Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc.

Size: px
Start display at page:

Download "Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc."

Transcription

1 Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT Report Number: C Rendered to: Tubelite Inc. Walker, Michigan MODEL DESIGNATION: 400 Series Curtainwall with 4 Sided SSG PRODUCT TYPE: Curtainwall This report contains in its entirety: Cover Page: 1 page Report Body: 8 pages Appendix A: 5 sheets Appendix B: 22 sheets Appendix C: 3 sheets Alteration Log: 1 page Revision Log: 1 page :23:47-04'00' Test Dates: Report Date: 7/9/2012 7/12/2012 7/24/12

2 Test Report No.: C Report Date: 7/24/2012 Test Record Retention End Date: 7/24/2016 Page: 1 of CLIENT IDENTIFICATION 1.1 Report Issued To: Tubelite Inc Walker Ridge Drive NW Walker, Michigan Contact Person: Steve Wilkening 2.0 LABORATORY IDENTIFICATION 2.1 Laboratory Location: Architectural Testing, Inc Garden Road Riviera Beach, Florida Laboratory Phone Number: PROJECT SUMMARY 3.1 Introduction: Tubelite Inc. retained Architectural Testing, Inc. to conduct ASTM E283, E330, and E331 testing on their 400 Series Curtainwall with 4 Sided SSG. 3.2 Summary of Test Results: Table 1 provides a summary of the test results for each test specimen. Testing commenced July 9, 2012 and was completed July 12, Table 1: Summary of Test Results Specimen # Test Method Test Conditions Test Conclusion Air Infiltration Test 75 & 300 Pa (ASTM E283) (1.57 & 6.24 psf) PASS Water Infiltration Test 718 Pa K (ASTM E331) (15 psf) PASS +2871/-2871 Pa Static Load Test (+60/-60 psf) (ASTM E330) Design Wind Load PASS 3.3 Test Record Retention End Date: All test records for this report will be retained until July 24, APPLICABLE TEST METHODS, SPECIFICATIONS, AND PROTOCOLS ASTM E Standard Test Method for Determining Rate of Air Leakage through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen ASTM E Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference ASTM E Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference

3 Test Report No.: C Report Date: 7/24/2012 Test Record Retention End Date: 7/24/2016 Page: 2 of TEST SPECIMEN IDENTIFICATION 5.1 Test Specimen Type: Curtainwall 5.2 Model Designation: 400 Series Curtainwall with 4 Sided SSG 5.3 Overall Size: 4407 mm (w) x 3188 mm (h) (w) x (h) 5.4 Configuration O/O/O-O/O/O-O/O/O-O/O/O 5.5 Number of Operable Door Leaves: None tested 5.6 Drawings: Test specimen construction was verified by Architectural Testing, Inc. per the drawings located in Appendix A. Any deviations are documented herein and/or on the drawings. 5.7 Test Specimen Source: Tubelite Inc. provided the test specimen. 6.0 TEST SPECIMEN DESCRIPTION 6.1 Frame Construction The frame was fabricated using the aluminum extrusions defined in Table 2. Table 2: Aluminum Frame Extrusion Details Frame Member Part # Description Material Head, sill, and jamb E55TB02 Curtainwall tube Intermediate horizontal mullion E5TB108 Curtainwall tube 6063-T5 Aluminum Intermediate vertical mullion E55TB04 Butt glazing tube Corner Construction At each frame corner, the vertical frame member ran through while the horizontal frame member end was square cut, butted and mechanically attached to the vertical member via an aluminum shear block. The additional details of the corner construction are described in Table 3. Table 3: Corner Construction Location Construction Details Joint Sealant Head and sill corners A mm (4.918") long shear block (Part # PTB49) was attached to the horizontal frame member using two (2), #10-24 x 3/4 SS PH screws (Part # S270) into the exterior of the horizontal through the shear block screw splines. The shear block was attached to the vertical frame member using two (2), 1/4-20 x 1 HH Type D screws (Part # S328). Intermediate horizontal corners at jambs Corners at the intermediate vertical and horizontal mullions A mm (4.288") long shear block (Part # PTB96C) was attached to the horizontal frame member using two (2), #10-24 x 3/4 SS PH screws (Part # S270) into the exterior of the horizontal through the shear block screw splines. The shear block was attached to the vertical frame member using two (2), 1/4-20 x 1 HH Type D screws (Part # S328). A mm (4.288") long shear block (Part # PTB96C) was attached to the horizontal frame member using two (2), #10-24 x 3/4 SS PH screws (Part # S270) into the exterior of the horizontal through the shear block screw splines. The shear block was attached to the vertical frame member using two (2), 1/4-20 x 1 HH Type D screws (Part # S328). Each joint was sealed using Dow Corning 983 Silicone Glazing and Curtainwall Adhesive/Sealant A single pocket foam water dam (Part # PTB93) and an ethafoam rod (Part # P1094) were utilized at the end of each horizontal member and each joint was sealed using Dow Corning 983 Silicone Glazing and Curtainwall Adhesive/Sealant

4 Test Report No.: C Report Date: 7/24/2012 Test Record Retention End Date: 7/24/2016 Page: 3 of Pressure Plate and Snap Cover Assembly Table 4 provides the extrusions used in the pressure plate and snap cover assemblies. There was a continuous rubber thermal barrier (Part # PTB94) between each pressure plate and the adjacent frame member. Table 4: Pressure Plate and Snap Cover Details Frame Member Part # Material Description Head, sill, and jamb pressure plate Pressure plate cover M4TB225 E4TB T5 Aluminum 6063-T5 Aluminum The pressure plate was attached to the adjacent frame member using a single row of 1/4-20 x 3/4 HH Type F screws (Part # S362) spaced 50.8 mm (2 ) from each end and at mm (6 ) on center thereafter. Each fastener head was sealed using silicone sealant. Face cover snap-fit to the adjacent pressure plate 6.3 Glazing Details Glazing Materials Glass Types GL1 through GL4 consisted of 25.4 mm (1 ) thick (nominal) insulated glass comprised of the following components: mm (1/4") tempered glass mm (1/2 ) air space mm (1/4") tempered glass Glazing Method The test specimen was exterior glazed. A 4.8 mm (3/16") thick EPDM setting block (Part # P6550) was used at the intermediate horizontals and a 7.9mm (5/16") thick EPDM setting block was used at the sill. Table 5 provides the interior and exterior glazing procedures (typical) used in the test specimen. Table 5: Glazing Procedures (typical) Location Interior Glazing Procedure Exterior Glazing Procedure Use a 50 ±5 durometer, 3.2 mm Use a 50 ±5 durometer, 3.2 mm Head, sill, and (1/8") thick EPDM glazing gasket (1/8") thick EPDM glazing gasket jambs (Part # PTB28) (Part # PTB28) Intermediate horizontal and vertical mullions Use a 70 ±5 durometer, 9.5 mm (3/8") thick rubber glazing gasket (Part # PTB75) followed by a 9.5 mm x 12.7 mm (3/8 x 1/2 ) bead of Dow Corning 983 Silicone Glazing and Curtainwall Adhesive/Sealant A bead of Dow Corning 983 Silicone Glazing and Curtainwall Adhesive/Sealant was applied between adjacent glass lites. The bead was 19.1 mm (3/4") wide at the horizontals and 9.5 mm (3/8") wide at the verticals.

5 Glazing Type Test Report No.: C Report Date: 7/24/2012 Test Record Retention End Date: 7/24/2016 Page: 4 of Daylight Opening and Glass Bite Table 6 provides the daylight opening and glass bite for each lite used in each test specimen. GL1 4 GL2 6 GL3 2 GL4 3 Table 6: Daylight Opening Size and Glass Bite Details Quantity Location Daylight Opening Size Glass Bite Far right and left of top and bottom rows Intermediate left, middle, and intermediate right of top and bottom rows Far right and left of middle row Intermediate left, middle, and intermediate right of middle row mm (w) x mm (h) 10-7/16" (w) x 10-5/8" (h) mm (w) x mm (h) 45-7/8" (w) x 10-5/8" (h) mm (w) x mm (h) 10-7/16" (w) x 94-1/4" (h) mm (w) x mm (h) 45-7/8" (w) x 94-1/4" (h) 12.7 mm (1/2") at head, sill, and jamb 22.2 mm (7/8") at intermediate horizontals 27.0 mm (1-1/16") at intermediate verticals 12.7 mm (1/2") at head and sill 22.2 mm (7/8") at intermediate horizontals 27.0 mm (1-1/16") at intermediate verticals 12.7 mm (1/2") at jambs 22.2 mm (7/8") at intermediate horizontals 27.0 mm (1-1/16") at intermediate verticals 22.2 mm (7/8") at intermediate horizontals 27.0 mm (1-1/16") at intermediate verticals 6.4 Weather Stripping An EPDM glazing gasket (Part # PTB28) slid into the raceway around the entire frame perimeter of the specimen. 6.5 Hardware No hardware was used. 6.6 Drainage Table 7 provides details of the drainage openings used in the test specimen. A weep baffle (Part # PTB42) was used inside the horizontal pressure plate covers at each opening location. Table 7: Drainage Opening Details Quantity Location Description Three (3) per Horizontal pressure plates - at mid-bay and location halfway between the 1/4 points and ends 6.4 mm (1/4 ) diameter hole Two (2) per location Horizontal pressure plate covers - 1 from each end to center of slot 6.4 mm x 12.7 mm (1/4 x 1/2 ) slot

6 6.7 Sealants Table 8 provides details of the sealants used in each test specimen. Test Report No.: C Report Date: 7/24/2012 Test Record Retention End Date: 7/24/2016 Page: 5 of 8 Location All sealant locations Table 8: Sealant Details Sealant Description Dow Corning 983 Silicone Glazing and Curtainwall Adhesive/Sealant 7.0 TEST SPECIMEN INSTALLATION Table 9 provides details of the test specimen installation into the steel opening. The rough opening allowed for a 12.7 mm (1/2 ) shim space. Table 9: Test Specimen Installation Details Location Fastener Description Quantity Head The locking nut (Part # P1267) was attached to the shear block with two (2), 3/8-16 x 2" Type F (Part # S218) and drilled for pipe sleeve (Part # P2028) clearance. One (1), 3/8-16 x 2-1/2 HH screw with the pipe sleeve attached through the shear block to the opening. Sill 8.0 TEST SEQUENCE One (1), 3/8-16 x 2-1/2 HH screw and locking nut (Part # P1267) attached through the shear block to the opening. Table 10 provides a summary of the test sequence for the test specimen. 9.0 TEST RESULTS Table 10: Test Sequence Test Specimen K 1. Air Infiltration Test 2. Water Infiltration Test 3. Water Infiltration Test 4. Uniform Static Load Test: Positive Design Load 5. Uniform Static Load Test: Negative Design Load 6. Water Infiltration Test 7. Uniform Static Load Test: Positive Proof Load 8. Uniform Static Load Test: Negative Proof Load 9.1 Air Infiltration Test Results Table 11 provides the results for the air infiltration test. Sequence #* 1 Table 11: Air Infiltration Test Results Test Pressure Measured Pa (psf) (cfm/ft 2 ) Allowed (cfm/ft 2 ) +75 (+1.57) 0.01 N/A +300 (+6.24) *Please refer to Section 8.0, Test Sequence for a description of the sequence number. 1 per jamb, 2 per intermediate mullion

7 Test Report No.: C Report Date: 7/24/2012 Test Record Retention End Date: 7/24/2016 Page: 6 of Conclusion Architectural Testing, Inc. observed a measured air infiltration less than the allowed air infiltration through the test specimen; as such, the test specimen satisfies the requirements of ASTM E Water Infiltration Test Results Table 12 provides the results for the water infiltration test. Table 12: Water Infiltration Test Results Sequence Test Pressure #* Pa (psf) Result 2 Fail (15) Pass 6 Pass *Please refer to Section 8.0, Test Sequence for a description of the sequence number Conclusion Architectural Testing, Inc. observed zero (0) water infiltration through the innermost plane of the test specimen; as such, the test specimen satisfies the requirements of ASTM E Uniform Static Load Test Deflection Gage Locations Figure 1 shows the deflection gage locations for the uniform static load test. Figure 1: Deflection Gage Locations Ambient Conditions The temperature range during the uniform static load test was 84 F to 88 F.

8 Test Report No.: C Report Date: 7/24/2012 Test Record Retention End Date: 7/24/2016 Page: 7 of Results Tables 13 and 14 provide the positive and negative uniform static load test results, respectively. The results are for the deflection gage locations shown in Section The deflection reported is the overall deflection between three points (longest unsupported span) which accounts for support movement. Sequence #* Load (psf) Table 13: Positive Uniform Static Load Test Results Gage Deflection Permanent Set Percent Location mm inch mm inch Recovery (%) Specimen #K B E H B E H *Please refer to Section 8.0, Test Sequence for a description of the sequence number. Sequence #* Load (psf) Table 14: Negative Uniform Static Load Test Results Gage Deflection Permanent Set Percent Location mm inch mm inch Recovery (%) Specimen #K B E H B E H *Please refer to Section 8.0, Test Sequence for a description of the sequence number Conclusion Architectural Testing, Inc. observed no signs of failure in any area of the test specimen during the uniform static load test; as such, the test specimen satisfies the uniform static load test requirements of ASTM E TEST EQUIPMENT DEFLECTION MEASURING DEVICE: Linear transducers 11.0 LABORATORY COMPLIANCE STATEMENTS All tests performed on this test specimen were conducted in accordance with the specifications of the applicable standards and test methods listed herein. All results obtained apply only to the specimen tested. The following are provided as required by the protocols for the testing reported herein: Tape or film was not used to seal against air leakage during structural testing.

9 Test Report No.: C Report Date: 7/24/2012 Test Record Retention End Date: 7/24/2016 Page: 8 of 8 Test specimen construction was verified by Architectural Testing, Inc. per the drawings located in Appendix A. Any deviations are documented herein and/or on the drawings. Architectural Testing, Inc. will service this report for the entire test record retention period. Test records that are retained, such as detailed drawings, data sheets, representative samples of test specimens, or other pertinent project documentation, will be retained by Architectural Testing, Inc. for the entire test record retention. If any test specimen contains glazing, no conclusions of any kind regarding the adequacy or inadequacy of the glass in any glazed test specimen can be made. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimens tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc APPENDICES This test report is incomplete if not accompanied by the following Appendices: Appendix A: Test Specimen Drawings... 5 Sheets Appendix B: Die/Part Drawings Sheets Appendix C: Specification Sheets... 3 Pages Alteration Log... 1 Page Revision Log... 1 Page 13.0 WITNESSES Name Title Company Steve Wilkening Client Solutions Manager Tubelite, Inc. Vinu Abraham Vice President Southeast Region Architectural Testing Jeff McGovern Director Regional Operations Architectural Testing Kristin Nolan Lab Manager Architectural Testing Martin Gibbard Foreman Architectural Testing Veron Wickham Test Technician Architectural Testing 14.0 SIGNATURES Alan Rule Project Coordinator Vinu Abraham Vice President Southeast Region This report produced from controlled document template ATI 00607, issued 06/12/12.

10 Test Report No.: C Report Date: 7/24/2012 Test Record Retention End Date: 7/24/2016 APPENDIX A: Test Specimen Drawing: TUBELITE 400 CURTAINWALL TEST SPECIMEN K 5 SHEETS

11

12

13

14

15

16 Test Report No.: C Report Date: 7/24/2012 Test Record Retention End Date: 7/24/2016 APPENDIX B: Die/Part Drawings 22 SHEETS

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39 Test Report No.: C Report Date: 7/24/2012 Test Record Retention End Date: 7/24/2016 APPENDIX C: Specification Sheets 3 PAGES

40

41

42

43 Test Report No.: C Report Date: 7/24/2012 Test Record Retention End Date: 7/24/2016 Alteration Log Alteration Date Cause for Alteration Remedial Action Taken # 1 7/24/2012 N/A No alterations were required.

44 Test Report No.: C Report Date: 7/24/2012 Test Record Retention End Date: 7/24/2016 Revision Log Rev. # Date Page(s) Section # Revision(s) 0 7/24/2012 N/A N/A Original report issued.

TEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California

TEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California TEST REPORT Report No.: G9949.01-303-47 Rendered to: CR LAURENCE CO., INC. Vernon, California PRODUCT TYPE: Fixed Lite Storefront System SERIES/MODEL: IT451 Title Summary of Results Design Pressure ±1440

More information

TEST REPORT. Report No.: A Rendered to: TUBELITE, INC. Walker, Michigan

TEST REPORT. Report No.: A Rendered to: TUBELITE, INC. Walker, Michigan Architectural Testing TEST REPORT Report No.: A2941.01 109 44 Rendered to: TUBELITE, INC. Walker, Michigan PRODUCT TYPE: Aluminum Side Hinge Door SERIES/MODEL: Thermal=Block Summary of Results Title Test

More information

PERFORMANCE TEST REPORT. Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly

PERFORMANCE TEST REPORT. Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly PERFORMANCE TEST REPORT Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly Title Summary of Results Air Infiltration

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A2653.02 401 44 Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama PRODUCT TYPE: Curtain Wall SERIES/MODEL: PW257 Captured

More information

TEST REPORT. Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California. SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window

TEST REPORT. Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California. SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window TEST REPORT Report No.: D8932.01-301-44 Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window SPECIFICATION: AAMA/WDMA/CSA 101/I.S.2/A440-08,

More information

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Solar Gard Armorcoat 8-mil Film PRODUCT TYPE: Fixed Window with Applied

More information

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT This report contains in its entirety: Cover Page: 1 page Report Body: 10 pages Sketches: 2 pages Photographs: 4 pages Drawings: 7 pages Report

More information

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California TEST REPORT Report No.: G6910.01-303-47 Rendered to: C.R. LAURENCE CO., INC. Vernon, California PRODUCT TYPE: Side Hinged Door - Outswing SERIES/MODEL: 925 Title Summary of Results Design Pressure ±2640

More information

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California TEST REPORT Report No.: E5564.01-301-44 Rendered to: INTERNATIONAL WINDOW Fullerton, California PRODUCT TYPE: Sliding Glass Door (XXO) SERIES/MODEL: 8880 SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,

More information

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test

More information

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California TEST REPORT Report No.: G8680.01-303-47 Rendered to: C.R. LAURENCE CO., INC. Vernon, California PRODUCT TYPE: Double Side Hinged Door - Outswing SERIES/MODEL: 925 Title Summary of Results Design Pressure

More information

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California TEST REPORT Report No.: E5562.01-301-44 Rendered to: INTERNATIONAL WINDOW Fullerton, California PRODUCT TYPE: Sliding Glass Door (XO) SERIES/MODEL: 8920 SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,

More information

Architectural Testing TEST REPORT. Rendered to: COEUR D'ALENE WINDOW Spokane Valley, Washington. PRODUCT TYPE: PVC Fixed Window SERIES/MODEL: 3310

Architectural Testing TEST REPORT. Rendered to: COEUR D'ALENE WINDOW Spokane Valley, Washington. PRODUCT TYPE: PVC Fixed Window SERIES/MODEL: 3310 Architectural Testing TEST REPORT Report No.: E2257.01-901-44 Rendered to: COEUR D'ALENE WINDOW Spokane Valley, Washington PRODUCT TYPE: PVC Fixed Window SERIES/MODEL: 3310 SPECIFICATIONS: AAMA/WDMA/CSA

More information

MOCK-UP TEST REPORT. Rendered to: TUBELITE INC. PROJECT: 300 ES Interior Glazed Curtain Wall

MOCK-UP TEST REPORT. Rendered to: TUBELITE INC. PROJECT: 300 ES Interior Glazed Curtain Wall Architectural Testing MOCK-UP TEST REPORT Rendered to: TUBELITE INC PROJECT: 300 ES Interior Glazed Curtain Wall Report No: 94346.01-602-32 Test Completion Date: 09/10/09 Report Date: 09/14/09 Record Retention

More information

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS SERIES/MODEL: 800MD Signature PRODUCT TYPE: Fixed Plastic Glazed Skylight Title Summary

More information

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors/Round Top Double PRODUCT TYPE: In-swing Round Top Double Door LH-4-5/8 Title Uniform Load Deflection

More information

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California TEST REPORT Report No.: E5468.01-301-44 Rendered to: INTERNATIONAL WINDOW Fullerton, California PRODUCT TYPE: Sliding Glass Door (OXXO) SERIES/MODEL: 8920 SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,

More information

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California TEST REPORT Report No.: E5467.01-301-44 Rendered to: INTERNATIONAL WINDOW Fullerton, California PRODUCT TYPE: Sliding Glass Door (OXO) SERIES/MODEL: 8920 SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,

More information

TEST REPORT. ASSOCIATED MATERIALS, INCORPORATED Cuyahoga Falls, Ohio. Rendered to: PRODUCT TYPE: Fixed Window SERIES/MODEL: A780 SPECIFICATIONS:

TEST REPORT. ASSOCIATED MATERIALS, INCORPORATED Cuyahoga Falls, Ohio. Rendered to: PRODUCT TYPE: Fixed Window SERIES/MODEL: A780 SPECIFICATIONS: Architectural Testing TEST REPORT Report No.: D7201.01-901-44 Rendered to: ASSOCIATED MATERIALS, INCORPORATED Cuyahoga Falls, Ohio PRODUCT TYPE: Fixed Window SERIES/MODEL: A780 SPECIFICATIONS: AAMA/WDMA/CSA

More information

PERFORMANCE TEST REPORT. Report No.: H Rendered to: VELUX America LLC Greenwood, South Carolina

PERFORMANCE TEST REPORT. Report No.: H Rendered to: VELUX America LLC Greenwood, South Carolina PERFORMANCE TEST REPORT Report No.: H0140.01-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Curb Mounted Skylight SERIES/MODEL: Specials Dome Skylight 0.118 Thickness PC

More information

TEST REPORT. Report No.: A Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina

TEST REPORT. Report No.: A Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina Architectural Testing TEST REPORT Report No.: A6303.08-250-44 Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina PRODUCT TYPE: Double Hung Window SERIES/MODEL: VictorBilt Palmetto

More information

TEST REPORT. Rendered to: EARTHWISE GROUP, LLC Liberty Township, Ohio

TEST REPORT. Rendered to: EARTHWISE GROUP, LLC Liberty Township, Ohio TEST REPORT Report No.: E6273.02-501-47 Rendered to: EARTHWISE GROUP, LLC Liberty Township, Ohio PRODUCT TYPE: PVC Single Hung Window SERIES/MODEL: 143.095 Single Hung SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,

More information

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: FLEETWOOD WINDOWS & DOORS. SERIES/MODEL: Norwood 3070HI OOX PRODUCT TYPE: Sliding Glass Door

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: FLEETWOOD WINDOWS & DOORS. SERIES/MODEL: Norwood 3070HI OOX PRODUCT TYPE: Sliding Glass Door MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Rendered to: FLEETWOOD WINDOWS & DOORS SERIES/MODEL: Norwood 3070HI OOX PRODUCT TYPE: Sliding Glass Door This report contains in its entirety: Cover Page: 1 page

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A7795.01 109 44 Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut INSULPANE OF CT INC. Hamden, Connecticut PRODUCT

More information

TEST REPORT. Report No.: B Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania

TEST REPORT. Report No.: B Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania Architectural Testing TEST REPORT Report No.: B2133.01-109-47 Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania PRODUCT TYPE: PVC Single Hung Window (Fin) SERIES/MODEL: 3540 SPECIFICATION: AAMA/WDMA/CSA

More information

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC. Architectural Testing AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: 300ES Curtainwall (8" System) TYPE: Glazed Wall Systems (Site-built) Summary of Results Thermal

More information

TEST REPORT. Report No.: F Rendered to: MI WINDOWS AND DOORS, LLC Gratz, Pennsylvania

TEST REPORT. Report No.: F Rendered to: MI WINDOWS AND DOORS, LLC Gratz, Pennsylvania TEST REPORT Report No.: F7299.01-109-47 Rendered to: MI WINDOWS AND DOORS, LLC Gratz, Pennsylvania PRODUCT TYPE: Polyvinyl Chloride (PVC) Picture Window SERIES/MODEL: HM155 SPECIFICATION(S): AAMA/WDMA/CSA

More information

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11 TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11 REPORT NO.: 1391.04-106-11 RENDERED TO: PRODUCT TYPE: GAMCO CORPORATION Flushing, New York Aluminum Outswing Casement Window SERIES / MODEL: W250C Test Summary

More information

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: ALUMIL US. SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO)

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: ALUMIL US. SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO) AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: ALUMIL US SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO) Title Summary of Results Primary Product Designator HS-C30

More information

TEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey

TEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey TEST REPORT Report No.: F399.01-109-44 Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey PRODUCT TYPE: ACP Panel System (Dry Seal) SERIES/MODEL: Dry Econect-RS Title Design Pressure Air Infiltration

More information

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana Architectural Testing TEST REPORT Report No.: D0162.01-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite

More information

INTERNATIONAL WINDOW TEST REPORT

INTERNATIONAL WINDOW TEST REPORT INTERNATIONAL WINDOW TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-08 AND -11 TESTING ON 7223 O/X AWNING WINDOW REPORT NUMBER H5789.01-301-44 R1 TEST DATE(S) 09/13/17-09/18/17 ISSUE DATE REVISION

More information

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11 TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11 REPORT NO.: 1391.02-106-11 RENDERED TO: PRODUCT TYPE: GAMCO CORPORATION Flushing, New York Aluminum fixed window SERIES / MODEL: W250C Test Summary of Results

More information

Structural Performance Certification Authorization Report

Structural Performance Certification Authorization Report Document Title: Doc No: FRM B1-02 Rev No: Pa ge: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-115.0 Issue Date: Revision Date:

More information

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A AAMA TEST REPORT SUMMARY

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A AAMA TEST REPORT SUMMARY AAMA/WDMA/CSA 101/I.S.2/A440-08 AAMA/WDMA/CSA 101/I.S.2/A440-05 AAMA 910-93 TEST REPORT SUMMARY Rendered to: GIESSE NORTH AMERICA 2014 Holston Industrial Drive Blountville, TN 37617 PRODUCT TYPE: XO Sliding

More information

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: BUILDERS ACCESSORIES, INC.

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: BUILDERS ACCESSORIES, INC. AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: BUILDERS ACCESSORIES, INC. SERIES/MODEL: 6490 PRODUCT TYPE: Polyvinyl Chloride (PVC) Casement Window Title Summary of Results Primary Product Designator

More information

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT SUMMARY. Rendered to:

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT SUMMARY. Rendered to: AAMA/WDMA/CSA 101/I.S.2/A440-08 AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT SUMMARY Rendered to: AluminTechno LLC. 12 Selitskog Street, Room 211 FEZ Minsk, Minsk District, Minsk Region 220075 Republic

More information

Structural Performance Certification Authorization Report

Structural Performance Certification Authorization Report Document Title: Doc No: FRM B1-02 Rev No: Page: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-113.0 Issue Date: Revision Date:

More information

ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC.

ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC. ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT Rendered to: MASTER WINDOW SYSTEMS, INC. SERIES/MODEL: Master 1000 Sliding Window PRODUCT: PVC Horizontal Sliding Window Summary of Results Title Test Specimen

More information

Structural Performance Certification Authorization Report

Structural Performance Certification Authorization Report Document Title: Doc No: FRM B1-02 Rev No: Page: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-109.0 Issue Date: Revision Date:

More information

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio TEST REPORT Report No.: E9891.01-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Wall Panel System SERIES/MODEL: Vulkem 116 Illmod 600 Acrytec Panel SPECIFICATION: ASTM E 330, Standard

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A7921.02 501 44 Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee PRODUCT TYPE: PVC Double Hung Window SERIES/MODEL: 4650DH

More information

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built)

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built) AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: GAMCO CORPORATION SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built) Summary of Results Thermal Transmittance (U-Factor) 0.47 Condensation

More information

PERFORMANCE TEST REPORT. Rendered to: ALL-WEATHER INSULATED PANELS. SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel

PERFORMANCE TEST REPORT. Rendered to: ALL-WEATHER INSULATED PANELS. SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel PERFORMANCE TEST REPORT Rendered to: ALL-WEATHER INSULATED PANELS SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel Title Summary of Results Air Infiltration

More information

AAMA 506 TEST REPORT. Report No.: G Rendered to: VEKA INC. Fombell, Pennsylvania

AAMA 506 TEST REPORT. Report No.: G Rendered to: VEKA INC. Fombell, Pennsylvania AAMA 506 TEST REPORT Report No.: G0434.01-501-44 Rendered to: VEKA INC. Fombell, Pennsylvania PRODUCT TYPE: PVC Double Hung Window SERIES/MODEL: DH57WW/AL-Insert Test Date(s): 06/28/16 Test Record Retention

More information

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio Architectural Testing TEST REPORT Report No.: B2739.02-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Air Barrier System SERIES/MODEL: ExoAir 230, ProGlaze ETA System 1, Spectrem

More information

TEST REPORT. Rendered to: ALL WEATHER INSULATED PANELS Vacaville, California. PRODUCT TYPE: Wall Panels SERIES/MODEL: DM45 Series

TEST REPORT. Rendered to: ALL WEATHER INSULATED PANELS Vacaville, California. PRODUCT TYPE: Wall Panels SERIES/MODEL: DM45 Series Architectural Testing TEST REPORT Report No.: D5082.01-301-32 Rendered to: ALL WEATHER INSULATED PANELS Vacaville, California PRODUCT TYPE: Wall Panels SERIES/MODEL: DM45 Series Title Summary of Results

More information

Structural Performance Certification Authorization Report

Structural Performance Certification Authorization Report Document Title: Doc No: FRM B1-02 Rev No: Page: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-105.0 Issue Date: Revision Date:

More information

TEST REPORT. Report No.: F Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia

TEST REPORT. Report No.: F Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia TEST REPORT Report No.: F7657.01-550-44 Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia PRODUCT TYPE: Metal Wall Panel System SERIES/MODEL: Low Profile Accu-Trac System ES with Stiffeners

More information

Dennis Fassnacht Jr :59:35-04'00'

Dennis Fassnacht Jr :59:35-04'00' Document Title: Doc No: FRM B1-02 Rev No: Page: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-103.0 Issue Date: Revision Date:

More information

Installation Instructions

Installation Instructions Installation Instructions 400SS Series Curtainwall 3056 WALKER RIDGE DR. NW, SUITE G WALKER, MI 49544 800-866-2227 dependable@tubeliteinc.com Revised June 2016 dependable@tubeliteinc.com Page 1 TABLE OF

More information

SECTION ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS

SECTION ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS SECTION 08 4113 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Aluminum entrance doors and frames. 2. Glass infill panels. 3. Door hardware. B. Related Sections:

More information

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio TEST REPORT Report No.: E9792.01-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Wall Panel System SERIES/MODEL: ExoAir 230, Dymonic 100 SPECIFICATION: ASTM E 331, Standard Test

More information

ETC Laboratories Measuring Up To Your Standards And More

ETC Laboratories Measuring Up To Your Standards And More ETC Laboratories Measuring Up To Your Standards And More Corporate Offices / Laboratories 460 Buffalo Rd. Rochester, NY 14611 (585) 328-7668 Fax: (585) 328-7777 Report Number: ETC-09-329-22959.2 Test Start

More information

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: COASTAL INNOVATIVE PRODUCTS

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: COASTAL INNOVATIVE PRODUCTS Architectural Testing AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: COASTAL INNOVATIVE PRODUCTS SERIES/MODEL: Outswing Aluminum Bi-Folding System TYPE: Swinging Door with Frame Summary of Results

More information

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: BRICK-IT. SERIES/MODEL: Brick Veneer Panel Systems PRODUCT TYPE: Wall Panel Systems

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: BRICK-IT. SERIES/MODEL: Brick Veneer Panel Systems PRODUCT TYPE: Wall Panel Systems This report contains in its entirety: Cover Page: 1 page Report Body: 15 pages Sketches: 7 pages Drawing: 1 page MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Rendered to: BRICK-IT SERIES/MODEL: Brick Veneer

More information

TEST REPORT. Rendered to: All Weather Insulated Panels Vacaville, California. PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series

TEST REPORT. Rendered to: All Weather Insulated Panels Vacaville, California. PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series Architectural Testing TEST REPORT Report No.: C6304.01-301-44 Rendered to: All Weather Insulated Panels Vacaville, California PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series Title Summary of Results

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey. TYPE: Bi-fold Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey. TYPE: Bi-fold Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey TYPE: Bi-fold Door Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC

More information

TEST REPORT ASTM E331. Report No.: E Rendered to: IMISON USA Houston, Texas

TEST REPORT ASTM E331. Report No.: E Rendered to: IMISON USA Houston, Texas TEST REPORT ASTM E331 Report No.: E2907.01-801-42 Rendered to: IMISON USA Houston, Texas PRODUCT TYPE: Foam and Plaster Wall System SERIES/MODEL: Fibrecote Title Water Penetration Resistance Test Pressure

More information

Cardinal Commercial Products ALUMINUM STOREFRONT SYSTEM SERIES CF450 GUIDE SPECIFICATIONS SECTION ALUMINUM ENTRANCES AND STOREFRONT SYSTEMS

Cardinal Commercial Products ALUMINUM STOREFRONT SYSTEM SERIES CF450 GUIDE SPECIFICATIONS SECTION ALUMINUM ENTRANCES AND STOREFRONT SYSTEMS Cardinal Commercial Products ALUMINUM STOREFRONT SYSTEM SERIES CF450 GUIDE SPECIFICATIONS SECTION 08410 ALUMINUM ENTRANCES AND STOREFRONT SYSTEMS This suggested guide specification has been developed using

More information

7000 Series Curtain Wall Information Specifications

7000 Series Curtain Wall Information Specifications 7000 Series Curtain Wall Information Specifications Information All framing members shown in this section, unless noted otherwise, are stock items in dark bronze or clear anodic coatings and are available

More information

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE B PRODUCT TYPE: Venting Curb Mounted Skylight

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE B PRODUCT TYPE: Venting Curb Mounted Skylight OSHA FALL PROTECTION TEST REPORT Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE 4646 2004B PRODUCT TYPE: Venting Curb Mounted Skylight Report No: Test Date: 01/06/10 Report Date: 03/15/10 Expiration

More information

METL-VISION WINDOW SYSTEM FOR HORIZONTAL WALL

METL-VISION WINDOW SYSTEM FOR HORIZONTAL WALL METL-VISION WINDOW SYSTEM FOR HORIZONTAL WALL TEchnical bulletin PIONEERING INSULATED METAL PANEL TECHNOLOGY PIONEERING INSULATED METAL PANEL TECHNOLOGY CONTENTS DETAIL TITLE FILE NO. PAGE NO. INTRODUCTION.......................................................................

More information

TMW 450 TECHNICAL MANUAL

TMW 450 TECHNICAL MANUAL ARCHITECTURAL METALS, INC. TMW 450 TMW 450 TECHNICAL MANUAL TMW 450 ARCHITECTURAL METALS, INC. BLANK PAGE FEATURES ARCHITECTURAL METALS, INC. TMW 450 FEATURES TMW 450 is 6 3/4" deep with a 2" wide sightline

More information

Tender No Section St. James - Assiniboia Centennial Pool Fitness Facility Addition Page 1

Tender No Section St. James - Assiniboia Centennial Pool Fitness Facility Addition Page 1 Fitness Facility Addition Page 1 PART 1 GENERAL 1.1 SECTION INCLUDES.1 Extruded aluminum windows with fixed sash..2 Factory glazed..3 Perimeter sealant. 1.2 RELATED SECTIONS.1 Section 05500 - Metal Fabrications.2

More information

MOCK-UP TEST REPORT. Report No: NCTL Test Dates:06/22, 07/23-27/10 Test Dates: 08/23-25/10 Report Date: 08/26/10

MOCK-UP TEST REPORT. Report No: NCTL Test Dates:06/22, 07/23-27/10 Test Dates: 08/23-25/10 Report Date: 08/26/10 MOCK-UP TEST REPORT Report No: NCTL-110-11828-3 Test Dates:06/22, 07/23-27/10 Test Dates: 08/23-25/10 Report Date: 08/26/10 Client: Alumil N.A. Corporation 4401 21 st. Street, Suite 203 Long Island City,

More information

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: W250C Awning TYPE: Projecting (Awning)

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: W250C Awning TYPE: Projecting (Awning) AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: GAMCO CORPORATION SERIES/MODEL: W250C Awning TYPE: Projecting (Awning) Summary of Results Thermal Transmittance (U-Factor) 0.48 Condensation Resistance

More information

Construction Consulting Laboratory, International

Construction Consulting Laboratory, International Construction Consulting Laboratory, International Test Report CCLI-14-060 Client MI Windows and Doors, LLC. 1001 West Crosby Road Carrollton, TX 75006 Product Type: Aluminum Fixed Window Series / Model:

More information

C.R. Laurence Co., Inc. Los Angeles, California

C.R. Laurence Co., Inc. Los Angeles, California TEST REPORT: AAMA 501-05 Performance and ASTM E 1996-09 and ASTM E 1886-05 Impact and Cyclic Test Report C. R. Laurence Co., Inc. Series: StormWall L Product/Type: SSG Twin Span Curtain Wall Test Date:

More information

OSHA FALL PROTECTION TEST REPORT. Rendered to: SERIES/MODEL: FS S PRODUCT TYPE: Fixed Deck Mounted Skylight

OSHA FALL PROTECTION TEST REPORT. Rendered to: SERIES/MODEL: FS S PRODUCT TYPE: Fixed Deck Mounted Skylight OSHA FALL PROTECTION TEST REPORT Rendered to: VELUX America LLC SERIES/MODEL: FS S06 2004 PRODUCT TYPE: Fixed Deck Mounted Skylight Report No: 96238.02-109-44 Test Date: 01/06/10 Report Date: 01/09/18

More information

TMS 114 XT TECHNICAL MANUAL

TMS 114 XT TECHNICAL MANUAL TECHNICAL MANUAL BLANK PAGE FEATURES FEATURES is center set flush glazed systems that are 4 1/2" deep with a 2" wide sightline Glaze from the outside or inside Screw spline or shear block fabrication Glazing

More information

FL200 13/4 x41/2 GUIDE SPECIFICATION. Non-Thermal Storefront

FL200 13/4 x41/2 GUIDE SPECIFICATION. Non-Thermal Storefront Manufacturer: Coral Architectural Products 3010 Rice Mine Road Tuscaloosa, AL. 35406 Voice: (800) 772-7737 Fax: (800) 443-6261 SECTION 08410 ALUMINUM ENTRANCES AND STOREFRONT SYSTEMS This suggested guide

More information

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: TUBELITE, INC.

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: TUBELITE, INC. Architectural Testing NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: 400 Series Curtain Wall (6" Standard Tube Backmember) - Fiberglass

More information

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK AAMA 1801 TESTING ON IT451, STOREFRONT WINDOW REPORT NUMBER H7645.03-303-11 R0 TEST DATE 11/03/17 ISSUE DATE 11/17/17 RECORD RETENTION

More information

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina TEST REPORT Report No.: G4210.01-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Skylight with Curb SERIES/MODEL: Specials Dome Skylight 0.150 thickness 100% IMA smooth/0.118

More information

TEST REPORT. Report No.: F Rendered to: VELUX America LLC Greenwood, South Carolina

TEST REPORT. Report No.: F Rendered to: VELUX America LLC Greenwood, South Carolina TEST REPORT Report No.: F8969.01-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Skylight SERIES/MODEL: Dynamic Double Dome Skylight 100% IMA Smooth/50% IMA Prismatic (5'

More information

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK AAMA 1801 TESTING ON IT451, STOREFRONT WINDOW REPORT NUMBER H7645.02-303-11 R0 TEST DATE 11/03/17 ISSUE DATE 11/17/17 RECORD RETENTION

More information

SECTION ALUMINUM STORM WINDOWS

SECTION ALUMINUM STORM WINDOWS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 08 51 69.11 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: GAMCO CORPORATION. Series/Model: CW250

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: GAMCO CORPORATION. Series/Model: CW250 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: GAMCO CORPORATION Series/Model: CW250 Type: Two-Lite Curtain Wall System Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390. TYPE: Sliding Glass Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390. TYPE: Sliding Glass Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390 TYPE: Sliding Glass Door Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC

More information

STRUCTURAL PERFORMANCE TEST REPORT. Series Casement (Rep/Impact/AAMA) C-C70 940mm x 1930mm (37 x 76 )

STRUCTURAL PERFORMANCE TEST REPORT. Series Casement (Rep/Impact/AAMA) C-C70 940mm x 1930mm (37 x 76 ) Element Materials Technology 115 South 84th Ave Wausau, WI 54401, USA 407-505-8102 Report No.: ESP101311P-6_012404P-6 Report Date: July 18, 2012 STRUCTURAL PERFORMANCE TEST REPORT Test Requested By: Earthwise

More information

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440. TYPE: Sliding Glass Door

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440. TYPE: Sliding Glass Door Architectural Testing AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440 TYPE: Sliding Glass Door ATI Data File No. 71967.01 Summary of Test

More information

SECTION METAL FRAMED SKYLIGHT. A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system.

SECTION METAL FRAMED SKYLIGHT. A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system. SECTION 08625 METAL FRAMED SKYLIGHT PART 1 GENERAL 1.01 SECTION INCLUDES: A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system. B. Fabrication

More information

Series B450 Guide Specification

Series B450 Guide Specification Boyd Aluminum Manufacturing Company P.O. Box 1565 3248 E. Division Street Springfield, MO 65801-1565 800-737-2800 417-862-1232 fax boydaluminum.com STOREFRONT SERIES B450 Shear Block Air Infiltration:

More information

TEST REPORT. Rendered to: SENTINEL FENCE AND RAIL. For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post

TEST REPORT. Rendered to: SENTINEL FENCE AND RAIL. For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post TEST REPORT Rendered to: SENTINEL FENCE AND RAIL For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post Report No: Report Date: 10/23/12 130 Derry Court York, PA 17406-8405

More information

SECTION / METAL FRAMED SKYLIGHTS

SECTION / METAL FRAMED SKYLIGHTS Specifier Notes: This product guide specification is written according to the Construction Specifications Institute (CSI) Format, including MasterFormat, SectionFormat, and PageFormat, contained in the

More information

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP TYPE: Picture Window ATI Data File No. 71965.01A 71965.01B Summary of Test Results Glazing

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500. TYPE: Double Hung Window

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500. TYPE: Double Hung Window ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500 TYPE: Double Hung Window Data File No. 97455.01 Summary of Test Results Glazing (Nominal Dimensions)

More information

System WV410 Storefront Window System

System WV410 Storefront Window System E F C O C O R P O R A T I O N Visit us on the web at efcocorp.com Manufacturer Of Architectural Configurations Project-out Casement-out The WV410 storefront vent system is designed to be field glazed and

More information

Series 700 Series 7000 * 4 Heavy Commercial Roto-Vent Rotating Ventilator Window

Series 700 Series 7000 * 4 Heavy Commercial Roto-Vent Rotating Ventilator Window Windows Curtain Walls Entrances Storefronts Series 700 Series 7000 * 4 Heavy Commercial Roto-Vent Rotating Ventilator Window Configurations Roto-Vent Fixed Series 700 and 7000 retain an AAMA Heavy Commercial

More information

TMS 152 / 152T / 152XT TECHNICAL MANUAL

TMS 152 / 152T / 152XT TECHNICAL MANUAL TMS 152 / 152T / 152XT TECHNICAL MANUAL BLANK PAGE FEATURES FEATURES TMS 152 (non-thermal), 152T (single thermal barrier), and 152XT (double thermal barrier) are front set flush glazed systems that are

More information

Heavy Commercial / Architectural Projected Windows Series L900T AW150

Heavy Commercial / Architectural Projected Windows Series L900T AW150 Heavy Commercial / Architectural Projected Windows Series L900T AW150 Section 08520...Aluminum Windows PART 1: WORK INCLUDED GUIDE SPECIFICATION A. The conditions of the contract and applicable sections

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 6/8 Sliding Patio Door ATI Data File No. 74387.01 74387.01A* Summary of Test Results Glazing (Nominal

More information

FL550 21/2 x5 GUIDE SPECIFICATION. Impact-Resistant Storefront

FL550 21/2 x5 GUIDE SPECIFICATION. Impact-Resistant Storefront Manufacturer: Coral Architectural Products 3010 Rice Mine Road Tuscaloosa, AL. 35406 Voice: (800) 772-7737 Fax: (800) 443-6261 SECTION 08410 ALUMINUM ENTRANCES AND STOREFRONT SYSTEMS This suggested guide

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: THERMA-TRU CORPORATION Series/Model: 3/0 x 6/8 Fiber-Classic/Smooth-Star, Full Lite Flush Glazed Type: Side-Hinged Single Door System Summary of

More information

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: SHA4. TYPE: Single Hung Window

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: SHA4. TYPE: Single Hung Window ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: SHA4 TYPE: Single Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door with Impact Glass ATI Data File No. 74391.01 74391.01A* Summary of Test Results

More information

SECTION E INDEX CURTAINWALL FRAMING SYSTEMS

SECTION E INDEX CURTAINWALL FRAMING SYSTEMS SECTION E INDEX CURTAINWALL FRAMING SYSTEMS E PAGE DESCRIPTION 0 CURTAINWALL FRAMING SPECIFICATION 0 SERIES /" () WIDE THERMALLY IMPROVED CURTAIN WALL FRAMING SYSTEM FOR SEALED UNIT GLAZING. 00 SERIES

More information

YSD 700H PRODUCT DATA

YSD 700H PRODUCT DATA SYSTEM DESCRIPTION: The ProTek YSD 700 sliding glass door is designed to provide protection from the fierce cyclical pressures and projectiles associated with hurricane force winds. The engineering behind

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: THERMA-TRU CORPORATION Series/Model: 3/0 x 6/8 Fiber-Classic/Smooth-Star, Full Lite 1" IG Impact Glass with BTS Lite Frame Type: Side-Hinged Single

More information