Tech Tips SidePlate Connections FAQ 09/30/2017

Size: px
Start display at page:

Download "Tech Tips SidePlate Connections FAQ 09/30/2017"

Transcription

1 Tech Tips SidePlate Connections FAQ 09/30/2017 Page 1 of 15

2 Introduction to SidePlate Connection Technology SidePlate Connection Technology is ideally suited to protect structures against seismic events, wind, terrorism and other disasters through a single proven, and cost-effective structural system. SidePlate currently has 4 distinct Connection Types: 1. Moment Frame Field Bolted (R=3) 2. Ordinary Moment Frame Field Bolted (R=3.5) 3. Special Moment Frame Field Bolted (SMF R=8 or IMF R=4.5) 4. Special Moment Frame Field Welded (R=8) In addition to the four standard connection types, narrow configurations are also available where needed at edge of slab or openings. See Figure 1 below for typical connection geometry. Figure 1 SidePlate Connection Technology a) SidePlate Field Bolted - Standard b) SidePlate SMF Field Bolted - Standard c) SidePlate SMF Field Welded - Standard d) SidePlate Field Bolted - Narrow e) SidePlate SMF Field Bolted - Narrow f) SidePlate SMF Field Welded - Narrow In conjunction with this document, please refer to the Connection Stiffness Implementation document related to the structural analysis program you are using to model your SidePlate moment frame building. The following design guidelines are intended as a reference for your convenience, and feature some of the best practices and practical advice for designing with SidePlate Connections. For a more detailed list of code compliant design requirements, refer to AISC supplement No.2. NOTE: SidePlate has developed a Revit Family Tool to easily import generic or project specific SidePlate connections into your Revit model for easy coordination of required clearances. Page 2 of 15

3 Architectural Considerations and Schematic Design SELECTION OF FRAME COLUMN DEPTHS SidePlate is well suited for any desired columns whether square (e.g. W10x, W12x, W14x, HSS, Box) or rectangular (e.g. W18x, W21x, W24x to W36x). A rectangular column will be more economical (1-3 psf steel savings) wherever the architecture allows for it. Note that SidePlate is not limited to rectangular columns. SLAB EDGE CONSIDERATIONS In order to ensure that the SidePlate Connections at the perimeter of a building or adjacent to an opening will fit within the building envelope, the distance from the center line of the column to the edge of slab should be coordinated. As shown in Figure 3, deeper rectangular columns can be shifted off grid to fit within the building envelope, when needed. Approximate minimum slab edge (illustrated in Figure 2, variables defined in Figure 11) can be calculated using the equations below (we recommend adding up to a ½ inch of tolerance to these minimum calculations for construction tolerances): When column web is perpendicular to slab edge (Along Grid A in Figure 3) SidePlate Field Bolted or Welded ½* dc + tbf + ½ When column web is parallel to slab edge (Along Grid 1 in Figure 3) SidePlate Field Bolted, Standard ½* bcf + tbf + 4 SidePlate SMF Field Bolted, Standard ½* bcf * tbf + 1 /8 + 4 SidePlate SMF Field Welded ½* bcf + 2* tbf + ½ Please contact SidePlate Systems for project specific dimensions, if needed. Figure 2 - SidePlate Field Bolted Standard and Narrow Sections NOTE: If a minimal slab edge is needed, the narrow bolted configuration (shown in Figure 1) that moves the top set of angles from the outside to the inside face of the side plates may be used. To calculate the approximate minimum slab edge, replace the 4 with 1 1/2 for bolt nut. Page 1 of 15

4 Figure 3 Typical Lateral Column Plan View BEAM DEPTH CONSIDERATIONS SidePlate can accommodate a range of wide flange, HSS, and built-up beam sizes. The largest beam allowed for SMF Bolted is up to 48 depth weighing up to 529 lb/ft. Sizes as small as W8x have also been used. Deeper beams generally equate to greater economy. Often the optimal beam depth for SidePlate is shallower than the optimal beam depth for other moment frame systems. The optimal beam depth will vary from project to project depending on building geometry, criteria, and weather seismic provisions, like SCWB and Span to Depth, apply. Figure 2 and 4 show preliminary dimensions for coordination of the side plates. Figure 4 - SidePlate Field Bolted Elevation If you are concerned about issues related to column or beam depth, please contact SidePlate Systems. Page 2 of 15

5 CURVED OR SKEWED MOMENT FRAMES The SidePlate Connection adds torsional capacity to the frame beam and therefore curved moment frames may be used without compromising performance. To achieve a skewed moment frame, the side plates or beams can be skewed, the column can be rotated, or a subtle skew can applied to the cover plates and angle details. Examples of skewed beam configurations are shown in Figure 5 below. Please contact SidePlate Systems if you have further questions or require specific details. Figure 5 Plan Views of Skewed and Subtle Skewed SidePlate SMF Field Bolted Standard Connection Page 3 of 15

6 SLOPING BEAMS Sloping beams can easily be incorporated into the design of the SidePlate Connection. An example of a sloped condition is shown in Figure 6 below. Any combination of slopes can be accommodated (i.e. both sides sloped, one side sloped, etc.). For beam slopes greater than 1 per foot, contact SidePlate Systems for more details. Figure 6 Sloped SidePlate Field Bolted Special Moment Frame Connection SLAB DEPRESSIONS AT MOMENT FRAMES The top of a SidePlate Connection may extend vertically above the top of steel which may need coordination at slab depressions. For the field bolted - standard configuration, the top cover plate and bolts will extend into the slab, typically on the order 2-3 inches. For the field bolted - narrow configuration the side plate may extend approximately 4-1/2 inches into the slab. For the standard field welded configuration the top cover plate on the beam, side plate, and the horizontal shear plate extend into the slab roughly inches depending on member size. See the illustrations in Figure 7 below. For larger slab depressions, consider using a Stepped Moment Frame. Please contact SidePlate Systems for details. Figure 7 Standard SidePlate Connections at concrete over metal deck, a) field bolted and b) field welded Page 4 of 15

7 STEPPED MOMENT FRAMES SidePlate Connections may be used with varying amounts of stepping across a two-sided connection. For small steps it may be possible to keep the depth of the side plate identical on each side. For more severe steps there are several options such as the detail shown below in Figure 8. If needed, the connection can be both stepped and sloped. Figure 8 Universal Step Detail OPENINGS IN MOMENT FRAME BEAMS Openings in moment frame beams are not generally recommended. As with typical gravity framing, any openings in steel moment frame beams should be carefully coordinated and designed by the engineer. For situations where openings occur in non-seismic moment frame beams, we recommend that the opening occur within an area made up of the intersection of the middle third of the beam depth and length. The opening should also not be wider than the depth of the beam. All beam openings should be reinforced for shear, bending, and serviceability requirements as needed. See Figure 9 below. For Special Moment Frame (SMF) projects, we do not recommend openings in moment frame beams. Special Moment Frames rely on the ability of the beam to form a hinge at a specific and predictable location under seismic load. Adding openings to an SMF beam may lead to unexpected hinging at or near the opening location. If there is no other alternative and an opening must occur, please contact SidePlate Systems. Figure 9 Beam Penetrations for Low Seismic BIAXIAL COLUMNS SidePlate Connections may be used in biaxial configurations with either built up column sections (cruciform or boxed) or HSS columns. Biaxial configurations with WF columns require an extension of 6-8 above the roof. For biaxial connections, please contact SidePlate Systems for further coordination. Page 5 of 15

8 Structural Coordination with SidePlate Connections COMPUTER MODELING To appropriately represent the connection stiffness properties of SidePlate, the computer model must reflect the following two items, also described in Figure 10: 100% RIGID PANEL ZONE CONNECTION PROPERTIES BEYOND COLUMN FLANGE Figure 10 Connection Stiffness and Stress Modeling Refer to the SidePlate Connection Stiffness Implementation documents for proper implementation. RAM Connection Stiffness Implementation How to model SidePlate in RAM Tutorial ETABS-SAP Connection Stiffness Implementation RISA 3D Connection Stiffness Implementation STAAD Pro Connection Stiffness Implementation Page 6 of 15

9 COLUMN-BEAM RELATIONSHIP (GEOMETRIC COMPATABILITY) For a SidePlate Connection to be constructed, there must be adequate room for the flange of the beam to fit in between the side plates that are attached to the flanges of the column. To ensure that a compatible beam is chosen for a given column size, follow the guidelines in Figure 11 below. Bolted Geometric Compatibility: bbf + 1 bcf Welded Geometric Compatibility: bbf + 1.1* tbf + 1 /2 bcf Figure 11 - Partial SidePlate Connection Showing Geometric Compatibility BASE FIXITY In an ideal world, for steel moment frame economy, every base condition would be completely fixed. It is important to consider the base detailing at a building before deciding how to model it. See the below matrix of advantages and disadvantages for each: Advantage Fixed Lighter / shallower steel columns and beams Minimal issues with weak / soft story (R=8) Pinned Ease of detailing base plate and footings Decrease in footing size Disadvantage Complications in base detailing Increases in footing size Grade beams may be needed Issues with weak / soft story (R=8) Higher drifts in the lower floors Heavier / deeper steel columns and beams at lower floors Page 7 of 15

10 CANTILEVERS Cantilevers can be used at SidePlate Connections whether they are framing into the face of the actual side plate or the moment frame column flange. In order to ensure that the best solution is provided and the detailing is clear, please coordinate these connections with SidePlate Systems. Typical cantilever details fall into two main categories those that are perpendicular, or run through the SidePlate Connection, and those that are in-plane, or opposite of a one-sided SidePlate Connection at the end of the frame. In Plane / Parallel In-plane or parallel cantilever connections occur at the end of a moment frame. These cantilever stubs often use complete joint penetration (CJP) welding of the beam flange to the column flange and rely on continuity plates between the column flanges. Although this configuration can often be used without interfering with the SidePlate connection, some beams widths or offsets from the column center line will require detailing coordination. NOTE: In some instances changing the SidePlate Connection to a two-sided connection for an in-plane cantilever may be more economical and/or easier to erect. Contact SidePlate Systems to discuss the options. Out of Plane / Perpendicular Out of plane or perpendicular cantilever connections may occur at any point along the moment frame. Where these connections occur at the SidePlate Connection on the column, they must be coordinated with SidePlate Systems. Provide the cantilever and backspan beam sizes as well as the loading (if it is not taken from the analysis software) and precise location (if other than centered). NOTE: If a field bolted SidePlate Connection is being used for the moment frame, the cantilever portion of the connection may not be field bolted. COLLECTORS AND CHORDS In some configurations of moment frames, the load path for chords, collectors, or other axially loaded members will need to pass through or into the SidePlate Connection. Coordination of these details will be similar to the coordination of cantilevers and will rely on the configuration of the engineer s details. In Plane / Parallel Unless the detailing will conflict with the SidePlate Connection, there is not a need for coordination. It is often assumed that the complete collector force occurs at the end of the moment frame. Out of Plane / Perpendicular Out of plane or perpendicular drag connections must be coordinated with SidePlate Systems in the same way out of plane cantilevers are. In order to coordinate the design of these connections, SidePlate will need to know the collector or chord beam sizes as well as the axial force, and the preferred type of detailing (whether it be through a shear tab, top flange welded, or another mechanism). Page 8 of 15

11 CAP PLATES Cap plate detailing will require coordination with the SidePlate Connection detailing only if the cap plate is located at the top of the side plate and takes the place of the horizontal shear plate. For the field bolted connection, it is preferable to extend the column above the side plate and add a cap. If a cap plate is placed at the top of side plate, the cap plate will need to be 1 inch thick to match the top of steel. For the field welded connection, the top of side plate is typically about 3 inches above the top of steel. See Figure 12 below. a) b) Figure 12 SidePlate Connections with Cap Plate; a) field bolted and b) field welded In some cases, such as at cantilevered columns with high moments, stiffeners below the cap plate will provide the most efficient design and performance. Note that the minimum thickness of any column cap plate acting as the SidePlate horizontal shear plate will be 3/8. Also note that for most SidePlate Connections, welding the cap plate all around will not be permitted. Please coordinate the attachment of posts, davits, and column lifting lugs to the cap plate with SidePlate Systems. Page 9 of 15

12 INTERACTION WITH BRACED FRAMES Where braced frames are being used at the top of the building or run perpendicular to a moment frame column, the SidePlate Connection may be coordinated to work with the gusset plate and beam framing. Typically the roof configuration includes a cap plate on top of the side plate, and it will vary depending on the intended working point of the braced frame and the type of SidePlate Connection (whether field welded or bolted). Note that there is a physical gap between the beam and column (typically between 1-1/2 to 5 ) which the gusset plate would need to span over. Gusset plates perpendicular to SidePlate Connections may need to be cut around the horizontal shear plate, per Figure 13. Please contact SidePlate Systems to coordinate details incorporating braced frames. Figure 13 Perpendicular Braced Frame Elevation Detail FACADE ATTACHMENT Although the curtain wall and façade detailing is often left until the end of the design process, it may be important to think through how these elements will be detailed at the SidePlate connections. At perimeter moment frame columns, the top of the horizontal shear plates may not be at the top of steel and should be coordinated with the façade manufacturer. On Special and Intermediate Moment Frame (SMF and IMF) projects, protected zones are required on the side plate and the beam where welded attachments are not permitted. Areas outside of the protected zones may be used for the attachment of these systems. If the loading of the curtain wall or façade is heavy (greater than 25 psf) and the attachments occur at the SidePlate connections, contact SidePlate Systems to coordinate the detailing. OPEN WEB STEEL JOISTS Open web steel joists are fairly common at roof conditions in steel buildings and are often spaced closely enough that one or more may require the support of a SidePlate Connection. The type of SidePlate Connection will once again affect how the joist is supported. For the SidePlate Field Bolted Narrow and SidePlate Field Welded Connections, the side plate is taller than the top of steel by 3 or more inches. In this configuration, provide a joist seat off of the face of the side plate which avoids any bolts. For the SidePlate Field Bolted Standard Connection, the joist seat may either rest on the top cover plate and avoid the horizontal rows of bolts or use an extended seat off of the face of the side plate. Joist bracing may be connected to the SidePlate Connection outside of the protected zones. Page 10 of 15

13 DECK SUPPORT Deck support angles may be added to SidePlate Connections for edge and end bearing as needed, see Figure 14. Deck support angles may be added to the face of the side plate on the field welded SidePlate Connection and any of the narrow-type SidePlate Connections. For the SidePlate Field Bolted Standard Connection, the angle {G} at the top of the side plate may be extended to provide deck support. Note that deck support angles may not be welded within the protected zone on the side plate where it occurs. Also note that it is often wise to place a notch in the deck support angles at the location of the beam to column gap in order to prevent the support angle from becoming a strong-back during fabrication. Figure 14 Angle Extension at SidePlate Field Bolted Standard Connection FIREPROOFING When required by the governing code for certain types of construction, steel SidePlate Connections shall have a fire-resistance rating like that of a "structural frame." The minimum thickness of sprayed on fire-resistive material (SFRM) for steel SidePlate Connection plates, not encased in concrete, shall be determined just like that of a pipe/tube column section with a constant steel wall thickness, which are uniformly heated and protected (the fire exposure of a pipe/tube column is directly analogous to a plate with a 1-sided fire exposure and protection). The SFRM shall have been tested in accordance with ASTM E119 and listed for fire resistive pipe/tube column applications for no less than the required rated time. The contractor shall provide the means for fireproofing across the physical column/beam separation between the bottom beam flange cover plate and the face of the column flange. Page 11 of 15

14 Seismic Provisions MOMENT FRAME PROTECTED ZONES The AISC Seismic Provisions (ANSI/AISC 341) prohibit certain attachments in the protected zone for all Special and Intermediate Moment Frame applications. A protected zone (PZ) occurs where the beam or column is subject to inelastic strain and a plastic hinge forms or, more simply, the element bends and buckles under high seismic loads. For the SidePlate Connection there are protected zones on the beam and on the side plate. The protected zone locations are illustrated in Figure 15 below. a) b) Figure 15 SidePlate Connection Protected Zones; a) field bolted and b) field welded Note that it is acceptable to weld to the face of the side plates outside of the protected zone provided that connections do not interfere with the fabrication and erection of the system. Page 12 of 15

15 SPAN TO DEPTH Each configuration of the SidePlate Connection have a span to depth limit. The hinge-to-hinge span of the beam can be approximated by the following equation (final span to depth calculations are done by SidePlate connection design software and provided in calculations): LL h = LL 1 2 dd cccccc,1 + dd cccccc,2 2.2dd bb The ratio of the hinge-to-hinge span of the beam, Lh, to beam depth, d, shall be limited to: SMF Field Bolted: 3.5 or greater. IMF Field Bolted or Welded: 3 or greater. SMF Field Welded: 4.5 or greater. NOTE: For projects under California s OSHPD jurisdiction, Lh to d, shall be limited to 5.0 or greater. LATERAL BRACING OF BEAMS The engineer shall provide lateral bracing of the frame beam s bottom flange in accordance with the latest AISC Seismic Provisions. The distance of unbraced length can be calculated from the ends of the side plates, as they provide lateral bracing of the beam, unless otherwise prohibited by the jurisdiction. Beams should be laterally braced at a distance not to exceed: rr yy EE ss FF yy, or even more simply, approximately 5555rr yy for Special Moment Frame (SMF) projects rr yy EE ss FF yy, or approximately rr yy for Intermediate Moment Frame (IMF) projects. The requirements for lateral bracing are based off of testing, as discussed in this section of the Commentary on the Seismic Provisions for Structural Steel Buildings (341-02). Supplemental top and bottom flange bracing at the expected hinge is not required for SidePlate because it is provided by the side plates. Lateral bracing of the bottom beam flange may not be possible in some rare cases, such as at large openings. In those instances the engineer may consider torsional bracing such as built-up sections, or adding supplemental gravity columns between floors. Please contact SidePlate Systems to discuss these alternatives. NOTE: For projects under California s OSHPD jurisdiction, unbraced length must be measured from the centerline of each column. Page 13 of 15

16 LATERAL JOINT BRACING Although AISC 341 requires lateral joint bracing at the top and bottom of beams in Special Moment Frames (SMF), these requirements do not apply to the SidePlate Connection. Since there is a physical gap between the beam and the column, the load path does not use continuity plates at the joint, and localized buckling of the column is very unlikely. Additionally, the connection of the side plate to the column flanges provides additional stability at the joint. As a result, the SidePlate Connection may be considered braced at the joint by simply providing a perpendicular beam shear tab connection within the joint region. At locations where no perpendicular framing occurs, the effects of a multi-story unbraced column should be considered, especially in weak axis bending and buckling outside of the SidePlate Connection joint region. PENTHOUSES A penthouse structure is meant to be an unoccupied space (likely for mechanical purposes) at the uppermost level of a structure. Per the IBC Section , if a penthouse s area is greater than 1/3 of the area of the story below, it must also be considered a story. If a structure has a penthouse level that does not meet these requirements (either it is occupied or it is greater than 1/3 the area), it should be considered a story. The uppermost story may use an alternate lateral system provided it meets the requirements of the code. It is important to note the exceptions to Table in ASCE If Special Moment Frames are selected as the lateral system for the penthouse level, the columns must be continuous to the base of the building. Page 14 of 15

17 Questions? SidePlate is here to help you! If you are considering using SidePlate Connections in your building, please send us your building model or frame layout for review, even if it is only schematic. We will run your model and layout through our connection design software to catch any flags or special checks and ensure that you have the best performing and most optimal lateral design for your client. If your client is requesting a pricing exercise, we can also provide a pricing package containing detailed connection and steel take-off information. Please feel free to contact SidePlate Systems at solutions@sideplate.com anytime with questions or concerns. Page 15 of 15

THE PLAZA AT PPL CENTER ALLENTOWN, PA

THE PLAZA AT PPL CENTER ALLENTOWN, PA : MOMENT FRAME COMPARISON Introduction Design Intent IBC 2000 and ASCE 7-98 recognizes steel frames designed with a response modification factor, R, less than or equal to three as structural steel systems

More information

Danielle Shetler - Structural option Courtyard by Marriott Lancaster, PA

Danielle Shetler - Structural option Courtyard by Marriott Lancaster, PA Structural Analysis Overview: During the structural analysis of the in Lancaster, Pa, a redesign of the lateral and gravity system from masonry bearing and shear walls to a staggered truss system was performed.

More information

Supplement No. 1 to AISC Prequalified Connections for Special and Intermediate Steel Moment Frames for Seismic Applications

Supplement No. 1 to AISC Prequalified Connections for Special and Intermediate Steel Moment Frames for Seismic Applications 1 1 DRAFT AISC 358-16s1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 Supplement No. 1 to AISC 358-16 Prequalified Connections for Special and Intermediate

More information

manualwise BRACED FOR BETTER SEISMIC DESIGN

manualwise BRACED FOR BETTER SEISMIC DESIGN An introduction to the newest edition of AISC s Seismic Design Manual. manualwise BRACED FOR BETTER SEISMIC DESIGN BY ERIC BOLIN, PE, AND MICHAEL GANNON, SE, PE DO YOU DESIGN PROJECTS with seismic systems?

More information

MOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS

MOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS MOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS PARKERSBURG, WEST VIRGINIA DOMINIC MANNO STRUCTURAL OPTION FACULTY CONSULTANT: DR. ANDRES LEPAGE Technical Report 3 11-21-08 TABLE OF CONTENTS TABLE OF

More information

There are countless ways to improve constructability on your next project. Here are 50 of them. the need for it or specify it on the design drawings.

There are countless ways to improve constructability on your next project. Here are 50 of them. the need for it or specify it on the design drawings. There are countless ways to improve constructability on your next project. Here are 50 of them. Tips to Take your Team to the Top By Matthew D. Brady, P.E., and Cliff Schwinger, P.E. We hear the word constructability

More information

STEEL STRUCTURAL SYSTEMS

STEEL STRUCTURAL SYSTEMS STEEL STRUCTURAL SYSTEMS Steel elements are of two basic types: Structural steel shapes are formed into their final shapes by hot-rolling. This method produces such common elements as wide flange sections,

More information

Technical Report #2. Matthew R Peyton

Technical Report #2. Matthew R Peyton Technical Report #2 This Document is Technical Report #2 for 5th year senior thesis in the Architectural Engineering Departments at The Pennsylvania State University. This Report is to prepare a study

More information

OCTAGONAL SHAPE REDUCES AIRPLANE HANGAR COSTS

OCTAGONAL SHAPE REDUCES AIRPLANE HANGAR COSTS OCTAGONAL SHAPE REDUCES AIRPLANE HANGAR COSTS While a square hangar would have been simpler to design, an octagonal building substantially reduced life cycle costs By Charles Sacre, P.E. THE PROGRAM FOR

More information

Office Building-G. Thesis Proposal. Carl Hubben. Structural Option. Advisor: Dr. Ali Memari

Office Building-G. Thesis Proposal. Carl Hubben. Structural Option. Advisor: Dr. Ali Memari Office Building-G Thesis Proposal Structural Option December 10, 2010 Table of Contents Executive Summary... 3 Introduction... 4 Gravity System...4 Lateral System:...6 Foundation System:...6 Problem Statement...

More information

Structural Redesign Gravity System

Structural Redesign Gravity System Redesign Gravity System Design Considerations A composite floor system was used for this design to maximize the efficiency of the material being used. This type of system requires less material and provides

More information

Supplemental Structural Correction Sheet Steel Moment Frame Design (2017 LABC)

Supplemental Structural Correction Sheet Steel Moment Frame Design (2017 LABC) Supplemental Structural Correction Sheet Steel Moment Frame Design (2017 LABC) Plan Check/PCIS Application No.: Checked By: Your feedback is important, please visit our website to complete a Custom Survey

More information

TECHNICAL REPORT 1. Structural Concepts / Structural Existing Conditions. Penn State Hershey Medical Center Children s Hospital. Hershey, Pennsylvania

TECHNICAL REPORT 1. Structural Concepts / Structural Existing Conditions. Penn State Hershey Medical Center Children s Hospital. Hershey, Pennsylvania TECHNICAL REPORT 1 Structural Concepts / Structural Existing Conditions Penn State Hershey Medical Center Children s Hospital Matthew V Vandersall The Pennsylvania State University Architectural Engineering

More information

THE BRACE CONNECTION THE BOLTED OPTION FIGURE 1 MODEL SHOWING THE BOILER AND THE STRUCTURAL SUPPORT SYSTEM (BOILER BUILDING)

THE BRACE CONNECTION THE BOLTED OPTION FIGURE 1 MODEL SHOWING THE BOILER AND THE STRUCTURAL SUPPORT SYSTEM (BOILER BUILDING) Comparative Study of Bolted versus Welded SCBF Connections Authors: Robert P. Krumpen III P.E., Bechtel Corporation, rpkrumpe@bechtel.com Dr. Peter J. Carrato P.E. S.E., Bechtel Corporation, pcarrato@bechtel.com

More information

CHAPTER 14 SLOTTEDWEB (SW) MOMENT CONNECTION

CHAPTER 14 SLOTTEDWEB (SW) MOMENT CONNECTION 1 CHAPTER 14 SLOTTEDWEB (SW) MOMENT CONNECTION The user s attention is called to the fact that compliance with this chapter of the standard requires use of an invention covered by patent rights. 1 By publication

More information

Types Of Roofs - Vault

Types Of Roofs - Vault 1 Types Of Roofs - Vault Implementation Of the Concrete On Vault Implementation Of Vault Earthquake Damage 2 Types Of Roofs - Joist And Block 3 Types Of Coverage Roofs-Composite 4 5 Building Structure

More information

Whose responsibility is it? Design Responsibility. Steel Joist Institute. Standard Assumptions. Common Pitfalls in Steel Joist Specification

Whose responsibility is it? Design Responsibility. Steel Joist Institute. Standard Assumptions. Common Pitfalls in Steel Joist Specification Common Pitfalls in Steel Joist Specification Whose responsibility is it? Joist supplier? Steel fabricator? Contractor? Other trades? Specifier? Design Responsibility Joist Supplier s responsibilities include

More information

CONNECTION STIFFNESS IMPLEMENTATION PROCEDURE

CONNECTION STIFFNESS IMPLEMENTATION PROCEDURE CONNECTION STIFFNESS IMPLEMENTATION PROCEDURE FOR Risa 3D USERS 09/29/17 Modeling of Lateral Frames Using SidePlate Connection Technology: The inherent SidePlate connection stiffness can be implemented

More information

EngDoc.ir. Page 1 of 51

EngDoc.ir. Page 1 of 51 Page 1 of 51 1994 Northridge Earthquake Widespread failure of welded flange - bolted web moment connections Page 2 of 51 Damage Observations: Steel Moment Connections Pre-Northridge Welded Flange Bolted

More information

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan Brief Building Overview: 200 Minuteman Park stands as a 200,000 square foot Class A office building in Andover, Massachusetts, worth roughly $15,000,000. Although the building has a large square footage,

More information

Best Buy Corporate Building D (4) Richfield, MN

Best Buy Corporate Building D (4) Richfield, MN Best Buy Corporate Building D (4) Thesis Proposal Professor Boothby December 12 th, 2008 Executive Summary: The Best Buy Corporate Building D is a 6 story building with a total area of 304,610 square feet.

More information

Thesis Proposal. Office Building. Sayre, PA. Faculty Advisor: Dr. Thomas E. Boothby Revised: January 9, 2013

Thesis Proposal. Office Building. Sayre, PA. Faculty Advisor: Dr. Thomas E. Boothby Revised: January 9, 2013 Faculty Advisor: Dr. Thomas E. Boothby Revised: January 9, 2013 Office Building Sayre, PA Seth M. Moyer Structural Table of Contents Executive Summary 3 Building Introduction 4 Structural Overview..6 Foundations

More information

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan Structural Design: Goals: The original design of 200 Minuteman Drive was dictated largely by Brickstone Properties, the building s owner. The new design of 200 Minuteman Drive, with additional floors,

More information

Thesis Proposal. Office Building. Sayre, PA. Faculty Advisor: Dr. Thomas E. Boothby Revised: April 1, 2013

Thesis Proposal. Office Building. Sayre, PA. Faculty Advisor: Dr. Thomas E. Boothby Revised: April 1, 2013 Faculty Advisor: Dr. Thomas E. Boothby Revised: April 1, 2013 Office Building Sayre, PA Seth M. Moyer Structural Table of Contents Executive Summary 3 Building Introduction 4 Structural Overview..6 Foundations

More information

151 First Side. Technical Assignment 2 November 16 th, William J. Buchko. AE 481w Senior Thesis The Pennsylvania State University

151 First Side. Technical Assignment 2 November 16 th, William J. Buchko. AE 481w Senior Thesis The Pennsylvania State University November 16 th, 2007 William J. Buchko AE 481w Senior Thesis The Pennsylvania State University Thesis Advisor: Kevin Parfitt Table of Contents Executive Summary... 3 Structural System Overview Foundation...

More information

OVERALL STRUCTURAL SYSTEM

OVERALL STRUCTURAL SYSTEM EXECUTIVE SUMMARY The at the Pittsburgh International Airport, PA, is a 275,000 square foot multi-use building located directly adjacent to the airport s landside terminal. The building consists of an

More information

steelwise WHAT S NEW WITH PREQUALIFIED CONNECTIONS? A look at the latest version of AISC 358.

steelwise WHAT S NEW WITH PREQUALIFIED CONNECTIONS? A look at the latest version of AISC 358. A look at the latest version of AISC 358. steelwise WHAT S NEW WITH PREQUALIFIED CONNECTIONS? BY MICHAEL D. ENGELHARDT, PhD, AND MARGARET A. MATTHEW, PE WHEN IT COMES to the chronicles of steel construction,

More information

Xyston Inn. NY. Proposal. Xiaodong Jiang. Structure Option. Advisor: Dr. Linda Hanagan

Xyston Inn. NY. Proposal. Xiaodong Jiang. Structure Option. Advisor: Dr. Linda Hanagan Proposal Xiaodong Jiang Structure Option Advisor: Dr. Linda Hanagan December 12, 2014 Executive Summary Xyston Inn is a 17-story hotel building that will be located in Brooklyn, New York. The design of

More information

On Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866)

On Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866) TECHNICAL NOTE On Cold-Formed Steel Construction $5.00 Light Gauge Steel Engineers Association Washington, D.C. 20005 Toll Free (866) 465-4732 www.lgsea.com DESIGN OF BY-PASS SLIP CONNECTORS IN COLD-FORMED

More information

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance APPLIED ARCHITECTURAL STRUCTURES: STRUCTURAL ANALYSIS AND SYSTEMS DR. ANNE NICHOLS FALL 2013 lecture fifteen design for lateral loads Lateral Load Resistance stability important for any height basic mechanisms

More information

Learning Objectives. Topics. Moment Frames: Design and Detailing per AISC 341 and 358. Topics. Lateral Analysis/Choosing your Code

Learning Objectives. Topics. Moment Frames: Design and Detailing per AISC 341 and 358. Topics. Lateral Analysis/Choosing your Code Topics Moment Frames: Design and Detailing per AISC 341 and 358 By Matthew J. Mester, PE, SE SidePlate Systems, Inc. SE University, June, 2017 www.learnwithseu.com 2 Learning Objectives Topics Identify

More information

Pro-Con Structural Study for Alternative Floor Systems October 27, 2004

Pro-Con Structural Study for Alternative Floor Systems October 27, 2004 Ismail Al-Hadhrami Structural Option Faculty Consultant: Dr. Thomas Boothby Agricultural Hall and Annex East Lansing, MI Pro-Con Structural Study for Alternative Floor Systems October 27, 2004 Executive

More information

181 Fremont San Francisco, CA. Tech Report 3 10/17/2014. PSUAE Structural Option Advisor: Dr. Thomas Boothby

181 Fremont San Francisco, CA. Tech Report 3 10/17/2014. PSUAE Structural Option Advisor: Dr. Thomas Boothby 181 Fremont San Francisco, CA Tech Report 3 10/17/2014 PSUAE Structural Option Advisor: Dr. Thomas Boothby Caroline Klatman cjk5258@psu.edu October 17, 2014 Dr. Thomas Boothby The Pennsylvania State University

More information

CHAPTER 1 INTRODUCTION 1.1 MOMENT END-PLATE CONNECTIONS

CHAPTER 1 INTRODUCTION 1.1 MOMENT END-PLATE CONNECTIONS CHAPTER 1 INTRODUCTION 1.1 MOMENT END-PLATE CONNECTIONS The typical moment end-plate connection shown in Fig. 1-1 consists of a plate that is shop-welded to the end of a beam which is then bolted to the

More information

SECTION PLATE CONNECTED WOOD TRUSSES

SECTION PLATE CONNECTED WOOD TRUSSES SECTION 06173 PLATE CONNECTED WOOD TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Shop fabricated wood trusses for roof and floor framing. 2. Bridging, bracing, and anchorage. B. Related Sections:

More information

[TECHNICAL REPORT 3] Lateral System Analysis

[TECHNICAL REPORT 3] Lateral System Analysis Science Center Research Park 3711 Market St. The Pennsylvania State University Department of Architectural Engineering Senior Thesis 2009-2010 Prepared by: November 30, 2009 [TECHNICAL REPORT 3] Lateral

More information

Thesis Proposal. La Jolla Commons Phase II Office Tower San Diego, California. December 13, 2013

Thesis Proposal. La Jolla Commons Phase II Office Tower San Diego, California. December 13, 2013 Thesis Proposal December 13, 2013 La Jolla Commons Phase II Office Tower San Diego, California Alyssa Stangl Structural Option Advisor: Dr. Linda Hanagan Table of Contents Executive Summary... 3 Purpose

More information

Structural System. Design Criteria Fire Resistance Concrete designed for 2 HR rating (worst case) Geotechnical Report Allowable Bearing Capacity

Structural System. Design Criteria Fire Resistance Concrete designed for 2 HR rating (worst case) Geotechnical Report Allowable Bearing Capacity System Codes and Criteria Design Codes and Standards The design code used is the Wisconsin Administrative Code along with the State of Wisconsin Department of Commerce-Safety & Buildings Chapters Comm

More information

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance APPLIED ARCHITECTURAL STRUCTURES: STRUCTURAL ANALYSIS AND SYSTEMS DR. ANNE NICHOLS SPRING 2017 lecture fifteen design for lateral loads Lateral Load Resistance stability important for any height basic

More information

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance

fifteen design for lateral loads Lateral Load Resistance Load Direction Lateral Load Resistance APPLIED ARCHITECTURAL STRUCTURES: STRUCTURAL ANALYSIS AND SYSTEMS DR. ANNE NICHOLS FALL 2014 lecture fifteen design for lateral loads Lateral Load Resistance stability important for any height basic mechanisms

More information

VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.)

VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.) DIVISION 94 VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.) SEC. 91.9401. PURPOSE. (Amended by Ord. No. 172,592, Eff. 6/28/99,

More information

Composite Steel/Concrete

Composite Steel/Concrete Composite Steel/Concrete Composite Steel and Concrete Clinton O. Rex, P.E., PhD Originally developed by James Robert Harris, P.E., PhD, and Frederick R. Rutz, P.E., PhD Disclaimer Instructional Material

More information

SJI Updates Expanded Load Tables for Noncomposite Joists / Joist Girders and Development of New Composite Joist Series

SJI Updates Expanded Load Tables for Noncomposite Joists / Joist Girders and Development of New Composite Joist Series SJI Updates Expanded Load Tables for Noncomposite Joists / Joist Girders and Development of New Composite Joist Series SUMMARY David Samuelson Steel joists are growing in recognition as being a very economical

More information

John Jay College Expansion Project

John Jay College Expansion Project Technical Report #3 Michael Hopper Mike AE Consultant: Dr. Lepage [Type the company name] November 21 st, 2008 Technical Report #3 Table of Contents Executive Summary.3 Introduction.4 Existing Composite

More information

Belmont Executive Center; Building A

Belmont Executive Center; Building A Nicholas L. Ziegler: Structural Advisor: Professor M. Kevin Parfitt December 1, 2009 1 Table of Contents Executive Summary...3 Introduction...3 Structural System...4 Foundation System... 4 Column System...

More information

Design- Lateral System:

Design- Lateral System: Design- Lateral System: Investigation: When considering the design of the lateral load resisting system, first a look was taken at the existing shear walls. The existing lateral system in The Lexington

More information

Xyston Inn. NY. Proposal. Xiaodong Jiang. Structure Option. Advisor: Dr. Linda Hanagan

Xyston Inn. NY. Proposal. Xiaodong Jiang. Structure Option. Advisor: Dr. Linda Hanagan Proposal Xiaodong Jiang Structure Option Advisor: Dr. Linda Hanagan December 12, 2014 Executive Summary Xyston Inn is a 17-story hotel building that will be located in Brooklyn, New York. The design of

More information

Executive Summary Building Description: Introduction... 13

Executive Summary Building Description: Introduction... 13 Table of Contents Executive Summary... 2 Building Description:... 2 Report Summary:... 2 Introduction... 3 Building Description:... 3 Current Framing Layout... 4 Report Topics:... 4 Loads and Load Cases...

More information

Franklin Square Hospital Center Patient Tower

Franklin Square Hospital Center Patient Tower Thomas Weaver Structural Option Franklin Square Hospital Center Patient Tower Baltimore, MD Thomas Weaver Structural Option AE 481W Senior Thesis Consultant: Professor M. Kevin Parfitt 12/14/2009 Page

More information

THE FORENSIC MEDICAL CENTER

THE FORENSIC MEDICAL CENTER THE FORENSIC MEDICAL CENTER Image courtesy of Gaudreau, Inc. TECHNICAL REPORT #2 OCTOBER 26, 2007 KEENAN YOHE STRUCTURAL OPTION DR. MEMARI FACULTY ADVISOR EXECUTIVE SUMMARY Image courtesy of Gaudreau,

More information

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan Executive Summary: 200 Minuteman Park currently stands as a three story commercial building. The original design was limited to three stories by an industrial zoning law in Andover, Massachusetts. If this

More information

Point Pleasant Apartments Point Pleasant, NJ Ryan P. Flynn Structural Option Faculty Consultant: Dr. Hanagan

Point Pleasant Apartments Point Pleasant, NJ Ryan P. Flynn Structural Option Faculty Consultant: Dr. Hanagan Point Pleasant Apartments Point Pleasant, NJ Ryan P. Flynn Structural Option Faculty Technical Report #3: Lateral System Analysis and Confirmation Design Table of Contents Introduction... 3 Executive Summary...

More information

HIGH RISE CONDO SOHO, NEW YORK, NY

HIGH RISE CONDO SOHO, NEW YORK, NY HIGH RISE CONDO SOHO, NEW YORK, NY TECHNICAL ASSIGNMENT 1 October 5, 2006 Joseph The Pennsylvania State University Structural Option Faculty Advisor: Andres Lepage TABLE OF CONTENTS TABLE OF CONTENTS 2

More information

AISC Steel & Timber Research for High-Rise Residential Buildings

AISC Steel & Timber Research for High-Rise Residential Buildings AISC Steel & Timber Research for High-Rise Residential Buildings Final Report December 4 th, 2017 SOM Designed Benchmark Concrete Building Skidmore, Owings, and Merrill, LLP 2017 224s Michigan Avenue Suite

More information

Kevin Wigton Structural Option. Technical Report III. Simmons College School of Management, Boston, Ma

Kevin Wigton Structural Option. Technical Report III. Simmons College School of Management, Boston, Ma Kevin Wigton Structural Option Technical Report III Simmons College School of Management, Boston, Ma Advisor: Professor Parfitt 12/1/2009 Table of Contents Executive Summary: Technical Report III... 3

More information

Tables with Allowable ASD Seismic Values For Design at R = 6.5. Special Moment Frame MF1-12

Tables with Allowable ASD Seismic Values For Design at R = 6.5. Special Moment Frame MF1-12 Tables with Allowable ASD Seismic Values For Design at R = 6.5 Special Moment Frame MF1-12 Hardy Frames, Inc manufactures and markets pre-fabricated shear wall systems. We have been the innovative leader

More information

Stephan Northrop Structural Option Dr. Linda Hanagan. North Shore Equitable Building Pittsburgh, PA Senior Thesis Proposal

Stephan Northrop Structural Option Dr. Linda Hanagan. North Shore Equitable Building Pittsburgh, PA Senior Thesis Proposal Stephan Northrop NORTHROP THESIS PROPOSAL PAGE - 1 TABLE OF CONTENTS Executive Summary.. 3 1. Introduction.. 4 2. Structural Systems.. 5 Foundation.. 5 General Floor Framing.. 6 Turret Framing.. 7 Roof

More information

Lateral Design of Mid- Rise Wood Structures

Lateral Design of Mid- Rise Wood Structures Lateral Design of Mid- Rise Wood Structures Presented by Ricky McLain, MS, PE, SE Technical Director WoodWorks Texas Workshops December, 2016 Insert picture of me graduating college Follow the load Following

More information

Kaleida Health Global Heart and Vascular Institute University at Buffalo CTRC/Incubator. Buffalo, New York. Technical Report #2

Kaleida Health Global Heart and Vascular Institute University at Buffalo CTRC/Incubator. Buffalo, New York. Technical Report #2 University at Buffalo CTRC/Incubator Buffalo, New York William McDevitt October 27, 2010 Table of Contents Executive Summary...3 Introduction...4 Structural System Overview...5 Foundation...5 Floor System...5

More information

Park Potomac Office Building E

Park Potomac Office Building E Kyle Wagner (IP) Advisor: Professor Kevin Parfitt 12/11/2009 Table of Contents I. Executive Summary. 3 II. Introduction / Material Strengths. 4 III. Codes and Design Standards.. 5 IV. Existing Structural

More information

Arlington, Virginia December 3, 2007 TECHNICAL REPORT III LATERAL SYSTEM ANALYSIS AND CONFIRMATION DESIGN

Arlington, Virginia December 3, 2007 TECHNICAL REPORT III LATERAL SYSTEM ANALYSIS AND CONFIRMATION DESIGN TECHNICAL REPORT III LATERAL SYSTEM ANALYSIS AND CONFIRMATION DESIGN EXECUTIVE SUMMARY The is the practice facility for the NHL franchise, Washington Capitals. It is located in Arlington, Virginia just

More information

Technical Report 3. Alyssa Stangl Structural Option Advisor Dr. Linda Hanagan L A J O L L A C O M M O N S P H A S E I I O F F I C E T O W E R

Technical Report 3. Alyssa Stangl Structural Option Advisor Dr. Linda Hanagan L A J O L L A C O M M O N S P H A S E I I O F F I C E T O W E R Technical Report 3 Alyssa Stangl Structural Option Advisor Dr. Linda Hanagan L A J O L L A C O M M O N S P H A S E I I O F F I C E T O W E R Site and Location La Jolla Commons, San Diego, California General

More information

Southwest Housing, Arizona State University

Southwest Housing, Arizona State University Prepared by KSENIA TRETIAKOVA Structural Option 01.09.2012 Architectural Engineering Pennsylvania State University 2012 Southwest Housing, Arizona State University Technical Report #3 Lateral System 01.09.2012

More information

CORPORATE HEADQUARTERS

CORPORATE HEADQUARTERS TECHNICAL REPORT 1 `` CORPORATE HEADQUARTERS Great Lakes Region, U.S.A. M. JULIA HAVERTY STRUCTURAL OPTION ADVISOR: H. SUSTERSIC 12 SEPTEMBER 2014 Contents Executive Summary... 2 Purpose and Scope... 3

More information

Pro-Con Structural Study of Alternate Floor Systems

Pro-Con Structural Study of Alternate Floor Systems Andrew Covely Structural Dr. Linda Hanagan The Helena New York City, NY October 27, 2004 Pictures courtesy of Fox & Fowle Architects Pro-Con Structural Study of Alternate Floor Systems Executive Summary

More information

Thesis Proposal. University Hospitals Case Medical Center Cancer Hospital. Daniel C. Myers. December 12, 2009

Thesis Proposal. University Hospitals Case Medical Center Cancer Hospital. Daniel C. Myers. December 12, 2009 Thesis Proposal University Hospitals 11100 Euclid Avenue Cleveland, Ohio December 12, 2009 Daniel C. Myers Advisor: Dr. Ali Memari http://www.engr.psu.edu/ae/thesis/portfolios/2009/dcm234 Executive Summary

More information

Thesis Proposal December 5, 2003

Thesis Proposal December 5, 2003 Executive Summary Thesis Proposal December 5, 2003 Brennan Hall is a five-story office/classroom building. It is located on a slightly sloping site, surrounded by other structures and a small green space.

More information

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel

More information

ISSUE A Code Change # 2 Class 3 and Class 4 Buildings

ISSUE A Code Change # 2 Class 3 and Class 4 Buildings ISSUE A Code Change # 2 Class 3 and Class 4 Buildings (new) Section 1604.9 Disproportionate Collapse. Design for structural integrity of new buildings to protect against disproportionate collapse shall

More information

CORPORATE HEADQUARTERS

CORPORATE HEADQUARTERS TECHNICAL REPORT 1 REVISIONS `` Image Courtesy RTKL CORPORATE HEADQUARTERS Great Lakes Region, U.S.A. M. JULIA HAVERTY STRUCTURAL OPTION ADVISOR: H. SUSTERSIC 12 DECEMBER 2014 Contents Executive Summary...

More information

Dead Loads (psf): Concrete Floor Slab on Metal Deck 45 psf Mechanical and Ceiling 7 psf Miscellaneous 5 psf Exterior Wall 80 psf

Dead Loads (psf): Concrete Floor Slab on Metal Deck 45 psf Mechanical and Ceiling 7 psf Miscellaneous 5 psf Exterior Wall 80 psf CODES AND REQUIREMENTS The structural design of Northbrook Corporate Center was based on the International Building Code 2003, which incorporates many of the provisions of ASCE 7. The lateral load design

More information

50 Tips for Designing Steel Framed Buildings September 27, AISC Live Webinar. AISC Live Webinars

50 Tips for Designing Steel Framed Buildings September 27, AISC Live Webinar. AISC Live Webinars AISC Live Webinars 1 Thank you for joining our live webinar today. We will begin shortly. Please standby. AISC Live Webinars Thank Thank you. you for joining our live webinar today. Need We will Help?

More information

Question 8 of 55. y 24' 45 kips. 30 kips. 39 kips. 15 kips x 14' 26 kips 14' 13 kips 14' 20' Practice Exam II 77

Question 8 of 55. y 24' 45 kips. 30 kips. 39 kips. 15 kips x 14' 26 kips 14' 13 kips 14' 20' Practice Exam II 77 Question 8 of 55 A concrete moment frame building assigned to SDC = D is shown in the Figure. Equivalent lateral force analysis procedure is used to obtain the seismic lateral loads, E h, as shown. Assume

More information

181 Fremont San Francisco, CA. Tech Report 1 9/12/2014. Caroline Klatman Structural Option Advisor: Dr. Thomas Boothby

181 Fremont San Francisco, CA. Tech Report 1 9/12/2014. Caroline Klatman Structural Option Advisor: Dr. Thomas Boothby 181 Fremont San Francisco, CA Tech Report 1 9/12/2014 Caroline Klatman Structural Option Advisor: Dr. Thomas Boothby Table of Contents Executive Summary... 2 Introduction... 3 Purpose... 3 Building Summary...

More information

Structural Design Engineers 120 Montgomery Street, Suite 1410 San Francisco, California / Fax 415/

Structural Design Engineers 120 Montgomery Street, Suite 1410 San Francisco, California / Fax 415/ 120 Montgomery Street, Suite 1410 San Francisco, California 94104 415/781-1505 Fax 415/781-2718 sde@sdesf.com Rajendra Sahai, SE Principal John W. Laws, SE Principal Steven Lepisto, SE Principal STRUCTURAL

More information

Open-Web Trusses. Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses. Design Flexibility. Outstanding Strength-to-Weight Performance

Open-Web Trusses. Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses. Design Flexibility. Outstanding Strength-to-Weight Performance Open-Web Trusses Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses Download your free copy at RedBuilt.com. Specify Open-Web trusses for your next project using RedSpec single-member sizing software.

More information

Open-Web Trusses. Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses. Design Flexibility. Outstanding Strength-to-Weight Performance

Open-Web Trusses. Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses. Design Flexibility. Outstanding Strength-to-Weight Performance Open-Web Trusses Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses Download your free copy at RedBuilt.com. Specify Open-Web trusses for your next project using RedSpec single-member sizing software.

More information

Table of Contents.2. Introduction...3 Gravity Loading and Deflections..4. Existing Structural System..8

Table of Contents.2. Introduction...3 Gravity Loading and Deflections..4. Existing Structural System..8 WISCONSIN PLACE RESIDENTIAL TECHNICAL ASSIGNMENT 2 OCTOBER 29, 2007 KURT KRASAVAGE THE PENNSYLVANIA STATE UNIVERSITY STRUCTURAL OPTION FACULTY ADVISOR: DR. ALI MEMARI 1 Table of Contents Table of Contents.2

More information

FINAL REPORT. Structural Redesign of Hershey Medical Center Children s Hospital. Penn State Hershey Medical Center Children s Hospital

FINAL REPORT. Structural Redesign of Hershey Medical Center Children s Hospital. Penn State Hershey Medical Center Children s Hospital FINAL REPORT Structural Redesign of Hershey Medical Center Children s Hospital Penn State Hershey Medical Center Children s Hospital The Pennsylvania State University Architectural Engineering Adviser:

More information

CURVED STEEL I GIRDER BRIDGES RAMP GH OVER THE ERIE CANAL INTRODUCTION BEHAVIOR OF CURVED BRIDGES DIFFERENCES FROM STRAIGHT BRIDGES

CURVED STEEL I GIRDER BRIDGES RAMP GH OVER THE ERIE CANAL INTRODUCTION BEHAVIOR OF CURVED BRIDGES DIFFERENCES FROM STRAIGHT BRIDGES DIFFERENCES FROM STRAIGHT BRIDGES Torsion effects Flange lateral bending Global stability CURVED STEEL I GIRDER BRIDGES RAMP GH OVER THE ERIE CANAL Constructability concerns INTRODUCTION COMPARISON WITH

More information

FDA OC/ORA Office Building

FDA OC/ORA Office Building FDA OC/ORA Office Building Adam Love Page 2 of 158 Table of Contents Executive Summary... 6 Introduction... 7 Structural System... 8 Foundation:... 8 Floor System:... 10 Building 31:... 10 Building 32:...

More information

AIA St. Louis January 4 th, 2017 Phillip Shinn, PE Jacobs Engineering Washington University in St. Louis, Sam Fox School of Design and Visual Arts

AIA St. Louis January 4 th, 2017 Phillip Shinn, PE Jacobs Engineering Washington University in St. Louis, Sam Fox School of Design and Visual Arts AIA St. Louis January 4 th, 2017 Phillip Shinn, PE Jacobs Engineering Washington University in St. Louis, Sam Fox School of Design and Visual Arts Owners are NOT Architects (but they ARE the Owners) Steel

More information

Structural Technical Report 1 Structural Concepts / Structural Existing Conditions Report

Structural Technical Report 1 Structural Concepts / Structural Existing Conditions Report Michael A. Troxell Structural Option Advisor: Professor Parfitt College of Business Administration Oct. 5, 2005 Structural Technical Report 1 Structural Concepts / Structural Existing Conditions Report

More information

LPI 56 Technical Guide

LPI 56 Technical Guide LPI 56 Technical Guide Floor & Roof Applications Product Specifications & Design Values 2 Floor Tables 3 Uniform Floor Load (PLF) Tables: Simple s 4 Uniform Floor Load (PLF) Tables: Continuous s 5 Uniform

More information

Steel Expansion. Located along the Grand River in

Steel Expansion. Located along the Grand River in Steel Expansion by Michael Gustafson, P.E. The DeVos Place convention center in Grand Rapids, MI, is undergoing a multi-year expansion featuring steel-framed column-free exhibit space. Located along the

More information

Date: 'Comments' b Steel Quantity Takeoff. 'Quantities' b Design Loads and Parameters

Date: 'Comments' b Steel Quantity Takeoff. 'Quantities' b Design Loads and Parameters HILTON GARDEN INN 866.ask.aisc solutions@aisc.org SSC Advisor: Erika Winters Downey Date: 7.3.2007 This Package includes: Excel Tab Name b Comments on the Provided Solution 'Comments' b Steel Quantity

More information

TECHNICAL REPORT III LATERAL STRUCTURAL SYSTEM ANALYSIS

TECHNICAL REPORT III LATERAL STRUCTURAL SYSTEM ANALYSIS TECHNICAL REPORT III LATERAL STRUCTURAL SYSTEM ANALYSIS Chris Vanaskie Structural Peninsula Regional Medical Center Salisbury, MD January 10, 2009 TABLE OF CONTENTS Executive Summary... 3 Introduction...

More information

CODE OF STANDARD PRACTICE

CODE OF STANDARD PRACTICE CODE OF STANDARD PRACTICE FOR STEEL JOISTS AND JOIST GIRDERS SECTION 1. GENERAL 1.1 SCOPE Adopted by the Steel Joist Institute April 7, 1931 Revised to Nov. 10, 2014 - Effective Jan.1, 2015 The practices

More information

Temecula Medical Center Temecula, CA

Temecula Medical Center Temecula, CA Temecula Medical Center Temecula, CA Technical Assignment #2 Sean F. Beville The Pennsylvania State University Architectural Engineering Structural Option Senior Thesis Project Student Advisor: Thomas

More information

STEEL DESIGNERS MANUAL

STEEL DESIGNERS MANUAL STEEL DESIGNERS MANUAL SIXTH EDITION The Steel Construction Institute Edited by Buick Davison Department of Civil & Structural Engineering, The University of Sheffield Graham W. Owens Director, The Steel

More information

Open-Web Trusses. Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses. Design Flexibility. Outstanding Strength-to-Weight Performance

Open-Web Trusses. Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses. Design Flexibility. Outstanding Strength-to-Weight Performance Open-Web Trusses Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses Download your free copy at RedBuilt.com. Specify Open-Web trusses for your next project using RedSpec single-member sizing software.

More information

SEISMIC DESIGN GUIDELINES

SEISMIC DESIGN GUIDELINES INTRODUCTION The purpose of these Seismic Design Guidelines is to provide additional information and clarification to Civil or Structural engineers in order to comply with Ordinance No. 18-O- 2767 for

More information

David A. Walenga Technical Assignment #1

David A. Walenga Technical Assignment #1 Executive Summary Contained in this report is design information related to the structural system of the Residence Inn by Marriot located in Stamford, Connecticut. Specifically, this report covers: code

More information

These systems are evaluated on the basis of serviceability issues such as:

These systems are evaluated on the basis of serviceability issues such as: 1 Traci Peterson Option: Structural Faculty Consultant: Memari The Del Monte Center at The North Shore Pittsburgh, PA Structural Technical Report 2 Pro Con Structural Study of Alternate Floor Systems Date

More information

CVEN 483. Structural System Overview

CVEN 483. Structural System Overview CVEN 483 Structural System Overview Dr. J. Bracci Fall 2001 Semester Presentation Overview 1. Building system primary function 2. Types of load 3. Building materials 4. Structural members 5. Structural

More information

SJI Code of Standard Practice

SJI Code of Standard Practice Standard Practice CODE OF STANDARD PRACTICE FOR STEEL JOISTS AND JOIST GIRDERS SECTION 1 GENERAL 1.1 SCOPE Adopted by the Steel Joist Institute April 7, 1931 Revised to May 18, 2010 - Effective December

More information

MCEER Hospital Demonstration Project

MCEER Hospital Demonstration Project 15 MCEER Hospital Demonstration Project Tsung Yuan Tony Yang Department of Civil, Structural & Environmental Engineering, University of Buffalo Research Supervisor: Andrew S. Whittaker, Associate Professor

More information

The Harry and Jeanette Weinberg Center Mercy Hospital Medical Office Building Baltimore, MD. Thesis Proposal

The Harry and Jeanette Weinberg Center Mercy Hospital Medical Office Building Baltimore, MD. Thesis Proposal The Harry and Jeanette Weinberg Center Mercy Hospital Medical Office Building Baltimore, MD Thesis Proposal Kevin Clouser December 15, 2006 Structural Option Faculty Consultant: Dr. Boothby 1 Executive

More information

STEEL REACTION FRAME

STEEL REACTION FRAME STEEL REACTION FRAME Kyle Coleman, CEE Laboratory Manager Andrew Myers, Assistant Professor Jerome F. Hajjar, Professor and Chair, Director, STReSS Laboratory Department of Civil and Environmental Engineering,

More information

Survey and Testing of Pre-1988 Braced Frame Structures From The West Coast of the United States

Survey and Testing of Pre-1988 Braced Frame Structures From The West Coast of the United States Survey and Testing of Pre-1988 Braced Frame Structures From The West Coast of the United States Dan Sloat 1, Charles W. Roeder 2, Dawn E. Lehman 3, and Jeffrey W. Berman 4 1 Graduate Student, Dept. of

More information