Acoustic design of industrial spaces. The reduction of noise levels and increase of production

Size: px
Start display at page:

Download "Acoustic design of industrial spaces. The reduction of noise levels and increase of production"

Transcription

1 Acoustic design of industrial spaces The reduction of noise levels and increase of production

2 Contents. Introduction. Acoustic measurements Effect of acoustical treatment with suspended ceiling and wall panels > Acoustic design with wall panels > Positioning of wall panels > Case study 4. Case Study: Oatly Health Products Facility > Room > Activity > Acoustic design > Room acoustic measurements > Results > Additional actions 6. Appendix Results of measurements before and after

3 Introduction The main purpose of acoustic design in industrial spaces is usually to reduce the overall noise levels. In addition acoustic treatment with sound absorbers with good high frequency absorption gives increased speech intelligibility and better directional hearing, making it easier to hear the location of different sound sources. This document explores the key measurement criteria, the effects of adding absorption to a space and demonstrates through a case study what can be achieved in real world applications. Before acoustic design it is recommended to interview the staff and identify the main acoustic problems and how noise affects the people working there. Besides the acoustics, it is also important to establish if other demands have to be fulfilled, for example cleaning or hygiene criteria. Once the key objectives have been defined, appropriate acoustic treatments can be developed to meet the specific challenges of the project. By lowering the noise levels, decreasing the reverberation time and increasing the speech intelligibility the acoustic comfort in the space will be improved, which studies have shown will have a positive effect on staff wellbeing. Before acoustic design it is recommended to interview the staff and identify the main acoustic problems and how noise affects the people working there. The main purpose of acoustic design in industrial spaces is usually to reduce the overall noise levels.

4 Acoustic Measurements To objectively measure the acoustic conditions in an industrial space several room acoustic parameters have to be measured. It s common to measure parameters related to reverberance, sound strength and speech clarity. The parameters are described in table. TABLE Parameter Designation Unit Explanation Standard Reverberation time T s Speed at which sound disappears ISO 8-/ Speech Clarity C5 or D db or % Measure the perception of speech in a room. If these values increase the speech intelligibility increases. ISO 8-/ To objectively measure the acoustic conditions in an industrial space several room acoustic parameters have to be measured. Sound level decrease L db Measure the decrease in sound pressure level

5 Effect of acoustical treatment with suspended ceiling and wall panels It s very important to keep in mind that acoustical treatment with acoustic suspended ceilings and wall absorbers in industrial spaces mainly influences the general noise level. The sound field normally consists of direct sound and a reverberant sound. The direct part reaches the operators ears without hitting the room surfaces. Thus, this part is not affected by the acoustic ceiling and wall panels. To decrease the direct sound you often have to use screens, hoods or changing the mechanical process that generates the sound. The sound level that originates from the reverberant sound will be affected by the absorbing ceiling and wall panels. A realistic goal concerning the reduction of the db(a) level in the reverberant field by adding porous absorbers is in the region 5 to db(a). The perception of change in sound pressure level is given in table. TABLE Changes in sound level Subjective perception Only the noise that originates from the reverberant sound will be affected by the absorbing ceiling and wall panels. db Reduction or increase is hardly perceivable 5 db Reduction or increase is clearly perceivable db Reduction or increase results in halving or doubling of perceived sound level

6 The effect of added absorption in an industrial space is illustrated in Figure. The effect of the acoustic treatment depends on the amount of absorption before treatment. In Figure the effect of additional absorption is measured by the reverberation time. If the space is very reverberant and consequently has a long reverberation time, the effect of added absorption will be higher compared to a space with shorter reverberation time. In Figure below the effect of added absorption is calculated for an industrial space with floor area 5 m and for two different ceiling heights. The room without added absorbers is supposed to have a reverberation time of seconds. The alpha w for the added absorbers is.95. When the amount of added absorbers exceeds the floor area it is assumed that the absorbers are attached to the walls. Figure refers to an industrial space with a volume of m. 8 Sound level reduction db Added amount of absorbers (m) alphaw=.95 (Class A) 4s s s Sound level reduction db ceiling height 4.5 m, floor area 5 m ceiling height 8. m, floor area 5 m Added amount of absorbers (m). Figure. The effect of added absorbers on the sound level in a room with a volume of m. The figures in the diagram refer to the reverberation time before acoustical treatment. Figure. The sound reduction in an industrial space with a floor area of 5 m and for two different ceiling heights. 4

7 stdev 9 8 Sound level reduction db ceiling height 4.5 m, floor area 5 m ceiling height 8m, floor area 5 m Added amount of absorbers (m).,5, K K 4K [Hz] Figure. The sound reduction in an industrial space with a floor area of 5 m and for two different ceiling heights. Figure 4. Reverberation time for the octave-band frequencies 5 to 4 Hz measured in a food factory before acoustic treatment It s common in industrial spaces that the reverberation time at low frequencies is lower than the reverberation time at high frequencies. This is illustrated in figure 4. The factory in this case is a food producer and the volume of the space is 576 m. This also means that acoustic treatment with porous absorbers will be very efficient since there is a lot of high frequency energy that will be absorbed by the absorbing ceiling and wall panels. It s not uncommon in industrial spaces that the reverberation time at low frequencies are lower than the reverberation time at high frequencies. 5

8 Acoustic design with wall panels From an acoustic point of view it s often advantageous to locate the absorbing material as close to the noise sources as possible. In this case an acoustic wall panel may be useful. If there is a risk for mechanical impact the panel could be protected by a cage. Normally, the wall panels works as a complement to a suspended ceiling. Positioning of wall panels The reduction of sound pressure level is related to the amount of absorbing material that is added to the room. When reducing sound pressure, the location of absorbers is of minor importance. However, when we are concerned with reducing reverberation time and improving speech clarity the distribution of the absorbers is important. Even a small quantity of wall panels in a room with absorbent ceiling could have a great influence on reverberation time and speech clarity. It s preferable to cover two adjacent walls with panels rather than two parallel walls to have the greatest effect on reducing reverberation within a room. The reduction of sound pressure level is related to the amount of absorbing material that is added to the room. Field study In the appendix the effect of acoustic treatment with a suspended ceiling and wall panels is shown for a factory building. The effect of acoustic treatment with a suspended ceiling and wall panels is shown for a factory building. 6

9 Case Study: Oatly Health Products Facility Oatly manufacture lactose-free oat based drinks that are consumed as a healthy alternative to milk. The company prides itself on its entrepreneurial spirit, curiosity and friendliness, often welcoming visitors to their factory located in Landskrona, Sweden. However, as with most industrial processes, the production facilities were noisy which was creating welfare issues for both staff and visitors. Employee issues: Table Property Designation Parameter Explanation Reverberance EDT, T Early decay time (s), Reverberation time (s) Speed at which sound disappears. A shorter reverberation time means that the room is perceived as more damped. > Complaints from employees about the noise level > Use of hearing protection limited conversation and observations within teams > Increased stress levels made it hard to relax when at home > Some employees reported disturbed sleep Speech clarity Sound strength C5, D, RASTI L Speech Clarity (db), Definition (%), RASTI Sound level decrease (db) Measure the perception of speech in a room. If these values increase the speech intelligibility increases Measure the decrease in sound pressure level Room Oatly s factory in Landskrona, Sweden. Volume: BxLxH= 9m x 7m x 6m=458 m Activity Machinery (conveyor belt) food packaging. Acoustic design To lower the general noise in the room and to create more favourable Acoustics, Hygiene Performance mm tiles were attached to the ceiling (complete coverage) and Hygiene Performance 4 mm to areas on three walls (see photo). Room acoustic measurements Before acoustic treatment the environment was judged as noisy with difficulties perceiving speech and having a conversation. The main purpose of the room acoustic measurements was to establish the effect of the acoustic treatment on noise level and speech intelligibility. Figure. Placement of ceiling and wall absorbers in Oatly factory premises. Table shows the room acoustic parameters measured. A brief explanation of the parameters is also given in the table. 7

10 Table shows the average values of the room acoustic parameters for the octave band 5 Hz and Hz. According to ISO 8- this average is suitable as a representative value for the room acoustic parameters. The values are given before and after acoustic treatment. In appendix the values are given for the octave band 6 Hz to 4 Hz. Table Property Parameter Before treatment After treatment EDT (s),4 s,6 s Reverberance T (s),4 s,6 s Extra action As an additional measure to improve the acoustics in certain areas of the factory the wall absorber Ecophon Advance Protection C was used. The wall absorbers were mounted in the corridor between the long walls and machines, see Figure. The tiles were placed at head height and mounted in a grid for protection against mechanical damage. The purpose of the absorbers is to reduce the high noise levels caused by multiple reflections between the wall and machine. The noise level was measured at three positions along the corridor before and after installation of the wall absorbers and show a decrease in db (A) level of between and db. Decrease in Sound Strength L (db) - 5 db C5 (db) -,9 db,7 db Speech clarity D (%) 4 % 7 % RASTI,47 (poor/fair),7 (good) Results Table shows that after the acoustic treatment, the noise level (general noise) in the room dropped by about 5 db. Before treatment the general noise level in the room was in the region 8-84 db(a) (Industrial Health measurements 98). After treatment the general noise level dropped to about 77 db(a) which means that the levels are below the action values according to Arbetsmiljöverket set (AFS 5:6). The values of speech perception also show a clear improvement. One reason for this is that the influence of so-called late reflections in the room has been reduced. Also the reverberation times decreased significantly. In the vicinity of some machines, the noise level is still above 8 db(a). This is because the direct sound from the machines dominate. Direct sound is not affected by the ceiling and wall absorbers, but must be addressed with direct measures of the sound source such as encapsulation or enclosure. Figure. Wall absorber Advance Protection C placed at head height along the walkways. Examples of spontaneous comments from staff after acoustic treatment were: > easier to hear what is said > easier to detect where the sound comes from > nice not having to wear hearing protection > not so tired when I get home, sleep better 8

11 Appendix Results of measurements before and after Measurement results in octave bands before and after treatment EDT (s) T (S),5 Early decay time (s),5,5 Reverberation (S),5,5, Frequency (Hz) Frequency (Hz) EDT (S) Before EDT (S) After T (S) Before T (S) After EDT [s] T [s] Before After Before After 6,, 5,,9 5,8,7 5,,6,4,6,9,6 4,6,7 6,6,5 5,7, 5,,8 5,5,6,4,6,9,6 4,7,6 9

12 L (db) C5 (db) Reduction in Sound Pressure (db) Speech Clarity db Frequency (Hz) - -4 AL [db] Frequency (Hz) C5 (db) Before C5 (db) After ΔL [db] 6,5 5, 5, 5 5,8 4,7 4, 4,5 4,6 C5 [db] Before After 6,,6 5,,6 5 -,,6 5 -,4,6 -,5,8 -,9, 4 -,,4

REPORT SUNDBYBERG KOMMUNHUS, EVALUATION OF OPEN PLAN OFFICES ACC. TO ISO

REPORT SUNDBYBERG KOMMUNHUS, EVALUATION OF OPEN PLAN OFFICES ACC. TO ISO REPORT SUNDBYBERG KOMMUNHUS, EVALUATION OF OPEN PLAN OFFICES ACC. TO ISO 3382-3 2014-09-03 Project: 253520, Sundbyberg, mätning av rumsakustiska parametrar enligt SS-EN 3382-3 Report title: Version: Date:

More information

ACOUSTIC DESIGN OF THE AUDITORIUM IN THE CHURCH OF RISPESCIA

ACOUSTIC DESIGN OF THE AUDITORIUM IN THE CHURCH OF RISPESCIA ACOUSTIC DESIGN OF THE AUDITORIUM IN THE CHURCH OF RISPESCIA Sergio Luzzi and Lucia Busa Vie en.ro.se. ingegneria, Via Stradivari, 19, 50127 Florence, Italy email: sergio.luzzi@vienrose.it The authors

More information

Custom Audio Designs Ltd

Custom Audio Designs Ltd Understanding the New BB93 Acoustics in Schools Recent studies have shown that many classrooms have poor acoustics. As a result, children with normal hearing are often unable to make out what is being

More information

Noise reduction. in the pharmaceutical industry. Fiskeri/Engelsviken fotas

Noise reduction. in the pharmaceutical industry. Fiskeri/Engelsviken fotas Noise reduction in the pharmaceutical industry Fiskeri/Engelsviken fotas An acoustic wall to wall ceiling decreases the sound spreading from production equipment, creating better working conditions at

More information

Noise reduction. in the electronics industry

Noise reduction. in the electronics industry Noise reduction in the electronics industry Room Acoustic Comfort in industrial premises Less noise creates a calm, pleasant atmosphere, and provides a higher degree of safety. Room Acoustic Comfort is

More information

IndustrY special FOR SUSTAINABLE DESIGN. Better acoustic environment in industry and catering with strict hygiene requirements

IndustrY special FOR SUSTAINABLE DESIGN. Better acoustic environment in industry and catering with strict hygiene requirements IndustrY special FOR SUSTAINABLE DESIGN Better acoustic environment in industry and catering with strict hygiene requirements Better acoustic environment in industry and catering with strict hygiene requirements

More information

The objective is to achieve room acoustics conditions that correspond to the intended use and ensure appropriate user comfort.

The objective is to achieve room acoustics conditions that correspond to the intended use and ensure appropriate user comfort. SOC1.3 Acoustic comfort Objective The objective is to achieve room acoustics conditions that correspond to the intended use and ensure appropriate user comfort. Benefits Good acoustic conditions are an

More information

Relationship between flanking noise through a common ceiling plenum and plenum absorption George van Hout, John Pearse and Brian Donohue

Relationship between flanking noise through a common ceiling plenum and plenum absorption George van Hout, John Pearse and Brian Donohue Proceedings of ACOUSTICS 2016 9-11 November 2016, Brisbane, Australia Relationship between flanking noise through a common ceiling plenum and plenum absorption George van Hout, John Pearse and Brian Donohue

More information

Association of Australian Acoustical Consultants Guideline for Commercial Building Acoustics. May 2011

Association of Australian Acoustical Consultants Guideline for Commercial Building Acoustics. May 2011 Association of Australian Acoustical Consultants Guideline for Commercial Building Acoustics TABLE OF CONTENTS 1.0 INTRODUCTION... 3 2.0 OBJECTIVES... 3 3.0 CRITERIA... 5 2 1.0 INTRODUCTION Members of

More information

Introduction 1. The challenge of meeting both acoustic and thermal comfort in 21 st century school classrooms

Introduction 1. The challenge of meeting both acoustic and thermal comfort in 21 st century school classrooms The challenge of meeting both acoustic and thermal comfort in 21 st century school classrooms Colin Campbell (1), Holger Brokmann (2), Erling Nilsson (3) (1) Saint-Gobain Ecophon, Hyllinge, Sweden (2)

More information

4-Acoustics: Background

4-Acoustics: Background 4-Acoustics: Background In the past acoustics for buildings especially concert halls was done by luck. A design would be done that worked well and then it would be mimicked. Other times awful designs emerged

More information

Comparative Impact Performances of Lightweight Gym Floors

Comparative Impact Performances of Lightweight Gym Floors Comparative Impact Performances of Lightweight Gym Floors Lloyd Cosstick, Evan Hong and Tim Murray Embelton Noise and Vibration, Melbourne VIC 3058, Australia ABSTRACT Gyms are a common source of complaints

More information

Reverberation Time Design for IM Building Addition

Reverberation Time Design for IM Building Addition INTRAMURAL BUILDING Reverberation Time Design for IM Building Addition Project 1 Andrew Brouwers Kelly Cerri Melissa Consiglio Michael Devaney Kenna Markel March 20, 2014 Table of Contents Introduction......................................................

More information

ROOM ACOUSTICS DESIGN. Room Acoustics Design Intent Appropriate Articulation

ROOM ACOUSTICS DESIGN. Room Acoustics Design Intent Appropriate Articulation ROOM ACOUSTICS DESIGN (and continuing to look at OPR) http://mikebm.files.wordpress.com/2008/06/walt-disney-hall-1.jpg Ball State Architecture ENVIRONMENTAL SYSTEMS 1 Grondzik 1 Room Acoustics Design Intent

More information

IAC Acoustics Noise-Foil Sound Absorption Panels for Industrial Applications. Dan O Brien

IAC Acoustics Noise-Foil Sound Absorption Panels for Industrial Applications. Dan O Brien IAC Acoustics Noise-Foil Sound Absorption Panels for Industrial Applications Presented by Dan O Brien Industrial Business Unit Manager IAC Acoustics, A Division of Sound Seal 401 Airport Road North Aurora,

More information

SELWYN PRIMARY SCHOOL, LONDON ENVIRONMENTAL NOISE SURVEY

SELWYN PRIMARY SCHOOL, LONDON ENVIRONMENTAL NOISE SURVEY 202 Uxbridge Road London W12 7JP Tel: +44(0)203 475 2280 Fax: +44(0)203 475 2281 info@clementacoustics.co.uk www.clementacoustics.co.uk SELWYN PRIMARY SCHOOL, LONDON ENVIRONMENTAL NOISE SURVEY Report 8991-ENS-03

More information

Enhancing Acoustic Performance through the use of Window Shade Fabric White Paper

Enhancing Acoustic Performance through the use of Window Shade Fabric White Paper Enhancing Acoustic Performance through the use of Window Shade Fabric White Paper As architecture and design evolve, more demand can be seen for obtaining creative solutions for occupancy comfort. In designing

More information

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CASINO 600MM

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CASINO 600MM RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

Acoustical Data cloud softlight pendants

Acoustical Data cloud softlight pendants Acoustical Data cloud softlight pendants molo design, ltd 1470 Venables Street Vancouver, B.C. Canada V5L 2G7 t +1 604 696 2501 f +1 604 685 0342 info@molodesign.com www.molodesign.com cloud softlight

More information

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS EXPOSED NU SHADEX PERFORATED PLASTER CEILING TILES (600MM

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS EXPOSED NU SHADEX PERFORATED PLASTER CEILING TILES (600MM RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CELL AIR 1200MM

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF BAILEY INTERIORS CELL AIR 1200MM RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

Acoustics and Classrooms BARD MANUFACTURING COMPANY REGISTERED AIA PRESENTER VAUGHAN SMITH

Acoustics and Classrooms BARD MANUFACTURING COMPANY REGISTERED AIA PRESENTER VAUGHAN SMITH Acoustics and Classrooms BARD MANUFACTURING COMPANY REGISTERED AIA PRESENTER VAUGHAN SMITH Acoustics and Classrooms SOURCES OF NOISE ACOUSTICAL TERMS AND DEFINITIONS ANSI STANDARD OCCUPIED AND UNOCCUPIED

More information

Testing Procedure: AS ISO

Testing Procedure: AS ISO RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

Evaluation of a Modern Catholic Church by Acoustical Software Based on the Ray-Tracing Method

Evaluation of a Modern Catholic Church by Acoustical Software Based on the Ray-Tracing Method rychtarikova.qxd 11.8.2004 20:52 StrÆnka 21 RECEIVED 5. 6. 2003 ACCEPTED 15. 12. 2003 M. RYCHTÁRIKOVÁ, M. MUSABUDA, F. OHRABLO Evaluation of a Modern Catholic Church by Acoustical Software Based on the

More information

Achieving acoustical standards in the classroom Study of HVAC systems and classroom acoustics

Achieving acoustical standards in the classroom Study of HVAC systems and classroom acoustics Achieving acoustical standards in the classroom Study of HVAC systems and classroom acoustics Trane believes the facts and suggestions presented here to be accurate. However, final design and application

More information

21 ST CENTURY LEARNING ACOUSTICS. Steve Meszaros, M.Sc., P.Eng Acoustical Technical Director / Associate

21 ST CENTURY LEARNING ACOUSTICS. Steve Meszaros, M.Sc., P.Eng Acoustical Technical Director / Associate 21 ST CENTURY LEARNING ACOUSTICS Steve Meszaros, M.Sc., P.Eng Acoustical Technical Director / Associate Introduction Steve Meszaros B.Sc. (Mechanical Engineering) University of Manitoba M.Sc. (Biosystems

More information

Freight Rail Noise Policy and Practice

Freight Rail Noise Policy and Practice Freight and Logistics Council of Western Australia BULLETIN # 07 Introduction Bulletin No. 7 from the Freight and Logistics Council of Western Australia discusses recent research by the Council into freight

More information

Proceedings of Meetings on Acoustics

Proceedings of Meetings on Acoustics Proceedings of Meetings on Acoustics Volume 19, 2013 http://acousticalsociety.org/ ICA 2013 Montreal Montreal, Canada 2-7 June 2013 Noise Session 4aNSa: Effects of Noise on Human Performance and Comfort

More information

Pladur FON+ Systems. Acoustic conditioning solutions FON + Acoustic Solutions

Pladur FON+ Systems. Acoustic conditioning solutions FON + Acoustic Solutions Systems Acoustic conditioning solutions FON + Acoustic Solutions suspended ceilings The range of Pladur FON + perforated suspended ceiling are unique in terms of their design and features: Improving acoustic

More information

ACOUSTIC METAL CEILINGS

ACOUSTIC METAL CEILINGS ACOUSTIC METAL CEILINGS 2017 EDITION - NO. 2 up to 1 D n,f,w up to 53 db ALPHA ALPHA PLUS DECIBEL Enhanced performance Whole system supplied Wide choice of configurations Acoustic and stylish: solutions

More information

SoundScreen. Peace and quiet where you need it most

SoundScreen. Peace and quiet where you need it most Peace and quiet where you need it most You care about your home environment and your family. You want to create a comfortable, peaceful and safe home where you can enjoy life without the worry of noisy

More information

ACOUSTICS. Piano acoustic furniture

ACOUSTICS. Piano acoustic furniture 350 ACOUSTICS Piano acoustic furniture 351 PIANO ACOUSTIC Sound absorbing furniture Acoustics are essential in making our surroundings enjoyable by minimising noise, controlling reverberations and general

More information

KINETICS NOISE CONTROL TEST REPORT #AT001032

KINETICS NOISE CONTROL TEST REPORT #AT001032 KINETICS NOISE CONTROL TEST REPORT #AT001032 KINETICS NOISE CONTROL PRODUCTS: o ICC ACOUSTICAL RATINGS: o STC 84 o IIC 70 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B-3448.12 KINETICS DRAWING NUMBER:

More information

Sound Control Manual Sound Construction Room Acoustics

Sound Control Manual Sound Construction Room Acoustics Sound Control Manual Sound Construction Room Acoustics Acoustics is usually very broadly defined as "the science of sound." The term "Room Acoustics" can be more narrowly defined as the shaping and equipping

More information

Noise-Foil Acoustic Metal Panels Sound Absorption Systems for Industry & Commerce

Noise-Foil Acoustic Metal Panels Sound Absorption Systems for Industry & Commerce Noise-Foil Acoustic Metal Panels Sound Absorption Systems for Industry & Commerce Abuse resistant metal jacketed constructions Lab certified acoustic performances Suitable for interior and exterior installations

More information

Testing Procedure: AS ISO

Testing Procedure: AS ISO RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

SOUND ABSORBING SYSTEMS 2013

SOUND ABSORBING SYSTEMS 2013 SOUND ABSORBING SYSTEMS 2013 UNDERSTANDING + SOLUTIONS ACOUSTIC WELL-BEING silence screen silence wall silence cabinets sn silence silence parasta Keeping the noise at an acceptable level in offices has

More information

ATRIA IN SHOPPING CENTRES, OFFICE BUILDINGS AND HOSPITALS. E.Ph.J. de Ruiter. Adviesbureau Peutz & Associés BV., The Hague, Holland

ATRIA IN SHOPPING CENTRES, OFFICE BUILDINGS AND HOSPITALS. E.Ph.J. de Ruiter. Adviesbureau Peutz & Associés BV., The Hague, Holland ATRIA IN SHOPPING CENTRES, OFFICE BUILDINGS AND HOSPITALS E.Ph.J. de Ruiter Adviesbureau Peutz & Associés BV., The Hague, Holland 1 Introduction A growing number of buildings are being provided with large,

More information

The attached report includes:

The attached report includes: Customer Name: Wood Shop, Inc. Location: 123 Main St. Chaska, MN 55375 Dates: Data Gathered: 8/14/12 Report Provided: 9/4/12 Service: Validation Report Cover Letter (this page) The following information

More information

Acoustics and sound reinforcement issues in a modern-style basilica

Acoustics and sound reinforcement issues in a modern-style basilica Acoustics and sound reinforcement issues in a modern-style basilica Marko Horvat, Kristian Jambrošić, Hrvoje Domitrović University of Zagreb, Faculty of Electrical Engineering and Computing, Zagreb, Croatia

More information

Applied Noise Control. D. W. Herrin, Ph.D., P.E. University of Kentucky Department of Mechanical Engineering

Applied Noise Control. D. W. Herrin, Ph.D., P.E. University of Kentucky Department of Mechanical Engineering D. W. Herrin, Ph.D., P.E. Department of Mechanical Engineering Outline of Topics 1. Introduction 2. Noise Control at Source 3. Noise Control of Transmission Path 4. Protection at Receiver 5. Summary 2

More information

Hospitals Soundproofing. Hospital Soundproofing & Soundproofing Solutions

Hospitals Soundproofing. Hospital Soundproofing & Soundproofing Solutions Hospitals Soundproofing Hospital Soundproofing & Soundproofing Solutions Hospital Soundproofing Clean room environments impose sanitation constraints diametrically opposed to the basic construction of

More information

Introduction to Acoustics:

Introduction to Acoustics: Introduction to Acoustics: How I Learned to Stop Worrying and Love the Sound Level Meter Samantha Rawlings, LEED AP BD+C For IFMA New Mexico 07.14.2015 Veneklasen Associates INTRODUCTION Consultants in

More information

Equipment Floor Plan. Page 138

Equipment Floor Plan. Page 138 Acoustical Breadth The acoustical breadth scope was to analyze the existing conditions in the wood shop classroom and surrounding areas on the lower level of the building. The criteria used to evaluate

More information

Kinetics Noise Control

Kinetics Noise Control Kinetics Noise Control Acoustical Curtain Systems www.kineticsnoise.com Acoustical Curtain Systems Kinetics Noise Control s acoustical curtain systems are custom engineered to your application for acoustic

More information

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF 2MM ECHOPANEL WALL TESTED WITH NO AIR GAP MEASURED IN A REVERBERATION ROOM.

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF 2MM ECHOPANEL WALL TESTED WITH NO AIR GAP MEASURED IN A REVERBERATION ROOM. RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

UNDERSTANDING SOUND/NOISE

UNDERSTANDING SOUND/NOISE UNDERSTANDING SOUND/NOISE Noise has been an environmental issue throughout the ages. Ancient Romans complained about chariots rattling on cobble stone roadways. Renaissance metal smiths often lost their

More information

THE FRAME RESIDENTIAL DEVELOPMENT, SPORTCITY, MANCHESTER THE CONCRETE CENTRE LTD 1.0 INTRODUCTION...2

THE FRAME RESIDENTIAL DEVELOPMENT, SPORTCITY, MANCHESTER THE CONCRETE CENTRE LTD 1.0 INTRODUCTION...2 Concrete Centre Limited The Frame Residential Development, Sport City, Manchester Sound Insulation Test Report 2 August 2005 PROJECT: CLIENT: The Frame Residential Development, Sportcity, Manchester Concrete

More information

Design of a standalone, modular test facility for measuring sound transmitted through a common ceiling plenum

Design of a standalone, modular test facility for measuring sound transmitted through a common ceiling plenum Design of a standalone, modular test facility for measuring sound transmitted through a common ceiling plenum Edward A. BARCLAY 1 ; Robin R. WAREING 2 ; John R. PEARSE 3 1, 2, 3 University of Canterbury,

More information

KINETICS NOISE CONTROL TEST REPORT #AT001021B

KINETICS NOISE CONTROL TEST REPORT #AT001021B KINETICS NOISE CONTROL TEST REPORT #AT001021B KINETICS NOISE CONTROL PRODUCTS: o ICW ACOUSTICAL RATINGS: o STC 76 o IIC 62 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B3463.13 KINETICS DRAWING NUMBER:

More information

KINETICS NOISE CONTROL TEST REPORT #AT001110

KINETICS NOISE CONTROL TEST REPORT #AT001110 KINETICS NOISE CONTROL TEST REPORT #AT001110 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o STC 53 o IIC 29 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o REPORT NO. A1-010601.1 o DATED:

More information

Determination of the sound reduction and sound absorption of a railroad noise barrier

Determination of the sound reduction and sound absorption of a railroad noise barrier TEST REPORT No. VTT-S-04940-14 October 29, 2014 Determination of the sound reduction and sound absorption of a railroad noise barrier Requested by: Soundim Oy TEST REPORT No. VTT-S-04940-14 1 (3) Requested

More information

NEW HOUSE RESIDENCE HALL CARNEGIE MELLON UNIVERSITY, OAKLAND, PA

NEW HOUSE RESIDENCE HALL CARNEGIE MELLON UNIVERSITY, OAKLAND, PA Acoustical Analysis: Design Objective The primary acoustical goal of space planning is to place noisy equipment as far as possible from noise sensitive areas. New House did everything possible to achieve

More information

Rectangular sound attenuator

Rectangular sound attenuator Rectangular sound attenuator Description The type sound attenuator was designed to fit rectangular ducts. The attenuator was developed specifically to reduce noise in certain octave bands primarily in

More information

GOOD PRACTICE GUIDELINES FOR CONTROLLING NOISE ON OFFSHORE INSTALLATIONS

GOOD PRACTICE GUIDELINES FOR CONTROLLING NOISE ON OFFSHORE INSTALLATIONS GOOD PRACTICE GUIDELINES FOR CONTROLLING NOISE ON OFFSHORE INSTALLATIONS Graham McPherson (CMFOH) OH2017 Harrogate International Centre 24 27 April 2017 Introduction UK Noise Regulations also apply in

More information

THE REFURBISHMENT OF THE PORTUGUESE PUBLIC SECONDARY SCHOOL NETWORK: AN ACOUSTICAL PERSPECTIVE

THE REFURBISHMENT OF THE PORTUGUESE PUBLIC SECONDARY SCHOOL NETWORK: AN ACOUSTICAL PERSPECTIVE THE REFURBISHMENT OF THE PORTUGUESE PUBLIC SECONDARY SCHOOL NETWORK: AN ACOUSTICAL PERSPECTIVE Octávio Inácio InAcoustics, Lda. octavio.inacio@inacoustics.com Abstract In 2007 a modernization program for

More information

Noise reduction. in catering kitchens

Noise reduction. in catering kitchens Noise reduction in catering kitchens Photo: Thierry Le Guyader A good sound environment creates better conditions for work that needs a high level of concentration. Room Acoustic Comfort in kitchen premises

More information

SWEDISH STANDARD SS

SWEDISH STANDARD SS SWEDISH STANDARD SS 02 52 68 Approved 2001-06-21 Edition 1 Acoustics Sound classification of spaces in buildings Institutional premises, rooms for education, preschools and leisure-time centres, rooms

More information

Lindab Acoustics Where sound is a science and silence is an off-the-shelf item

Lindab Acoustics Where sound is a science and silence is an off-the-shelf item lindab we simplify construction Lindab Acoustics Where sound is a science and silence is an off-the-shelf item Everyone has the right to quiet and comfortable indoor climate Decades of research and development

More information

ENVIRONMENTAL PRODUCT DECLARATION In accordance with EN and ISO 14025

ENVIRONMENTAL PRODUCT DECLARATION In accordance with EN and ISO 14025 ENVIRONMENTAL PRODUCT DECLARATION In accordance with EN 15804 and ISO 14025 Ecophon Solo TM Realization date : 2015-06-02 Version : 1.0 Summary Environmental product declaration Verified by Registration

More information

ACOUSTIC TREATMENT. 1 Reverberation. Inside a given internally reflective enclosure, the human ear receives:

ACOUSTIC TREATMENT. 1 Reverberation. Inside a given internally reflective enclosure, the human ear receives: ACOUSTIC TREATMENT Acoustic Treatment addresses the quality, intelligibility and level of sound INSIDE a room and has nothing to do with how much internal sound is or is not heard outside the given room,

More information

Communal 51 Ceiling Systems by Vogl

Communal 51 Ceiling Systems by Vogl 33 commercial connections LIMITED Sound and thermal insulation specialists Communal 51 Ceiling Systems by Vogl Designed to meet Regulations Northern Ireland Regulation 51 Part G 2012 Republic of Ireland

More information

Laboratory measurements of the reduction of transmitted impact sound by floor coverings on a heavyweight reference floor (According to ISO )

Laboratory measurements of the reduction of transmitted impact sound by floor coverings on a heavyweight reference floor (According to ISO ) Reference no. T1638-1 Laboratory measurements of the reduction of transmitted impact sound by floor coverings on a heavyweight reference floor (According to ISO 10140 3) AUCKLAND UNISERVICES LIMITED a

More information

Optimization of Sound Absorbers Number and Placement in an Enclosed Room by Finite Element Simulation

Optimization of Sound Absorbers Number and Placement in an Enclosed Room by Finite Element Simulation Journal of Physics: Conference Series PAPER OPEN ACCESS Optimization of Sound Absorbers Number and Placement in an Enclosed Room by Finite Element Simulation To cite this article: S F Lau et al 2017 J.

More information

Testing Procedure: AS ISO

Testing Procedure: AS ISO RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON

More information

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE Copyright SFA - InterNoise 2000 1 inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering 27-30 August 2000, Nice, FRANCE I-INCE Classification: 4.3 LABORATORY TEST

More information

1.0 INTRODUCTION BUILDING REGULATIONS SOUND INSULATION REQUIREMENTS TEST PROCEDURE AND ANALYSIS...3

1.0 INTRODUCTION BUILDING REGULATIONS SOUND INSULATION REQUIREMENTS TEST PROCEDURE AND ANALYSIS...3 Concrete Centre Limited Bron Derw Residential Development, Colwyn Bay Sound Insulation Test Report 25 July 2005 PROJECT: CLIENT: Bron Derw Residential Development, Colwyn Bay Concrete Centre Limited Riverside

More information

KINETICS NOISE CONTROL TEST REPORT #AT001049

KINETICS NOISE CONTROL TEST REPORT #AT001049 KINETICS NOISE CONTROL TEST REPORT #AT001049 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o STC 53 o IIC 27 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA o B-3463.1

More information

B Page 1 of 21-

B Page 1 of 21- Airborne and impact sound transmission measurements were performed on three floor assemblies which comprised the NRC 150 mm reference concrete slab and a 102 mm floating concrete slab. For report purposes,

More information

Introduction to Acoustics

Introduction to Acoustics Introduction to Acoustics Absorption Have you walked into a racquetball court and heard the echo as the ball strikes the wall? Or have you been in the country with snow on the ground and noticed how quiet

More information

Rainfall and impact noise measurements on metal roof tiles

Rainfall and impact noise measurements on metal roof tiles Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research TNO report DGT-RPT-040015 Rainfall and impact noise measurements on metal

More information

Final year projects offered by Professor Jie Pan ( )

Final year projects offered by Professor Jie Pan ( ) Final year projects offered by Professor Jie Pan (2012-2013) Project 1: Design and analysis of sound absorber at a pipe bent Project 2: Correlation of pump vibration with unsteady flow inside of the pump

More information

Church Soundproofing. Church Soundproofing & Soundproofing Solutions

Church Soundproofing. Church Soundproofing & Soundproofing Solutions Church Soundproofing Church Soundproofing & Soundproofing Solutions Church Soundproofing This type of acoustic need requires special attention and knowledge to the nuances of voluminous spaces & hard surfaces,

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Atlanta, GA Sound Absorption CONDUCTED: 2016-09-09 Page 1 of 7 ON: D-GIK (24"x48" panels) TEST METHOD Riverbank Acoustical Laboratories is accredited by the U.S. Department of Commerce, National Institute

More information

Experimental study of sound insulation performance in the wood-framed building

Experimental study of sound insulation performance in the wood-framed building Experimental study of sound insulation performance in the wood-framed building Atsuo HIRAMITSU Research Engineer Building Research Institute Ibaraki, Japan Hirotsugu HOUNO Director Japan 2x4 Home Builders

More information

Office Soundproofing. Office Soundproofing & Soundproofing Solutions

Office Soundproofing. Office Soundproofing & Soundproofing Solutions Office Soundproofing Office Soundproofing & Soundproofing Solutions Office Soundproofing Proper office design will factor in the sound levels within the office space and determine where office noise control

More information

CONSIDERATIONS REGARDING IMPACT SOUND INSULATION PERFORMANCES OF DIFFERENT FLOOR MATERIALS

CONSIDERATIONS REGARDING IMPACT SOUND INSULATION PERFORMANCES OF DIFFERENT FLOOR MATERIALS JAES_1(14)_1_2011 TAMAS-GAVREA D.R. et all, pp.111-116 SECTION Civil Engineering and Installations CONSIDERATIONS REGARDING IMPACT SOUND INSULATION PERFORMANCES OF DIFFERENT FLOOR MATERIALS TĂMAŞ-GAVREA

More information

NOISE AND VIBRATIONS HIGH SPEED, LIGHT CRAFT AND NAVAL SURFACE CRAFT RULES FOR CLASSIFICATION OF DET NORSKE VERITAS

NOISE AND VIBRATIONS HIGH SPEED, LIGHT CRAFT AND NAVAL SURFACE CRAFT RULES FOR CLASSIFICATION OF DET NORSKE VERITAS RULES FOR CLASSIFICATION OF HIGH SPEED, LIGHT CRAFT AND NAVAL SURFACE CRAFT SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 12 NOISE AND VIBRATIONS JANUARY 2011 CONTENTS PAGE Sec. 1 Noise

More information

ENVIRONMENTAL PRODUCT DECLARATION In accordance with EN and ISO 14025

ENVIRONMENTAL PRODUCT DECLARATION In accordance with EN and ISO 14025 ENVIRONMENTAL PRODUCT DECLARATION In accordance with EN 15804 and ISO 14025 Ecophon Advantage TM Realization date : 2015-10-26 Version : 1.0 Summary Environmental product declaration Content summary Verified

More information

INTRODUCTION SPECIMEN DESCRIPTION

INTRODUCTION SPECIMEN DESCRIPTION INTRODUCTION SPECIMEN DESCRIPTION Airborne sound transmission measurements were performed on a wall assembly with a single layer of the product identified by the client as QuietRock QR-530 Serenity on

More information

STRUCTURE-BORNE SOUND CONTRIBUTION INTO EARTH-MOVING MACHINE CABS.

STRUCTURE-BORNE SOUND CONTRIBUTION INTO EARTH-MOVING MACHINE CABS. ICSV14 Cairns Australia 9-12 July, 2007 STRUCTURE-BORNE SOUND CONTRIBUTION INTO EARTH-MOVING MACHINE CABS Nickolay Ivanov 1, David Copley 2, Natalia Tyurina 1 1 Baltic State Technical University, St. Petersburg,

More information

RIVERBANK ACOUSTICAL LABORATORIES

RIVERBANK ACOUSTICAL LABORATORIES FOR: Owatonna, MN. Sound Absorption CONDUCTED: 2014-12-16 Page 1 of 6 ON: Large Motorized Enclosure - Retractable Drapery - Outer Fabric is 22oz. Encore Velour - 4" Airspace - Inner Fabric is Quilted Material

More information

ACOUSTICAL TREATMENT OF EMERGENCY POWER GENERATOR. Dr. M.Abd El Gawad Saif

ACOUSTICAL TREATMENT OF EMERGENCY POWER GENERATOR. Dr. M.Abd El Gawad Saif ICSV14 Cairns Australia 9-12 July, 2007 ACOUSTICAL TREATMENT OF EMERGENCY POWER GENERATOR Dr. M.Abd El Gawad Saif Housing & Building National Research Center, Dokki, Giza, Egypt msaifeldin2002@yahoo.com

More information

Hive Acoustic Report.

Hive Acoustic Report. Hive Acoustic Report www.connection.uk.com Introduction An acoustic report of the equivalent sound absorption area of selected Connection products carried out by AIRO Acoustics Laboratory. The original

More information

Stretch Ceiling CLIPSO Type 495D white with 10 mm Absorbent Material

Stretch Ceiling CLIPSO Type 495D white with 10 mm Absorbent Material BAE Fiedler Mühlweg 21 D-35633 Lahnau Germany Phone 0049 6441/9625-43 Fax 0049 6441/9625-44 Stretch Ceiling CLIPSO Type 495D white with 10 mm Absorbent Material Construction Height 10 mm Measurement of

More information

ACOUSTICAL INFORMATION

ACOUSTICAL INFORMATION ACOUSTICAL INFORMATION Alpro has been successfully used for over 50 years to provide sound absorption for a variety of environments from gymnasiums and auditoriums to water treatment plants and outdoor

More information

Acoustics in Green Buildings

Acoustics in Green Buildings Acoustics in Green Buildings Dr. Kenneth P. Roy, fellow ASA Sr. Principal Research Scientist Armstrong Building Products Technology, R&D Lancaster, PA, USA kproy@armstrong.com Buildings and People Architecture

More information

Acoustics Size and Modes of the Small Room for Home Theatre

Acoustics Size and Modes of the Small Room for Home Theatre Acoustics Size and Modes of the Small Room for Home Theatre S. Jerin Winne 1, Durai Jayaprakash 2 1 Asst. Professor, Sathyabama University, Chennai, India 2 Composer, IMI mobiles, Hyderabad, India Abstract:

More information

Rainfall and impact noise measurements on metal roof tiles

Rainfall and impact noise measurements on metal roof tiles Nederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / Netherlands Organisation for Applied Scientific Research TNO report DGT-RPT-040015 Rainfall and impact noise measurements on metal

More information

Numerical prediction and experimental validation of sound transmission loss for different acoustic materials

Numerical prediction and experimental validation of sound transmission loss for different acoustic materials J. Build. Mater. Struct. (2018) 5: 95-101 Original Article DOI : 10.5281/zenodo.1297183 Numerical prediction and experimental validation of sound transmission loss for different acoustic materials Kirti

More information

NOISE MODELING STUDY REPORT NO A ROARING BROOK WIND FARM PROJECT AND ENVIRONMENTAL IMPACT ASSESSMENT

NOISE MODELING STUDY REPORT NO A ROARING BROOK WIND FARM PROJECT AND ENVIRONMENTAL IMPACT ASSESSMENT 3862 Clifton Manor Place Suite B Haymarket, Virginia 20169 USA Phone: 703-753-1602 Fax: 703-753-1522 Website: www.hesslernoise.com REPORT NO. 1802-091507-A REV: A DATE OF ISSUE: OCTOBER 12, 2007 NOISE

More information

Some Investigations on the Sound Field (Sound Propagation) Measurement in a Rectangular Room

Some Investigations on the Sound Field (Sound Propagation) Measurement in a Rectangular Room International Journal of Engineering Research and Technology. ISSN 097-315 Volume, Number (013), pp. 7-9 International Research Publication House http://www.irphouse.com Some Investigations on the Sound

More information

Low frequency sound transmission in multifamily wooden houses

Low frequency sound transmission in multifamily wooden houses Low frequency sound transmission in multifamily wooden houses Klas HAGBERG 1 ; Delphine BARD 2 ; 1 SP Wood, Sweden 2 Lund University, Sweden ABSTRACT In the recently finished research projects, AkuLite

More information

Corporate Environments

Corporate Environments Acoustics and the Impact on Corporate Environments falconproducts.com Achieving High-Quality Acoustics in Corporate Settings Knowledge is power. Here s what you need to know about sound, noise and creating

More information

19 th INTERNATIONAL CONGRESS ON ACOUSTICS MADRID, 2-7 SEPTEMBER 2007 A METHODOLOGY TO MEASURE THE ACOUSTIC PERFORMANCE OF ACCESS FLOORS

19 th INTERNATIONAL CONGRESS ON ACOUSTICS MADRID, 2-7 SEPTEMBER 2007 A METHODOLOGY TO MEASURE THE ACOUSTIC PERFORMANCE OF ACCESS FLOORS 19 th INTERNATIONAL CONGRESS ON ACOUSTICS MADRID, 2-7 SEPTEMBER 2007 A METHODOLOGY TO MEASURE THE ACOUSTIC PERFORMANCE OF ACCESS FLOORS PACS: 43.55.-e Asdrubali, Francesco 1 ; D Alessandro, Francesco 2

More information

SABIN 3.0 tutorial. The reverberation time of a newly designed room has to be given a certain desired value.

SABIN 3.0 tutorial. The reverberation time of a newly designed room has to be given a certain desired value. SABIN 3.0 tutorial The step by step procedures described below are meant to clarify the use of Sabin. For three different problems a solution using Sabin is shown. In all examples the database file Demo.mdb

More information

((( CONTENTS ))) Acoustic absorption 2. Products 3. Phonicéram 4 Phonicéram db 5 Phonbric 6 Acoustic shingles 7 Acoustic bricks 8 A.M.B.

((( CONTENTS ))) Acoustic absorption 2. Products 3. Phonicéram 4 Phonicéram db 5 Phonbric 6 Acoustic shingles 7 Acoustic bricks 8 A.M.B. ((( CONTENTS ))) Acoustic absorption 2 Products 3 Phonicéram 4 Phonicéram db 5 Phonbric 6 Acoustic shingles 7 Acoustic bricks 8 A.M.B. 9 TERREAL Solutions 10 Residence 10 Education 12 Industry 14 Tertiary

More information

Impact Sound Testing of Floor Covering on a Heavyweight Standard Floor

Impact Sound Testing of Floor Covering on a Heavyweight Standard Floor Impact Sound Testing of Floor Covering on a Heavyweight Standard Floor Report INR171/R1 June 2011 Gerflor Australasia Pty Ltd 17 Cato Street Hawthorn East VIC 3123 Enquiries should be addressed to: Manager

More information

Sound Attenuation. Slide 1 of 48. PAC International Inc START

Sound Attenuation.   Slide 1 of 48. PAC International Inc START Sound Attenuation START www.pac-intl.com Slide 1 of 48 Sound Attenuation PAC International 7310 Smoke Ranch Rd Suite "E" Las Vegas, NV. 89128 Course Number: XXXXXX Learning Units: 1.00 PAC International

More information

A L I O N Technical Center. Test Report. SPONSOR: a-light Architectural Lighting

A L I O N Technical Center. Test Report. SPONSOR: a-light Architectural Lighting SPONSOR: Oceanside, CA Sound Absorption CONDUCTED: 2019-03-06 Page 1 of 7 ON: ABH-4', spaced 48 in. on center, 21.5 in. from test surface TEST METHODOLOGY Riverbank Acoustical Laboratories is accredited

More information