Smoke Control Damper ESAM Instructions for installation, operation and maintenance 10/2014

Size: px
Start display at page:

Download "Smoke Control Damper ESAM Instructions for installation, operation and maintenance 10/2014"

Transcription

1 Instructions for installation, operation and maintenance 0/204 General The rectangular smoke control damper ESAM is specially designed for use in multi fire-compartment applications as a closing or opening damper for smoke extraction purposes. ESAM meets the European product standard EN 20- requirements for multi-compartment applications and is CE marked. The product has been tested according to EN 3-0, fulfilling fire class EI 20S / EI 90S with pressure class 000 Pa. ESAM dampers are suitable for both automatic operation by fire-alarm-activated systems (AA) and by manual operation by fire-fighter-activated systems (MA, installed in the duct). The duct outlet must be placed so that the smoke control damper is protected from water and moisture coming from outside as well as ice and snow that could hinder the opening of the damper. The ductwork section between the smoke control damper and the duct outlet must be designed and insulated so that the heat insulation and tightness requirements are met. The ductwork design should also take into account possible condensation and mitigate against it. The smoke control damper can be installed with the actuator box on the side, top or bottom. Fig.. Wiring diagram for Belimo actuators VAC/DC A L-L2 open (90 ) L-L3 closed (0 ) N L~ + T 2 3 PE ~ ~ + AC 230 V AC 24 V DC 24 V a b Closed (<3 ) Open (> ) Contact between Contact between S-S2 S4-S S S2 S3 S4 S S <3 < < > B PA Only a qualified electrician is allowed to perform the electrical wiring according to drawings and wiring diagrams. Wiring diagrams for damper actuators: see Figures and 2. The entire cable system with connection boxes has to be fire resistant as designed. The connection of the damper actuator to a fire-resistant cable must be made inside the calcium-silicate actuator box so that the actuator cables are shielded by the box. Installation Careful installation is required to ensure the proper functioning of the ESAM smoke control damper. Please especially note the following points: Cross-measures have to be the same from both corners. The damper must be fixed in place and supported taking into account the weight of the product and the fire-resistance requirements. See installation examples on next page. The electrical connection must be made inside the calcium-silicate box. A hole must be drilled in the actuator box on site for the power cable. When the cable has been installed, the cable entry must be sealed with an appropriate fire-rated sealant. In the case of smoke control dampers over 3 mm in height, the damper blade will project outside the damper casing in the open position, i.e. the 'open' depth is greater than the 'closed' depth. This must be taken into account when installing the product, ensuring that the blade can move freely into the 'open' position. The required direction of gas flow is indicated on the outside of the smoke control damper. The damper must be installed so that gases flow through it in the direction indicated. Heater Fig. 2. Wiring diagram for Schischek actuators.

2 0 mm Smoke Control Damper ESAM Installation examples mm * Fig. 3. Installation in solid wall constructions.. Smoke Control Damper ESAM 2. Solid construction 3. Board construction 4. Mineral wool (stone wool), min. density 40 kg/m 3. High-temperature ceramic fibre paper, e.g. Ceramat Protecta. Fire-rated sealant, min. thickness mm, e.g. Promatec Mastik. Calcium-silicate board, min. thickness mm, e.g. Promatec H or L. Fixings and supports, e.g. galvanised angle iron, min. thickness 2 mm, secured with acid-proof screws, and/or threaded rod M-M20, min. grade. *) The cover of the actuator box must be able to open after installation mm * 0 mm Fig. 4. Installation in board constructions such as drywall. Fläkt Woods 900 GB Specifications are subject to alteration without notice.

3 Installation examples (continue) 2 2 Fig.. Installation on solid ceiling constructions.. Smoke Control Damper ESAM 2. Solid construction 3. Board construction 4. Mineral wool (stone wool), min. density 40 kg/m 3. High-temperature ceramic fibre paper, e.g. Ceramat Protecta. Fire-rated sealant, min. thickness mm, e.g. Promatec Mastik. Calcium-silicate board, min. thickness mm, e.g. Promatec H or L. Fixings and supports, e.g. galvanised angle iron, min. thickness 2 mm, secured with acid-proof screws, and/or threaded rod M-M20, min. grade. Fläkt Woods 900 GB Specifications are subject to alteration without notice.

4 Installation examples (continue) Fig.. Installation in a horizontal duct Installation opening W (220*) H (30*) *) With a Schischek InMax actuator Fig.. Dimensions of the installation opening. Fläkt Woods 900 GB Specifications are subject to alteration without notice.

5 Fixing examples without anchor 2 3 Fixing to solid constructions with anchor with fixing plate and anchors Fixing plates 20 0 M-M20 2 x Ø9 0 4 x Ø9 M - M Threaded rod M-M20 2. Nut 3. Washer 4. Sleeve nut. Steel anchor. Fixing plate, min. thickness 0 mm 00 0 Fig.. Examples of fixing to solid constructions Threaded rod 2. Nut 3. C washer 4. Mounting rail 4x4x2. Washer. Bolt. L bracket. Screw (acid-proof) 9. Support rail 0. Angle bracket Fig. 9. Examples of fixings. Fläkt Woods 900 GB Specifications are subject to alteration without notice.

6 Inspection and maintenance The function of smoke control dampers must always be checked before and after installation. According to product standard EN 20-, smoke control dampers should be checked periodically at least every six months to ensure the grade is maintained as designed (see the example check list). Special attention should be paid to the tightness of seams and joints to ensure they do not let the heat out. Any defects must be repaired. Damper reference Date of inspection Check actuator and end-switch wiring for damage. Check damper cleanliness and clean where necessary. Check the condition of the blade and seals; rectify and report where necessary. Confirm operation of the damper to OPEN (within 0 s) and CLOSE (within 0 s) by use of the control system and physical observation of the damper; rectify and report where necessary. Confirm operation of OPEN and CLOSED end-switches; rectify and report where necessary. Confirm that the damper fulfils its function as part of the smoke control system. Confirm that the damper is left in its standby position. NOTE! A smoke control damper is part of a smoke control system. As this is the case, the whole system should be checked as governed by the operation and maintenance requirements for the system. The smoke control damper is made of impact-sensitive material. Visually check the material for cracks. If any are found, please contact your nearest Fläkt Woods representative. Fläkt Woods 900 GB Specifications are subject to alteration without notice.

7 DECLARATION OF PERFORMANCE No. 02CPR Unique identification code of the product-type: Smoke Control Damper ESAM 2. Type, batch or serial number or any other element allowing identification of the construction product as required under Article (4): Smoke Control Damper ESAM-aaaa-bbbb-c-d 3. Intended use or uses of the construction product, in accordance with the applicable harmonised technical specification, as foreseen by the manufacturer: Smoke control dampers that are to be used in smoke control systems, in multi compartment applications, either up to 00 C or at fire temperatures 4. Name, registered trade name or registered trade mark and contact address of the manufacturer as required pursuant Article (): Fläkt Woods Oy, Kalevantie 39, 2020 Turku, Finland Tel , Fax: , info.fi@flaktwoods.com Manufacturer: Mandik, Product code: SEDM. System or systems of assessment and verification of constancy of performance of the construction product as set out in Annex V: System. PAVUS, a.s., Nr. 039 Performed determination the product type on the basis of type testing; initial inspection of the manufacturing plant and of factory production control; continuous surveillance, assessment and evaluation of the factory production control (FPC) under system and issued: certificate of constancy of performance - EC Certificate of Conformity 39-CPD-009/202/O.. Declared performance: Essential characteristics Performance Harmonized technical Nominal activation conditions/sensitivity Response delay (response time) Operational reliability Pass Pass Pass / C0000 specification Fire resistance EN 20 :20 inte grity E insulation EI smoke le akage ES, EIS mechanical stability (under E) Pass maintenance of the cross section (under E) Pass Durability: Pass / C0000 of response delay of operational re liability Classification in accordance with EN 30 4+A: Dimensions Supporting construction Classification 200 x x 00 Vertical duc t EI 20 (h od i< >o)s000c 0000 MAmulti EI 20 (h od i< >o)s000c 0000 AAmulti 200 x x 00 Aerated concrete ceiling, thickness 0 mm EI 90 (h ow i< >o)s000c 0000 AAmulti 200 x x 00 Aerated concrete wall, thickness 00 mm EI 20 (v ew i< >o)s000c 0000 AAmulti 200 x x 00 Gypsum board wall, thickness 00 mm EI 20 (v ew i< >o)s000c 0000 AAmulti 200 x x 00 Horizontal duc t EI 20 (v ed i< >o)s000c 0000 MAmulti EI 20 (v ed i< >o)s000c 0000 AAmulti. The performance of the product identified in points and 2 is in conformity with the declared performance in point. This declaration of performance is issued under the sole responsibility of the manufacturer identified in point 4. Signed for and on behalf of the manufacturer by: Raimo Perttunen, Product Manager Turku

8 Fläkt Woods Oy Kalevantie 39 FI-2020 Turku, Finland Tel Fax GB 204.0

Declaration of performance

Declaration of performance Product Unique identification code of the product type FKRS-EU Intended use Fire damper Manufacturer TROX GmbH Phone +49 (0)2845 2020 Fax +49 (0)2845 202265 Heinrich-Trox-Platz E-mail trox@trox.de 47504

More information

3. Dimensions, weights Placement and Assembly Statement of installations Electrical Components, Connection Diagrams...

3. Dimensions, weights Placement and Assembly Statement of installations Electrical Components, Connection Diagrams... These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers) FDMC. It is valid for production, designing, ordering, delivery, assembly and operation.

More information

1. Description Damper Design Dimensions, weights Placement and Assembly Statement of installations...

1. Description Damper Design Dimensions, weights Placement and Assembly Statement of installations... These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers) CFDM. It is valid for production, designing, ordering, delivery, assembly and operation.

More information

PRODUCT CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE

PRODUCT CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE Certificate No C-11669-16 Issued June 14, 2016 Updated September 12, 2018 PRODUCT CERTIFICATE NAME OF PRODUCT Knauf Insulation Fire Insulation System for ventilation ducts MANUFACTURER Knauf Insulation

More information

*1MUBWK25EN* *1MUBWK25EN-LIND* rev rev *1MUBWK25EN-LIND* WK25. RECTANGULAR SERIES WK Pa. Cert. N 1812-CPR-1045 EN 15650

*1MUBWK25EN* *1MUBWK25EN-LIND* rev rev *1MUBWK25EN-LIND* WK25. RECTANGULAR SERIES WK Pa. Cert. N 1812-CPR-1045 EN 15650 WK25 Installation booklet English RECTANGULAR SERIES WK25-500 Pa Cert. N 1812-CPR-1045 EN 15650 *1MUBWK25EN* *1MUBWK25EN-LIND* rev 17-04 rev 17-04 *1MUBWK25EN* *1MUBWK25EN-LIND* www.mp3-italia.it www.lindab.com

More information

DECLARATION OF PERFORMANCE. DoP No CPD GB (Version 1)

DECLARATION OF PERFORMANCE. DoP No CPD GB (Version 1) DECLARATION OF PERFORMANCE DoP No. 0756-CPD-447 - GB (Version 1) 1. Unique identification code of the product-type: SPIT TAPCON-6 2. Type, batch or serial number or any other element allowing identification

More information

Date of update January 25, 2018 Valid until

Date of update January 25, 2018 Valid until CERTIFICATE PRODUCT APPLICATION VTT-C-4805-09 Date of update January 25, 2018 Valid until 12.10.2020 U Protect fire insulation solutions for ventilation ducts MANUFACTURER Saint-Gobain Finland Oy / ISOVER

More information

Installation in ceilings

Installation in ceilings Installation instructions EI90 BET Cable Boxes "System Wichmann" ceiling 350 mm depth, rectangular ETA 13/0902 BET Cable Box to be poured in the concrete» Technical datasheet - page 4-7 Installation in

More information

Declaration of Performance

Declaration of Performance Product Unique identification code of the product type FK-EU Intended use Fire damper Manufacturer TROX GmbH Phone +49 (0)2845 2020 Fax +49 (0)2845 202265 Heinrich-Trox-Platz E-mail trox@trox.de 47504

More information

1. Description Damper Design Dimensions, weights Placement and Assembly Statement of installations...

1. Description Damper Design Dimensions, weights Placement and Assembly Statement of installations... These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers) CFDM. It is valid for production, designing, ordering, delivery, assembly and operation.

More information

1. Description Damper Design Dimensions, weights Placement and Assembly Statement of installations...

1. Description Damper Design Dimensions, weights Placement and Assembly Statement of installations... These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers) CFDM. It is valid for production, designing, ordering, delivery, assembly and operation.

More information

*1MUBWK45EN* *1MUBWK45EN-LIND* WK45. RECTANGULAR SERIES WK Pa / 300 Pa. Cert. N 1812-CPR-1006 EN Installation booklet English

*1MUBWK45EN* *1MUBWK45EN-LIND* WK45. RECTANGULAR SERIES WK Pa / 300 Pa. Cert. N 1812-CPR-1006 EN Installation booklet English WK45 Installation booklet English RECTANGULAR SERIES WK45-500 Pa / 300 Pa Cert. N 1812-CPR-1006 EN 15650 *1MUBWK45EN* *1MUBWK45EN-LIND* rev 17-04 rev 17-04 *1MUBWK45EN* *1MUBWK45EN-LIND* www.mp3-italia.it

More information

2500 Series Fire Smoke Dampers

2500 Series Fire Smoke Dampers General Description The model 2550 is designed to prevent the spread of fire and smoke through ventilation ductwork in walls and floors. From receiving an alarm the power to the damper actuator is removed

More information

CERTIFICATE OF APPROVAL No CF 5073 LEMINAR AIR CONDITIONING INDUSTRIES L.L.C.

CERTIFICATE OF APPROVAL No CF 5073 LEMINAR AIR CONDITIONING INDUSTRIES L.L.C. CERTIFICATE OF APPROVAL No CF 5073 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of PO Box 33539, Dubai,

More information

DECLARATION OF PERFORMANCE. DoP No CPD GB (Version 1)

DECLARATION OF PERFORMANCE. DoP No CPD GB (Version 1) DECLARATION OF PERFORMANCE DoP No. 0679-CPD-0074 - GB (Version 1) 1. Unique identification code of the product-type: SPIT EPOMAX 2. Type, batch or serial number or any other element allowing identification

More information

DECLARATION OF PERFORMANCE

DECLARATION OF PERFORMANCE 1.0 Unique Identification Code of the Product Type(s): Pyroplex CE Marked Intumescent Acrylic 2.0 Type, batch or serial number or any other element allowing identification of the products as required under

More information

PRODUCT APPLICATION MANUFACTURER INTRODUCTION CERTIFICATION PROCEDURE. Date of update April 6, 2018 Valid until

PRODUCT APPLICATION MANUFACTURER INTRODUCTION CERTIFICATION PROCEDURE. Date of update April 6, 2018 Valid until CERTIFICATE VTT-C-12188-17 Date of update April 6, 2018 Valid until 6.12.2022 PRODUCT APPLICATION CONLIT insulation solutions for ventilation ducts MANUFACTURER Rockwool Finland Oy P.O. Box 78 FI-01511

More information

Declaration of Performance (DOP)

Declaration of Performance (DOP) Declaration of Performance (DOP) No. 9174 009 DOP 2014-01-27 1. Unique identification code of the product-type: Multi-wall chimney system type DW-VISION according to 2. Type, batch or serial number or

More information

MULTIBLADE SMOKE CONTROL DAMPER BRK-J/EI90

MULTIBLADE SMOKE CONTROL DAMPER BRK-J/EI90 MULTIBLADE SMOKE CONTROL DAMPER BRK-J/EI90 Table of contents MULTIBLADE SMOKE CONTROL DAMPER BRK-J/EI90... 2 MULTIBLADE SMOKE CONTROL DAMPER BRK-J/EI90... 3 MULTIBLADE SMOKE CONTROL DAMPER BRK-J/EI90 DIMENSIONS...

More information

*1MUBWKS25EN* *1MUBWKS25EN-LIND* rev rev *1MUBWKS25EN-LIND* WKS25. RECTANGULAR SERIES WKS Pa. Cert. N 1812-CPR-1046 EN 15650

*1MUBWKS25EN* *1MUBWKS25EN-LIND* rev rev *1MUBWKS25EN-LIND* WKS25. RECTANGULAR SERIES WKS Pa. Cert. N 1812-CPR-1046 EN 15650 WKS25 Installation booklet English RECTANGULAR SERIES WKS25-500 Pa Cert. N 1812-CPR-1046 EN 15650 *1MUBWKS25EN* *1MUBWKS25EN-LIND* rev 17-04 rev 17-04 *1MUBWKS25EN* *1MUBWKS25EN-LIND* www.mp3-italia.it

More information

Internal Partitions - Timber Studs Internal Partitions - Steel Stud

Internal Partitions - Timber Studs Internal Partitions - Steel Stud Timber Studs PH Internal Partitions - Steel Stud / hour fire rating, integrity and insulation in accordance with the criteria of BS : Part and AS 0: Part. Nominal thickness of partition: mm PROMATECT -H

More information

mcr Silboard self-supporting ventilation and smoke extraction ducts

mcr Silboard self-supporting ventilation and smoke extraction ducts mcr Silboard self-supporting ventilation and smoke extraction ducts INTENDED USE mcr Silboard is a calcium-silicate fireproof board designed for the construction of e.g. self-supporting fireproof general

More information

Voie Romaine F Maizières-lès-Metz Tel.: +33 (0) Fax.: +33 (0) Operating vacuum pressure: - 500Pa

Voie Romaine F Maizières-lès-Metz Tel.: +33 (0) Fax.: +33 (0) Operating vacuum pressure: - 500Pa Voie Romaine F-57280 Maizières-lès-Metz Tel.: +33 (0)3 87 51 11 11 Fax.: +33 (0)3 87 51 10 58 CLASSIFICATION REPORT CLASSIFICATION REPORT no. 09 - A - 363 According to standards EN 15650: 2010 and EN 13501-3:

More information

Declaration of Performance (DOP)

Declaration of Performance (DOP) Declaration of (DOP) No. 9174 073 DOP 2015-07-27 1. Unique identification code of the product-type: Multi-wall chimney system type FURADO-F according to 2. Type, batch or serial number or any other element

More information

Installation instruction

Installation instruction Installation instruction Ci51 www.contura.eu 114 CERTIFICATE Declaration of performance according to Regulation (EU) 305/2011 No. Ci51-CPR-150821-SE-2 PRODUCT Product type Type designation Manufacturing

More information

0160 Series Curtain Fire Dampers

0160 Series Curtain Fire Dampers Burrell Way, General Description The 0160 series curtain fire dampers are designed to stop the spread of fire through ductwork, walls and floors in ventilation systems. When the fusible link reaches elevated

More information

CERTIFICATE OF APPROVAL No CF 429 PROMAT UK LTD

CERTIFICATE OF APPROVAL No CF 429 PROMAT UK LTD CERTIFICATE OF APPROVAL No CF 429 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of The Sterling Centre,

More information

KWP-L TECHNICAL DOCUMENTATION SMOKE &FIRE ZONE. Fire Damper

KWP-L TECHNICAL DOCUMENTATION SMOKE &FIRE ZONE. Fire Damper SMOKE &FIRE ZONE TECHNICAL DOCUMENTATION KWP-L Fire Damper SMAY Sp. z o.o. / ul. Ciepłownicza 29 / 31-587 Kraków tel. +48 12 680 20 80 / e-mail: info@smay.eu www.smay.eu 1438 SMAY Sp. z o.o. 17 1438-CPR-0509

More information

GENERAL MECHANICAL SYSTEM REQUIREMENTS

GENERAL MECHANICAL SYSTEM REQUIREMENTS CHAPTER 13 GENERAL MECHANICAL SYSTEM REQUIREMENTS SECTION M1301 GENERAL M1301.1 Scope. The provisionsof thischapter shall governthe installation of mechanical systems not specifically covered in other

More information

PASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: Ductwork

PASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: Ductwork PASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: Ductwork For Promat Asia Pacific Organisation February 0 Ductwork General Information i Steel duct claddings inside the Changi Water Reclamation

More information

lindab we simplify construction LindabSmoke control system single compartment Rectangular Mounting instruction

lindab we simplify construction LindabSmoke control system single compartment Rectangular Mounting instruction lindab we simplify construction LindabSmoke control system single compartment Rectangular Mounting instruction Content Introduction...3 Intended use...3 Transport and delivery...4 Storage...4 Operation...4

More information

NEW. FR90 fire dampers. Maintenance-free

NEW. FR90 fire dampers. Maintenance-free NEW Maintenance-free FR90 fire dampers in short lengths for installation in rigid walls and ceilings and in metal stud walls Sizes: DN mm to DN 315 mm Fire classification: EI /60/90/120 (ve - ho, i o)

More information

YOUR BEST CONNECTIONS 1 HALFEN GmbH

YOUR BEST CONNECTIONS 1 HALFEN GmbH DECLARATION OF PERFORMANCE HALFEN HB-BZ/HB-BZ-IG WEDGE ANCHOR No. H40-07/0249 1. 2. Unique identification code of the HALFEN HB-BZ/HB-BZ-IG WEDGE ANCHOR product-type Type, batch or serial number or any

More information

FIRE damper type FDMD, is in all variants classified: as acc. EN and tested acc. EN and acc. EN

FIRE damper type FDMD, is in all variants classified: as acc. EN and tested acc. EN and acc. EN FIRE damper type FDMD, is in all variants classified: as acc. EN 13501 3 and tested acc. EN 1366 2 and acc. EN 15650. Installation in a solid wall construction 40 Solid wall construction Mortar or gypsum

More information

LindabSmoke control system

LindabSmoke control system lindab we simplify construction LindabSmoke control system single compartment Rectangular Mounting instruction Content Introduction...3 Intended use...3 Transport and delivery...4 Storage...4 Operation...4

More information

PAROC FIRE PROTECTION SOLUTIONS FOR PIPE PENETRATIONS

PAROC FIRE PROTECTION SOLUTIONS FOR PIPE PENETRATIONS PAROC FIRE PROTECTION SOLUTIONS FOR PIPE PENETRATIONS APPROVED FIRE SAFETY WITH PAROC STONE WOOL EN 1366-3 is a harmonized European standard for fire resistance tests for penetration seals. The test method

More information

GENERAL MECHANICAL SYSTEM REQUIREMENTS

GENERAL MECHANICAL SYSTEM REQUIREMENTS CHAPTER 13 GENERAL MECHANICAL SYSTEM REQUIREMENTS SECTION M1301 GENERAL M1301.1 Scope. The provisions of this chapter shall govern the installation of mechanical systems not specifically covered in other

More information

DECLARATION OF PERFORMANCE Sikaplan WP HL

DECLARATION OF PERFORMANCE Sikaplan WP HL Waterproofing EC Declaration of Performance Edition 03.12.2012 Identification no.02 07 04 10 100 0 150000 Version no. 1 EN 13967 04 1349 DECLARATION OF PERFORMANCE Sikaplan WP 1100 15HL 02 07 04 10 100

More information

CERTIFICATE OF APPROVAL No CF 5034 FISCHERWERKE GMBH & CO. KG.

CERTIFICATE OF APPROVAL No CF 5034 FISCHERWERKE GMBH & CO. KG. CERTIFICATE OF APPROVAL No CF 5034 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Weinhalde 14-18,

More information

7/S1 FIRE DAMPER FD25/40, FDC25/40. v 3.1 (en)

7/S1 FIRE DAMPER FD25/40, FDC25/40. v 3.1 (en) 7/S v 3. (en) FIRE DMPER FD/4, FDC/4 3 www.klimaoprema.hr www.klimaoprema.hr 33 FIRE DMPER FDC/4 Used for the isolation of duct penetrations between fire compartments. Fire dampers consist of housing,

More information

FLAMRO FKS Ready Cable Duct System

FLAMRO FKS Ready Cable Duct System Mounting Instructions FLAMRO FKS Ready Cable Duct System These mounting instruction do not replace the test certificate of the fire protection cable ducts! They must be kept for the installation of fire

More information

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 11

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 11 07 21 16 Blanket Insulation Page 1 of 11 Unifrax I LLC Design No. UNI/BI 120-14 FIRE RESISTANT GREASE DUCT FyreWrap Elite 1.5 Duct Insulation ASTM E 2336-16 and ICC-ES Acceptance Criteria for Grease Duct

More information

Installation instructions

Installation instructions Installation instructions Holetherm Double-walled flue gas discharge system (DW) 2016 All information in this release is subject to misprints. No liability is accepted for the consequences of misprints.

More information

OPERATION AND MAINTENANCE MANUAL

OPERATION AND MAINTENANCE MANUAL OPERATION AND MAINTENANCE MANUAL Type mcr PLD Gdańsk 06.12.2012. Version PLD 06.12.12 DEPARTMENT OF FIRE VENTILATION SYSTEMS GDAŃSK 2012 1 TABLE OF CONTENTS 1. INTRODUCTION 2. SUBJECT OF DOCUMENTATION

More information

Pressure loss Noise data Entry into service and revisions... 26

Pressure loss Noise data Entry into service and revisions... 26 These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers) FDMS. It is valid for production, designing, ordering, delivery, assembly and operation.

More information

Intended uses of the construction product, in accordance with the applicable harmonized technical specification as foreseen by the manufacturer:

Intended uses of the construction product, in accordance with the applicable harmonized technical specification as foreseen by the manufacturer: DoP SMRPT001 page 1 / 5 SMRPT001 Unique identification code of the product-type: SMRPT Type or serial number or any other element allowing identification of the construction product as required pursuant

More information

Operating and Installation Manual Fire Damper Type FKA-EU

Operating and Installation Manual Fire Damper Type FKA-EU FKA-EU/DE/SCDE/ en Operating and Installation Manual Fire Damper Type FKA-EU according to Declaration of Performance DoP / FKA-EU / DE / 2013 / 001 3 Contents 1 PageHeaderToc 1 General information 3 Scope

More information

MULTIBLADE FIRE DAMPER BSK-J/EI90

MULTIBLADE FIRE DAMPER BSK-J/EI90 MULTIBLADE FIRE DAMPER BSK-J/EI90 Table of contents: MULTIBLADE FIRE DAMPER BSK-J/EI90 - OVERVIEW... 3 FIRE DAMPER EI90 - GENERAL INFORMATION... 4 MULTIBLADE FIRE DAMPER BSK-J/EI90 - DIMENSIONS AND WEIGHTS...

More information

Blast Damper HV PROTECTIVE SHIELD. Features. Protection and Airflow. V00129, D

Blast Damper HV PROTECTIVE SHIELD. Features. Protection and Airflow.  V00129, D Blast Damper HV Protection and Airflow HV Series Blast Damper is designed to protect personnel and critical equipment against blast wave created by explosion in industrial facility. Gas explosions occur

More information

ASF FR Board PRO RANGE Coated Mineral Wool Board for the Professional

ASF FR Board PRO RANGE Coated Mineral Wool Board for the Professional Technical Data Sheet Version: 1 Revision Date: 11-04-2011 Description ASF FR Board has been designed to maintain the fire resistance of separating walls and floors where they are breached by single or

More information

Type or serial number or any other element allowing identification of the construction product as

Type or serial number or any other element allowing identification of the construction product as DoP SMRPF001 (rev.1) page 1 / 5 SMRPF001 Unique identification code of the product-type: SMRPF Type or serial number or any other element allowing identification of the construction product as required

More information

Annex to the Accreditation Certificate D-ZE according to DIN EN ISO/IEC 17065:2013

Annex to the Accreditation Certificate D-ZE according to DIN EN ISO/IEC 17065:2013 Deutsche Akkreditierungsstelle GmbH Annex to the Accreditation Certificate D-ZE-11267-01-00 according to DIN EN ISO/IEC 17065:2013 Period of validity: 17.08.2018 to 01.10.2022 Holder of certificate: Materialprüfanstalt

More information

Fire damper. Type FKS-EU. Installation and operating manual. GB/en. according to Declaration of Performance DoP / FKS-EU / DE / 003

Fire damper. Type FKS-EU. Installation and operating manual. GB/en. according to Declaration of Performance DoP / FKS-EU / DE / 003 and operating manual GB/en Fire damper Type FKS-EU according to Declaration of Performance DoP / FKS-EU / DE / 003 Read the instructions prior to performing any task! TROX GmbH Heinrich-Trox-Platz 47504

More information

Ordering example: BKI-K90/SFR1.90T/B=1000xH=1000xH=1000xL=250. Standard damper length; special dimensions are available on request

Ordering example: BKI-K90/SFR1.90T/B=1000xH=1000xH=1000xL=250. Standard damper length; special dimensions are available on request Ordering example: Damper BKI-K90/SFR1.90T/B=1000xH=1000xH=1000xL=250 Standard damper length; special dimensions are available on request Dimensions B x H (width x height) in mm, side H = operating side

More information

CERTIFICATE OF APPROVAL No CF 517 FSI LIMITED

CERTIFICATE OF APPROVAL No CF 517 FSI LIMITED CERTIFICATE OF APPROVAL No CF 517 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Westminster Industrial

More information

DIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS

DIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS PART 1 - GENERAL 01.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification sections, apply to work of this Section.

More information

Code Compliance Research Report CCRR-0257

Code Compliance Research Report CCRR-0257 Code Compliance Research Report CCRR-0257 Issued: 12-21-2016 Renewal Due: 12-21-2018 Revised: 12-20-2017. DIVISION: 05 50 00 Metal Fabrications Section: 05 52 00 Metal Railings REPORT HOLDER: VINYLAST,

More information

DECLARATION OF PERFORMANCE

DECLARATION OF PERFORMANCE EN DECLARATION OF PERFORMANCE according to Annex III of the Regulation (EU) Nr. 305/2011 (Construction Products Regulation) Hilti Firestop Block CFS-BL No. Hilti CFS 0761-CPD-0270 1. Unique identification

More information

CERTIFICATE OF APPROVAL No CF 5295 NULLIFIRE LIMITED

CERTIFICATE OF APPROVAL No CF 5295 NULLIFIRE LIMITED CERTIFICATE OF APPROVAL No CF 5295 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Coupland Road, Hindley

More information

Fire damper WK25. Dimensions

Fire damper WK25. Dimensions Dimensions 310 d b e c a 22 22 S2 S1 Description Rectangular fire damper for air duct system that penetrate fire resistance walls or floors. With 25 thick closing blade made from refractory material. Casing

More information

Type or serial number or any other element allowing identification of the construction product as

Type or serial number or any other element allowing identification of the construction product as DoP SMRPT001 page 1 / 5 SMRPT001 Unique identification code of the product-type: SMRPT Type or serial number or any other element allowing identification of the construction product as required pursuant

More information

Code Compliance Research Report CCRR-0238

Code Compliance Research Report CCRR-0238 Code Compliance Research Report CCRR-0238 Issued: 11-09-2016 Renewal Due: 11-09-2018 Revised: 11-10-2017 DIVISION: 05 00 00 METALS Section: 05 52 00 Metal Railings CPG Building Products LLC 894 Prairie

More information

European Technical Assessment. ETA-11/0372 of Member of. General part

European Technical Assessment. ETA-11/0372 of Member of. General part INSTITU Schenkenstrasse 4 T +43 1 533 65 50 1010 Vienna Ι Austria F +43 1 533 64 23 www.oib.or.at Ι mail@oib.or.at Designated according to Article 29 of Regulation (EU) No 305/2011 Member of www.eota.eu

More information

Fire Protection Valves

Fire Protection Valves 4/4/EN/6 Fire Protection Valves Type FV-K90 FVZ-K30 with German Test Certificate (General Building Approval) Z-41.3-317 Z-41.3-319 TROX GmbH Telephone +49/28 45/2 02-0 Telefax +49/28 45/202-265 Heinrich-Trox-Platz

More information

DECLARATION OF PERFORMANCE

DECLARATION OF PERFORMANCE DECLARATION OF PERFORMANCE 1. Unique identification code of the product-type: MULTI-MONTI-plus (MMS-plus) 2. Type, batch or serial number or any other element allowing identification of the construction

More information

Code Compliance Research Report CCRR-0238

Code Compliance Research Report CCRR-0238 Code Compliance Research Report CCRR-0238 Issue Date: 11-09-2016 Revision Date: 11-29-2018 Renewal Date: 11-09-2019 DIVISION: 05 00 00 METALS Section: 05 52 00 Metal Railings CPG Building Products LLC

More information

Trade name EZ-Path Fire-Rated Pathway (Series 33 and Series 44+) Cable Penetration Seals

Trade name EZ-Path Fire-Rated Pathway (Series 33 and Series 44+) Cable Penetration Seals UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. Phone : +44 1483 302130 Fax : +44 1483 302230 Email : Inform.NB@uk.ul.com Website

More information

Operating and Installation Manual Fire damper Type FKR-EU

Operating and Installation Manual Fire damper Type FKR-EU Operating and Installation Manual Fire damper Type FKR-EU tested to EN 1366-2 with EC Certificate of Conformity BC1-606 - 4645-15650.03-4651 Contents 1 General information 3 Other applicable documentation

More information

Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19

Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19 Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19 Page 1 or 8 APPLICATION This fi re damper is intended to restrict the passage of fl ame. The standard installation requires that the

More information

ETA 17/0081 of 21/06/2017. European Technical Assessment. Technical Assessment Body issuing the ETA and designated according to Article 29 of the

ETA 17/0081 of 21/06/2017. European Technical Assessment. Technical Assessment Body issuing the ETA and designated according to Article 29 of the Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)

More information

Xtratherm Thin-R Thermal Liner (XT/TL Grade)

Xtratherm Thin-R Thermal Liner (XT/TL Grade) CERTIFICATE NO. 03/0183 DETAIL SHEET 4 Xtratherm Thin-R Thermal Liner (XT/TL Grade) PRODUCT DESCRIPTION: This Detail Sheet relates to Xtratherm Thin-R Thermal Liner, as defined in NSAI Agrément Certificate

More information

HELIOSTAR 252, 218 VERTICAL, FREE INSTALLATION

HELIOSTAR 252, 218 VERTICAL, FREE INSTALLATION HELIOSTAR 252, 218 VERTICAL, FREE INSTALLATION INSTRUCTION MANUAL ENERGY AND SANITARY SYSTEMS Installation requirements General requirements The free-standing installation set is to be used or installing

More information

Birsta 3PH2b WORKING DESCRIPTION INSTALLATION, REPAIRS AND MAINTENANCE. Doc. No.: Birsta 3PH2b - Rev. 0

Birsta 3PH2b WORKING DESCRIPTION INSTALLATION, REPAIRS AND MAINTENANCE. Doc. No.: Birsta 3PH2b - Rev. 0 Birsta 3PH2b WORKING DESCRIPTION INSTALLATION, REPAIRS AND MAINTENANCE Doc. No.: Birsta 3PH2b - Rev. 0 Working Description Prepared by: Fredrik Sangö Doc. no.: Birsta 3PH2b Introduction/data: Birsta 3P

More information

Planning and installation instructions

Planning and installation instructions Planning and installation instructions Stofix Oy Ahlmaninkatu 2 E 40100 Jyväskylä Finland stofixgroup@stofix.com www.stofix.com 2 PLANNING AND INSTALLATION INSTRUCTIONS... 1 1 General... 3 2 Project Design...

More information

European Technical Assessment. ETA-15/0540 of Member of. General part

European Technical Assessment. ETA-15/0540 of Member of. General part INSTITU Schenkenstrasse 4 T +43 1 533 65 50 1010 Vienna Ι Austria F +43 1 533 64 23 www.oib.or.at Ι mail@oib.or.at Designated according to Article 29 of Regulation (EU) No 305/2011 Member of www.eota.eu

More information

Insulation boards PhoneStar

Insulation boards PhoneStar Sound Insulation Bavaria Insulation boards PhoneStar Installation instructions Wall Version 15.05. 2015 ONE solution universal in every area PhoneStar is an innovative, very efficient insulation board

More information

Sandwich panel SPA Product description

Sandwich panel SPA Product description Sandwich panel SPA Product description Ruukki offers a sandwich panel system that combines an attractive appearance with excellent thermal insulation and fire-resistance. The panels are of a lightweight,

More information

UL- E U C E R T I F I C A T E

UL- E U C E R T I F I C A T E UL- E U C E R T I F I C A T E Page 1/6 Certificate Holder Manufacturer Certified Product Type Product Trade Name Trademark Rating/Classification Polyseam AS Ravneveien 7 Linnestad Næringsområde N-3174

More information

TEST REPORT. Rendered to: SENTINEL FENCE AND RAIL. For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post

TEST REPORT. Rendered to: SENTINEL FENCE AND RAIL. For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post TEST REPORT Rendered to: SENTINEL FENCE AND RAIL For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post Report No: Report Date: 10/23/12 130 Derry Court York, PA 17406-8405

More information

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)

More information

Tehnical Data Sheet Astro HS FM Compound. UIC of product-type: HSFMC CPR-JA5013 ETA-14/0047. ETAG 026-Part 1 ETAG 026-Part 2

Tehnical Data Sheet Astro HS FM Compound. UIC of product-type: HSFMC CPR-JA5013 ETA-14/0047. ETAG 026-Part 1 ETAG 026-Part 2 1121 Astroflame Fireseals Ltd Unit 8 The I O Centre 14 1121-CPR-JA5013 ETA-14/0047 ETAG 026-Part 1 ETAG 026-Part 2 FM Compound see ETA-14/0047 for relevant characteristics APPROVED CF613 EN13501-2 EN1366-3:2009

More information

European Technical Approval ETA-11/0083

European Technical Approval ETA-11/0083 SINTEF Building and Infrastructure P.O.Box 124 Blindern N-0314 Oslo Tel. 47 22 96 55 55 Fax 47 22 69 54 38 Authorised and notified according to Article 10 of the Council Directive 89/106/EEC of 21 December

More information

Stack Parking Surface Mounted Stackers

Stack Parking Surface Mounted Stackers 1 / 6 Stack Parking Surface Mounted Stackers swiss-park V-2 Comfort The V-2 is designed to park cars of any size thanks to its vertical adjustability. It will accommodate cars as tall as the garage ceiling

More information

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)

More information

UL- E U C E R T I F I C A T E

UL- E U C E R T I F I C A T E UL- E U C E R T I F I C A T E Page 1/7 Certificate Holder ASTROFLAME FIRESEALS LIMITED UNIT 8 THE IO CENTRE SEGENSWORTH FAREHAM PO15 5RU United Kindgom Manufacturer A/008 Certified Product Type Product

More information

DECLARATION OF PERFORMANCE

DECLARATION OF PERFORMANCE ROCKWOOL B.V. / ROCKPANEL Group Konstruktieweg 2 NL-6045 JD Roermond www.rockpanel.com DECLARATION OF PERFORMANCE No. 0764-CPR-0249 UK vs01 1. Unique identification code of the product-type: ROCKPANEL

More information

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)

More information

R4224KPCPR. Declaration of Performance. [CompanyGraphic]

R4224KPCPR. Declaration of Performance. [CompanyGraphic] Declaration of [CompanyGraphic] 1. Unique identification code of the product-type: FKD-S without facing, FKD-S with facing, SmartRoof Thermal, NaturBoard POD STANDARD, SmartRoof Thermal 2 2. Type, batch

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report Ad-hoc fire resistance test on a galvanised steel Tunnel Ventilation Damper employing procedures and criteria from BS 476: Part 20 : 1987. Prepared for: Betec Cad Industries Date:

More information

Application & General Notes: Installation Supplements: Safety Warning: Other Installation References: Receiving & Handling: Electrical Guidelines:

Application & General Notes: Installation Supplements: Safety Warning: Other Installation References: Receiving & Handling: Electrical Guidelines: TRUE ROUND FIRE & FIRE/SMOKE DAMPER INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS R8218 FSD-RD FD(D)-RD UL/ULC File: R8218 New York BSA/MEA Listing: 79-03-M California State Fire Marshall Listing:

More information

DECLARATION OF PERFORMANCE according to Annex III of the Regulation (EU) Nr. 305/2011 (Construction Products Regulation)

DECLARATION OF PERFORMANCE according to Annex III of the Regulation (EU) Nr. 305/2011 (Construction Products Regulation) EN DECLARATION OF PERFORMANCE according to Annex III of the Regulation (EU) Nr. 305/2011 (Construction Products Regulation) Hilti nailed shear connector HVB with powder-actuated fastener X-ENP-21 HVB No.

More information

Österreichisches Institut für Bautechnik Schenkenstrasse Vienna Austria T F

Österreichisches Institut für Bautechnik Schenkenstrasse Vienna Austria T F Authorised and notified according to Article 10 of the Council Directive 89/ 106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating

More information

General Design Approval

General Design Approval General Design Approval Approval body for construction products and types of construction A public agency financed jointly by the Federal Government and the Länder Member of EOTA, UEAtc and WFTAO Date:

More information

HELIOSTAR 252, 218 HORIZONTAL, FREE INSTALLATION

HELIOSTAR 252, 218 HORIZONTAL, FREE INSTALLATION HELIOSTAR 252, 218 HORIZONTAL, FREE INSTALLATION INSTALLATION INSTRUCTIONS ENERGY AND SANITARY SYSTEMS Installation requirements General requirements The free-standing installation set is to be used for

More information

A EN ROUND STORAGE SILO. Ø480cm, Ø560cm, Ø640cm, Ø720cm ASSEMBLY AND USER MANUAL. ARSKAMETALLI LTD

A EN ROUND STORAGE SILO. Ø480cm, Ø560cm, Ø640cm, Ø720cm ASSEMBLY AND USER MANUAL. ARSKAMETALLI LTD A70-1001-EN-201805 ROUND STORAGE SILO Ø480cm, Ø560cm, Ø640cm, Ø720cm ASSEMBLY AND USER MANUAL ARSKAMETALLI LTD www.arskametalli.fi CONTENTS Introduction Delivery information EU Declaration of Conformity

More information

Birsta 3PH4b WORKING DESCRIPTION INSTALLATION, REPAIRS AND MAINTENANCE. Doc. No.: Birsta 3PH4b - Rev. 0

Birsta 3PH4b WORKING DESCRIPTION INSTALLATION, REPAIRS AND MAINTENANCE. Doc. No.: Birsta 3PH4b - Rev. 0 Birsta 3PH4b Doc. No.: Birsta 3PH4b - Rev. 0 Working Description Prepared by: Fredrik Sangö Doc. no.: Birsta 3PH4b Introduction/data: Birsta 3PH4b has been full-scale tested according to EN 1317-2 (TB11

More information

Kemwell Impact Board. PASSIVE FIRE PROTECTION Specialists for the construction, infrastructure, transport, energy, industrial and commercial sectors.

Kemwell Impact Board. PASSIVE FIRE PROTECTION Specialists for the construction, infrastructure, transport, energy, industrial and commercial sectors. Uniclass L68111:P91 CI/SfB Ry September 2017 Epic F811 (K2) Kemwell Impact Board A1 Non-combustible high performance fire, blast and impact protection board for critical applications in the commercial,

More information

This European technical approval

This European technical approval Authorised and notified according to Article 10 of the Council Directive 89/ 106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating

More information

BLUEKIT VENTILATION FLAPS

BLUEKIT VENTILATION FLAPS BLUEKIT VENTILATION FLAPS www.bluekit.eu 1 Horizontal mounting into the shaft/the roof Vertical mounting into the shaft/ the facade 5 4 3 2 1 2 EN_BLUEKIT_VENTILATIONFLAPS_20150909 Summary New building...

More information

LLOYD INDUSTRIES INC. DAMPER INSTALLATION INSTRUCTIONS

LLOYD INDUSTRIES INC.   DAMPER INSTALLATION INSTRUCTIONS Installation and Maintenance Instructions 1-1/2 Hour Rated, UL Classified model 75 fire dampers For use in fire barriers with ratings of less than 3 hours INSPECTION 1. Inspect for shipping damage. 2.

More information