The Rijksmuseum Amsterdam - Hygrothermal analysis and dimensioning of thermal insulation

Size: px
Start display at page:

Download "The Rijksmuseum Amsterdam - Hygrothermal analysis and dimensioning of thermal insulation"

Transcription

1 The Rijksmuseum Amsterdam - Hygrothermal analysis and dimensioning of thermal insulation J. Grunewald, U. Ruisinger & P. Häupl Department of Mechanical and Aerospace Engineering, Syracuse University, 9 Link Hall, Syracuse, NY 3-, USA Dresden University of Technology, Institute of Building Climatology, Zellescher Weg 7, D-6 Dresden, Germany Contact: john.grunewald@gmx.de ABSTRACT: The vitalization of the historical building stock demands planning of reconstruction measures that increasingly aim at protection of our cultural heritage and at energy-efficient renovation as well. But these requirements can be contradictory sometimes. Questions arise, e.g.: What are the potentials and the risks of a thermal insulation? Which materials and which thickness would be appropriate for application in historical buildings? The external walls of the Rijksmuseum Amsterdam, being under reconstruction currently, suffered from moisture originated damages. Therefore, it was intended to apply an adequate thermal insulation to provide a proper micro climate near the internal wall surfaces and to minimize fluctuations in indoor climate. The insulation has to be properly dimensioned to limit extreme values in temperature and relative humidity. In addition, the measures should reduce interstitial condensation and prevent consecutive frost damages at outer parts of the facade. Two internal insulation options were discussed, one based on vapor-tight cellular glass and another one using capillary-active calcium silicate. Both variants and, as a reference case, the existing construction without insulation were investigated by application of numerical simulation software. Results are presented here for undisturbed one-dimensional wall constructions exposed to climate conditions of Amsterdam on an hourly basis. INTRODUCTION The protection of historical buildings often demands measures due to their particular utilization requirements. Examples are libraries or museums where indoor temperature and relative humidity have to be kept within certain tolerances in order to maintain exhibits and works of art permanently in a good state. A thermal upgrade of the building envelope by external insulation is often not applicable to historical facades. Aspects of energy-efficient renovation supervene in old residential houses. These contradictory requirements put questions about potentials and the risks of internal thermal insulation. The Rijksmuseum Amsterdam, as one of the ten principal museums in the world, is widely acclaimed for its collection of paintings from the Golden Age. The Rijksmuseum is a museum of art and history with five different collections under a single roof painting, sculpture and decorative arts, drawings, prints and photographs, Asiatic art, and Dutch history. The Rijksmuseum has numerous features that no longer meet today s safety requirements, and modern concepts regarding many aspects make an urgent call for new facilities. The starting point of the renovation is to restore light, air and architectural transparency to the building, and to design it so that it meets the needs of today s visitors. The renovation is one of the most radical operations the Rijksmuseum has ever had to undergo. Figure. The Rijksmuseum in the city of Amsterdam is a cultural centre of excellent reputation. As part of the planning works, an expertise was prepared by Arup (), stating that among other building physical problems the external walls show abnormal high moisture contents. Gravimetric measurements of selected bricks taken from different

2 parts of the building envelope ware carried out in the Building Physical Laboratory of the Institute of Building Climatology. Higher moisture penetration, sometimes full saturation, was found. Since rising damp can be excluded as reason for the high moisture contents, condensation and rain penetration were the remaining possible reasons. During the rehabilitation works, the facade was checked for cracks and open joints and, if necessary, repaired. Most windows have been replaced, which was considered a reasonable measure for safety, art conservation and reduction of heating energy losses. Naturally, due to the lower thermal transmittance of the new windows, the sheet glass surface temperature is higher than before. Therefore, substitution of the old windows had to be accompanied by a thermal upgrade of thermally weak parts of the outer walls. If the adjacent wall constructions are not insulated additionally, there would be a risk of condensation at the wall surfaces. Even if no condensation on the inner surface of outer walls takes place, there is a risk for mould growth. The critical relative humidity for mould growth is disputed among experts. Under optimal conditions - depending, for example, on the period of the climatic load, temperature and organic substrate - very few mould species grow on surfaces buildings below 7% relative humidity, Sedlbauer (). It is undisputed that a relative humidity higher than 8% should be avoided in any case. In this expertise it is considered acceptable if a relative humidity of 7% is not exceeded for more than - partially sequentially - ten days per year, Seifert et al. (). As one conclusion of the current situation, it was decided to provide an adequate internal thermal insulation of the exterior facades. Two insulation options were discussed: 3mm cellular glass, attached with mm glue mortar, and with a mm clay plaster layer as surface finish on the interior, calcium silicate, thickness still to be determined, attached with mm glue mortar, and with a mm lime cement plaster layer as surface finish on the interior. The Institute of Building Climatology was instructed to prepare several expertises for decision making. The hygrothermal behavior of the two proposed insulation options, in comparison to the non-insulated case were investigated. In addition, construction details as window recesses, air ducts and geometric thermal bridges were examined. As result of the hygrothermal analysis, recommendations for the constructive execution were given. The analysis was carried out using the simulation software DELPHIN developed at the Institute for Building Climatology at the Dresden University of Technology. CLIMATIC CONDITIONS During the simulation, the constructions are exposed to non-steady-state climatic conditions at interior and exterior sides. The annual course of temperature and relative humidity, the impact of driving rain, short and long wave radiation were taken into account on hourly basis. An hourly climatic data set of Amsterdam provided by Arup () was used for the external conditions; the set contained temperature, relative humidity, radiation and wind measured over one year. Hourly rainfall values were taken from the weather station most close to the city of Amsterdam. The monthly rainfall values (in total 88 l/m² a) used in the analysis are slightly higher than the monthly average rainfall data of Amsterdam from 98 to 99 (in total 83 l/m² a). The driving rain density on the wall surfaces is calculated from wind direction, wind speed and rain fall density on a horizontal surface area (Figure ). The highest rainfall density is reached at constructions exposed to the west, here, about / of the rain fall density on a horizontal surface area. That is reason why, in order to be on the save side, all build-ups have been analyzed as west-facing. Rain fall density in l/mh Time in days Figure. Rainfall on a horizontal surface (data from nordic coast region of Germany) The impact of direct solar radiation has been calculated for a west-facing wall too. In addition, the diffuse solar radiation and the long wave radiation balance were taken into account. The simulations are usually conducted for a time period of several years. It was assumed that the climatic conditions will recur periodically every year. Interior conditions are described according to the ambient design conditions communicated by Arup () (summer 3 C / % r.h., winter C / % r.h., tolerance ±K / % r.h.). The interior climate has been modelled by sinusoidal functions as shown in Figure 3. The temperature curve represents exactly the proposed conditions, without the allowed tolerance of K. To achieve conservative, worst-case results, the relative humidity is assumed to be at the upper limit of its tolerance (%) band, which could be caused, for example, by a high visitor frequency. 3 3

3 To achieve results of two-dimensional simulations in a reasonable time, some details of the construction have been simplified. Because the software can reproduce rectangular edges only, curved surfaces have been modelled as even. Double glass panes have been simulated as one pane with adjusted values identical to double panes. Coatings on the internal surface has been assumed diffusion-open. The effects on results are assumed to be very small. The simplifications were chosen such that the results will always be on the safer side, i.e. the real hygrothermal behavior will be less problematic. Since the time for preparation of the expertises was short for material measurements, most of hygrothermal material data has been taken from the material data base of DELPHIN. The material parameters of brick incorporate vapor diffusion resistance values and moisture retention values from Dutch guidelines for building materials too. At the same time, it was agreed on conduction of supplementary material tests to be carried out at the Institute of Building Climatology and on subsequent simulations with updated material data to check the results. The most important material parameters used for simulations are collected in Table. The two insulation materials have oppositional properties. Cellular glass has no liquid water conductivity and a very high resistance to water vapor diffusion, whereas calcium silicate is characterized by high liquid water conductivity (capillary activity) and low water vapor diffusion resistance. The material parameters presented in Table form the basic input to the simulation program. The storage and transport coefficients used in differential equations for heat and moisture transfer require specification of material properties as functions of temperature and moisture content. To generate those functions, material models are employed. Here the material property specification is based on the Engineering model of hygrothermal material characteristics Scheffler & Grunewald (). 3 Table. Basic material parameters for simulation Temperature in C Indoor temperature (ARUP-specification) Outdoor temperature Time in days Time in days 3 Indoor relative humidity (ARUP-specification) Outdoor relative humidity Density Specific heat capacity Thermal conductivity Vapour diffusion resistance Water content at 8% R.H. Capillary saturation Water uptake coefficient / kgk / Symbol ρ c λ R µ dry θ 8 θ cap A w Unit kg / J W - m 3 /m 3 m 3 /m 3 kg / m 3 mk m s. Historical brick LC-plaster Cellular 7. 7 e-. glass Glue mortar Clay plaster Calcium silicate Clinker Figure 3. Courses of indoor and outdoor temperature and relative humidity used for simulation 3 MATERIAL DATA CONSTRUCTION Two insulation options were investigated, cellular glass and calcium silicate, in comparison to the existing non-insulated wall construction. The three buildups used for analysis of the undisturbed wall area are represented in Figure. Layering, dimensions and material selection followed the specifications made by Arup (). The numerical analysis includes: annual courses of temperature, relative humidity and water contents, temporal courses of integral moisture contents and condensate mass, proof of condensation risk at internal wall surfaces as well as compliance of humidity criterion concerning mold growth (short term exceeding of 7% R.H. for maximum days), quantification of energy savings. The initial conditions were chosen to account for the experimental results of the brick moisture mea-

4 surements. According to own investigations, the inner brick range (historical brick) was assumed entirely saturated by about Vol%. The outer clinker layer and the insulation layer were set initially to moisture contents in equilibrium to 8% R.H. The initial temperature of the whole construction was C. Without insulation Cellular glass insulation mm Clay plaster, 3mm Cellular glass, mm Glue mortar Calcium silicate insulation mm Lime cement plaster, 3mm Calcium silicate, mm Glue mortar Figure. Build-up of the existing non-insulated construction (top), insulation option one with cellular glass (middle) and insulation option two with calcium silicate (below) After a certain settling time, the physical quantities (e.g. water content and temperature) in every part of the construction recur in the simulation over the year. This means that they reach, according to the cyclic climatic conditions, a quasi-stationary state. This process can take years, but the main changes take place during the first months or years. This process is pronounced by the material properties and by the chosen initial conditions. The duration of simulations of five years was long enough to reach almost quasi-stationary conditions. RESULTS mm mm 8mm mm mm Insulation Lime Historical Clinker system Brick cement plaster Lime cement plaster In the graphs in Figure, the simulation results are represented in terms of relative humidity and water contents as function of location and time. The water content fields on the right side document the drying stage of the three build-ups reached at Dec.3 after years drying time. The image presentation allows a quick overview of the moisture situation and gives a descriptive impression about the differences in drying behavior of the constructions. For the reference build-up without insulation, moisture distribution has reached a maximum between outer clinker layer and inner brick layer. While drying can take place in both directions, the only possible moisture penetration is that from caused by rain. Obviously, the drying process dominates the water penetration by rain; otherwise no drying would have taken place. It must be concluded that the reasons for the high initial moisture contents found in Rijksmuseum must lay in imperfections of the envelope walls that could have forwarded a moisture penetration. The higher moisture level in the build-up with cellular glass insulation can be immediately recognized. The diffusion-tight barrier formed by the cellular glass prevents any drying towards the interior side. The drying potential towards exterior is limited due to the temperature drop in the wall cross section. This leads to an increase in moisture contents up to Vol% at the interface between existing construction and applied insulation layer. It is remarkable that this increase still exists after five years drying time. The build-up with diffusion-open insulation provided by calcium silicate shows a moisture response comparable to the reference construction without insulation. The maximum in moisture contents forms again between outer clinker layer and inner brick layer. This is of particular interest since it indicates that interstitial condensation (to be expected here between calcium silicate glue mortar) is very little in terms of moisture contents compared to the moisture penetration due to driving rain. A more detailed quantitative image give the graphs on the left side of Figure where the relative humidity profiles are depicted during a full course over the fifth year. The black range indicates the local variation of the relative humidity over the year at the respective position. Zones in which the relative humidity exceeds the 9%-limit at least once a year are considered temporarily wet. A maximum overhygroscopic penetration depth can be introduced indicating the width of the zone subjected to higher moisture contents. The heat losses in this range increase due to the higher thermal conductivity of wet materials and the resistance against frost damages will be lowered according to the rise of the freezing point temperature. The graphs support the conclusions drawn from the moisture fields. The reference buildup and the calcium silicate version behave comparably while the cellular glass variant stays wet. In addition, there is a remarkable improvement of the local climate at the internal side for both insulated variants, indicated by the diminished variation of the surface relative humidity. At the interface between insulation and glue mortar, calcium silicate shows the highest variation.

5 Relative humidity profiles Water content fields. Reference case without insulation LC-Plaster Brick LC-Plaster Clinker Existing construction, Water content in Vol% Maximum overhygroscopic penetration depth 3 Location in mm Build-up with 3mm cellular glass insulation Cellular glass insulation + glue mortar Clay plaster LC-Plaster Brick LC-Plaster Clinker Maximum overhygroscopic penetration depth 3 Location in mm 6 Cellular glass, Water content in Vol% Build-up with 3mm calcium silicate insulation Calcium silicate insulation + glue mortar LC-Plaster LC-Plaster Brick LC-Plaster Clinker Maximum overhygroscopic penetration depth 3 Location in mm 6 Calcium silicate, Water content in Vol% Figure. Profiles of relative humidity versus location during the th year (left) and water content fields at the end of five years simulation (right). Existing construction (top), 3mm foam glass insulation (middle) and 3mm calcium silicate insulation (below).

6 The integral moisture mass of the wall cross section is an indicator for the long term behavior. The comparison of the three build-ups, shown in Figure 6, demonstrates a clear difference between cellular glass and calcium silicate. While calcium silicate follows closely the drying curve of the reference case without insulation, the cellular curve shows a distinct course. The application of cellular glass decreases the drying potential of the construction and retards the drying process remarkably. After five years, the integral moisture content remains three times higher than in the constructions with maintained drying potential. After five years the build-ups have nearly reached a quasi-stationary state in which the annual average rain penetration approximately equals the drying rate. That means the constructions will retain their moisture levels reached in Figure 6. This level is inacceptable high for the cellular case and the probability for consecutive moisture damages raises. Integral water mass in kg/m Without insulation 3mm Cellular glass insulation 3mm Calcium silicate insulation 3 Figure 6. Integral moisture content for different build-ups over years Reminding the improvement of the internal micro climate near the wall surface provided by both insulation variants and the long term drying behavior, where cellular glass fails, the comparison of the results justifies the conclusion that calcium silicate insulation would be the most appropriate solution. But the thermal insulation value of calcium silicate is not as high as the one of cellular glass (compare thermal conductivity values in Table ). Therefore the consequences of an increased thickness of the insulation layer were investigated. Integral water mass in kg/m mm Calcium silicate insulation mm Calcium silicate insulation mm Calcium silicate insulation..6 Figure 7. Integral moisture content for different calcium silicate thicknesses in the th year.8 The curves in Figure 7 show the integral moisture contents of build-ups with 3mm, mm and mm thick calcium silicate insulation. While the curves for 3mm and mm are practically identical, a slight increase can be noticed for mm. This slightly increased moisture content is interstitial condensation that forms due to the lowered temperature in the condensation layer between calcium silicate and glue mortar. However, the course of the integral water mass is dominated by rain penetration.. Evaluation of the condensation risk During the heating period, especially on the of wall surfaces and on the cold side of the insulation layer, the occurrence of condensation becomes probable. Condensation can form as surface condensation or as interstitial condensation. For evaluation of the condensation risk, overhygroscopic water mass by condensation and by rain penetration must be distinguished. Therefore, condensate is defined here as a moisture content that is not caused by rain penetration and that exceeds the natural moisture content of the material in equilibrium to a relative humidity of 9%. The graphs in Figure 8 show the amount of interstitial condensate as function of time for different thickness of calcium silicate. The higher condensation values during the first two years are caused by redistribution of the initial moisture of the brick layer. After decaying of the high initial values, the condensate is constantly less than 3 g/m, which can be regarded as harmless. Condensate in kg/m mm Calcium silicate insulation mm Calcium silicate insulation mm Calcium silicate insulation 3 Figure 8. Amount of interstitial condensate for different thicknesses of the calcium silicate layer over years The risk of mould growth and surface condensation can be evaluated knowing the temperatures and relative humidity on the inner surface of the walls. Apart from a lower risk of mould growth and condensation, higher surface temperatures also create a more comfortable room climate and better conditions for art storage. A lower difference between room and surface temperature will also cause lower airflow velocity in rooms.

7 Figure 9 shows the course of the relative humidity on the inner wall surfaces during the fifth year. With none of the listed constructions surface condensation is predicted. The risk of mould growth is also low for the existing built up as well, because very few mould species are able to grow at these courses of relative humidity. But these conclusions do not refer to thinner walls and thermal bridges like room corners, where the temperature is lower and the relative humidity is higher than in undisturbed wall areas. Condensate in kg/m mm Calciumsilikat on mm brick wall 3mm Calciumsilikat on 6mm brick wall mm brick wall without insulation 3mm Cellular glass on 6mm brick wall 3mm Calcium silicate on 6mm brick wall..6 Figure 9. Course of relative humidity on inner wall surface during the th year for a brick wall of 6mm thickness If a construction with mm brick is considered the need for internal insulation becomes more evident, see Figure. A difference of about % in relative humidity and 3.3 C in temperature between the current situation and the build-up with foam glass can be observed in this case. At the end of December, the surface of the existing built up cools down to C. Here, mould growth and surface condensation is likely, in particular at critical construction details A comparison of the interstitial condensate between the mm and 6mm brick walls is shown in Figure. The risk of condensation normally increases with lower wall thickness. Here, the mm brick wall shows slightly increased values but lays still in the harmless range of max.. kg/m. In the first winter, it falls below the curve of the 6mm wall due to its faster drying behavior..8 mm brick wall without insulation 3mm Cellular glass on mm brick wall 3mm Calcium silicate on mm brick wall Figure. Course of relative humidity on inner wall surface during the th year for a brick wall of mm thickness.8 Figure. Course of interstitial condensate during the years for brick walls of different thicknesses. Reduction of thermal energy transmission The heat transfer coefficient (U-value) characterizes the thermal transmission through the envelope walls. Under stationary conditions, the U-value is calculated from the thermal conductivities and the layer thickness of the materials taking into account the convective heat exchange coefficients at the surfaces. The transient U-value can be derived from an average heat flux over the inner wall surface divided by an average (internal-external) temperature difference. Both quantities are averaged over the heating period under consideration (here Oct.- to Mar-3). Table shows the transient U-values of tested wall constructions (temperature difference ΔT= 6.36 C) and the reduction of thermal energy transmission in percent. Table. Transient U-values of different build-ups based on 6mm brick wall Without insulation Cellular glass 3 mm Calcium silicate 3 mm Calcium silicate mm Calcium silicate mm Average heat flux (W/m ) U-value (W/m K) Reduction of thermal energy transmission (%) All insulation variants reduce the transmission of thermal energy remarkably (up to 6%). From this point of view, a thermal insulation is recommended. It can be noticed that mm calcium silicate achieves the same reduction as 3mm cellular glass. But the advantage of mm calcium silicate over mm would be not very big. A further increase of the thickness would lower the cost-value ratio and can be regarded as inefficient.

8 6 SUMMARY AND CONCLUSIONS The building physical state of the Rijksmuseum Amsterdam caused serious concerns due to higher moisture contents in the envelope parts and unfavorable micro climatic conditions near the internal wall surfaces. The need for application of an internal thermal insulation has been commonly recognized ARUP/DGMR (). It was to decide which insulation option would be most appropriate to regulate the hygrothermal behavior of the exterior walls according to the requirements of the exhibits. Two insulation options cellular glass and calcium silicate were discussed and both were compared with the reference case original construction without insulation. The solution was achieved by using the method of numerical simulation that yields the temporal courses of temperature, relative humidity, water content and condensate. Statements about advantages and disadvantages of the insulation options can be derived from that.. Envelope walls of a thickness d 6mm should be generally insulated. If paintings are attached, the walls should be insulated up to a thickness of 9mm. This has positive effects on the micro climate near the internal surfaces. Application of an insulation layer of minimum 3mm thickness would keep the relative humidity permanently below 7%.. The application of foam glass forms a vapor barrier at the internal surfaces preventing drying towards the inner surface. The drying potential of wet building elements is drastically decreased. Thus, the moisture equilibrium of the envelope walls between rain penetration and evaporation adjusts at an up to three times higher moisture level. 3. With calcium silicate insulation the drying potential of the envelope walls is kept. Sufficiently high temperatures and low relative humidity on the interior surface would prevent mould growth and surface condensation. As a result indoor climate quality would also be improved.. The favorite build-up is an insulation system with mm calcium silicate. The thermal transmission through the walls can be reduced by about %. A higher insulation layer thickness would lower the cost-value ratio. The analysis of the undisturbed wall areas has been complemented by two-dimensional analysis of critical construction elements. Since the results shown here were conservatively interpreted they could be confirmed by the results of the D-simulations. In addition, the increased risk of frost damages at thin wall structures was assessed. The freezing point temperature in porous media is decreased in dependence on the moisture content, Xu (998). The increase of frost damage risk by calcium silicate insulation was found to be very low. The temperature drop in the outer parts of the wall cross section was lower than K. The simulations were based on material data from the simulation program s data base and from literature. To justify the results, the material parameters of bricks and mortar from the Rijksmuseum were determined in the Laboratory of the Institute of Building Climatology. Repeated simulations with updated material data confirmed the results and conclusions. Additionally, a mock-up area was built up in the Rijksmuseum where calcium silicate insulation was applied. Sensor technology for measurement of relative humidity, temperature and heat fluxes has been installed. Continuous monitoring of the hygrothermal behavior by in-situ measurements is in progress. 7 REFERENCES Arup DGMR, : Rijksmuseum Amsterdam - Preliminary Design (VO) Report Building Physics. Arup BV, Issue 3, Dec., Job Number 98 Arup DGMR, : Personal communication between Arup BV and the Authors: Build-ups -dimensional analysis and Climatic data from Amsterdam, received by . Grunewald, J. 997: Diffusiver und konvektiver Stoff- und Energietransport in kapillarporösen Baustoffen. Dissertation, Dresden University of Technology, Institute Building Climatology Grunewald J., R. Plagge, P. Häupl, : A -levelled Hygrothermal Material Database for the Numerical Simulation Program DELPHIN, 6th Symposium on Building Physics in the Nordic Countries, Trondheim, Norway Grunewald J., P. Häupl, 3: Gekoppelter Feuchte-, Luft-, Salz-, und Wärmetransport in porösen Baustoffen. Bauphysik-Kalender 3. Berlin: Ernst & Sohn Verlag Scheffler, G., Grunewald, J : Calibration of an Engineering Model of hygrothermal material characterisation, CIB W Meeting in Glasgow Sedlbauer, K.. Vorhersage von Schimmelpilzbildung auf und in Bauteilen. Dissertation, Universität Stuttgart Seifert, B. et al. : Leitfaden zur Vorbeugung, Untersuchung, Bewertung und Sanierung von Schimmelpilzwachstum in Innenräumen ( Schimmelpilz-Leitfaden ). Berlin: Umweltbundesamt (UBA) Berlin Xu, Y. 998: Numerische Simulation der Eisbildung in kapillarporösen Baustoffen unter Berücksichtigung der gekoppelten Wärme- und Feuchtetransportprozesse. Dissertation, in: Dresdner Bauklimatische Hefte, Heft, TU Dresden, Dresden

COMBINED EFFECT OF TEMPERATURE AND HUMIDITY ON THE DETORIATION PROCESS OF INSULATION MATIRIALS IN ETICS

COMBINED EFFECT OF TEMPERATURE AND HUMIDITY ON THE DETORIATION PROCESS OF INSULATION MATIRIALS IN ETICS COMBINED EFFECT OF TEMPERATURE AND HUMIDITY ON THE DETORIATION PROCESS OF INSULATION MATIRIALS IN ETICS Andreas Holm, Dipl.-Phys. Hartwig M. Künzel, Dr.-Ing. * 1. THE PROBLEM When an exterior thermal insulation

More information

The quantification of the moisture distribution in renovated historical wall structures and exposed monuments

The quantification of the moisture distribution in renovated historical wall structures and exposed monuments The quantification of the moisture distribution in renovated historical wall structures and exposed monuments P. Haupl, H. Fechner, J. Grunewald & H. Petzold Dresden University of Technology, Germany Abstract

More information

Improving the Energy Performance of Mass Masonry Enclosures

Improving the Energy Performance of Mass Masonry Enclosures Improving the Energy Performance of Mass Masonry Enclosures APT DC Symposium Energy Efficiency of Historic Sites Chrissie Parker, P.E. Simpson Gumpertz & Heger www.sgh.com Presentation Outline Background

More information

Moisture transfer in internally insulated buildings

Moisture transfer in internally insulated buildings Moisture transfer in internally insulated buildings Valentina Marincioni Research Engineer Bartlett School of Graduate Studies, UCL (English Heritage, 2011) Liquid transfer and sources RAIN Flow through

More information

A well-planned building envelope is a requirement for achieving high user comfort and low energy costs.

A well-planned building envelope is a requirement for achieving high user comfort and low energy costs. TEC1.3 Quality of the building envelope Objective Our objective is to minimise the energy demand for room conditioning of buildings while at the same time ensuring high thermal comfort and preventing building

More information

Design of Mineral Fibre Durability Test Based on Hygrothermal Loads in Flat Roofs.

Design of Mineral Fibre Durability Test Based on Hygrothermal Loads in Flat Roofs. Design of Mineral Fibre Durability Test Based on Hygrothermal Loads in Flat Roofs. Daniel Zirkelbach 1 Hartwig M. Künzel 2 Christian Bludau 3 T 22 ABSTRACT The durability of mineral fiber insulations depends

More information

Peter Häupl ON USE OF CAPILLARY ACTIVE MATERIALS FOR REHABILITATION OF HISTORIC BUILDINGS. Extract from lectures at SU presented by Mark Bomberg

Peter Häupl ON USE OF CAPILLARY ACTIVE MATERIALS FOR REHABILITATION OF HISTORIC BUILDINGS. Extract from lectures at SU presented by Mark Bomberg Peter Häupl ON USE OF CAPILLARY ACTIVE MATERIALS FOR REHABILITATION OF HISTORIC BUILDINGS Extract from lectures at SU presented by Mark Bomberg Test houses with capillary active interior thermal insulation

More information

Condensation Problems in Cool Roofs

Condensation Problems in Cool Roofs Condensation Problems in Cool Roofs Christian Bludau 1 Daniel Zirkelbach 2 Hartwig M. Künzel 3 T 22 ABSTRACT In some regions of the United States so called cool roofs have become mandatory in order to

More information

LIGHTWEIGHT WOOD-BASED WALLS WITH VARIOUS THERMAL INSULATIONS: LONG-TIME MEASUREMENT AND SUBSEQUENT COMPARISON WITH HAM SIMULATION

LIGHTWEIGHT WOOD-BASED WALLS WITH VARIOUS THERMAL INSULATIONS: LONG-TIME MEASUREMENT AND SUBSEQUENT COMPARISON WITH HAM SIMULATION LIGHTWEIGHT WOOD-BASED WALLS WITH VARIOUS THERMAL INSULATIONS: LONG-TIME MEASUREMENT AND SUBSEQUENT COMPARISON WITH HAM SIMULATION Pavol Durica 1, Peter Juras 2, Vladimir Gaspierik 1, Jan Rybarik 1, Daniela

More information

MOISTURE VAPOR MOVEMENT AND VAPOR PERMEANCE

MOISTURE VAPOR MOVEMENT AND VAPOR PERMEANCE HOW VAPOR RESISTANCE PROPERTIES OF COATINGS AFFECT EXTERIOR WALL MOISTURE PERFORMANCE Garth D. Hall, Senior Architect, AIA, Kenneth M. Lies, Principal, AIA, and Sarah K. Flock, Architect III Raths, Raths,

More information

Proceedings Cold Climate HVAC Sisimiut, Greenland, March 2009

Proceedings Cold Climate HVAC Sisimiut, Greenland, March 2009 Proceedings Cold Climate HVAC Sisimiut, Greenland, 16-19 March 2009 Flat Roofs in Cold Climates - Climatic Limits for Building Flat Roofs with a Permeable Vapour Retarder Christian Bludau 1,*, Hartwig

More information

PH-CALCULATION Dynamic simulation with WUFI

PH-CALCULATION Dynamic simulation with WUFI 03.04 DYNAMIC SIMULATION 03.04_PH-SUMMER SCHOOL PH-CALCULATION Dynamic simulation with WUFI Composition: Christoph BUXBAUM and Ernst HEIDUK Language support: Mark TOLSON Date: 2008-09-18 This presentation

More information

Mathematical Applications in Science and Mechanics

Mathematical Applications in Science and Mechanics Energy Balance of AAC Building Envelopes with Mineral-Wool Thermal Insulation: Effect of Moisture Content VÁCLAV KOČÍ, ROBERT ČERNÝ Department of Materials Engineering and Chemistry, Faculty of Civil Engineering,

More information

EXPERIMENTAL ANALYSIS OF WATER AND WATER VAPOR TRANSPORT IN COATING- SUBSTRATE SYSTEMS

EXPERIMENTAL ANALYSIS OF WATER AND WATER VAPOR TRANSPORT IN COATING- SUBSTRATE SYSTEMS EXPERIMENTAL ANALYSIS OF WATER AND WATER VAPOR TRANSPORT IN COATING- SUBSTRATE SYSTEMS Milena Jiřičková, Robert Černý Czech Technical University, Faculty of Civil Engineering, Department of Structural

More information

RESTORATION MEASURES THAT SAVE ENERGY. Insulating Without Losing Face

RESTORATION MEASURES THAT SAVE ENERGY. Insulating Without Losing Face RESTORATION MEASURES THAT SAVE ENERGY Insulating Without Losing Face DOING SOMETHING TO PROTECT THE CLIMATE There s a lot to be done yet Our climate concerns us all! The subjects of energy and climate

More information

Performance of internal wall insulation systems - experimental test for the validation of a hygrothermal simulation tool

Performance of internal wall insulation systems - experimental test for the validation of a hygrothermal simulation tool Performance of internal wall insulation systems - experimental test for the validation of a hygrothermal simulation tool Valentina Marincioni, M.Sc. 1 Hector Altamirano-Medina, Ph.D. 1 Ian Ridley, Ph.D.

More information

Buildings XI Conference Workshop 2: Thermal Mass IV Assessing Thermal and Moisture Control Benefits of PCM Components by Hygrothermal Simulation

Buildings XI Conference Workshop 2: Thermal Mass IV Assessing Thermal and Moisture Control Benefits of PCM Components by Hygrothermal Simulation Buildings XI Conference Workshop 2: Thermal Mass IV Assessing Thermal and Moisture Control Benefits of PCM Components by Hygrothermal Simulation Hartwig M. Künzel, Fraunhofer Institute for Building Physics

More information

Hygrothermal behaviour of timber frame walls finished with a brick veneer cladding

Hygrothermal behaviour of timber frame walls finished with a brick veneer cladding Available online at www.sciencedirect.com ScienceDirect Energy Procedia 132 (2017) 363 368 www.elsevier.com/locate/procedia 11th Nordic Symposium on Building Physics, NSB2017, 11-14 June 2017, Trondheim,

More information

External thermal insulation composite system

External thermal insulation composite system Ytong Multipor Mineral Insulation Boards External thermal insulation composite system Ytong Multipor in external thermal insulation composite system Ytong Multipor: the sustainable external thermal insulation

More information

Detailed heat, air and moisture transport modelling in cavity walls ::::::: M. Van Belleghem, M. De Paepe M. Steeman L. De Backer & A.

Detailed heat, air and moisture transport modelling in cavity walls ::::::: M. Van Belleghem, M. De Paepe M. Steeman L. De Backer & A. ::::::: Detailed heat, air and moisture transport modelling in cavity walls M. Van Belleghem, M. De Paepe M. Steeman L. De Backer & A. Janssens Ghent University CESBP 2013 Introduction: cavity walls Building

More information

Study on Waterproof and Air Permeability of Inorganic Insulated Decorative Panel

Study on Waterproof and Air Permeability of Inorganic Insulated Decorative Panel Study on Waterproof and Air Permeability of Inorganic Insulated Decorative Panel Hu Xiang-lei 1, a, Wang Hong-jun 1 and Gao Ying 2 1 College of Architecture and Urban Planning, Tongji University, China

More information

Available online at ScienceDirect. Procedia Engineering 111 (2015 )

Available online at  ScienceDirect. Procedia Engineering 111 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 111 (2015 ) 311 316 XXIV R-S-P seminar, Theoretical Foundation of Civil Engineering (24RSP) (TFoCE 2015) Analysis of the possibilities

More information

CEN/TC 89 - Thermal performance of buildings and building components

CEN/TC 89 - Thermal performance of buildings and building components CEN/TC 89 - Thermal performance of buildings and building components Standard reference EN 1934:1998 EN 1946-1:1999 EN 1946-2:1999 EN 1946-3:1999 EN 1946-4:2000 EN 1946-5:2000 6946:2007 7345:1995 8497:1996

More information

Thermal Patterns Created By Moisture Accumulation Within Exterior Masonry Walls by A. Colantonio* and G. Desroches ** * Public Works And Government Services Canada, Ottawa, Canada ** Public Works And Government

More information

Optimizimg energy-efficiency of late 19th century ( Gründerzeit ) buildings

Optimizimg energy-efficiency of late 19th century ( Gründerzeit ) buildings Optimizimg energy-efficiency of late 19th century ( Gründerzeit ) buildings Practical suggestions for the construction of details of interior insulation with special regard to the requirements of the energy

More information

Experimental Study to Evaluate the Performance of Iraqi Passive House in Summer Season

Experimental Study to Evaluate the Performance of Iraqi Passive House in Summer Season Journal of Energy and Power Engineering 9 (2015) 386-392 doi: 10.17265/1934-8975/2015.04.008 D DAVID PUBLISHING Experimental Study to Evaluate the Performance of Iraqi Passive House in Summer Season Ghanim

More information

Hygrothermal Performance of Flat Roofs with Construction Moisture

Hygrothermal Performance of Flat Roofs with Construction Moisture Hygrothermal Performance of Flat Roofs with Construction Moisture Christian Bludau Hartwig M. Künzel, DrIng Daniel Zirkelbach Member ASHRAE ABSTRACT Rainwater intrusion in a flat roof during construction

More information

Flexible Vapor Control Solves Moisture Problems of Building Assemblies - Smart Retarder to Replace the Conventional PE-Film

Flexible Vapor Control Solves Moisture Problems of Building Assemblies - Smart Retarder to Replace the Conventional PE-Film Flexible Vapor Control Solves Moisture Problems of Building Assemblies - Smart Retarder to Replace the Conventional PE-Film HARTWIG M. KÜNZEL Fraunhofer-Institute of Building Physics (Director: Prof. Dr.-Ing.

More information

Air leakage and hygrothermal performance of an internally insulated log house

Air leakage and hygrothermal performance of an internally insulated log house Air leakage and hygrothermal performance of an internally insulated log house Üllar Alev, M.Sc 1 Andres Uus, M.Sc 2,3 Marko Teder, M.Sc 2 Martti-Jaan Miljan, M.Sc 2 Targo Kalamees, Professor 1 1 Tallinn

More information

Prevent damp and mold issues once and for all

Prevent damp and mold issues once and for all Prevent damp and mold issues once and for all Why SkamoWall? SkamoWall is the answer to a recurrent challenge for those who have problems with cold and damp interior walls that accumulate moisture and

More information

Thermal Performance Degradation of Foam Insulation in Inverted Roofs Due to Moisture Accumulation

Thermal Performance Degradation of Foam Insulation in Inverted Roofs Due to Moisture Accumulation Thermal Performance Degradation of Foam Insulation in Inverted Roofs Due to Moisture Accumulation Daniel Zirkelbach 1 Beate Schafaczek 2 Hartwig Künzel 3 ABSTRACT A normal roofing membrane is exposed to

More information

On the hygrothermal performance of straw bale wall elements in Belgium

On the hygrothermal performance of straw bale wall elements in Belgium Sustainability in Energy and Buildings: Research Advances: Vol 3: Sustainability in Energy and Buildings (SEB-14) Short Papers pp.37-42 : seb14s-007 On the hygrothermal performance of straw bale wall elements

More information

GLASS SELECTION GUIDE

GLASS SELECTION GUIDE GLASS SELECTION GUIDE www.metrotech.co.nz GLASS SELECTION The Glass Selection Flow Chart should be used in conjunction with the Selection Sheets and Section 11.1.2 of the Catalogue and Reference Guide

More information

IBP. akustik Hygrothermics

IBP. akustik Hygrothermics IBP FRAUNHOFER Institute for Building Physics IBP akustik Hygrothermics »Water is fluid, soft and yielding. But water will wear away rock.«lao Tzu Hygrothermics The Hygrothermics Department specializes

More information

A NEW MODEL FOR PREDICTION AND ITS APPLICATION IN PRACTICE

A NEW MODEL FOR PREDICTION AND ITS APPLICATION IN PRACTICE A NEW MODEL FOR PREDICTION AND ITS APPLICATION IN PRACTICE M. Krus, and K. Sedlbauer Fraunhofer Institute for Building Physics, Holzkirchen, Germany ABSTRACT In buildings growing conditions for mould fungi

More information

STUDY ON WETTING AND DRYING OF CLAY BRICK HAVING SURFACE COATINGS

STUDY ON WETTING AND DRYING OF CLAY BRICK HAVING SURFACE COATINGS 10 th Canadian Masonry Symposium, Banff, Alberta, June 8 12, 2005 STUDY ON WETTING AND DRYING OF CLAY BRICK HAVING SURFACE COATINGS P.J. Kelly Senior Product Quality Manager, Hanson Brick ABSTRACT This

More information

Heat, Air and Moisture (HAM) modeling of historic windows

Heat, Air and Moisture (HAM) modeling of historic windows Heat, Air and Moisture (HAM) modeling of historic windows H.L. (Henk) Schellen (PhD) Eindhoven University of Technology, Department of Building and Architecture, VRT 6.29; P.O. Box 513; 5600 MB Eindhoven;

More information

THERMAL PERFORMANCE OF WALL-ROOF INTERSECTION AREAS IN THE EXTERNAL ENVELOPE OF RESIDENTIAL BUILDINGS M.C. ALTUN

THERMAL PERFORMANCE OF WALL-ROOF INTERSECTION AREAS IN THE EXTERNAL ENVELOPE OF RESIDENTIAL BUILDINGS M.C. ALTUN CIB World Building Congress, April 2001, Wellington, New Zealand Page 1 of 9 THERMAL PERFORMANCE OF WALL-ROOF INTERSECTION AREAS IN THE EXTERNAL ENVELOPE OF RESIDENTIAL BUILDINGS M.C. ALTUN Faculty of

More information

AN EXPERIMENTAL STUDY OF

AN EXPERIMENTAL STUDY OF Micro-CT and nano-ct for the hierarchical analysis of materials May 24 th, 2011 AN EXPERIMENTAL STUDY OF THE HYGRIC PERFORMANCE OF DIFFERENT INTERIOR INSULATION SYSTEMS PhD Hygrothermal analysis of interior

More information

Evaluation of the hygrothermal performance of a concrete wall construction with Icynene open cell insulation

Evaluation of the hygrothermal performance of a concrete wall construction with Icynene open cell insulation Fraunhofer-Institut für Bauphysik IBP Forschung, Entwicklung, Demonstration und Beratung auf den Gebieten der Bauphysik Zulassung neuer Baustoffe, Bauteile und Bauarten Bauaufsichtlich anerkannte Stelle

More information

Hygrothermal Calculations applied to water-repellent surfaces - Validation and Application -

Hygrothermal Calculations applied to water-repellent surfaces - Validation and Application - Krus, M.: Hygrothermal calculations applied to water-repellent surfaces validation and application. Proceedings Second International Conference on Surface Technology with Water Repellent Agents, ETH Zürich,

More information

Concept 9: Exterior refurbishment of wooden frame walls with flex system board insulation

Concept 9: Exterior refurbishment of wooden frame walls with flex system board insulation Concept 9: Exterior refurbishment of wooden frame walls with flex system board insulation Cross section figures of the existing wall / the refurbishment concept Market potential and reasoning Application

More information

INVESTIGATIONS OF GYPSUM BOARDS WITH REGARD TO THE MOISTURE-BUFFERING-EFFECTS

INVESTIGATIONS OF GYPSUM BOARDS WITH REGARD TO THE MOISTURE-BUFFERING-EFFECTS INVESTIGATIONS OF GYPSUM BOARDS WITH REGARD TO THE MOISTURE-BUFFERING-EFFECTS Kristin Lengsfeld, Andreas Holm, and Martin Krus Department of Indoor Environment and Climate Impacts, Fraunhofer-Institute

More information

Control of Moisture Safety Design by Comparison between Calculations and Measurements in Passive House Walls Made of Wood

Control of Moisture Safety Design by Comparison between Calculations and Measurements in Passive House Walls Made of Wood Control of Moisture Safety Design by Comparison between Calculations and Measurements in Passive House Walls Made of Wood S. Olof Hägerstedt 1 Lars-Erik Harderup 2 ABSTRACT The use of passive house technique

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Impact on indoor climate depending on the moisture buffering of building materials

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Impact on indoor climate depending on the moisture buffering of building materials Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0101 ISBN: 978-83-7947-232-1 Impact on indoor climate depending on the moisture buffering of building materials Kristin Lengsfeld 1,*,

More information

Thermal Control in Buildings by John Straube (updated )

Thermal Control in Buildings by John Straube (updated ) building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Building Science Digest 011 Thermal Control in Buildings 2006-11-02 by John Straube (updated 2011-12-12)

More information

Introduction Retrofit interior insulation of masonry buildings Exterior insulation ideal solution Interstitial condensation, freeze thaw issues

Introduction Retrofit interior insulation of masonry buildings Exterior insulation ideal solution Interstitial condensation, freeze thaw issues Introduction Retrofit interior insulation of masonry buildings Exterior insulation ideal solution Interstitial condensation, freeze thaw issues Kohta Ueno, Building Science Corporation Masonry Wall Interior

More information

IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE

IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE Dr. Essam Al-Sayed Omar Department Manager Kuwait Institute for Scientific Research Kuwait ABSTRACT This paper addresses the

More information

Moisture problems of functional joints of wooden windows causes analysis

Moisture problems of functional joints of wooden windows causes analysis Moisture problems of functional joints of wooden windows causes analysis Adela Palková 1,*, Milan Palko 1, and Peter Buday 1 1 Department of Building Constructions, Slovak University of Technology in Bratislava,

More information

Title Inner Wall in Hagia Sophia, Istanbu. Citation Energy Procedia (2015), 78:

Title Inner Wall in Hagia Sophia, Istanbu. Citation Energy Procedia (2015), 78: Title Influence of the Infiltrated Rainwa Inner Wall in Hagia Sophia, Istanbu Author(s) Mizutani, Etsuko; Ogura, Daisuke; I Masaru; Sasaki, Juni Citation Energy Procedia (2015), 78: 1353-13 Issue Date

More information

MOISTURE CONDITIONS IN WALLS AND CEILINGS OF A SIMULATED OLDER HOME DURING WINTER

MOISTURE CONDITIONS IN WALLS AND CEILINGS OF A SIMULATED OLDER HOME DURING WINTER MOISTURE CONDITIONS IN WALLS AND CEILINGS OF A SIMULATED OLDER HOME DURING WINTER USDA FOREST SERVICE RESEARCH PAPER FPL 290 1977 U.S. DEPARTMENT OF AGRICULTURE FOREST SERVICE FOREST PRODUCTS LABORATORY

More information

CAE 331/513 Building Science Fall 2017

CAE 331/513 Building Science Fall 2017 CAE 331/513 Building Science Fall 2017 November 14, 2017 Heating load calculations Advancing energy, environmental, and sustainability research within the built environment www.built-envi.com Twitter:

More information

Hygrothermal behaviour of compact roofs under Belgian climate

Hygrothermal behaviour of compact roofs under Belgian climate Hygrothermal behaviour of compact roofs under Belgian climate Glenn De Meersman 1 Nathan Van Den Bossche 2 Arnold Janssens 3 Robbe Verelst 4 T 2 ABSTRACT Compact flat roofs are more and more constructed

More information

Observation of Liquid-filled Window without Presence of Liquid in Test Chamber

Observation of Liquid-filled Window without Presence of Liquid in Test Chamber SSP - JOURNAL OF CIVIL ENGINEERING Vol. 11, Issue 2, 2016 DOI: 10.1515/sspjce-2016-0020 Observation of Liquid-filled Window without Presence of Liquid in Test Chamber Ján Lojkovics Technical University

More information

Numerical Simulation of a Building Envelope with High Performance Materials

Numerical Simulation of a Building Envelope with High Performance Materials Excerpt from the Proceedings of the COMSOL Conference 2010 Paris Numerical Simulation of a Building Envelope with High Performance Materials Mohammad H. Baghban *1, Per J. Hovde 1 and Arild Gustavsen 2

More information

Investigation of post-insulated walls with wooden beam ends

Investigation of post-insulated walls with wooden beam ends Investigation of post-insulated walls with wooden beam ends Risk analysis for different insulation techniques J. Borderon, E. Héberlé, A. Cuny and J. Burgholzer Centre for studies and expertise on risks,

More information

HEAT AND MOISTURE TRANSPORT IN A CAST GYPSUM WALL WITH EXTERIOR THERMAL INSULATION

HEAT AND MOISTURE TRANSPORT IN A CAST GYPSUM WALL WITH EXTERIOR THERMAL INSULATION HEAT AND MOISTURE TRANSPORT IN A CAST GYPSUM WALL WITH EXTERIOR THERMAL INSULATION Jiří Maděra, Pavel Tesárek, Robert Černý Department of Structural Mechanics, Faculty of Civil Engineering, Czech Technical

More information

Moisture convection performance on the joint of external wall and attic floor - laboratory tests and two-dimensional simulation model validation

Moisture convection performance on the joint of external wall and attic floor - laboratory tests and two-dimensional simulation model validation Moisture convection performance on the joint of external wall and attic floor - laboratory tests and two-dimensional simulation model validation Targo Kalamees, Jarek Kurnitski HVAC-Laboratory, Helsinki

More information

Application of a Computer Model for Integrated Hygrothermal Building Analysis

Application of a Computer Model for Integrated Hygrothermal Building Analysis Application of a Computer Model for Integrated Hygrothermal Building Analysis Carsten Rode, Technical University of Denmark car@byg.dtu.dk Lars C. Sørensen Birch & Krogboe A/S LCS@birch-krogboe.dk Karl

More information

Index. STP779-EB/Jul. 1982

Index. STP779-EB/Jul. 1982 STP779-EB/Jul. 1982 Index A Absorption of moisture (see Moisture absorption) Adsorption, 191 Capillary versus time, 197 Isotherms For glass fiber, 194, 195 For various materials, 196 Air leakage (exfiltration,

More information

Material characterization models and test methods for historic building materials

Material characterization models and test methods for historic building materials Downloaded from vbn.aau.dk on: januar 19, 2019 Aalborg Universitet Material characterization models and test methods for historic building materials Hansen, Tessa Kvist; Peuhkuri, Ruut Hannele; Møller,

More information

Mold in Building Constructions in the Nordic Countries With Emphasis on Roofs

Mold in Building Constructions in the Nordic Countries With Emphasis on Roofs Mold in Building Constructions in the Nordic Countries With Emphasis on Roofs Erik Brandt Danish Building Research Institute (SBI) Tommy Bunch Nielsen Danish Roofing Advisory Board (TOR) Roof Consultants

More information

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS 1. ABSTRACT In modern architecture the buildings are often designed with large glass facades or windows. Due to these

More information

Concept 4: T1b. ETICS applied to sandwich element internal layer with smooth element surface

Concept 4: T1b. ETICS applied to sandwich element internal layer with smooth element surface Concept 4: T1b. ETICS applied to sandwich element internal layer with smooth element surface Cross section figures of the existing wall / the refurbishment concept Market potential and reasoning Application

More information

A sound indoor climate for a museum in a monumental building Schellen, H.L.; Martens, M.H.J.

A sound indoor climate for a museum in a monumental building Schellen, H.L.; Martens, M.H.J. A sound indoor climate for a museum in a monumental building Schellen, H.L.; Martens, M.H.J. Published in: Symposium Building Physics in honour of Prof. Hugo Hens, Leuven, October 2008 Published: 01/01/2008

More information

Hygrothermal Performance of Timber External Walls Insulated with Natural and Industrial Materials

Hygrothermal Performance of Timber External Walls Insulated with Natural and Industrial Materials Hygrothermal Performance of Timber External Walls Insulated with Natural and Industrial Materials Martti-Jaan Miljan 1[0000-0001-7038-5653] and Jaan Miljan 1[0000-0001-6800-8859] 1 Estonian University

More information

Refurbishment measures of historic masonry construction Vilnius

Refurbishment measures of historic masonry construction Vilnius Refurbishment measures of historic masonry construction 2012-04-13 Vilnius Protection of architectural monuments External wall insulation on external facades are the most popular methods according to construction

More information

2006 Building Science Press All rights of reproduction in any form reserved.

2006 Building Science Press All rights of reproduction in any form reserved. building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Building Science Digest 011 Thermal Control in Buildings 2006-11-07 by John Straube Abstract: Providing

More information

A sound indoor climate for a museum in a monumental building Schellen, H.L.; Martens, M.H.J.

A sound indoor climate for a museum in a monumental building Schellen, H.L.; Martens, M.H.J. A sound indoor climate for a museum in a monumental building Schellen, H.L.; Martens, M.H.J. Published in: Symposium Building Physics in honour of Prof. Hugo Hens, Leuven, October 2008 Published: 01/01/2008

More information

Comparative evaluation of the predictions of two established mould growth models

Comparative evaluation of the predictions of two established mould growth models 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116,part 2). For personal use only. Additional reproduction,

More information

Royal Institute for Cultural Heritage (KIK-IRPA), Laboratories Department, Brussels, Belgium; 2 Daidalos-Peutz Engineers, Leuven, Belgium

Royal Institute for Cultural Heritage (KIK-IRPA), Laboratories Department, Brussels, Belgium; 2 Daidalos-Peutz Engineers, Leuven, Belgium Hygrothermal analysis of the façades of the former veterinary school in Anderlecht (Belgium) for the risk assessment of internal thermal insulation Roel Hendrickx 1 ; Hilde De Clercq 1 ; Friedl Decock

More information

Investigation of interior post-insulated masonry walls with wooden beam ends

Investigation of interior post-insulated masonry walls with wooden beam ends Downloaded from orbit.dtu.dk on: Sep 02, 2018 Investigation of interior post-insulated masonry walls with wooden beam ends Morelli, Martin; Svendsen, Svend Published in: Journal of Building Physics Link

More information

Assessment of the Risk for Mold Growth in a Wall Retrofitted with Vacuum Insulation Panels

Assessment of the Risk for Mold Growth in a Wall Retrofitted with Vacuum Insulation Panels Assessment of the Risk for Mold Growth in a Wall Retrofitted with Vacuum Insulation Panels Pär Johansson, M.Sc. 1 1 Chalmers University of Technology, Sweden KEYWORDS: vacuum insulation panels, retrofitting,

More information

Rasmus Elbæk Hedegaard et al. / Energy Procedia 132 (2017)

Rasmus Elbæk Hedegaard et al. / Energy Procedia 132 (2017) Available online at www.sciencedirect.com ScienceDirect Energy Procedia 132 (2017) 982 987 www.elsevier.com/locate/procedia 11th Nordic Symposium on Building Physics, NSB2017, 11-14 June 2017, Trondheim,

More information

COMPARISON OF THERMAL PERFORMANCE OF DIFFERENT WALL STRUCTURES

COMPARISON OF THERMAL PERFORMANCE OF DIFFERENT WALL STRUCTURES HEFAT2012 9 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 16 18 July 2012 Malta COMPARISON OF THERMAL PERFORMANCE OF DIFFERENT WALL STRUCTURES Ozel M.* and Ozel C. *Author

More information

Hygrothermal modelling of a sustainable retrofit taking into account the urban microclimate. Case study of the medieval city center of Cahors (France)

Hygrothermal modelling of a sustainable retrofit taking into account the urban microclimate. Case study of the medieval city center of Cahors (France) Hygrothermal modelling of a sustainable retrofit taking into account the urban microclimate. Case study of the medieval city center of Cahors (France) Sophie Claude 1, Stéphane Ginestet 1, Marion Bonhomme

More information

Effect of insulation ground on anti-condensation in rural residence

Effect of insulation ground on anti-condensation in rural residence Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia International High- Performance Built Environment Conference A Sustainable

More information

Lecture 3: Utilization of Passive Solar Technology

Lecture 3: Utilization of Passive Solar Technology Lecture 3: Utilization of Passive Solar Technology http://www.cs.kumamoto-u.ac.jp/epslab/apsf/ Lecturers: Syafaruddin & Takashi Hiyama syafa@st.eecs.kumamoto-u.ac.jp hiyama@cs.kumamoto-u.ac.jp Time and

More information

Adhered Veneers and Inward Vapor Drives: Significance, Problems and

Adhered Veneers and Inward Vapor Drives: Significance, Problems and Feature Adhered Veneers and Inward Vapor Drives: Significance, Problems and Solutions By Dr. John Straube, P.Eng., Chris Schumacher, Jonathan Smegal and Marcus Jablonka Adhered veneers, in which masonry

More information

Combined heat, moisture and CFD modelling to assess the impact of climate control on local climates near cultural objects in a museum exhibition room

Combined heat, moisture and CFD modelling to assess the impact of climate control on local climates near cultural objects in a museum exhibition room Combined heat, moisture and CFD modelling to assess the impact of climate control on local climates near cultural objects in a museum exhibition room K. Kompatscher *1, S. Kochen 1, A.W.M. van Schijndel

More information

Assessing the energy performance of modern glass facade systems

Assessing the energy performance of modern glass facade systems Assessing the energy performance of modern glass facade systems Abdelsalam Aldawoud * Architectural Engineering Department, University of Sharjah Sharjah, United Arab Emirates Abstract. The design and

More information

Hygrothermal properties applied in numerical simulation: Interstitial condensation analysis Received (in revised form): 24th July 2009

Hygrothermal properties applied in numerical simulation: Interstitial condensation analysis Received (in revised form): 24th July 2009 Original Article Hygrothermal properties applied in numerical simulation: Interstitial condensation analysis Received (in revised form): 24th July 29 Nuno M o n te i ro Ram os is Assistant Professor since

More information

2001 National Workshop on State Building Energy Codes July th, 2001 Burlington, Vermont

2001 National Workshop on State Building Energy Codes July th, 2001 Burlington, Vermont 2001 National Workshop on State Building Energy Codes July 16-19 th, 2001 Burlington, Vermont A Systems Engineering Approach to the Design of Energy and Resource Efficient Homes Presented By: Mark LaLiberte

More information

Properties of the render FIXIT 222 and its potential use in building retrofit -A case study in Switzerland -Simulation with Norwegian Climate data

Properties of the render FIXIT 222 and its potential use in building retrofit -A case study in Switzerland -Simulation with Norwegian Climate data Willkommen Welcome Bienvenue Properties of the render FIXIT 222 and its potential use in building retrofit -A case study in Switzerland -Simulation with Norwegian Climate data Presentation in Oslo, Norway

More information

Thermal Rehabilitation of Existing Building Enclosures by Using VIP (Vacuum Insulation Panel) Sandwich and Timber Based Panels

Thermal Rehabilitation of Existing Building Enclosures by Using VIP (Vacuum Insulation Panel) Sandwich and Timber Based Panels Thermal Rehabilitation of Existing Building Enclosures by Using VIP (Vacuum Insulation Panel) Sandwich and Timber Based Panels Dr. Christoph Buxbaum 1, Wolfgang Gallent 1, Sandra Kircher 2, Oskar Pankratz

More information

THEORETICAL RESEARCH REGARDING HEAT TRANSFER BETWEEN GREENHOUSES AND ENVIRONMENT

THEORETICAL RESEARCH REGARDING HEAT TRANSFER BETWEEN GREENHOUSES AND ENVIRONMENT 3 rd International Conference Research & Innovation in Engineering COMAT 2014 16-17 October 2014, Braşov, Romania THEORETICAL RESEARCH REGARDING HEAT TRANSFER BETWEEN GREENHOUSES AND ENVIRONMENT Bodolan

More information

This presentation. Functions of the building enclosure. University of Waterloo and Balanced Solutions. Straube Presentation Building Canada

This presentation. Functions of the building enclosure. University of Waterloo and Balanced Solutions. Straube Presentation Building Canada Hygrothermal Basement Performance, or Why do we get water when we dig holes in the ground? Dr John Straube October, 2004 This presentation What do basements do Examine performance Why problems What solutions

More information

Adhered Veneers and Inward Vapor Drives: Significance, Problems and

Adhered Veneers and Inward Vapor Drives: Significance, Problems and Feature Adhered Veneers and Inward Vapor Drives: Significance, Problems and Solutions By Dr. John Straube, P.Eng., Chris Schumacher, Jonathan Smegal and Marcus Jablonka ADHERED VENEERS, IN WHICH MA- SONRY

More information

WUFI: Moisture Engineering in the 21 st Century (and Beyond)

WUFI: Moisture Engineering in the 21 st Century (and Beyond) WUFI: Moisture Engineering in the 21 st Century (and Beyond) Andre Desjarlais Oak Ridge National Laboratory 15 September 2011 What is WUFI? 2 Managed by UT-Battelle Presentation Summary Are we concerned

More information

Lime Render & Why Buildings Need to Breathe

Lime Render & Why Buildings Need to Breathe Lime Render & Why Buildings Need to Breathe Paint More Than Colour Keim Mineral Paints - The Mineral Difference The need for buildings to breathe Before the twentieth century, building techniques and materials

More information

A SYSTEMATIC APPROACH TO HYGROTHERMAL MODELING AND COMPLIANCE WITH FAILURE CRITERIA USING WUFI

A SYSTEMATIC APPROACH TO HYGROTHERMAL MODELING AND COMPLIANCE WITH FAILURE CRITERIA USING WUFI August 1-3, A SYSTEMATIC APPROACH TO HYGROTHERMAL MODELING AND COMPLIANCE WITH FAILURE CRITERIA USING WUFI Pallavi Mantha 1 and Lois B. Arena 1 1 Steven Winter Associates Inc., Norwalk, CT ABSTRACT Simulating

More information

RESULTS OF LONG-TERM ENERGY EFFICIENCY MONITORING OF TEST BUILDINGS UNDER REAL CLIMATIC CONDITIONS

RESULTS OF LONG-TERM ENERGY EFFICIENCY MONITORING OF TEST BUILDINGS UNDER REAL CLIMATIC CONDITIONS Section Green Buildings Technologies and Materials RESULTS OF LONG-TERM ENERGY EFFICIENCY MONITORING OF TEST BUILDINGS UNDER REAL CLIMATIC CONDITIONS Dr. Staņislavs Gendelis Assoc. Prof. Dr. Andris Jakovičs

More information

COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES

COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES Lusi Susanti 1, Hiroshi Matsumoto 2, and Hiroshi Homma 2 1 Department of

More information

Control of moisture safety design by comparison between calculations and measurements in passive house walls made of wood

Control of moisture safety design by comparison between calculations and measurements in passive house walls made of wood Control of moisture safety design by comparison between calculations and measurements in passive house walls made of wood Mundt Petersen, Solof; Harderup, Lars-Erik Published in: Proceedings fo the 12th

More information

DATA SHEET. Multi-adherent coating: adheres on all construction materials, including iron, galvanized and aluminum

DATA SHEET. Multi-adherent coating: adheres on all construction materials, including iron, galvanized and aluminum DATA SHEET DESCRIPTION REVECORK is a: Thermal coating: reduces heat and cold flow Acoustic coating: reduces the aerial and impact noise Elastic coating: supports contractions and expansions Multi-adherent

More information

Analysis of the suitability of mould growth models for the risk assessment of woodfibre internal wall insulation

Analysis of the suitability of mould growth models for the risk assessment of woodfibre internal wall insulation Available online at www.sciencedirect.com ScienceDirect Energy Procedia 132 (2017) 183 188 www.elsevier.com/locate/procedia 11th Nordic Symposium on Building Physics, NSB2017, 11-14 June 2017, Trondheim,

More information

New Approaches to Energy Efficiency & Green Building. Who is Icynene Inc.? World-Wide Distribution. The Icynene Insulation System

New Approaches to Energy Efficiency & Green Building. Who is Icynene Inc.? World-Wide Distribution. The Icynene Insulation System The Icynene Insulation System New Approaches to Energy Efficiency & Green Building Control of Air Leakage and Moisture Vapour Transmission Who is Icynene Inc.? Founded in November, 1986 in Toronto Canada

More information

Insulating Basements: Part 1 Fundamentals

Insulating Basements: Part 1 Fundamentals The Pennsylvania Housing Research Center Insulating Basements: Part 1 Fundamentals Builder Brief: BB0510 Brian Wolfgang, PHRC Fellow INTRODUCTION The perception of a basement has changed significantly

More information

Simulink modelling tool for HAM-system analyses in building physics

Simulink modelling tool for HAM-system analyses in building physics Simulink modelling tool for HAM-system analyses in building physics Angela Sasic Kalagasidis, MSc Carl-Eric Hagentoft, Professor, Dr.Sc. * 1. INTRODUCTION A calculation tool for HAM (heat, air and moisture)

More information