Smoke Control Damper ESAM Instructions for installation, operation and maintenance 10/2014
|
|
- Jordan Wright
- 6 years ago
- Views:
Transcription
1 Instructions for installation, operation and maintenance 0/204 General The rectangular smoke control damper ESAM is specially designed for use in multi fire-compartment applications as a closing or opening damper for smoke extraction purposes. ESAM meets the European product standard EN 20- requirements for multi-compartment applications and is CE marked. The product has been tested according to EN 3-0, fulfilling fire class EI 20S / EI 90S with pressure class 000 Pa. ESAM dampers are suitable for both automatic operation by fire-alarm-activated systems (AA) and by manual operation by fire-fighter-activated systems (MA, installed in the duct). The duct outlet must be placed so that the smoke control damper is protected from water and moisture coming from outside as well as ice and snow that could hinder the opening of the damper. The ductwork section between the smoke control damper and the duct outlet must be designed and insulated so that the heat insulation and tightness requirements are met. The ductwork design should also take into account possible condensation and mitigate against it. The smoke control damper can be installed with the actuator box on the side, top or bottom. Fig.. Wiring diagram for Belimo actuators VAC/DC A L-L2 open (90 ) L-L3 closed (0 ) N L~ + T 2 3 PE ~ ~ + AC 230 V AC 24 V DC 24 V a b Closed (<3 ) Open (> ) Contact between Contact between S-S2 S4-S S S2 S3 S4 S S <3 < < > B PA Only a qualified electrician is allowed to perform the electrical wiring according to drawings and wiring diagrams. Wiring diagrams for damper actuators: see Figures and 2. The entire cable system with connection boxes has to be fire resistant as designed. The connection of the damper actuator to a fire-resistant cable must be made inside the calcium-silicate actuator box so that the actuator cables are shielded by the box. Installation Careful installation is required to ensure the proper functioning of the ESAM smoke control damper. Please especially note the following points: Cross-measures have to be the same from both corners. The damper must be fixed in place and supported taking into account the weight of the product and the fire-resistance requirements. See installation examples on next page. The electrical connection must be made inside the calcium-silicate box. A hole must be drilled in the actuator box on site for the power cable. When the cable has been installed, the cable entry must be sealed with an appropriate fire-rated sealant. In the case of smoke control dampers over 3 mm in height, the damper blade will project outside the damper casing in the open position, i.e. the 'open' depth is greater than the 'closed' depth. This must be taken into account when installing the product, ensuring that the blade can move freely into the 'open' position. The required direction of gas flow is indicated on the outside of the smoke control damper. The damper must be installed so that gases flow through it in the direction indicated. Heater Fig. 2. Wiring diagram for Schischek actuators.
2 0 mm Smoke Control Damper ESAM Installation examples mm * Fig. 3. Installation in solid wall constructions.. Smoke Control Damper ESAM 2. Solid construction 3. Board construction 4. Mineral wool (stone wool), min. density 40 kg/m 3. High-temperature ceramic fibre paper, e.g. Ceramat Protecta. Fire-rated sealant, min. thickness mm, e.g. Promatec Mastik. Calcium-silicate board, min. thickness mm, e.g. Promatec H or L. Fixings and supports, e.g. galvanised angle iron, min. thickness 2 mm, secured with acid-proof screws, and/or threaded rod M-M20, min. grade. *) The cover of the actuator box must be able to open after installation mm * 0 mm Fig. 4. Installation in board constructions such as drywall. Fläkt Woods 900 GB Specifications are subject to alteration without notice.
3 Installation examples (continue) 2 2 Fig.. Installation on solid ceiling constructions.. Smoke Control Damper ESAM 2. Solid construction 3. Board construction 4. Mineral wool (stone wool), min. density 40 kg/m 3. High-temperature ceramic fibre paper, e.g. Ceramat Protecta. Fire-rated sealant, min. thickness mm, e.g. Promatec Mastik. Calcium-silicate board, min. thickness mm, e.g. Promatec H or L. Fixings and supports, e.g. galvanised angle iron, min. thickness 2 mm, secured with acid-proof screws, and/or threaded rod M-M20, min. grade. Fläkt Woods 900 GB Specifications are subject to alteration without notice.
4 Installation examples (continue) Fig.. Installation in a horizontal duct Installation opening W (220*) H (30*) *) With a Schischek InMax actuator Fig.. Dimensions of the installation opening. Fläkt Woods 900 GB Specifications are subject to alteration without notice.
5 Fixing examples without anchor 2 3 Fixing to solid constructions with anchor with fixing plate and anchors Fixing plates 20 0 M-M20 2 x Ø9 0 4 x Ø9 M - M Threaded rod M-M20 2. Nut 3. Washer 4. Sleeve nut. Steel anchor. Fixing plate, min. thickness 0 mm 00 0 Fig.. Examples of fixing to solid constructions Threaded rod 2. Nut 3. C washer 4. Mounting rail 4x4x2. Washer. Bolt. L bracket. Screw (acid-proof) 9. Support rail 0. Angle bracket Fig. 9. Examples of fixings. Fläkt Woods 900 GB Specifications are subject to alteration without notice.
6 Inspection and maintenance The function of smoke control dampers must always be checked before and after installation. According to product standard EN 20-, smoke control dampers should be checked periodically at least every six months to ensure the grade is maintained as designed (see the example check list). Special attention should be paid to the tightness of seams and joints to ensure they do not let the heat out. Any defects must be repaired. Damper reference Date of inspection Check actuator and end-switch wiring for damage. Check damper cleanliness and clean where necessary. Check the condition of the blade and seals; rectify and report where necessary. Confirm operation of the damper to OPEN (within 0 s) and CLOSE (within 0 s) by use of the control system and physical observation of the damper; rectify and report where necessary. Confirm operation of OPEN and CLOSED end-switches; rectify and report where necessary. Confirm that the damper fulfils its function as part of the smoke control system. Confirm that the damper is left in its standby position. NOTE! A smoke control damper is part of a smoke control system. As this is the case, the whole system should be checked as governed by the operation and maintenance requirements for the system. The smoke control damper is made of impact-sensitive material. Visually check the material for cracks. If any are found, please contact your nearest Fläkt Woods representative. Fläkt Woods 900 GB Specifications are subject to alteration without notice.
7 DECLARATION OF PERFORMANCE No. 02CPR Unique identification code of the product-type: Smoke Control Damper ESAM 2. Type, batch or serial number or any other element allowing identification of the construction product as required under Article (4): Smoke Control Damper ESAM-aaaa-bbbb-c-d 3. Intended use or uses of the construction product, in accordance with the applicable harmonised technical specification, as foreseen by the manufacturer: Smoke control dampers that are to be used in smoke control systems, in multi compartment applications, either up to 00 C or at fire temperatures 4. Name, registered trade name or registered trade mark and contact address of the manufacturer as required pursuant Article (): Fläkt Woods Oy, Kalevantie 39, 2020 Turku, Finland Tel , Fax: , info.fi@flaktwoods.com Manufacturer: Mandik, Product code: SEDM. System or systems of assessment and verification of constancy of performance of the construction product as set out in Annex V: System. PAVUS, a.s., Nr. 039 Performed determination the product type on the basis of type testing; initial inspection of the manufacturing plant and of factory production control; continuous surveillance, assessment and evaluation of the factory production control (FPC) under system and issued: certificate of constancy of performance - EC Certificate of Conformity 39-CPD-009/202/O.. Declared performance: Essential characteristics Performance Harmonized technical Nominal activation conditions/sensitivity Response delay (response time) Operational reliability Pass Pass Pass / C0000 specification Fire resistance EN 20 :20 inte grity E insulation EI smoke le akage ES, EIS mechanical stability (under E) Pass maintenance of the cross section (under E) Pass Durability: Pass / C0000 of response delay of operational re liability Classification in accordance with EN 30 4+A: Dimensions Supporting construction Classification 200 x x 00 Vertical duc t EI 20 (h od i< >o)s000c 0000 MAmulti EI 20 (h od i< >o)s000c 0000 AAmulti 200 x x 00 Aerated concrete ceiling, thickness 0 mm EI 90 (h ow i< >o)s000c 0000 AAmulti 200 x x 00 Aerated concrete wall, thickness 00 mm EI 20 (v ew i< >o)s000c 0000 AAmulti 200 x x 00 Gypsum board wall, thickness 00 mm EI 20 (v ew i< >o)s000c 0000 AAmulti 200 x x 00 Horizontal duc t EI 20 (v ed i< >o)s000c 0000 MAmulti EI 20 (v ed i< >o)s000c 0000 AAmulti. The performance of the product identified in points and 2 is in conformity with the declared performance in point. This declaration of performance is issued under the sole responsibility of the manufacturer identified in point 4. Signed for and on behalf of the manufacturer by: Raimo Perttunen, Product Manager Turku
8 Fläkt Woods Oy Kalevantie 39 FI-2020 Turku, Finland Tel Fax GB 204.0
Declaration of performance
Product Unique identification code of the product type FKRS-EU Intended use Fire damper Manufacturer TROX GmbH Phone +49 (0)2845 2020 Fax +49 (0)2845 202265 Heinrich-Trox-Platz E-mail trox@trox.de 47504
More information3. Dimensions, weights Placement and Assembly Statement of installations Electrical Components, Connection Diagrams...
These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers) FDMC. It is valid for production, designing, ordering, delivery, assembly and operation.
More information1. Description Damper Design Dimensions, weights Placement and Assembly Statement of installations...
These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers) CFDM. It is valid for production, designing, ordering, delivery, assembly and operation.
More informationPRODUCT CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE
Certificate No C-11669-16 Issued June 14, 2016 Updated September 12, 2018 PRODUCT CERTIFICATE NAME OF PRODUCT Knauf Insulation Fire Insulation System for ventilation ducts MANUFACTURER Knauf Insulation
More information*1MUBWK25EN* *1MUBWK25EN-LIND* rev rev *1MUBWK25EN-LIND* WK25. RECTANGULAR SERIES WK Pa. Cert. N 1812-CPR-1045 EN 15650
WK25 Installation booklet English RECTANGULAR SERIES WK25-500 Pa Cert. N 1812-CPR-1045 EN 15650 *1MUBWK25EN* *1MUBWK25EN-LIND* rev 17-04 rev 17-04 *1MUBWK25EN* *1MUBWK25EN-LIND* www.mp3-italia.it www.lindab.com
More informationDECLARATION OF PERFORMANCE. DoP No CPD GB (Version 1)
DECLARATION OF PERFORMANCE DoP No. 0756-CPD-447 - GB (Version 1) 1. Unique identification code of the product-type: SPIT TAPCON-6 2. Type, batch or serial number or any other element allowing identification
More informationDate of update January 25, 2018 Valid until
CERTIFICATE PRODUCT APPLICATION VTT-C-4805-09 Date of update January 25, 2018 Valid until 12.10.2020 U Protect fire insulation solutions for ventilation ducts MANUFACTURER Saint-Gobain Finland Oy / ISOVER
More informationInstallation in ceilings
Installation instructions EI90 BET Cable Boxes "System Wichmann" ceiling 350 mm depth, rectangular ETA 13/0902 BET Cable Box to be poured in the concrete» Technical datasheet - page 4-7 Installation in
More informationDeclaration of Performance
Product Unique identification code of the product type FK-EU Intended use Fire damper Manufacturer TROX GmbH Phone +49 (0)2845 2020 Fax +49 (0)2845 202265 Heinrich-Trox-Platz E-mail trox@trox.de 47504
More information1. Description Damper Design Dimensions, weights Placement and Assembly Statement of installations...
These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers) CFDM. It is valid for production, designing, ordering, delivery, assembly and operation.
More information1. Description Damper Design Dimensions, weights Placement and Assembly Statement of installations...
These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers) CFDM. It is valid for production, designing, ordering, delivery, assembly and operation.
More information*1MUBWK45EN* *1MUBWK45EN-LIND* WK45. RECTANGULAR SERIES WK Pa / 300 Pa. Cert. N 1812-CPR-1006 EN Installation booklet English
WK45 Installation booklet English RECTANGULAR SERIES WK45-500 Pa / 300 Pa Cert. N 1812-CPR-1006 EN 15650 *1MUBWK45EN* *1MUBWK45EN-LIND* rev 17-04 rev 17-04 *1MUBWK45EN* *1MUBWK45EN-LIND* www.mp3-italia.it
More information2500 Series Fire Smoke Dampers
General Description The model 2550 is designed to prevent the spread of fire and smoke through ventilation ductwork in walls and floors. From receiving an alarm the power to the damper actuator is removed
More informationCERTIFICATE OF APPROVAL No CF 5073 LEMINAR AIR CONDITIONING INDUSTRIES L.L.C.
CERTIFICATE OF APPROVAL No CF 5073 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of PO Box 33539, Dubai,
More informationDECLARATION OF PERFORMANCE. DoP No CPD GB (Version 1)
DECLARATION OF PERFORMANCE DoP No. 0679-CPD-0074 - GB (Version 1) 1. Unique identification code of the product-type: SPIT EPOMAX 2. Type, batch or serial number or any other element allowing identification
More informationDECLARATION OF PERFORMANCE
1.0 Unique Identification Code of the Product Type(s): Pyroplex CE Marked Intumescent Acrylic 2.0 Type, batch or serial number or any other element allowing identification of the products as required under
More informationPRODUCT APPLICATION MANUFACTURER INTRODUCTION CERTIFICATION PROCEDURE. Date of update April 6, 2018 Valid until
CERTIFICATE VTT-C-12188-17 Date of update April 6, 2018 Valid until 6.12.2022 PRODUCT APPLICATION CONLIT insulation solutions for ventilation ducts MANUFACTURER Rockwool Finland Oy P.O. Box 78 FI-01511
More informationDeclaration of Performance (DOP)
Declaration of Performance (DOP) No. 9174 009 DOP 2014-01-27 1. Unique identification code of the product-type: Multi-wall chimney system type DW-VISION according to 2. Type, batch or serial number or
More informationMULTIBLADE SMOKE CONTROL DAMPER BRK-J/EI90
MULTIBLADE SMOKE CONTROL DAMPER BRK-J/EI90 Table of contents MULTIBLADE SMOKE CONTROL DAMPER BRK-J/EI90... 2 MULTIBLADE SMOKE CONTROL DAMPER BRK-J/EI90... 3 MULTIBLADE SMOKE CONTROL DAMPER BRK-J/EI90 DIMENSIONS...
More information*1MUBWKS25EN* *1MUBWKS25EN-LIND* rev rev *1MUBWKS25EN-LIND* WKS25. RECTANGULAR SERIES WKS Pa. Cert. N 1812-CPR-1046 EN 15650
WKS25 Installation booklet English RECTANGULAR SERIES WKS25-500 Pa Cert. N 1812-CPR-1046 EN 15650 *1MUBWKS25EN* *1MUBWKS25EN-LIND* rev 17-04 rev 17-04 *1MUBWKS25EN* *1MUBWKS25EN-LIND* www.mp3-italia.it
More informationInternal Partitions - Timber Studs Internal Partitions - Steel Stud
Timber Studs PH Internal Partitions - Steel Stud / hour fire rating, integrity and insulation in accordance with the criteria of BS : Part and AS 0: Part. Nominal thickness of partition: mm PROMATECT -H
More informationmcr Silboard self-supporting ventilation and smoke extraction ducts
mcr Silboard self-supporting ventilation and smoke extraction ducts INTENDED USE mcr Silboard is a calcium-silicate fireproof board designed for the construction of e.g. self-supporting fireproof general
More informationVoie Romaine F Maizières-lès-Metz Tel.: +33 (0) Fax.: +33 (0) Operating vacuum pressure: - 500Pa
Voie Romaine F-57280 Maizières-lès-Metz Tel.: +33 (0)3 87 51 11 11 Fax.: +33 (0)3 87 51 10 58 CLASSIFICATION REPORT CLASSIFICATION REPORT no. 09 - A - 363 According to standards EN 15650: 2010 and EN 13501-3:
More informationDeclaration of Performance (DOP)
Declaration of (DOP) No. 9174 073 DOP 2015-07-27 1. Unique identification code of the product-type: Multi-wall chimney system type FURADO-F according to 2. Type, batch or serial number or any other element
More informationInstallation instruction
Installation instruction Ci51 www.contura.eu 114 CERTIFICATE Declaration of performance according to Regulation (EU) 305/2011 No. Ci51-CPR-150821-SE-2 PRODUCT Product type Type designation Manufacturing
More information0160 Series Curtain Fire Dampers
Burrell Way, General Description The 0160 series curtain fire dampers are designed to stop the spread of fire through ductwork, walls and floors in ventilation systems. When the fusible link reaches elevated
More informationCERTIFICATE OF APPROVAL No CF 429 PROMAT UK LTD
CERTIFICATE OF APPROVAL No CF 429 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of The Sterling Centre,
More informationKWP-L TECHNICAL DOCUMENTATION SMOKE &FIRE ZONE. Fire Damper
SMOKE &FIRE ZONE TECHNICAL DOCUMENTATION KWP-L Fire Damper SMAY Sp. z o.o. / ul. Ciepłownicza 29 / 31-587 Kraków tel. +48 12 680 20 80 / e-mail: info@smay.eu www.smay.eu 1438 SMAY Sp. z o.o. 17 1438-CPR-0509
More informationGENERAL MECHANICAL SYSTEM REQUIREMENTS
CHAPTER 13 GENERAL MECHANICAL SYSTEM REQUIREMENTS SECTION M1301 GENERAL M1301.1 Scope. The provisionsof thischapter shall governthe installation of mechanical systems not specifically covered in other
More informationPASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: Ductwork
PASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: Ductwork For Promat Asia Pacific Organisation February 0 Ductwork General Information i Steel duct claddings inside the Changi Water Reclamation
More informationlindab we simplify construction LindabSmoke control system single compartment Rectangular Mounting instruction
lindab we simplify construction LindabSmoke control system single compartment Rectangular Mounting instruction Content Introduction...3 Intended use...3 Transport and delivery...4 Storage...4 Operation...4
More informationNEW. FR90 fire dampers. Maintenance-free
NEW Maintenance-free FR90 fire dampers in short lengths for installation in rigid walls and ceilings and in metal stud walls Sizes: DN mm to DN 315 mm Fire classification: EI /60/90/120 (ve - ho, i o)
More informationYOUR BEST CONNECTIONS 1 HALFEN GmbH
DECLARATION OF PERFORMANCE HALFEN HB-BZ/HB-BZ-IG WEDGE ANCHOR No. H40-07/0249 1. 2. Unique identification code of the HALFEN HB-BZ/HB-BZ-IG WEDGE ANCHOR product-type Type, batch or serial number or any
More informationFIRE damper type FDMD, is in all variants classified: as acc. EN and tested acc. EN and acc. EN
FIRE damper type FDMD, is in all variants classified: as acc. EN 13501 3 and tested acc. EN 1366 2 and acc. EN 15650. Installation in a solid wall construction 40 Solid wall construction Mortar or gypsum
More informationLindabSmoke control system
lindab we simplify construction LindabSmoke control system single compartment Rectangular Mounting instruction Content Introduction...3 Intended use...3 Transport and delivery...4 Storage...4 Operation...4
More informationPAROC FIRE PROTECTION SOLUTIONS FOR PIPE PENETRATIONS
PAROC FIRE PROTECTION SOLUTIONS FOR PIPE PENETRATIONS APPROVED FIRE SAFETY WITH PAROC STONE WOOL EN 1366-3 is a harmonized European standard for fire resistance tests for penetration seals. The test method
More informationGENERAL MECHANICAL SYSTEM REQUIREMENTS
CHAPTER 13 GENERAL MECHANICAL SYSTEM REQUIREMENTS SECTION M1301 GENERAL M1301.1 Scope. The provisions of this chapter shall govern the installation of mechanical systems not specifically covered in other
More informationDECLARATION OF PERFORMANCE Sikaplan WP HL
Waterproofing EC Declaration of Performance Edition 03.12.2012 Identification no.02 07 04 10 100 0 150000 Version no. 1 EN 13967 04 1349 DECLARATION OF PERFORMANCE Sikaplan WP 1100 15HL 02 07 04 10 100
More informationCERTIFICATE OF APPROVAL No CF 5034 FISCHERWERKE GMBH & CO. KG.
CERTIFICATE OF APPROVAL No CF 5034 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Weinhalde 14-18,
More information7/S1 FIRE DAMPER FD25/40, FDC25/40. v 3.1 (en)
7/S v 3. (en) FIRE DMPER FD/4, FDC/4 3 www.klimaoprema.hr www.klimaoprema.hr 33 FIRE DMPER FDC/4 Used for the isolation of duct penetrations between fire compartments. Fire dampers consist of housing,
More informationFLAMRO FKS Ready Cable Duct System
Mounting Instructions FLAMRO FKS Ready Cable Duct System These mounting instruction do not replace the test certificate of the fire protection cable ducts! They must be kept for the installation of fire
More informationDivision 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 11
07 21 16 Blanket Insulation Page 1 of 11 Unifrax I LLC Design No. UNI/BI 120-14 FIRE RESISTANT GREASE DUCT FyreWrap Elite 1.5 Duct Insulation ASTM E 2336-16 and ICC-ES Acceptance Criteria for Grease Duct
More informationInstallation instructions
Installation instructions Holetherm Double-walled flue gas discharge system (DW) 2016 All information in this release is subject to misprints. No liability is accepted for the consequences of misprints.
More informationOPERATION AND MAINTENANCE MANUAL
OPERATION AND MAINTENANCE MANUAL Type mcr PLD Gdańsk 06.12.2012. Version PLD 06.12.12 DEPARTMENT OF FIRE VENTILATION SYSTEMS GDAŃSK 2012 1 TABLE OF CONTENTS 1. INTRODUCTION 2. SUBJECT OF DOCUMENTATION
More informationPressure loss Noise data Entry into service and revisions... 26
These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers) FDMS. It is valid for production, designing, ordering, delivery, assembly and operation.
More informationIntended uses of the construction product, in accordance with the applicable harmonized technical specification as foreseen by the manufacturer:
DoP SMRPT001 page 1 / 5 SMRPT001 Unique identification code of the product-type: SMRPT Type or serial number or any other element allowing identification of the construction product as required pursuant
More informationOperating and Installation Manual Fire Damper Type FKA-EU
FKA-EU/DE/SCDE/ en Operating and Installation Manual Fire Damper Type FKA-EU according to Declaration of Performance DoP / FKA-EU / DE / 2013 / 001 3 Contents 1 PageHeaderToc 1 General information 3 Scope
More informationMULTIBLADE FIRE DAMPER BSK-J/EI90
MULTIBLADE FIRE DAMPER BSK-J/EI90 Table of contents: MULTIBLADE FIRE DAMPER BSK-J/EI90 - OVERVIEW... 3 FIRE DAMPER EI90 - GENERAL INFORMATION... 4 MULTIBLADE FIRE DAMPER BSK-J/EI90 - DIMENSIONS AND WEIGHTS...
More informationBlast Damper HV PROTECTIVE SHIELD. Features. Protection and Airflow. V00129, D
Blast Damper HV Protection and Airflow HV Series Blast Damper is designed to protect personnel and critical equipment against blast wave created by explosion in industrial facility. Gas explosions occur
More informationASF FR Board PRO RANGE Coated Mineral Wool Board for the Professional
Technical Data Sheet Version: 1 Revision Date: 11-04-2011 Description ASF FR Board has been designed to maintain the fire resistance of separating walls and floors where they are breached by single or
More informationType or serial number or any other element allowing identification of the construction product as
DoP SMRPF001 (rev.1) page 1 / 5 SMRPF001 Unique identification code of the product-type: SMRPF Type or serial number or any other element allowing identification of the construction product as required
More informationAnnex to the Accreditation Certificate D-ZE according to DIN EN ISO/IEC 17065:2013
Deutsche Akkreditierungsstelle GmbH Annex to the Accreditation Certificate D-ZE-11267-01-00 according to DIN EN ISO/IEC 17065:2013 Period of validity: 17.08.2018 to 01.10.2022 Holder of certificate: Materialprüfanstalt
More informationFire damper. Type FKS-EU. Installation and operating manual. GB/en. according to Declaration of Performance DoP / FKS-EU / DE / 003
and operating manual GB/en Fire damper Type FKS-EU according to Declaration of Performance DoP / FKS-EU / DE / 003 Read the instructions prior to performing any task! TROX GmbH Heinrich-Trox-Platz 47504
More informationOrdering example: BKI-K90/SFR1.90T/B=1000xH=1000xH=1000xL=250. Standard damper length; special dimensions are available on request
Ordering example: Damper BKI-K90/SFR1.90T/B=1000xH=1000xH=1000xL=250 Standard damper length; special dimensions are available on request Dimensions B x H (width x height) in mm, side H = operating side
More informationCERTIFICATE OF APPROVAL No CF 517 FSI LIMITED
CERTIFICATE OF APPROVAL No CF 517 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Westminster Industrial
More informationDIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS
PART 1 - GENERAL 01.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification sections, apply to work of this Section.
More informationCode Compliance Research Report CCRR-0257
Code Compliance Research Report CCRR-0257 Issued: 12-21-2016 Renewal Due: 12-21-2018 Revised: 12-20-2017. DIVISION: 05 50 00 Metal Fabrications Section: 05 52 00 Metal Railings REPORT HOLDER: VINYLAST,
More informationDECLARATION OF PERFORMANCE
EN DECLARATION OF PERFORMANCE according to Annex III of the Regulation (EU) Nr. 305/2011 (Construction Products Regulation) Hilti Firestop Block CFS-BL No. Hilti CFS 0761-CPD-0270 1. Unique identification
More informationCERTIFICATE OF APPROVAL No CF 5295 NULLIFIRE LIMITED
CERTIFICATE OF APPROVAL No CF 5295 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Coupland Road, Hindley
More informationFire damper WK25. Dimensions
Dimensions 310 d b e c a 22 22 S2 S1 Description Rectangular fire damper for air duct system that penetrate fire resistance walls or floors. With 25 thick closing blade made from refractory material. Casing
More informationType or serial number or any other element allowing identification of the construction product as
DoP SMRPT001 page 1 / 5 SMRPT001 Unique identification code of the product-type: SMRPT Type or serial number or any other element allowing identification of the construction product as required pursuant
More informationCode Compliance Research Report CCRR-0238
Code Compliance Research Report CCRR-0238 Issued: 11-09-2016 Renewal Due: 11-09-2018 Revised: 11-10-2017 DIVISION: 05 00 00 METALS Section: 05 52 00 Metal Railings CPG Building Products LLC 894 Prairie
More informationEuropean Technical Assessment. ETA-11/0372 of Member of. General part
INSTITU Schenkenstrasse 4 T +43 1 533 65 50 1010 Vienna Ι Austria F +43 1 533 64 23 www.oib.or.at Ι mail@oib.or.at Designated according to Article 29 of Regulation (EU) No 305/2011 Member of www.eota.eu
More informationFire Protection Valves
4/4/EN/6 Fire Protection Valves Type FV-K90 FVZ-K30 with German Test Certificate (General Building Approval) Z-41.3-317 Z-41.3-319 TROX GmbH Telephone +49/28 45/2 02-0 Telefax +49/28 45/202-265 Heinrich-Trox-Platz
More informationDECLARATION OF PERFORMANCE
DECLARATION OF PERFORMANCE 1. Unique identification code of the product-type: MULTI-MONTI-plus (MMS-plus) 2. Type, batch or serial number or any other element allowing identification of the construction
More informationCode Compliance Research Report CCRR-0238
Code Compliance Research Report CCRR-0238 Issue Date: 11-09-2016 Revision Date: 11-29-2018 Renewal Date: 11-09-2019 DIVISION: 05 00 00 METALS Section: 05 52 00 Metal Railings CPG Building Products LLC
More informationTrade name EZ-Path Fire-Rated Pathway (Series 33 and Series 44+) Cable Penetration Seals
UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. Phone : +44 1483 302130 Fax : +44 1483 302230 Email : Inform.NB@uk.ul.com Website
More informationOperating and Installation Manual Fire damper Type FKR-EU
Operating and Installation Manual Fire damper Type FKR-EU tested to EN 1366-2 with EC Certificate of Conformity BC1-606 - 4645-15650.03-4651 Contents 1 General information 3 Other applicable documentation
More informationStandard Installation Fire Damper Models: 119, 119(F), 119(SS), D19
Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19 Page 1 or 8 APPLICATION This fi re damper is intended to restrict the passage of fl ame. The standard installation requires that the
More informationETA 17/0081 of 21/06/2017. European Technical Assessment. Technical Assessment Body issuing the ETA and designated according to Article 29 of the
Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)
More informationXtratherm Thin-R Thermal Liner (XT/TL Grade)
CERTIFICATE NO. 03/0183 DETAIL SHEET 4 Xtratherm Thin-R Thermal Liner (XT/TL Grade) PRODUCT DESCRIPTION: This Detail Sheet relates to Xtratherm Thin-R Thermal Liner, as defined in NSAI Agrément Certificate
More informationHELIOSTAR 252, 218 VERTICAL, FREE INSTALLATION
HELIOSTAR 252, 218 VERTICAL, FREE INSTALLATION INSTRUCTION MANUAL ENERGY AND SANITARY SYSTEMS Installation requirements General requirements The free-standing installation set is to be used or installing
More informationBirsta 3PH2b WORKING DESCRIPTION INSTALLATION, REPAIRS AND MAINTENANCE. Doc. No.: Birsta 3PH2b - Rev. 0
Birsta 3PH2b WORKING DESCRIPTION INSTALLATION, REPAIRS AND MAINTENANCE Doc. No.: Birsta 3PH2b - Rev. 0 Working Description Prepared by: Fredrik Sangö Doc. no.: Birsta 3PH2b Introduction/data: Birsta 3P
More informationPlanning and installation instructions
Planning and installation instructions Stofix Oy Ahlmaninkatu 2 E 40100 Jyväskylä Finland stofixgroup@stofix.com www.stofix.com 2 PLANNING AND INSTALLATION INSTRUCTIONS... 1 1 General... 3 2 Project Design...
More informationEuropean Technical Assessment. ETA-15/0540 of Member of. General part
INSTITU Schenkenstrasse 4 T +43 1 533 65 50 1010 Vienna Ι Austria F +43 1 533 64 23 www.oib.or.at Ι mail@oib.or.at Designated according to Article 29 of Regulation (EU) No 305/2011 Member of www.eota.eu
More informationInsulation boards PhoneStar
Sound Insulation Bavaria Insulation boards PhoneStar Installation instructions Wall Version 15.05. 2015 ONE solution universal in every area PhoneStar is an innovative, very efficient insulation board
More informationSandwich panel SPA Product description
Sandwich panel SPA Product description Ruukki offers a sandwich panel system that combines an attractive appearance with excellent thermal insulation and fire-resistance. The panels are of a lightweight,
More informationUL- E U C E R T I F I C A T E
UL- E U C E R T I F I C A T E Page 1/6 Certificate Holder Manufacturer Certified Product Type Product Trade Name Trademark Rating/Classification Polyseam AS Ravneveien 7 Linnestad Næringsområde N-3174
More informationTEST REPORT. Rendered to: SENTINEL FENCE AND RAIL. For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post
TEST REPORT Rendered to: SENTINEL FENCE AND RAIL For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post Report No: Report Date: 10/23/12 130 Derry Court York, PA 17406-8405
More informationTechnical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd
Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)
More informationTehnical Data Sheet Astro HS FM Compound. UIC of product-type: HSFMC CPR-JA5013 ETA-14/0047. ETAG 026-Part 1 ETAG 026-Part 2
1121 Astroflame Fireseals Ltd Unit 8 The I O Centre 14 1121-CPR-JA5013 ETA-14/0047 ETAG 026-Part 1 ETAG 026-Part 2 FM Compound see ETA-14/0047 for relevant characteristics APPROVED CF613 EN13501-2 EN1366-3:2009
More informationEuropean Technical Approval ETA-11/0083
SINTEF Building and Infrastructure P.O.Box 124 Blindern N-0314 Oslo Tel. 47 22 96 55 55 Fax 47 22 69 54 38 Authorised and notified according to Article 10 of the Council Directive 89/106/EEC of 21 December
More informationStack Parking Surface Mounted Stackers
1 / 6 Stack Parking Surface Mounted Stackers swiss-park V-2 Comfort The V-2 is designed to park cars of any size thanks to its vertical adjustability. It will accommodate cars as tall as the garage ceiling
More informationTechnical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd
Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)
More informationUL- E U C E R T I F I C A T E
UL- E U C E R T I F I C A T E Page 1/7 Certificate Holder ASTROFLAME FIRESEALS LIMITED UNIT 8 THE IO CENTRE SEGENSWORTH FAREHAM PO15 5RU United Kindgom Manufacturer A/008 Certified Product Type Product
More informationDECLARATION OF PERFORMANCE
ROCKWOOL B.V. / ROCKPANEL Group Konstruktieweg 2 NL-6045 JD Roermond www.rockpanel.com DECLARATION OF PERFORMANCE No. 0764-CPR-0249 UK vs01 1. Unique identification code of the product-type: ROCKPANEL
More informationTechnical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd
Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)
More informationR4224KPCPR. Declaration of Performance. [CompanyGraphic]
Declaration of [CompanyGraphic] 1. Unique identification code of the product-type: FKD-S without facing, FKD-S with facing, SmartRoof Thermal, NaturBoard POD STANDARD, SmartRoof Thermal 2 2. Type, batch
More informationBRE Global Test Report
BRE Global Test Report Ad-hoc fire resistance test on a galvanised steel Tunnel Ventilation Damper employing procedures and criteria from BS 476: Part 20 : 1987. Prepared for: Betec Cad Industries Date:
More informationApplication & General Notes: Installation Supplements: Safety Warning: Other Installation References: Receiving & Handling: Electrical Guidelines:
TRUE ROUND FIRE & FIRE/SMOKE DAMPER INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS R8218 FSD-RD FD(D)-RD UL/ULC File: R8218 New York BSA/MEA Listing: 79-03-M California State Fire Marshall Listing:
More informationDECLARATION OF PERFORMANCE according to Annex III of the Regulation (EU) Nr. 305/2011 (Construction Products Regulation)
EN DECLARATION OF PERFORMANCE according to Annex III of the Regulation (EU) Nr. 305/2011 (Construction Products Regulation) Hilti nailed shear connector HVB with powder-actuated fastener X-ENP-21 HVB No.
More informationÖsterreichisches Institut für Bautechnik Schenkenstrasse Vienna Austria T F
Authorised and notified according to Article 10 of the Council Directive 89/ 106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating
More informationGeneral Design Approval
General Design Approval Approval body for construction products and types of construction A public agency financed jointly by the Federal Government and the Länder Member of EOTA, UEAtc and WFTAO Date:
More informationHELIOSTAR 252, 218 HORIZONTAL, FREE INSTALLATION
HELIOSTAR 252, 218 HORIZONTAL, FREE INSTALLATION INSTALLATION INSTRUCTIONS ENERGY AND SANITARY SYSTEMS Installation requirements General requirements The free-standing installation set is to be used for
More informationA EN ROUND STORAGE SILO. Ø480cm, Ø560cm, Ø640cm, Ø720cm ASSEMBLY AND USER MANUAL. ARSKAMETALLI LTD
A70-1001-EN-201805 ROUND STORAGE SILO Ø480cm, Ø560cm, Ø640cm, Ø720cm ASSEMBLY AND USER MANUAL ARSKAMETALLI LTD www.arskametalli.fi CONTENTS Introduction Delivery information EU Declaration of Conformity
More informationBirsta 3PH4b WORKING DESCRIPTION INSTALLATION, REPAIRS AND MAINTENANCE. Doc. No.: Birsta 3PH4b - Rev. 0
Birsta 3PH4b Doc. No.: Birsta 3PH4b - Rev. 0 Working Description Prepared by: Fredrik Sangö Doc. no.: Birsta 3PH4b Introduction/data: Birsta 3PH4b has been full-scale tested according to EN 1317-2 (TB11
More informationKemwell Impact Board. PASSIVE FIRE PROTECTION Specialists for the construction, infrastructure, transport, energy, industrial and commercial sectors.
Uniclass L68111:P91 CI/SfB Ry September 2017 Epic F811 (K2) Kemwell Impact Board A1 Non-combustible high performance fire, blast and impact protection board for critical applications in the commercial,
More informationThis European technical approval
Authorised and notified according to Article 10 of the Council Directive 89/ 106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating
More informationBLUEKIT VENTILATION FLAPS
BLUEKIT VENTILATION FLAPS www.bluekit.eu 1 Horizontal mounting into the shaft/the roof Vertical mounting into the shaft/ the facade 5 4 3 2 1 2 EN_BLUEKIT_VENTILATIONFLAPS_20150909 Summary New building...
More informationLLOYD INDUSTRIES INC. DAMPER INSTALLATION INSTRUCTIONS
Installation and Maintenance Instructions 1-1/2 Hour Rated, UL Classified model 75 fire dampers For use in fire barriers with ratings of less than 3 hours INSPECTION 1. Inspect for shipping damage. 2.
More information