The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma
|
|
- Elijah Chase
- 6 years ago
- Views:
Transcription
1 LEED Green Building Certification The purpose of the LEED Green Building Rating is to provide a national standard that aims to improve environmental, health and economic performance of buildings using established and/or advanced industry principles, practices, materials and standards. The purpose of this analysis is to assess the CAPA High School s mechanical system in each of the following categories: Water Efficiency, Energy and Atmosphere, Materials and Resources, Indoor Environmental Quality, and LEED Innovation Credits. Water Efficiency This category places an emphasis on the utilization of water efficient landscaping, innovative wastewater technologies, and through water use reduction. The design of the mechanical system for the CAPA High School does not provide for any reductions in the use of water and therefore scores no points in this section. Energy and Atmosphere In this category, the mechanical system for the CAPA building meets two of the three prerequisites and scores two points out of a possible seventeen. Prerequisite 1 requires a fundamental building systems commissioning which is not performed on the CAPA building. Prerequisite 2, Minimum Energy Performance is met as a result of the building s ability to meet the requirements stated in ASHRAE Std , and prerequisite 3, CFC Reduction in HVAC&R Equipment, is met via the use of R-134a, an HCFC refrigerant, in all HVAC equipment. The CAPA building receives two points for the HVAC system s design which reduces energy costs by 20% as compared to requirements listed in ASHRAE Std by utilizing economizers on all AHU s and VUV s, free-cooling in winter by converting condenser water into chilled water, use of VFD drives and high efficiency motors on the building s VAV system, minimizing outdoor air in auditorium and gym by using CO 2 monitors, and through the use of DDC temperature controls throughout the building. Other credits in this category are available for increased optimization of the energy performance, use of renewable energy, and additional commissioning, all of which are not provided for through the design of the building s mechanical system. Materials and Resources This category places an emphasis on the reuse and recycling of materials used throughout the project along with the use of materials found within the local region and the use of rapidly renewable materials. Most of this category is affected by the General Contractor s use of materials, and the building s mechanical system can only be credited for one point in this section, for the use of a minimum of 20% locally produced equipment. Building and Plant Energy Analysis Part A 1
2 Indoor Environmental Quality This category places an emphasis on taking measures to improve the indoor air quality (IAQ) of the building through the use of specific mechanical equipment to control CO 2 levels and thermal comfort. This section also gives points for the ability of users to control the mechanical system in there area and for providing daylight and views to the occupant as well as for using low-emitting materials and controlling the IAQ during construction. The CAPA building s mechanical system provides for compliance with the two prerequisites and scores 3 points in this section. Prerequisite 1, Minimum IAQ Performance, is provided for by the designer s use of the ventilation rate procedure to meet minimum requirements for ventilation stated in ASHRAE Std Prerequisite 2, Environmental Tobacco Smoke (ETS) Control, is provided for by the zero exposure of tobacco smoke to non-smokers via the prohibition of smoking in the building. The CAPA building receives one point for its use of CO 2 sensors in return air ductwork in return air ductwork for all AHU s and through the use of a CO 2 monitoring system for the auditorium and gymnasium. Another point is received for an increase in ventilation effectiveness provided for by the ventilation system s ability to meet the air change effectiveness (E=0.9) described in ASHRAE Std The third point is received for the controllability of the system which is provided through the building s design which allows for one operable window and one light control per 200 sq. ft. for occupied areas within 15 feet of perimeter walls. Innovation & Design Process Other points may be gained for the building through the use of non-chemical treatment of condenser water and a VFD ventilation exhaust fan used in the garage which is controlled by a carbon monoxide sensor. Additional points may also be received for the incorporation of a roof-top garden, which may provide additional help in dealing with run-off water during rainstorms and in reduction of heat islands. Building and Plant Energy Analysis Part A 2
3 ASHRAE Standard The purpose of this analysis is to determine if the CAPA High School s building envelope is within compliance with ASHRAE Std For this analysis section 5 of the standard was used to determine compliance. The first step in the procedure is to determine the CDD50 and HDD65 values for the city of Pittsburgh, PA which are 2836 and 5968 days, respectively. For these values it is necessary to use Table B-17 in Appendix B to determine the minimum and maximum values for compliance. The CAPA high school is classified as a non-residential building and has a roof with insulation entirely above deck, mass walls above grade, and steel joist floors. The exterior vertical fenestration comprises up 28% of the total exterior wall area and therefore falls into the % profile. When determining the U- and R-values for the building, I took the construction information off of the architectural drawings and inputted that material into Carrier s Hourly Analysis Program v.4.10, to determine the U- and R-values for the building materials. The CAPA High School was found to be compliant with Std and supporting information can be found on the table below. Building and Plant Energy Analysis Part A 3
4 Lighting Compliance For the lighting compliance section, I chose to look at 3 typical spaces within the building and compared the power density of the spaces to the maximum power allowance values in ASHRAE Std The three spaces I chose were a classroom, a corridor, and an office. All spaces were found to be compliant within the code limits and the calculations may be found in the following table Equipment Spacing I have gone through the drawings for the mechanical system and have verified that all of the mechanical equipment has adequate spacing around it to allow for servicing of the equipment. In order for the equipment to be serviced a distance equal to the width of the piece of equipment is required for each component in the mechanical room. The 2120 square foot mechanical room located in the basement, room B10, allows for enough space to house two water chillers, two hot water boilers and ten water pumps. The second floor mechanical room, 215, is 190 square feet and houses one air handling unit. The mechanical rooms on the fourth floor, 413 and 430, are 233 and 278 square feet, respectively. Room 412 houses one air handling unit and room 430 houses a heat recovery unit. The seventh floor penthouse is 4480 square feet and provides room for eight air-handling-units. Mechanical System Cost Breakdown The mechanical system for the CAPA High School costs approximately $4.2 million and makes up 12 percent of the total cost of the building. The price per square foot of the 175,140 square foot facility is approximately $24. HVAC Systems Cost Total Addition & Renovation $ 4,204,916 Area Addition & Renovation 175,140 sq ft Cost/sq ft $ Building and Plant Energy Analysis Part A 4
5 Lost Rentable Space The total amount of lost rentable space comprised of the mechanical rooms and duct chases, is equal to less than 3% of the total building area. Plenum spaces are also kept to a minimum throughout the building which has caused many construction issues concerning the placement of needed equipment in these spaces. Breakdown of lost rentable space due to mechanical equipment Floor Description Lost Area - sf Basement B01 - Environmental Mechanical 272 Basement B10 - Mechanical Equipment Room 2120 Basement B12 - Existing Emergency Generator Room 371 Basement Elevator Shaft - Exhaust Fan st Back Alley Chase 58 1 st East Stair Chase 34 1 st Pipe Chase st Elevator Shaft - Exhaust Fan 54 2 nd Mechanical Room nd Back Alley Chase 68 2 nd East Stair Chase 34 2 nd Pipe Chase nd Elevator Shaft - Exhaust Fan 54 3 rd Back Alley Chase 70 3 rd East Stair Chase 34 3 rd Pipe Chase th Back Alley Chase th East Stair Chase 34 4 th Pipe Chase th Mechanical Room th Mechanical Room th Bathroom Chase 11 5 th Back Alley Chase th East Stair Chase 34 5 th Pipe Chase th Bathroom Chase 94 6 th Back Alley Chase th East Stair Chase 35 6 th Pipe Chase th Bathroom Chase 94 Total 4949 Total Building Area 175,140 Percentage of Area 2.8 % Building and Plant Energy Analysis Part A 5
ENERGY AND ENVIRONMENT DESIGN AND CONSTRUCTION STANDARDS ENERGY AND ENVIRONMENT
ENERGY AND ENVIRONMENT The University has committed to approaching new building construction and major renovations with an emphasis on Life Cycle Cost (LCC). Part of this approach is a focus on maximizing
More informationKeith Beidel Mechanical Option Centre Community Hospital East Wing Expansion State College, PA 9/30/02
BUILDING AND PLANT ENERGY ANALYSIS REPORT: Part A Keith Beidel Mechanical Option Centre Community Hospital East Wing Expansion State College, PA 9/30/02 Executive Summary Centre Community Hospital East
More informationAppendix C APPLICATION #: ADDRESS: CITY OF SANTA CRUZ GREEN BUILDING PROGRAM GREEN POINTS CHECK LIST FOR NON-RESIDENTIAL BUILDINGS
Appendix C APPLICATION #: ADDRESS: CITY OF SANTA CRUZ GREEN BUILDING PROGRAM GREEN POINTS CHECK LIST FOR NON-RESIDENTIAL BUILDINGS November 2006 Version 2.2 Instructions for Completing Check List Use this
More informationGerald R. Ford Museum
Gerald R. Ford Museum Grand Rapids, Michigan Executive Summary Building and Plant Energy Analysis Report: Part I Brendan J. Cullen The Pennsylvania State University AE Senior Thesis Mechanical Option September
More informationTechnical Report Three Mechanical Systems Existing Conditions Evaluation
09 10 Technical Report Three Mechanical Systems Existing Conditions Evaluation WESTINGHOUSE ELECTRIC CO. NUCLEAR ENGINEERING HEADQUARTERS CAMPUS Pittsburgh, PA Daniel P. Aughenbaugh Mechanical Dr. Bahnfleth
More informationSpecial Mention, Architecture + Sustainability
Awards 2013 LOS ANGELES BUSINESS COUNCIL DESIGN AWARDS Grand Prize INTERNATIONAL INTERIOR DESIGN ASSOCIATION / SOUTHERN CALIFORNIA CALIBRE AWARDS Workplace Medium SAN FERNANDO VALLEY BUSINESS JOURNAL COMMERCIAL
More informationEnergyPro Building Energy Analysis. Single-story School Building
EnergyPro Building Energy Analysis Single-story School Building EnergyPro Building Energy Analysis for a single-story school bulding Project Scope The purpose of the EnergyPro energy model was to evaluate
More informationLEED Project Delivery Process Manual Appendices
LEED Project Delivery Process Manual Appendices November 2016 Second Edition Appendices Page Appendix 1: Other Alberta Requirements and Green Building Standards 3 Appendix 2: Integrated Design Process
More information10. LEED RATING EVALUATION
0. LEED RATING EVALUATION In order to quantify the green-ness of a building, the United States Green Building Council (USGBC) utilizes a point system for sustainable design elements. The total points a
More informationDelaware County Community College STEM Center
Mechanical Systems Existing Conditions Evaluation Delaware County Community College STEM Center Media, PA Dan Saxton Mechanical Option Faculty Consultant: Dr. Stephen Treado Date Submitted: Table of Contents
More informationBUILDING AND PLANT ENERGY ANALYSIS REPORT
BUILDING AND PLANT ENERGY ANALYSIS REPORT Alicia Carbin Longwood University s New Science Building in Farmville, VA 10-27-04 TABLE OF CONTENTS. 1.0 Executive Summary.........1 2.0 LEED Green Building Certification........2
More informationAnalysis 1. LEED Analysis of Laboratory Buildings. Penn State School of Forest Resources University Park, PA
Analysis 1 LEED Analysis of Laboratory Buildings Background The LEED program (Leadership in Energy and Environmental Design) established by the U.S. Green Building Council is becoming the standard by which
More informationLEED 2009 Core and Shell, Commercial Project Summary and Checklist New Construction
Date of Application Path Project Project Address Owner Architect Contractor Third Party Provider LEED 2009 Core and Shell, Commercial Project Summary and Checklist New Construction Summary Permit. Provider.
More informationLEED LEED. Leadership in Energy and Environmental Design. A voluntary, consensus-based. high-performance, sustainable buildings and neighborhoods
LEED An Introduction to LEED V3 2009 LEED Leadership in Energy and Environmental Design A voluntary, consensus-based national standard for developing high-performance, sustainable buildings and neighborhoods
More informationChilled Beams. The new system of choice?
Chilled Beams The new system of choice? Presented By: Kevin M. Pope P.E. Jason Leffingwell Hammel Green And Abrahamson, Inc. and Ken Bauer, P.E., LEED AP Butters-Fetting Co., Inc. History of Chilled Beams
More informationTHERMA-FUSER VARIABLE AIR VOLUME DIFFUSER SYSTEMS
SUSTAINABLE DESIGN FORM 010.901 REV 1211 THERMA-FUSER VARIABLE AIR VOLUME DIFFUSER SYSTEMS SUSTAINABLE DESIGN GUIDE StopWaste.Org LEED-NC Platinum Energy Foundation LEED-CI Platinum Adobe East Tower LEED-EB
More informationTechnical Assignment 2: Building and Plant Energy Analysis Report. Jason Jones Mechanical Option Multipurpose Athletic Center West Long Branch, NJ
Technical Assignment 2: Building and Plant Energy Analysis Report Jason Jones Multipurpose Athletic Center West Long Branch, NJ October 27, 2004 Table of Contents Table of Contents 1 Executive Summary
More informationItalcementi Center for Research and Innovation
Italcementi Center for Research and Innovation Bergamo, Italy LEED-NC v2.1 EAc1 A. Project Narrative (Viridian) analyzed the energy use of the proposed Italcementi Center for Research and Innovation located
More informationEnergyPro Building Energy Analysis. Nine-story Office Building
EnergyPro Building Energy Analysis Nine-story Office Building EnergyPro Building Energy Analysis for an office building Project Scope The purpose of the EnergyPro energy model was to evaluate the energy
More informationBuilding Energy Analysis for a Multi-Family Residential Building (Multi V III VRF Heat-Pump System)
Building Energy Analysis for a Multi-Family Residential Building (Multi V III VRF Heat-Pump System) Residential-Building Energy-Modeling Engineering Study VRF-ES-BH-001-US 012E03 Executive Summary Contents
More informationPrerequisite. prerequisite.
LEED v4 for Building Operations and Maintenance Summary of changes from LEED 2009 LOCATION AND TRANSPORTATION SUSTAINABLE SITES Alternative Transportation Site Management Policy LEED Certified Design and
More informationHow LEED v4 Impacts Energy Professionals and Mirrors Broader Sustainability Trends. Dan LeBlanc Senior Sustainability Manager
How LEED v4 Impacts Energy Professionals and Mirrors Broader Sustainability Trends Dan LeBlanc Senior Sustainability Manager dleblanc@yrgxyz.com LEED CERTIFICATION TRENDS MARKET SECTOR ADAPTATIONS Data
More informationEADQUARTERS. Thesis Revised Proposal. Stephanie Kunkel Mechanical Option
EADQUARTERS 707 N. Calvert St. Mechanical System Renovation Construction Management & Lighting/Electrical Breadths Stephanie Kunkel www.engr.psu.edu/ae/thesis/portfolios/2011/slk5061 Mechanical Option
More informationDayton Chapter February 9, Bob Thomson, P.E., LEED-AP, CDT
Dayton Chapter February 9, 2009 Bob Thomson, P.E., LEED-AP, CDT World Population is estimated to be 6,000,000,000 people U.S. Population is estimated to be 3,000,000 people U.S. makes up 5% of the world
More informationGeorgetown University New Science Center
Georgetown University New Science Center Final Thesis Proposal PENN STATE UNIVERSITY Prepared For: Dr. William P. Bahnfleth Department of Architectural Engineering Prepared By: Kevin M Edstrom Mechanical
More informationTechnical Report Three
Technical Report Three Mechanical System Existing Conditions Evaluation Prepared by: Timothy Berteotti Prepared for: Date: November 16, 2011 Table of Contents Executive Summary...3 Design Objectives...3
More information2-Pipe fan coil terminal units were selected as the parallel system to handle the remaining sensible cooling load.
Redesign Introduction This report is an in depth analysis of the mechanical systems of the Outreach Innovation Building located in University Park, PA and the impact these changes had on other systems
More informationSession: HVAC Technologies
Session: HVAC Technologies What s VRF? Mira Vowles Bonneville Power Administration August 10, 2016 Rhode Island Convention Center Providence, Rhode Island Why should I care about VRF? VRF systems: can
More informationLEED 2009 for New Construction and Major Renovations
LEED 2009 for New Construction and Major Renovations Bayshore District Operations Building Project Checklist 4.28.6 20 4 0 Sustainable Sites Possible Points: 26 Y? N d/c Notes: Y C Prereq Construction
More informationSustainable Design A DIVISION OF SHIVE-HATTERY
Sustainable Design A DIVISION OF SHIVE-HATTERY our transition to sustainability must be a deliberate choice to leave the linear surge of an extractive economy and enter a circulating, renewable one. Janine
More informationOPTION 1: PERFORMANCE RATING METHOD
OPTION 1: PERFORMANCE RATING METHOD I confirm that the energy simulation software used for this project has all capabilities described in EITHER section `G2 Simulation General Requirements' in Appendix
More informationCalifornia State University, Sacramento February 24, 2010
Leadership in Energy and Environmental Design (LEED) California State University, Sacramento February 24, 2010 Lower Operating Costs Reduce Energy Use Conserve Water Lower Maintenance Customer/Occupant
More informationPrerequisites must be achieved. Non-compliant prerequisites must be resolved before a certification can be awarded.
LEED Project 263 Version 2 How to Interpret this Report Purpose Environmental Categories LEED Prerequisites The Leadership in Energy and Environmental Design (LEED) Rating System was designed by the US
More informationNext Connecticut Energy Code
Connecticut Chapter Association of Energy Engineers Next Connecticut Energy Code 1 Next Connecticut State Building Code n 2012 International Building Code n 2012 International Existing Building Code n
More informationLincoln Public Schools
Lincoln Public Schools School Building Committee Meeting July 11, 2018 Today s Agenda Floor Plan Update Sustainable Design Features, NZE Systems & Exterior Building Envelope Project Schedule Construction
More informationSouth Jefferson High School Huyett Road Charles Town, WV 25414
Thesis Proposal Mechanical System Redesign Report Charles Town, WV 25414 Prepared for Dr. Jelena Srebric The Pennsylvania State University By Jonathon Gridley Friday, December 15, 2006 1.0 Table of Contents
More informationBETA OPTION 1: PERFORMANCE RATING METHOD. Section General Information
LEED-CS 2. Certification Submittal Template OPTION 1: PERFORMANCE RATING METHOD I confirm that the energy simulation software used for this project has all capabilities described in EITHER section `G2
More informationSUSTAINABILITY REPORT
Lane Community College Building 11 Remodel SUSTAINABILITY REPORT Introduction: Generally, the Building 11 Remodeling project consisted of interior reworking to provide several new classroom spaces on the
More informationIECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST
IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Project: Date: Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other
More informationUniversity of Minnesota Duluth Civil Engineering Building
Energy Data Attachment University of Minnesota Duluth Civil Engineering Building LEED Energy Modeling The energy modeling for LEED NC 2.2 was performed against ASHRAE 9.1-24 Appendix using equest version
More informationAppendix E-1f: Small Building Methodology for Pre-SB2030 Projects
Appendix E-1f: Small Building Methodology for Pre-SB2030 Projects Prescriptive Bundle Option Method for Office Buildings less than 30,000 GSF This section describes energy strategy requirements for three
More informationLEED LEED LEED. Earth Tech, Inc. Earth Tech, Inc. A Firm With Experience. A Firm With Experience. Operational Efficiencies & Resources Preservation
How the Five Principles of Pri Can LEAD to Improved Design Operational Efficiencies & Resources Preservation A Firm With Experience Earth Tech, Inc. Earth Tech, Inc. A Firm With Experience Earth Tech,
More informationThe Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario
The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario Visionwall Technologies Inc. 14904-123 Avenue Edmonton, Alberta, Canada T5V 1B4 Tel: 403 451 4000 Fax:
More informationALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations
ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations LEEDv4 Guideline February 1, 2017 Tony Sparks David Ritchey Stuart Ingham Karen Alarid Kris Callori Noreen Richards
More informationCoppin State University Physical Education Complex - Technical Report 2
Coppin State University Physical Education Complex - Technical Report 2 Building and Plant Energy Analysis Report Kaylee M Damico Advisor: Dr. Jelena Srebric Location: Baltimore, MD Table of Contents Contents
More informationFACILITY DESIGN PLAN FOR HARDING HALL RENOVATION AND ADDITION SOUTH DAKOTA STATE UNIVERSITY DATE: March 29, 2017
FACILITY DESIGN PLAN FOR HARDING HALL RENOVATION AND ADDITION SOUTH DAKOTA STATE UNIVERSITY DATE: March 29, 2017 SDSU requests approval of this Facility Design Plan for renovation and addition to Harding
More information43% reduction in water use below code maximum 100% 100% 14% reduction in lighting power density. 56% of offices have thermal comfort controls 100%
Insert school or unit logo Nocera Lab LEED CI v3.0 12 Oxford Street, Cambridge, MA GOLD Project Profile Laboratories are typically regarded as an energy intensive building typology. Many of these buildings
More informationAbove: Northwest corner Below: Southwest corner
Above: Northwest corner Below: Southwest corner Above: Northeast corner (Former Ice House) Below: Southeast corner (Parking garage) Above: Office main entry along Third Street Below: South courtyard showing
More informationProjected actual points. Responsible for UNC -- Project name. Remarks
UNC LEED Checklist Total points available Projected Responsible for UNC -- Project name Cost documentation Sustainable Sites Prerequisite- Erosion and Sediment control Prerequisite REQ Y All campus projects
More informationL E E D S C O R E C A R D ( B U I L D I N G D E S I G N & C O N S T R U C T I O N )
Project Zip Code: 92101 Project Anticipated Rating: LEED-NC Gold L E E D 2 0 0 9 S C O R E C A R D ( B U I L D I N G D E S I G N & C O N S T R U C T I O N ) 62 22 26 Project Totals A-Achieved X-Documented
More informationChanges to the Minnesota Commercial Energy Code. Presented by: Andy Thielen, PE
Changes to the Minnesota Commercial Energy Code Presented by: Andy Thielen, PE Warning! The following is an outline of proposed code changes. There is no guarantee that the final code adopted by the State
More informationEnergy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort
Please add relevant logo here Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort Presented by: Peter J. Arsenault, FAIA, NCARB, LEED-AP Disclaimer: This presentation was developed by
More informationHVAC SYSTEM DESIGN PROCESS
HVAC SYSTEM DESIGN PROCESS Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Summer 2011 Grondzik 1 HVAC System Design Process Establish design intents/criteria (including code/standard compliance) Establish
More informationNorth Pocono High School
Building System Integration Energy and Cost Analysis Architectural Engineering Senior Thesis Presentation Pennsylvania State University Presentation Outline Project Outline Existing System Design Conditions
More informationFernow Hall LEED FOR NEW CONSTRUCTION & MAJOR RENOVATIONS (V2009) LEED Certification Review Report
Page of 3 LEED Certification Review Report This report contains the results of the technical review of an application for LEED certification submitted for the specified project. LEED certification is an
More informationHPBS [ HIGH PERFORMANCE BUILDING STANDARD]
HPBS [ HIGH PERFORMANCE BUILDING STANDARD] STATE OF MONTANA HIGH PERFORMANCE BUILDING STANDARDS MINIMUM REQUIREMENTS FOR ALL PROJECTS UNDER 17-7-201, MCA PART 2 1.1 DESIGN AND DOCUMENTATION A. Incorporate
More informationThesis Proposal. Freetown Elementary School
Thesis Proposal Freetown Elementary School Glen Burnie, MD Matthew R. Buda The Pennsylvania State University Architectural Engineering Mechanical Option Advisor: Dr. Treado Table of Contents Executive
More informationGreen Building Guideline of Jordan
Green Building Guideline of Jordan T. Awadallah 1*, S. Habet 1, A. Mahasneh 1, H. Adas 2 1 Royal Scintific Society, Amman, Jordan 2 National Energy Research Center, Amman, Jordan * Corresponding author.
More informationHVAC SYSTEM SCHEMATIC DESIGN
HVAC SYSTEM SCHEMATIC DESIGN Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 HVAC System Design Process Establish HVAC-related owner s project requirements (OPR: design issues/intents/criteria;
More informationWinchester High School
Winchester High School Preliminary Sustainability Conference Winchester, MA June 13, 2012 AGENDA Introduction Sustainable Design Overview Sustainable Design Strategies Open Discussion/Q&A Sustainable Design
More informationMechanical Systems Proposal
Mechanical Systems Proposal Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option December
More informationBuilding Energy Efficiency Analysis for a High School
Building Energy Efficiency Analysis for a High School (LG Multi V Water II VRF System) School Building Air-Conditioning Engineering Study VRF-ES-BF-002-US 013A16 Contents Executive Summary...3 Introduction...4
More informationCITY COUNCIL AGENDA REPORT
CITY COUNCIL AGENDA REPORT Subject: COUNCIL MOTION SUSTAINABLE BUILDINGS On March 2, 2015 Councillor Prefontaine provided notice in accordance with Section 23 of Procedure Bylaw 35/2009 that he intended
More informationBuilding Energy Efficiency Analysis for a High School
Building Energy Efficiency Analysis for a High School (LG Multi V III VRF System) School Building Air-Conditioning Engineering Study VRF-ES-BH-002-US 013A30 Executive Summary Contents Executive Summary...2
More informationDesign Standard Sustainability
Design Standard Sustainability Purpose Educational institutions have the ability to influence the ideals and principles of our future decision makers; as such, East Side Union High School District (ESUHSD)
More informationAllowance Table for: General:
Allowance Table for: Adopting Credits from LEED Canada for New Construction and Major Renovations (NC) 2009 and LEED Canada for Core and Shell Development (CS) 2009 for LEED Canada-NC v1.0 (with or without
More informationLEED Application Guide for Multiple Buildings and On Campus Building Projects
LEED Application Guide for Multiple Buildings and On Campus Building Projects For Use with 2009 LEED Rating Systems for Design and Construction and Operations and Maintenance Released October 31, 2011
More informationLEED v4 LEED BD+C Credit-by-Credit Review
LEED v4 LEED BD+C Credit-by-Credit Review Location & Transportation Sustainable Sites Water Efficiency Energy & Atmosphere Materials & Resources Indoor Environmental Quality Innovation & Integrative Process
More informationCity High Middle School pre-design recommendations. March 29, 2017
City High Middle School pre-design recommendations March 29, 2017 City High Middle School table of contents 2 3 4 5 6 7 8 9 10 11 12 13 table of contents project description and purpose existing systems
More informationElement Z General Design Requirements Existing Facilities Information
Anderson Central 100B, PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G
More informationCREDIT COMPLIANCE (Please complete the color coded criteria(s) based on the option path selected)
(Responsible Individual) (Company Name) I,, from verify that the information provided below is accurate, to the best of my knowledge. CREDIT COMPLIANCE (Please complete the color coded criteria(s) based
More informationDate Rater Verified. Rater Verified. Slab / Pre-Drywall / Thermal Inspection
Slab on Grade & Basements: A capillary break is installed on top of all footings Slab / Pre-Drywall / Thermal Inspection A minimum of 4" of clean or washed gravel (0.5" diameter or greater) is placed over
More informationMechanical Systems Redesign Proposal. Thesis Proposal. Morton Hospital Expansion
Mechanical Systems Redesign Proposal Thesis Proposal Morton Hospital Expansion Taunton, MA Courtney Millett Mechanical Option Advisor: Dr. Bahnfleth December 12, 2014 Revised: January 16, 2015 Revised:
More informationBuilding and Plant Energy Analysis Report. Instructor: Dr. Freihaut. October 6, Thesis Building Sponsor s: INOVA Fairfax Hospital
David J. Peterson Mechanical Option Mechanical Technical Report #2a The INOVA HEART INSTITUTE AT, Falls Church, VA. Mechanical Technical Report #2a Building and Plant Energy Analysis Report Instructor:
More informationGreen Building Overview, Rating Systems and the (Proposed) ASHRAE Standard 189.1
Green Building Overview, Rating Systems and the (Proposed) ASHRAE Standard 189.1 Dr. Tom Lawrence, P.E., LEED-AP lawrence@engr.uga.edu Standard 189-1 Introduction and greetings from the University of Georgia
More informationThesis Proposal. Clemson University Advanced Material Research Laboratory Anderson, SC. David Anderson Mechanical Option. Photo by Fred Martin
Thesis Proposal Photo by Fred Martin Clemson University Advanced Material Research Laboratory Anderson, SC David Anderson Mechanical Option Friday, December 15, 2006 Table of Contents 1. Executive Summary
More informationUnderf loor For Schools
The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
More informationThe Application of LEED Green Building Rating System in Indonesia
The Application of LEED Green Building Rating System in Indonesia Baharuddin Hasanuddin University, Faculty of Engineering, Department of Architecture, Makassar-Indonesia baharsyah@yahoo.com Abstract:
More informationDavid H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option. Proposal
0 David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option Proposal David H. Koch Institute for Integrative Cancer Research Massachusetts Institute of Technology Cambridge,
More informationExample LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal
Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal The following documentation provides an example submittal for the LEED-NC v2.1 Energy & Atmosphere Credit 1 (EAc1). This sample EAc1 submittal
More informationP-7A PROGRAM GSF FAR / NSF FAR COMMENT Basement - BOH Program 3,975 0 Below grade NIC below grade Ground Level - Lobby Program 3,935 includes elevator floors 9'-0" Level 2 - Lounge/F+B Program 5,765 5,367
More informationLEED BUDGET IMPACTS. LEED Architectural Credits
LEED BUDGET IMPACTS LEED Architectural Credits Below is a summary description of the LEED points with architectural implications, provided by CKA / MHP. All costs are referenced from the Cost of LEED Report
More informationTechnical Report: Three
PSUAE Technical Report: Three Mechanical Systems Existing Conditions Evaluation Nicholas B Scheib 2010 M e c h a n i c a l O p t i o n - IP Table of Contents Executive Summary... 2 Mechanical System Description...
More informationHVAC SYSTEM DESIGN PROCESS
HVAC SYSTEM DESIGN PROCESS Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 HVAC System Design Process Establish design issues/intents/criteria (including code/standard compliance) Establish
More informationUpdate on LEED v3. All projects registered after June 26, 2009 must be under the guidelines of LEEDv3. A LEEDv3 summary of changes:
Update on v3 September 9, 2009 GP #7 The Green Building Rating system was recently updated and re-introduced April 27, 2009 as v3. This Green Piece will outline the major changes to the rating system and
More informationCOMcheck Software Version Envelope Compliance Certificate
COMcheck Software Version 4.0.2.8 Envelope Compliance Certificate Project Information Energy Code: 20 IECC Location: Cedar Hills, Utah Climate Zone: 5b Project Type: New Construction Vertical Glazing /
More informationEnergy Strategies That Work Case Studies
Energy Strategies That Work Case Studies Jean Ascoli, Architect, CEM, Program Director for New Construction Smart Energy Design Assistance Center University of Illinois, Urbana Champaign of Homeland Security
More informationThe baseline building system for compliance with Senate Bill 668 is defined by Appendix G,
Project: North Carolina A&T State University New Student Health Center SCO #: 08-08109-01A 1.0 Heating, Ventilating and Air Conditioning (HVAC) Baseline Building Systems Senate Bill 668 Compliance The
More informationSOUTH DAKOTA BOARD OF REGENTS. Budget and Finance ******************************************************************************
SOUTH DAKOTA BOARD OF REGENTS Budget and Finance AGENDA ITEM: 7 I DATE: May 9-11, 2017 ****************************************************************************** SUBJECT: SDSU Harding Hall Renovation
More informationProject Summary. Sustainability Facts. LEED for New Construction Rating (out of 69 possible points) Total Score 40 Sustainable Sites 7
Lindner Hall Martha S. and Carl H. Lindner III Hall was designed and constructed to be a high performance, sustainable building. It is the first building on campus to receive LEED Gold certification. LEED
More informationEnergy Efficiency Analysis for a Multi-Story Research Office Building (LG Multi V Water IV Heat Recovery VRF System)
Energy Efficiency Analysis for a Multi-Story Research Office Building (LG Multi V Water IV Heat VRF System) (* Source: http://kr.lgeaircon.com/) Commercial Air-Conditioning Engineering Study ES-MultiVWaterIV_EnergyAnalysis-08-14
More informationand LEED Energy and Atmosphere Credits Jean Ascoli, LEED AP BD+C Architect, Energy Specialist
ASHRAE University of Illinois Student Chapter April 20, 2011 Building Energy Efficiency and LEED Energy and Atmosphere Credits Jean Ascoli, LEED AP BD+C Architect, Energy Specialist Building Research Council,
More informationLEED And Your Indoor Environment
LEED And Your Indoor Environment An overview of LEED v3 and Indoor Air Quality David McCauley, CIE Council Certified Indoor Environmentalist ACAC CIE #1008005 USGBC's Mission To transform the way buildings
More informationCONSTRUCTION REQUIREMENTS
CONSTRUCTION REQUIREMENTS Note: The buildings on the UCCS campus are divided into two categories: General Fund and Auxiliaries. General Fund Buildings include academic and administrative functions. Auxiliary
More informationApril 16 th Linda Morrison Jesse Stanley
April 16 th 2010 Linda Morrison Jesse Stanley Energy efficiency Renewable energy Net zero buildings Envelope HVAC systems Water efficiency and metering Rating system, codes, best practice LEED-NC Version
More informationTHE ECONOMICS OF LEED FOR EXISTING BUILDINGS FOR INDIVIDUAL BUILDINGS 2008 EDITION A WHITE PAPER APRIL 21, 2008
THE ECONOMICS OF LEED FOR EXISTING BUILDINGS FOR INDIVIDUAL BUILDINGS 2008 EDITION A WHITE PAPER BY LEONARDO ACADEMY INC. APRIL 21, 2008 THIS WHITE PAPER SPONSORED BY JOHNSON CONTROLS This is a Leonardo
More informationEnergy Reduction Strategy Through 2020
Through 2020 Revised: August 2017 Executive Summary Auburn University is a land, sea and space grant university established in 1856. The university consists of 11,629,000 square feet on 1,840 acres and
More informationhow to read an energy model
how to read an energy model Kohler Ronan, LLC is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported
More informationWhite Paper ENVELOPE-FIRST APPROACH TO NET-ZERO ENERGY BUILDINGS
BOULDER CHICAGO NASHVILLE SALT LAKE CITY SAN FRANCISCO SPRINGFIELD, MO WASHINGTON, DC 2540 Frontier Avenue, Suite 100 Boulder, Colorado 80301 303.444.4149 White Paper ENVELOPE-FIRST APPROACH TO NET-ZERO
More informationIECC 2006 with Hawaii Amendments
IECC 2006 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other notes to the reviewer.
More information