupant 0.15 inches per occupant is used for fully sprinklered buildings also provided with an emergency voice/alarm communication system

31 Distribution of Egress Capacity (1005.5) Where more than one means of egress is required, egress capacity may be distributed among the exits and/or exit access doorways such that: the loss of one exit or exit access doorway will not reduce the available capacity by more than 50%. Where more means of egress are provided that the number required, the egress capacity may be distributed among all complying exits and/or exit access doorways.

32 Means of Egress Illumination (1006) The general provisions for means of egress illumination also apply to assembly uses, except: Aisle accessways are not required to be illuminated. In auditoriums, theaters, concert or opera halls and similar assembly spaces are permitted to reduce the lighting to 0.2 footcandles (2.15 lux) during performances provided the illumination automatically returns to the 1 footcandle level when the fire alarm system is activated.

33 Door Hardware - Lock and Latch Requirements ( ) In general, egress doors shall be readily openable without use of a key, special effort or special knowledge. Section : Key-operated locking device is permitted on main exterior door(s) of Group A occupancies with occupant loads of 300 or less, provided: Sign posted adjacent to door Door to remain unlocked when building is occupied Use of device is revocable by building official

34 Panic and Fire Exit Hardware ( ) Doors serving rooms or spaces with an occupant load of 50 or more in a Group A occupancy shall not be provided with a lock or latch unless it is panic hardware. This requirement is not only limited to the room classified as Group A, but also all intervening doors until completion of the means of egress. Delayed egress devices are not permitted to be installed on doors serving Group A occupancies.

35 Single Exit Rooms and Spaces (1015) A single exit or exit access doorway is permitted where both the occupant load and the common path of travel do not exceed the limitations of Section Maximum Number of Occupants Maximum Common Path of Egress Travel (feet) Group A Common path is typically not a restriction due to density level of assembly uses.

36 Exit Access Travel Distance (1016) Travel from the most remote point within a story to the nearest exit shall not exceed the travel distance limitations of Table Without Sprinkler System With Sprinkler System Group A 200 feet 250 feet Travel is to be measured along the natural and unobstructed path, both horizontal and vertical travel as applicable.

37 Corridor Fire-Resistance (1018) Corridors shall be fire-resistance-rated in accordance with Table Occupant Load Served by the Corridor Required Rating without Sprinkler System Required Rating with Sprinkler System Group A Greater than 30 1 hour 0 (no rating required)

38 Stories with One Exit (1021) A single means of egress from a story is permitted when in compliance with Table (2). Group A Story First Story or Basement Above the First Story Maximum Occupant Load per Story 49 occupants Maximum Exit Access Travel Distance 75 feet Single Means of Egress Not Permitted

39 Means of Egress Review Example #1 Meeting Rooms 40 Occupants 40 Occupants Folding Door

40 Means of Egress Review Example #2 Meeting Rooms 40 Occupants 40 Occupants

41 Means of Egress Review Example #3 Restaurant 40 Occupants 40 Occupants

42 Means of Egress Review Example #4 Meeting Rooms 60 Occupants 30 Occupants

43 Means of Egress Review Example #5 Meeting Rooms 5 Occ 5 Occ 5 Occ 10 Occupants 30 Occupants 10 Occupants

44 Assembly Means of Egress Requirements of Section 1028

45 Assembly Means of Egress (1028.1) Rooms or spaces used for assembly purposes which contain seats, tables, displays, equipment or other materials shall comply with Section 1028, except: Bleachers, grandstands, telescoping seating not considered as building elements shall comply with ICC 300. In addition, the provisions of Section regulating egress capacity are limited only to aisles.

46 Assembly Means of Egress (1028.1) The general means of egress provisions of Chapter 10 shall apply unless revised by the provisions of Section Section 1028 applies to not only Group A occupancies, but to all spaces and rooms used for assembly purposes. Includes those assembly uses classified as Group E or Group B.

47 Assembly Means of Egress Special provisions of Section 1028 focus on: Required capacity, including smoke-protected seating Travel distance Common path of egress travel Minimum aisle widths Aisle accessways Aisles treads and risers Seat stability Handrails Guards

48 Assembly Main Exit (1028.2) Main Exit: Has sufficient width to accommodate not less than one-half of occupant load. Accommodates not less than the total required width of all means of egress leading to the exit. Front onto a street or an unoccupied space that adjoins a street or public way if the building is classified as a Group A occupancy. Minimum width of space is not less than 10 feet (3048 mm).

49 Assembly Main Exit (1028.2)

50 Assembly Main Exit (1028.2)

51 Assembly Other Exits (1028.3) Additional means of egress must also provide at least 50% of occupant load capacity.

52 Foyers and Lobbies (1028.4) In Group A-1 occupancies where persons are admitted to building at times when seats are not available, waiting is permitted in lobby provided required width is maintained.

53 Foyers and Lobbies (1028.4)

54 Balconies (1028.5) Balconies, galleries and press boxes with capacity of 50 or more shall be provided with at least two means of egress. At least one means of egress shall be provided on each side of the balcony, gallery or press box. At least one means of egress must lead directly to an exit.

55 Balconies (1028.5)

56 Width and Capacity (1028.6) Required width and egress capacity is determined by multiplying the occupant load served by the appropriate egress width factor. Consistent with other occupancies, the means of egress capacity is based upon the occupant load using the system. Intended application of Section is limited to aisles only.

57 Width and Capacity (1028.6) 2012 IBC Definitions, Page 33 Egress width factors for the various elements will depend on whether the assembly space has smoke-protected seating or not. Smoke-protected assembly seating is considered as seating served by a means of egress that is not subject to smoke accumulation within or under a structure. Applicable to both indoor and outdoor assembly spaces.

58 Minimum Egress Width Without Smoke Protection ( ) Element Width requirement per occupant served Limitations Stair 0.3 inch Riser height 7 inches or less Tread depth 11 inches or greater

59 Minimum Egress Width Without Smoke Protection ( ) Element Stair (additional width for riser height greater than 7 inches) Width requirement per occupant served inch additional width (see limitations) Limitations inch of additional width is required for each occupant for each 0.10 inch of riser height above 7 inches

60 Minimum Egress Width Without Smoke Protection ( ) Element Stair (egress in descent) Width requirement per occupant served inch additional width (see limitations) Limitations inch of additional width is required for each occupant on stairs not having a handrail within a 30 inch horizontal distance

61 Minimum Egress Width Without Smoke Protection ( ) Element Level or Ramped (Slope 1:12 Width requirement per occupant served Limitations 0.2 inch For slopes not steeper than one unit vertical in 12 units horizontal ( 1:12, 8%)

62 Minimum Egress Width Without Smoke Protection ( ) Element Ramped (Slope >1:12) Width requirement per occupant served Limitations 0.22 inch For slopes steeper than one unit vertical in 12 units horizontal (>1:12, >8%). Maximum slope of 1:8 per Stair required if >1:8.

63 Smoke-Protected Seating ( ) 2012 IBC Definitions Page 33 Smoke-protected Assembly Seating Seating served by means of egress that is not subject to smoke accumulation within or under a structure.

64 Smoke-Protected Seating ( ) 2012 IBC Table Page 275 Required capacity for smoke-protected assembly seating to be determined based on Table TABLE WIDTH OF AISLES FOR SMOKE-PROTECTED ASSEMBLY

65 Smoke-Protected Seating ( ) Where the reduced width allowances of Table are applied, a life safety evaluation complying with NFPA 101 shall be performed. In addition, the means of egress shall be provided with either: A smoke control system per Section 909, or Natural ventilation designed to maintain the smoke level at least 6 feet above the floor of the means of egress.

66 Life-Safety Evaluation Complying with NFPA 101 The Life-Safety Code (NFPA 101) defines a life safety evaluation as A written review dealing with the adequacy of life safety features relative to fire, storm, collapse, crowd behavior, and other related safety considerations. (NFPA 101, Section )

67 Life-Safety Evaluation Complying with NFPA 101 The life safety evaluation is to: Be performed by a person acceptable to the Building Official (NFPA 101, Section ). Shall include assessments of both building systems and management features upon which reliance is placed for the safety of facility occupants (NFPA 101, Section ).

68 Life-Safety Evaluation Complying with NFPA 101 The life safety evaluation is to: Shall consider scenarios appropriate to the facility (NFPA 101, Section ). Shall be approved annually by the Building Official or Fire Code Official and shall be updated for special or unusual conditions (NFPA 101, Section ). Shall include a written assessment of all of the specified conditions and appropriate safety measures (NFPA 101, Section ).

69 Smoke-Protected Seating - Smoke Control ( )

70 Smoke-Protected Seating - Smoke Control ( ) The lowest portion of the roof deck shall be at least 15 feet above the highest aisle or aisle accessway.

71 Smoke-Protected Seating Roof Height ( ) In an outdoor stadium with a roof canopy, the 15-foot clearance is not required where there is 80 inches clear from the highest aisle or aisle accessway to the roof canopy.

72 Smoke-Protected Seating - Automatic Sprinklers ( )

73 Smoke-Protected Seating - Automatic Sprinklers ( ) A sprinkler system is required for fully enclosed areas containing smoke-protected assembly seating, except: Press boxes and storage areas less than 1,000 square feet. Outdoor seating facilities where seating and means of egress are essentially open to the outside.

74 Smoke-Protected Seating - Automatic Sprinklers ( ) In addition, sprinkler protection is not required over the floor area used for contests, performances or entertainment; provided The roof construction is more than 50 feet above the floor, and The area is limited to low fire hazard uses.

75 Outdoor Seating ( ) The clear width of outdoor assembly seating with an occupant load of 18,000 or less is determined using the factors in Section For stairs and aisles, a factor of 0.08 inches per occupant shall be applied. For ramps, corridors, tunnels and vomitories, a factor of 0.06 inches shall be applied.

76 Assembly Seating Capacity Comparison 1. Outdoor smoke-protected may use Section for smoke-protected seating where it permits less width. 2. Minimum factor. See for additional with factors that may apply based upon stair configuration, handrails and direction of travel. 3. Ramp factors are dependent upon whether slope is steeper than 1:12 or not. See Section , Item 4.

77 Travel Distance (1028.7) The limits on travel distance of 200 feet (nonsprinklered) and 250 feet (fully sprinklered) are consistent with the general requirements.

78 Travel Distance (1028.7) In smoke-protected assembly seating, travel distances are extended. For open air seating, travel distance: Is limited to 400 feet in Type III, IV and V buildings Unlimited in Type I and II buildings

79 Common Path Of Egress Travel (1028.8) 2012 IBC Definitions, Page 15 The common path of egress travel is that portion of exit access which occupants are required to traverse before two separate and distinct paths of egress travel to two exits are available. Paths that merge are common paths of travel. Common paths of egress travel limits in assembly seating areas are typically more restrictive than the general provisions.

80 Common Path of Egress Travel (1028.8) Common path limited to: 30 feet typically 50 feet in smokeprotected seating areas 75 feet where areas seating less than 50

81 Path Through Adjacent Row ( ) Where one of two paths of travel is across the aisle through a row of seats to another aisle, the number of seats between the adjacent aisles when traversing through the aisle accessway is limited to: 24 seats (general requirement) 40 seats if smoke-protected assembly seating

82 Path Through Adjacent Row ( ) Clear width between adjacent rows when traversing through the aisle accessway: 12 inches plus 0.6 inch (304.8 plus 15.2 mm) for each seat greater than seven in the row between the aisles (general requirement) 12 inches plus 0.3 inch (304.8 plus 7.6 mm) for each seat greater than seven in the row between the aisles if smoke-protected assembly seating

83 Path Through Adjacent Row ( )

84 Minimum Aisle Width ( ) Regardless of the required capacity based on the occupant load served by an aisle, minimum aisle widths are also established based on a variety of conditions. The greater of the calculated width and the component width shall be provided.

85 Minimum Aisle Width ( and )

86 Minimum Aisle Width Example Minimum clear width required for a stepped aisle serving seating on both sides is 48 inches. In an area without smoke-protection a stepped aisle is required to provide at least 0.3 inch of width for each occupant served (Section , item 1). Assuming the aisle serves 180 people, the minimum width to provide sufficient egress capacity for the number of people accommodated is 54 inches (180 x 0.3" = 54"). Therefore the aisle must be 54 inches in width and cannot use the 48 inch minimum specified in Section , Item 1.

87 Aisle Width ( ) Aisle widths are based upon a distribution of occupants among the available means of egress. These catchment areas assume a balanced use of all means of egress.

88 Converging Aisles ( ) Where aisles converge into a single path, the required capacity is based on the combined required capacity of the converging aisles.

89 Uniform Width ( ) Portions of aisles where egress is possible in either direction shall be uniform in required width.

90 Uniform Width ( )

91 Assembly Aisle Termination ( ) Unless in compliance with the dead-end limitations, aisles shall terminate at a cross aisle, foyer, doorway, vomitory or concourse having access to an exit.

92 Aisle Accessways ( ) An aisle accessway is that portion of an exit access that leads to an aisle. Therefore the aisle accessway is generally the starting point that the occupant must get through in order to reach the aisle and then ultimately to leave the room and reach an exit.

93 Aisle Accessways ( )

94 Aisle Accessway for Seating at Tables ( and ) Where seating is located at tables and counters, minimum widths are established based upon the specific condition.

95 Aisle Accessway for Seating at Tables ( and ) The required width of aisles and aisle accessways is typically achieved based on a uniform distribution of the established occupant load. The minimum widths established in Section are typically applied where: The actual occupant load exceeds the calculated occupant load as established by Section , or The occupant load is not uniformly distributed, or Inspections reveal a potential overcrowding condition.

96 Aisle Accessways Serving Seating in Rows ( ) Where aisles have 14 seats or fewer, the minimum clear width of the aisle accessway shall be 12 inches.

97 Aisle Accessways Serving Seating in Rows ( ) Where more than 14 seats, the width is increased at 0.3 inch/seat to a maximum of 22 inches. 100 SEATS MAXIMUM

98 2012 IBC Table Page 277 Aisle Accessways Serving Seating in Rows - Smoke Protected ( ) In smoke-protected areas, additional seats are permitted with 12-inch aisle accessways.

99 Assembly Aisle Walking Surfaces ( ) 1:8 slope is the threshold where the ramped/level aisle provisions are appropriate and where the stepped aisles requirements must be used.

100 Assembly Aisle Treads and Risers ( ) Tread depths shall be a minimum of 11 inches and be uniform. A maximum 3/16 inch tolerance is permitted between adjacent treads.

101 Assembly Aisle Treads and Risers ( ) Risers shall have a minimum height of 4 inches and a maximum height of 8 inches. Riser heights up to 9 inches are permitted where necessitated by slope of the adjacent seating to maintain sightlines.

102 Seat Stability ( ) Seats shall be securely fastened to the floor, unless: No ramped or tiered floor and 200 or fewer seats No ramped or tiered floor and seating is at tables No ramped or tiered floor, more than 200 seats fastened together in groups of three or less In tiered areas from flexibility of seating is integral part of function of the space and 200 or fewer seats Groups of 14 seats or less separated from other seating by railings, guards or similar barriers Seating intended for musicians or other performers

103 Aisle Handrails ( ) Handrails are required for ramped aisles having a slope exceeding 1:15 and for stepped aisles.

104 Aisle Handrails ( ) 3 exceptions eliminate or modify the handrail requirements. Ramped aisles with seating on both sides do not require a handrail if the ramp slope is no greater than 1:8. Where the side of an aisle is protected by a guard that complies with the handrail graspability requirements, a separate handrail is not required. Handrail extensions are not required beyond the top or bottom of an aisle stair or ramped aisle.

105 Discontinuous Handrails ( ) Where there is seating on both sides of an aisle, a center handrail shall be discontinuous with gaps at intervals not exceeding five rows. The purpose is to facilitate access to seating and permit access from one side of the aisle to the other. Where handrails are provided in the middle of aisle stairs, an additional rail is required approximately 12 inches below the main handrail.

106 Discontinuous and Intermediate Handrails ( and )

107 Guards ( ) Guards adjacent to assembly seating areas are specifically regulated for three conditions: Guards at cross aisles Guards that restrict sightlines Guards at the end of aisles Unless modified by Section , the general guard provisions of Section 1013 shall be applied.

108 Guards ( )

109 Guards ( )

110 Assembly Guards ( )

111 ICC 300 Standard for Bleachers, Folding and Telescopic Seating and Grandstands

112 Assembly Seating Bleachers ( and ICC 300) ICC-300, Standard on Bleachers, Folding and Telescopic Seating, and Grandstands, is adopted by reference in Section The standard addresses both temporary and permanent bleachers, folding and telescopic seating, and grandstands which are supported on their own dedicated structural system and are not constructed as part of the building. Such seating systems are required to comply with ICC-300 rather than the IBC.

113 ICC 300 The applicability of the standard is as follows: Provisions apply to both temporary and permanent installations. Temporary installations are those that are erected for less than 180 days in a calendar year. New bleachers, folding and telescopic seating and grandstands must comply with Chapters 1 through 4 of the standard. Existing installations must comply with Chapters 1, 2 and 5 of the standard.

114 ICC 300 The primary requirements of the standard are found within Chapters 3 and 4 which regulate the construction and means of egress requirements for the seating systems.

115 ICC 300 The main topics regulated in ICC-300 include: Location on lot for outdoor installations Structural design and support for interior installations Spaces beneath the seating system Clear height for the egress system and above seating area if a smoke-protected seating or outdoor installation with a roof canopy Fire alarm system requirements Accessibility for tiered seating areas Open spaces between footboards and seatboards Means of egress requirements

116 Construction Requirements (ICC 300 Chapter 3) Outdoor installations shall be located at least 10 feet from: Adjacent lot lines Other buildings on the same lot Unless exterior walls and openings of building protected

117 Construction Requirements (ICC 300 Chapter 3) Systems regulated by the ICC 300 standard are permitted to be constructed of combustible or noncombustible materials. Such systems are not building elements and therefore are not limited or regulated by the building's type of construction. They are also not to be considered as a part of the interior finish even when located within a building.

118 Spaces Beneath Seats (ICC 300 Section 305) Spaces beneath seating structures shall comply with the building and fire codes, including: Removal of combustible waste, or other materials. Fire separation where use of space is for ticket booths, toilet rooms or other purposes. Sprinkler requirements if enclosed spaces over 1,000 square feet. Any other applicable section.

119 Spaces Beneath Seats ICC 300 (Section 311) Where more than 30 inches above ground below, openings between seatboards and footboards shall not allow passage of a 4-inch sphere.

120 Minimum Number of Means of Egress (ICC 300 Section 404) The minimum number of exits from the seating area shall be based on the occupant loads established in Section

121 Exterior Installations Means of Egress (ICC 300 Section 404.3) In situations where the path of travel to the public way is not safe or achievable due to site constraints, security concerns or other reasons, Section allows the occupants of the seating facility to move to a safe dispersal area where they would be at least 50 feet away from the seating area and could safely wait until the exits are available or until the hazard is resolved.

122 Aisles (ICC 300 Section 405.1) Aisles are not required where 8 specified conditions are met.

123 Existing Bleachers, Folding and Telescopic Seating, and Grandstands (ICC 300 Chapter 5) Existing bleachers, folding and telescoping seating, and bleachers to comply with Chapters 1 and 5. Exception for tiered seating where top of seating not more than 30 inches above floor or grade below All tiered seating to be inspected and evaluated at least once a year by a qualified person. All folding and telescoping seating to be inspected to evaluate compliance with manufacturer s installation and operational instructions.

124 Maintenance and Repairs (ICC 300 Section 502) Existing tiered seating shall be maintained structurally sound. Materials used in outdoor installations shall be weather resistant. Wood to be naturally durable or preservative-treated wood Fasteners to be aluminum or other approved corrosion-resistant materials Spaces beneath or adjacent to seating structures shall comply with IBC and IFC.

125 Guards (ICC 300 Section 503) Areas of tiered seating located more than 30 inches above floor or grade below to be protected with minimum 36-inch-high guards. Not required where uppermost seat located less than 55 inches above floor or ground below Not required where next to a wall and space between wall and seating is less than 4 inches Except at foot of the aisle, minimum 26-inch-high guards permitted where higher guard would interfere with sightlines Open guards to restrict passage of 4-inch sphere, with 6 inches permitted at triangular opening at riser/tread/bottom rail.

126 Open Spaces at Footboards and Seatboards (ICC 300 Section 504) Openings at seatboards and footboards located more than 30 inches above floor or grade below to be closed such that a 4-inch diameter sphere cannot pass through. Not required where uppermost seat located less than 55 inches above floor or ground below

127 Relocating Existing Bleachers (ICC 300 Section 505) Relocating existing bleachers to a new location permitted where in compliance with Chapter 5, and: Foundations designed to support all loads Where indoors, floors to be designed to accommodate both live and dead loads associated with the movement of the seating Clear height of aisles, aisle accessways and other portions of means of egress to be at least 80 inches 15-foot clearance between highest aisle and roof to be provided where smoke-protected assembly seating is used (only 80 inches required to canopy where an outdoor installation) Electrical to comply with NEC Accessibility to be provided per IBC

128 Comparison of ICC 300 to IBC Requirement

129 Comparison of ICC 300 to IBC Requirement

130 Comparison of ICC 300 to IBC Requirement

131 Comparison of ICC 300 to IBC Requirement

132 Comparison of ICC 300 to IBC Requirement

133 Additional Provisions

134 Overview In addition, there are a variety of specific provisions throughout the IBC that selectively address means of egress in assembly uses, including special amusement buildings. The IFC also includes a number of egress provisions that may not occur in the IBC.

135 Special Amusement Building (202) 2012 IBC Definitions, Page 33 A special amusement building is any temporary or permanent building or portion thereof that is occupied for amusement, entertainment or educational purposes and that contains a device or system that conveys passengers or provides a walkway along, around or over a course in any direction so arranged that the means of egress path is not readily apparent due to visual or audio distractions or is intentionally confounded or is not readily available because of the nature of the attraction or mode of conveyance through the building or structure.

136 Special Amusement Buildings (411) The code requirements address many of the hazards related to special amusement buildings, including: Uncertainty of exit locations and access to them. Dark and confusing exiting system. Confusing or conflicting sounds and visual distractions. Lack of notification and awareness of fire (which led to additional people entering the building after the fire had begun). Flame spread of materials which lead to fire progression and smoke development.

137 Special Amusement Buildings (411) Note the key features are: The means of egress is not readily available or apparent The potential for sound or lighting which can distract or confound the occupants and affect their egress Buildings can be permanent or temporary Building could include a passenger conveying system or walkway through it

138 Special Amusement Buildings General (411.1) Special amusement buildings are classified as Group A occupancies where the occupant load is 50 or more.

139 Special Amusement Buildings General (411.1) Special amusement buildings are not regulated by Section 411 where smoke accumulation is prevented.

140 Exit Marking (411.7) Low-level exit signs and directional exit marking are required where the egress path is not readily apparent.

141 IFC Provisions Related to Places of Assembly Whenever dealing with assembly occupancies it is important to realize that the International Fire Code contains a number of requirements which are applicable and may include requirements that are not addressed within the IBC.

142 Operational Permits (IFC 105.6) Amusement buildings. (IFC Section ) Carnivals and fairs. (IFC Section ) Cellulose nitrate film. (IFC Section ) Exhibits and trade shows. (IFC Section ) Liquid- or gas-fueled vehicles or equipment in assembly buildings. (IFC Section ) Open flames and candles. (IFC Section ) Places of assembly. (IFC Section ) Temporary membrane structures and tents. (IFC Section ) Construction permits also required (IFC Section )

143 Emergency Planning and Preparedness (IFC Chapter 4) Chapter 4 of the IFC addresses the emergency planning and preparedness requirements. A number of sections affect the operation and use of assembly spaces (both indoor and outdoor).

144 Public Assemblages and Events (IFC 403) Section grants the code official the authority to require the owner, agent or lessee provide fire watch personnel to be on duty at places of assembly or events where they believe it is essential to the public safety. The duties of the fire watch personnel are listed in Section Crowd managers are required in larger facilities or events where more than 1,000 people will congregate.

145 Fire Safety and Evacuation Plans (IFC 403) Group A facilities used exclusively for religious worship which have an occupant load of less than 2,000 people are exempt from the fire safety and evacuation plan requirement. A plan is also required for any building with an atrium and a Group A occupancy.

146 Emergency Evacuation Drills (IFC 405) Evacuation drills are to be conducted for the employees of a Group A occupancy on a quarterly basis.

147 Employee Training and Response Procedures (IFC 406) Employees in Group A occupancies are to be trained in the fire emergency procedures described in their facilities fire evacuation and fire safety plans. Employees are to be trained as part of their new employee orientation and at least annually thereafter.

148 Use and Occupancy-Related Requirements (IFC 408) A detailed seating plan, occupant load and occupant load limit shall be included with the fire safety and evacuation plans.. An announcement regarding the location of exits is to be made in theaters, motion picture theaters, auditoriums and similar assembly occupancies used for noncontinuous programs.

149 Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation without written permission of the speaker is prohibited. International Code Council 2015

150 Thank you for participating!!

EGRESS CHAPTER ,500 3 Over 2,500 4 OCCUPANT LOAD REQUIRED MEANS OF EGRESS

EGRESS CHAPTER ,500 3 Over 2,500 4 OCCUPANT LOAD REQUIRED MEANS OF EGRESS CHAPTER 4 EGRESS SECTION 401 GENERAL 401.1 General. The means of egress for new bleachers, folding and telescopic seating, and grandstands shall comply with this chapter. SECTION 402 TRAVEL 402.1 Exit

More information

Work Group Item Stairways serving an occupant load of less than 50 shall have a width of not less than 36 inches (914 mm).

Work Group Item Stairways serving an occupant load of less than 50 shall have a width of not less than 36 inches (914 mm). IBC-12/13 1009.1, 1009.4, 1009.7.2, 1009.7.4, 1009.8, 1009.10, 1009.15 (IFC [B] 1009.1, 1009.4, 1009.7.2, 1009.7.4, 1009.8, 1009.10, 1009.15) Proponent: S. Bajnai, Chesterfield County, VA, ICC Building

More information

Standard for Bleachers, Folding and Telescopic Seating, and Grandstands

Standard for Bleachers, Folding and Telescopic Seating, and Grandstands International Code Council Standard for Bleachers, Folding and Telescopic Seating, and Grandstands ICC 300-2017 edition Public Comment Draft October 2017 The ICC Consensus Committee on Bleachers, Folding

More information

E?? , , , , , , , , , , , , Table ,

E?? , , , , , , , , , , , , Table , CTC to BCAC Unenclosed Exits 2015 Group A Code Change Cycle Copyright 2014 International Code Council, Inc. IBC 10-31 E?? 15 202, 1005.3.2, 1009.3, 1009.4, 1019.3, 1029.6, 1029.6.3, 1029.7, 1029.8, 1029.8.1,

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

EGRESS AZMIR SULTANA NICOLAS MIMU SAKUMA EDWIN VEGA CHAMORRO

EGRESS AZMIR SULTANA NICOLAS MIMU SAKUMA EDWIN VEGA CHAMORRO EGRESS AZMIR SULTANA NICOLAS CHAMORRO MIMU SAKUMA EDWIN VEGA DEFINITIONS NC ACCESSIBLE MEANS OF EGRESS. A continuous and unobstructed way of egress travel from any accessible point in a building or facility

More information

(Statute, Rule, FBC, Industry) FBC 406.3, see also FBC No provisions in FBC or FS

(Statute, Rule, FBC, Industry) FBC 406.3, see also FBC No provisions in FBC or FS Florida Specific Amendment Code Reference NFPA 101 Open Parking Structure. A parking structure that, at each parking level, has wall openings open to the atmosphere, for an area of not less than 1.4 ft2

More information

Report of project list/proposed changes for Dec. 5 and 6, 2017 BCAC face-to-face committee meeting and

Report of project list/proposed changes for Dec. 5 and 6, 2017 BCAC face-to-face committee meeting and BCAC MOE Work Group Summary with Files Revised 11-20-2017 with meeting notes Report of project list/proposed changes for Dec. 5 and 6, 2017 BCAC face-to-face committee meeting ITEM Topic SECTION Notes

More information

General Building Information

General Building Information Software Module s Description Page 1 General Building Information BUILDING AREA AND HEIGHT - This module designed to determine the height and area of buildings on the basis of occupancy group classification

More information

International Code Council

International Code Council International Code Council ICC 300-2012 edition Public comments received On the 2007 edition of the ICC 300 Standard For November 24, 2010 Meeting - Teleconference Page 1 of 15 2007 ICC 300 Standard Revision

More information

2015 IBC Special Building Types and Features IBC Special Building Types and Features. Copyright 2016 International Code Council 1

2015 IBC Special Building Types and Features IBC Special Building Types and Features. Copyright 2016 International Code Council 1 Description 2015 IBC Special Building Types and Features Based on the 2015 International Building Code (IBC ) This course provides an overview of selected 2015 IBC Chapter 4 provisions and the application

More information

IBC MEANS OF EGRESS. Code Change No: E5-07/08. Original Proposal

IBC MEANS OF EGRESS. Code Change No: E5-07/08. Original Proposal DOCUMENTATION IBC MEANS OF EGRESS Code Change No: E5-07/08 Sections: 1002.1 (IFC [B] 1002.1) Proponent: Gerard Hathaway, New York State Department of State Building Codes Division, representing himself

More information

2015 IBC Exit Systems

2015 IBC Exit Systems Objectives 2015 IBC Exit Systems Based on the 2015 International Building Code Upon completion, participants will be better able to: Determine those means of egress components that are defined as exits

More information

CHAPTER 10 MEANS OF EGRESS

CHAPTER 10 MEANS OF EGRESS CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

International Code Council

International Code Council Page 1 of 21 International Code Council ICC 300-2012 edition Committee Actions Report For Committee Actions taken at the November 24 th and December 14 th, 2010 meetings Page 2 of 21 IS-BLE1-10/11 ICC

More information

CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 10 MEANS OF EGRESS

CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 10 MEANS OF EGRESS CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 10 MEANS OF EGRESS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency authority and building

More information

2012 IBC Exit Systems

2012 IBC Exit Systems Accreditation Based on the 2012 International Building Code The International Code Council has been accredited as an Authorized Provider by the International Association for Continuing Education and Training

More information

2015 International Fire Code

2015 International Fire Code 1001, 1001.1, 1001.2, 1002, [BE] 1002.1, 1003, [BE] 1003.1, [BE] 1003.2, [BE] 1003.3, [BE] 1003.3.1, [BE] 1003.3.2, [BE] 1003.3.3, [BE] 1003.3.4, [BE] 1003.4, [BE] 1003.5, [BE] 1003.6, [BE] 1003.7, 1004,

More information

INTERNATIONAL CODE INTERPRETATIONS

INTERNATIONAL CODE INTERPRETATIONS 2012 INTERNATIONAL CODE INTERPRETATIONS PREFACE The 2012 International Codes promulgated by the International Code Council (ICC ) comprise a comprehensive set of model regulations for the construction

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

International Code INTERPRETATIONS

International Code INTERPRETATIONS 2015 International Code INTERPRETATIONS 2015 International Code Interpretations First Printing: June 2016 ISBN#978-1-60983-666.5 Copyright 2016 by International Code Council ALL RIGHTS RESERVED. This 2015

More information

TEXT OF RULE. 1. Section of Part 1219 of Title 19 of the Official Compilation of Codes, Rules

TEXT OF RULE. 1. Section of Part 1219 of Title 19 of the Official Compilation of Codes, Rules TEXT OF RULE 1. Section 1219.1 of Part 1219 of Title 19 of the Official Compilation of Codes, Rules and Regulations of the State of New York is amended to read as follows: Section 1219.1 Uniform Fire Prevention

More information

PRESCRIPTIVE COMPLIANCE METHOD

PRESCRIPTIVE COMPLIANCE METHOD CHAPTER 3 PRESCRIPTIVE COMPLIANCE METHOD [B] SECTION 301 GENERAL 301.1 Scope. The provisions of this chapter shall control the alteration, repair, addition and change of occupancy of existing structures,

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

Temporary Use Packet Permit Information

Temporary Use Packet Permit Information Permit Information Temporary Use Packet (Permit & Development Center - Community Development Department & the City of Des Moines Fire Department) Packet Information Includes: Explanation of Temporary Use

More information

SUPPLEMENTAL ACCESSIBILITY NO. 5 PLAN REVIEW CHECKLIST

SUPPLEMENTAL ACCESSIBILITY NO. 5 PLAN REVIEW CHECKLIST GEORGE CHAVEZ, City Building Official DAVID YELTON, Building Inspection Manager NESTOR OTAZU, Community Preservation Manager BUILDING & SAFETY DIVISION 455 North Rexford Drive, 1 st Floor Beverly Hills,

More information

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,

More information

TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES

TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES CHAPTER 24 TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES SECTION 2401 GENERAL 2401.1 Scope. Tents, canopies and membrane structures shall comply with this chapter. The provisions of Section 2403 are applicable

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

2015 IBC Accessible Means of Egress

2015 IBC Accessible Means of Egress 2015 IBC Accessible Means of Egress Based on the 2015 International Building Code Description Upon completion, the participant will be able to apply the accessible means of egress provisions of Section

More information

ORDINANCE NO BE IT ORDAINED BY THE GOVERNING BODY OF THE CITY OF MANHATTAN, KANSAS: Section Adoption of the International Building Code.

ORDINANCE NO BE IT ORDAINED BY THE GOVERNING BODY OF THE CITY OF MANHATTAN, KANSAS: Section Adoption of the International Building Code. ORDINANCE NO. 7222 AN ORDINANCE AMENDING CHAPTER 8 OF THE CODE OF ORDINANCES, REGULATING BUILDINGS WITHIN THE CORPORATE LIMITS OF THE CITY OF MANHATTAN, KANSAS; INCORPORATING BY REFERENCE THE INTERNATIONAL

More information

PRESCRIPTIVE COMPLIANCE METHOD

PRESCRIPTIVE COMPLIANCE METHOD CHAPTER PRESCRIPTIVE COMPLIANCE METHOD 3 SECTION 301 GENERAL 301.2 Building materials. Building materials shall comply with the requirements of this section. 301.2.1 Existing materials. Materials already

More information

CALIFORNIA BUILDING PLANS EXAMINER CONTENT OUTLINE 01. GENERAL ADMINISTRATION 3 % Project Administration 3%

CALIFORNIA BUILDING PLANS EXAMINER CONTENT OUTLINE 01. GENERAL ADMINISTRATION 3 % Project Administration 3% CALIFORNIA BUILDING PLANS EXAMINER CONTENT OUTLINE EXAM ID: I6 80 multiple-choice questions 3-1/2-hour time limit Open book 01. GENERAL ADMINISTRATION 3 % 0101. Project Administration 3% Verify that plans,

More information

INTERNATIONAL EXISTING BUILDING CODE

INTERNATIONAL EXISTING BUILDING CODE INTERNATIONAL EXISTING BUILDING CODE EB10-09/10, Part I IEBC 605.1, 705.2, 706.1, 805.4 (New), 805.4.1 (New), 912.4.1, 912.4.2, 912.8.2, 1004.1(New), 1005.1, 1103.3, 1105.6; IBC 3411.4, 3411.4.1, 3411.4.2,

More information

Corridor. An enclosed exit access component that defines and provides a path of egress travel to an exit.

Corridor. An enclosed exit access component that defines and provides a path of egress travel to an exit. ACTION: Original DATE: 09/15/2006 10:18 AM 1301:7-7-10 Means of egress. (A) Section 1001 General (1) 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required

More information

(1) [BE] Definitions. The following terms are defined in rule 1301: of the Administrative Code.

(1) [BE] Definitions. The following terms are defined in rule 1301: of the Administrative Code. ACTION: Final DATE: 12/04/2017 11:44 AM 1301:7-7-10 Means of egress. (A) Section 1001 General (1) 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required

More information

Report on First Revisions with Statement June 2014 NFPA 5000

Report on First Revisions with Statement June 2014 NFPA 5000 5000 FR1000 BLD-AXM (16.1 through 16.1.7) Recommendation: 16.1 General Requirements. 16.1.1 Application. 16.1.1.1 The requirements of this chapter shall apply to new buildings or portions thereof used

More information

1301: Means of egress.

1301: Means of egress. ACTION: Final DATE: 12/26/2018 8:54 AM 1301:7-7-10 Means of egress. (A) Section 1001 General (1) 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required

More information

Company Overview. Significant Code Changes Massachusetts State Building Code 9 th Edition (2015 International Code)

Company Overview. Significant Code Changes Massachusetts State Building Code 9 th Edition (2015 International Code) Significant Code Changes Massachusetts State Building Code 9 th Edition (2015 International Code) Company Overview R.W. Sullivan Engineering (RWS) was established in 1945 and currently has 95 employees.

More information

Plan Check No. A. ELEVATORS

Plan Check No. A. ELEVATORS Elevators, Egress and Areas of Refuge, Platform Lifts Plan Check No. A. ELEVATORS NOTE: In buildings two or more stories in height, served by an elevator, or a building served by an elevator required by

More information

2006 International Building Code Modified for the 2007 Florida Building Code 6/5/06

2006 International Building Code Modified for the 2007 Florida Building Code 6/5/06 Chapter 10 Means of Egress Chapter 10 Mean of Egress 1001.3 Maintenance. Means of egress shall be maintained in accordance with the International Fire Code. na 1001.3 Maintenance. Means of egress shall

More information

STAIRWAYS, HANDRAILS, AND GUARDRAILS (RESIDENTIAL)

STAIRWAYS, HANDRAILS, AND GUARDRAILS (RESIDENTIAL) 01/25/08 STAIRWAYS, HANDRAILS, AND GUARDRAILS (RESIDENTIAL) City of Austin International Residential Code: 500 Fourth Avenue NE R314.1 Width. Stairways shall not be less than 36 in clear width at all points

More information

TENTS AND OTHER MEMBRANE STRUCTURES

TENTS AND OTHER MEMBRANE STRUCTURES CHAPTER 31 TENTS AND OTHER MEMBRANE STRUCTURES SECTION 3101 GENERAL 3101.1 Scope. Tents and membrane structures shall comply with this chapter. The provisions of Section 3103 are applicable only to temporary

More information

311.7 Stairways Width Headroom. Exception: Walkline Stair treads and risers Tread depth.

311.7 Stairways Width Headroom. Exception: Walkline Stair treads and risers Tread depth. 311.7 Stairways. 311.7.1 Width. Stairways shall not be less than 36 inches (914 mm) in clear width at all points above the permitted handrail height and below the required headroom height. Handrails shall

More information

This worksheet must be signed by the architect or engineer of record for the entire project for commercial or mixed-use buildings.

This worksheet must be signed by the architect or engineer of record for the entire project for commercial or mixed-use buildings. Application - City of Oxnard WORKSHEET FOR COMMERCIAL PLAN REVIEWS This worksheet must be signed by the architect or engineer of record for the entire project for commercial or mixed-use buildings. Note:

More information

Code Technology Committee Area of Study Climbable Guards

Code Technology Committee Area of Study Climbable Guards Code Technology Committee Area of Study Climbable Guards 2009/2012 Cycle Code changes related to the CTC area of study noted above The following are code changes related to the CTC Climbable Guards Area

More information

Worksheet for Commercial Building Planning

Worksheet for Commercial Building Planning Worksheet for Commercial Building Planning Note: This checklist helps ensure that all major code items were checked BEFORE applying for permit. ADDRESS OF PROJECT: Chapter 3 Information 301-312 OCCUPANCY

More information

1997 Uniform Building Code To 2003 International Building Code Cross Reference Table

1997 Uniform Building Code To 2003 International Building Code Cross Reference Table 1997 Uniform Building Code To 2003 International Building Code Cross Reference Table [Updated from 1997 Uniform Building Code to 2000 International Building Code 1 Cross Reference Table Published by the

More information

E2-09/ (IFC [B] )

E2-09/ (IFC [B] ) Code Technology Committee 2010 Final Action Agenda The following are code changes and public comments to be considered at the 2010 Dallas Final Action Hearings that are related to the CTC Area of Study

More information

-=== Building Safety Departnlent 'Neil Avenue, Room 202 Cheyenne, WY Phone: (307) Fax: (307) RAMPS

-=== Building Safety Departnlent 'Neil Avenue, Room 202 Cheyenne, WY Phone: (307) Fax: (307) RAMPS Building Safety Departnlent 2101 0 'Neil Avenue, Room 202 Cheyenne, WY 82001 Phone: (307) 637-6265 Fax: (307) 637-6366 A COMMUNITY -=== II January 24,2017 OF CHOICE RAMPS This handout was prepared in an

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 1005 MEANS OF EGRESS SIZING [B] 1005.1 General. All portions of the means of egress system shall be sized in accordance with this section. Exception: Means of egress complying with Section 1028.

More information

COMMUNITY RISK REDUCTION BUREAU MANUAL CODE REQUREMENTS TEMPORARY TENTS AND MEMBRANE STRUCTURES EFFECTIVE: APRIL 1, 2016 AUTHORIZED: R.

COMMUNITY RISK REDUCTION BUREAU MANUAL CODE REQUREMENTS TEMPORARY TENTS AND MEMBRANE STRUCTURES EFFECTIVE: APRIL 1, 2016 AUTHORIZED: R. COMMUNITY RISK REDUCTION BUREAU MANUAL CODE REQUREMENTS 423.7 TEMPORARY TENTS AND MEMBRANE STRUCTURES EFFECTIVE: APRIL 1, 2016 AUTHORIZED: R. Pearce SCOPE This policy applies to temporary tents, air-supported,

More information

Project Address Applicant: (Please Print) Plan review Engineer: Phone: Date

Project Address Applicant: (Please Print) Plan review Engineer: Phone: Date BUILDING AND SAFETY Tenant Improvement Checklist Project Address Applicant: (Please Print) Plan review Engineer: Phone: Date APPLICATION The following items will be required at the permit counter before

More information

2015 IBC Update. Copyright 2014 International Code Council #1000PDF15 1

2015 IBC Update. Copyright 2014 International Code Council #1000PDF15 1 Goal 2015 IBC Update Based on the International Building Code (IBC ) The goal is to familiarize building officials, fire officials, plans examiners, inspectors, design professionals, contractors, and others

More information

Applying the Building Code During Design

Applying the Building Code During Design Applying the Building Code During Design A Step-By-Step Process AIA Learning Units The Salt Lake City CSI Chapter is a Registered Provider with The American Institute of Architects Continuing Education

More information

TENTS AND OTHER MEMBRANE STRUCTURES

TENTS AND OTHER MEMBRANE STRUCTURES CHAPTER 24 TENTS AND OTHER MEMBRANE STRUCTURES SECTION 2401 GENERAL 2401.1 Scope. Tents and membrane structures shall comply with this chapter. The provisions of Section 2403 are applicable only to temporary

More information

RESIDENTIAL STAIRWAYS, HANDRAILS,

RESIDENTIAL STAIRWAYS, HANDRAILS, City Of Austin 500 Fourth Avenue N.E. Austin, Minnesota 55912-3773 Building Department 507-437-9950 Fax 507-437-7101 RESIDENTIAL STAIRWAYS, HANDRAILS, *A Building permit is required for any alteration

More information

BCAC MOE list of changes to consider PC June 5, 2018

BCAC MOE list of changes to consider PC June 5, 2018 BCAC MOE list of changes to consider PC June 5, 2018 IBC 10-4/IRC 3-1 - EERO E108-D not an errata like Jeff Inks said E109-D committee confused this size with door allowances IBC 10-7 delayed egress locks

More information

SAFEGUARDS DURING CONSTRUCTION

SAFEGUARDS DURING CONSTRUCTION CHAPTER 14 SAFEGUARDS DURING CONSTRUCTION SECTION 1401 GENERAL [B] 1401.1 Scope. The provisions of this chapter shall govern safety during construction that is under the jurisdiction of this code and the

More information

CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY DRAFT. FLORIDA BUILDING CODE BUILDING, 5th EDITION (2014) 4.1

CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY DRAFT. FLORIDA BUILDING CODE BUILDING, 5th EDITION (2014) 4.1 CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,

More information

TENTS CANOPIES AND OTHER MEMBRANE STRUCTURES

TENTS CANOPIES AND OTHER MEMBRANE STRUCTURES CHAPTER 24 TENTS CANOPIES AND OTHER MEMBRANE STRUCTURES SECTION 2401 GENERAL 2401.1 Scope. Tents, canopies and membrane structures shall comply with this chapter. The provisions of Section 2403 are applicable

More information

Municipal Code of Chicago CHAPTER EXIT REQUIREMENTS

Municipal Code of Chicago CHAPTER EXIT REQUIREMENTS Municipal Code of Chicago CHAPTER 13-160 EXIT REQUIREMENTS 13-160-010 General provisions. 13-160-020 Definitions. 13-160-030 Exit types - Requirements. 13-160-040 Exit types - Above or below grade. 13-160-050

More information

&02.1. Level 3 Alterations. Level 3 Alterations shall comply with Sections & and &

&02.1. Level 3 Alterations. Level 3 Alterations shall comply with Sections & and & &01 GENERAL To be developed. All of the exceptions have to be coordinated. &02 SPECIAL USE AND OCCUPANCY &02.1. Level 3 Alterations. Level 3 Alterations shall comply with Sections &02.1.1 and &02.1.2.

More information

TENTS AND MEMBRANE STRUCTURES

TENTS AND MEMBRANE STRUCTURES CHAPTER 24 TENTS AND MEMBRANE STRUCTURES SECTION 2401 GENERAL 2401.1 Scope. Tents and membrane structures shall comply with this chapter. The provisions of Section 2403 are applicable only to temporary

More information

JC Code & Construction Consultants, Inc. Advanced 2010 FBC Update Ch. 1 to 16

JC Code & Construction Consultants, Inc. Advanced 2010 FBC Update Ch. 1 to 16 JC Code & Construction Consultants, Inc. Advanced 2010 FBC Update Ch. 1 to 16 Welcome! This course is designed to provide an overview of the most significant changes to the 2010 edition of the Florida

More information

INTERNATIONAL BUILDING CODE MEANS OF EGRESS

INTERNATIONAL BUILDING CODE MEANS OF EGRESS INTERNATIONAL BUILDING CODE MEANS OF EGRESS E1-09/10 1001.4 (New) (IFC [B] 1001.4 (New)) Proposed Change as Submitted Proponent: Paul K. Heilstedt, PE, FAIA, Chair, representing ICC Code Technology Committee

More information

MVRTA Newburyport Intermodal Parking Facility Newburyport, Massachusetts

MVRTA Newburyport Intermodal Parking Facility Newburyport, Massachusetts PARKING CONSULTANTS GREEN PARKING CONSULTING PLANNERS ARCHITECTS STRUCTURAL ENGINEERS RESTORATION ENGINEERS MVRTA Newburyport Intermodal Parking Facility Newburyport, Massachusetts Code Analysis 12/9/2016

More information

SUMMARY OF FIRE SPRINKLER REQUIREMENTS FOR ALTERATIONS TO EXISTING BUILDINGS 2015 I-Codes

SUMMARY OF FIRE SPRINKLER REQUIREMENTS FOR ALTERATIONS TO EXISTING BUILDINGS 2015 I-Codes SUMMARY OF FIRE SPRINKLER REQUIREMENTS FOR ALTERATIONS TO EXISTING BUILDINGS 2015 I-Codes SCOPE: The City of Lawrence requirements for application of current code provisions. This shall apply to alterations

More information

Comparison of the life safety elements of the 1997 UBC and the IBC 2000.

Comparison of the life safety elements of the 1997 UBC and the IBC 2000. Comparison of the life safety elements of the 1997 UBC and the IBC 2000. Introduction The Building Performance Research Institute s mission is primarily one of education on building safety and performance.

More information

COMMUNITY & DEVELOPMENT SERVICES 840 Northgate Drive, Richland, WA Phone: Fax:

COMMUNITY & DEVELOPMENT SERVICES 840 Northgate Drive, Richland, WA Phone: Fax: WORKSHEET FOR COMMERCIAL PLAN REVIEWS THIS WORKSHEET MUST BE SIGNED (AT END OF DOCUMENT) BY THE ARCHITECT OR ENGINEER OF RECORD FOR THE ENTIRE PROJECT (SEC. 106.3.4) FOR ALL COMMERCIAL OR MIXED-USE BUILDINGS

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary Chapter 10: Means of Egress General Comments The general criteria set forth in Chapter 10 regulating the design of the means of egress are established as the primary method for protection of people in

More information

Appendix GENERAL INFORMATION TECHNICAL INFORMATION BUILDING CODES INDEX

Appendix GENERAL INFORMATION TECHNICAL INFORMATION BUILDING CODES INDEX Appendix GENERAL INFORMATION TECHNICAL INFORMATION BUILDING CODES INDEX Building Codes Building Codes Prior to using any railing products, it is incumbent on designers, fabricators and installers to make

More information

GENERAL BUILDING HEIGHTS AND AREAS

GENERAL BUILDING HEIGHTS AND AREAS CHPTER GENERL BUILDING HEIGHT ND RE ECTION 0 GENERL 0. cope. The provisions of this chapter control the height and area of structures hereafter erected and additions to existing structures. [F] 0. ddress

More information

Advanced FBC: Significant Changes to the 5 th Edition (2014) Florida Building Code, Building and Residential. presented by

Advanced FBC: Significant Changes to the 5 th Edition (2014) Florida Building Code, Building and Residential. presented by Advanced FBC: Significant Changes to the 5 th Edition (2014) Florida Building Code, Building and Residential presented by T. Eric Stafford T. Eric Stafford & Associates, LLC This material is protected

More information

Americans with Disabilities Act Accessibility Survey

Americans with Disabilities Act Accessibility Survey Americans with Disabilities Act Accessibility Survey Self-Evaluation and Transition Plan Sarpy County Impound Facility 14242 S. 156th St. Springfield, Nebraska 68159 Prepared by Sarpy County Facilities

More information

TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES

TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES CHAPTER 24 TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES SECTION 2401 GENERAL 2401.1 Scope. Tents, canopies and membrane structures shall comply with this chapter. The provisions of Section 2403 are applicable

More information

City of Des Moines. Permit and Development Center 602 Robert D Ray Drive Des Moines, IA Phone: Fax:

City of Des Moines. Permit and Development Center 602 Robert D Ray Drive Des Moines, IA Phone: Fax: City of Des Moines Permit and Development Center 602 Robert D Ray Drive Des Moines, IA 50309 Phone: 515-283-4200 Fax: 515-283-4270 This Code Analysis Form must be completed and returned with the Building

More information

EFFECTIVE USE OF THE IBC/CBC

EFFECTIVE USE OF THE IBC/CBC Distilling the code review process down to a methodical, sequential list of considerations is generally problematic. In many cases, related provisions from various chapters of the code must be considered

More information

Stairs have many potential violations this Newsletter is Part 1 of two parts.

Stairs have many potential violations this Newsletter is Part 1 of two parts. Stairs have many potential violations this Newsletter is Part 1 of two parts. Violation 1 : Risers do not meet requirements: riser heights too high/low; too much variation between riser heights; risers

More information

GENERAL BUILDING HEIGHTS AND AREAS

GENERAL BUILDING HEIGHTS AND AREAS CHPTER GENERL BUILDING HEIGHT ND RE ECTION 0 GENERL 0. cope. The provisions of this chapter control the height and area of structures hereafter erected and additions to existing structures. [F] 0. ddress

More information

BUILDING CODE VARIANCE

BUILDING CODE VARIANCE BUILDING CODE VARIANCE April 2009 06-BCV-011-R1 Page 1 of 8 DISCUSSION MULTI-LEVEL STORAGE RACKING SYSTEMS The Alberta Building Code 2006 contains no specific requirements for multi-level storage racking

More information

2009 IBC Section 1024 Approved Luminous Egress Path Markings

2009 IBC Section 1024 Approved Luminous Egress Path Markings 2009 IBC Section 1024 Approved Luminous Egress Path Markings Where Required Buildings of Groups A (Assembly), B (Business), E (Education), I (Institutional), M (Mercantile) and R-1 (Residential transient

More information

SPECIAL CONSTRUCTION

SPECIAL CONSTRUCTION CHAPTER 31 SPECIAL CONSTRUCTION SECTION 3101 GENERAL 3101.1 Scope. The provisions of this chapter shall govern special building construction including membrane structures, temporary structures, pedestrian

More information

Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617)

Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) Code Requirements for Existing Buildings R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS) was established in 1945 and currently

More information

SPECIAL / OUTDOOR EVENTS REQUIREMENTS

SPECIAL / OUTDOOR EVENTS REQUIREMENTS SPECIAL / OUTDOOR EVENTS REQUIREMENTS The following requirements apply to outdoor and special events, including the use of tents at such events. Permits must be approved by zoning and 3 sets of site plans

More information

Description Accessibility Standards. University of Toronto

Description Accessibility Standards. University of Toronto Ramps The ramp must have a minimum clear width of 900 mm. The ramp must have a clear height that provides a minimum headroom clearance of 2,100 mm above the ramp. The surface of the ramp must be firm and

More information

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck)

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck) SECTION 13125 ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck) PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Description Accessibility Standards. AODA OBC 2015 Ramps

Description Accessibility Standards. AODA OBC 2015 Ramps Ramps OBC Ammendments are related to the following accessibility standards: The ramp must have a minimum clear width of 900 mm. The ramp must have a clear height that provides a minimum Tactile Attention

More information

APPLICATION NUMBER:, TAX MAP KEY: STREET ADDRESS:, PRPOJECT: APPLICANT:, PHONE NO: MAILING ADDRESS:, FAX NO:

APPLICATION NUMBER:, TAX MAP KEY: STREET ADDRESS:, PRPOJECT: APPLICANT:, PHONE NO: MAILING ADDRESS:, FAX NO: COUNTY OF KAUAI BUILDING DIVISION, DEPARTMENT OF PUBLIC WORKS 4444 RICE STREET, SUITE 175, LIHUE, HAWAII 96766 Telephone: (808) 241-6655 Fax Number: (808) 241-6806 BUILDING CODE COMMERCIAL CHECKLIST APPLICATION

More information

FRAMING INSPECTION GENERAL

FRAMING INSPECTION GENERAL FRAMING INSPECTION GENERAL 20 FRAMING INSPECTION GENERAL Tips Check habitable rooms for minimum light, ventilation and sanitation requirements. Check that stair framing meets headroom, width, and rise

More information

HOUSING CONVERSION Guidelines for the conversion of a house to commercial use.

HOUSING CONVERSION Guidelines for the conversion of a house to commercial use. PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT HOUSING CONVERSION Guidelines for the conversion of a house to commercial use. HAIR 105 January 2017 contents General Information 3 Zoning Information 4 Building

More information

1301: Individual canopies having a maximum size of 700 square feet (65 m 2 ).

1301: Individual canopies having a maximum size of 700 square feet (65 m 2 ). ACTION: Withdraw Proposed DATE: 06/10/2005 9:49 AM 1301:7-7-24 Tents and other membrane structures. (A) Section 2401 General (1) 2401.1 Scope. Tents, canopies and membrane structures shall comply with

More information

9/20/2016 4:01 PM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

9/20/2016 4:01 PM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement of 28 9/20/2016 4:01 PM Second Revision No. 5502-NFPA 101-2016 [ New Section after 36.2.1.5 ] 36.2.1.6 Grab Bars for Bathtubs, Bathtub-Shower Combinations, and Showers. 36.2.1.6.1 Where bathtubs, bathtub-shower

More information

2006 to 2012 IBC. Significant Changes

2006 to 2012 IBC. Significant Changes 2006 to 2012 IBC Significant Changes 1. Addition 303.3 Assembly Group A 2. Assembly uses intended for food and/or drink consumption including, but not limited to: Banquet halls Casinos (gaming areas) added

More information

The Building Codes A.R.E. Building Design and Construction Exam Prep

The Building Codes A.R.E. Building Design and Construction Exam Prep Know Thy Codes! The Building Codes Building Codes The Code of Hammurabi 4000bc Developed 19 th and 20 th c. Codes define what you can and can t do Allowable area and height based on degree of danger Fire

More information

EXIT ACCESS RAMP. An interior ramp that is not a required interior exit ramp.

EXIT ACCESS RAMP. An interior ramp that is not a required interior exit ramp. Coordination with language throughout code 10/05/2011 Stair vs. stairway Repetitive language with stairways and ramps Including ramps when applicable The locations for stair, stairway and ramp as used

More information

BRADYGLO EMERGENCY EGRESS MARKING HANDBOOK

BRADYGLO EMERGENCY EGRESS MARKING HANDBOOK BRADYGLO EMERGENCY EGRESS MARKING HANDBOOK BRADYGLO EMERGENCY EGRESS MARKING HANDBOOK Table of Contents Introduction to Code Changes...2 2009 International Building Code and International Fire Code...3

More information

Advanced Studies of the International Building Code. Presented by Steve Thomas, Colorado Code Consulting, LLC

Advanced Studies of the International Building Code. Presented by Steve Thomas, Colorado Code Consulting, LLC Advanced Studies of the International Building Code Presented by Steve Thomas, Colorado Code Consulting, LLC Advanced Studies of the International Building Code Instructor Steve Thomas, CBO President,

More information

Learning Objectives. Copyright Materials NONSTRUCTURAL PROVISIONS FOR MULTI STORY WOOD FRAMED BUILDINGS 2009 WASHINGTON STATE BUILDING CODE (WSBC )

Learning Objectives. Copyright Materials NONSTRUCTURAL PROVISIONS FOR MULTI STORY WOOD FRAMED BUILDINGS 2009 WASHINGTON STATE BUILDING CODE (WSBC ) NONSTRUCTURAL PROVISIONS FOR MULTI STORY WOOD FRAMED BUILDINGS 2009 WASHINGTON STATE BUILDING CODE (WSBC ) Prepared dfor Wood dproducts Council WoodWorks Presented by James E. Churchill, P.E. ChurchillEngineering

More information